This document outlines a federal contract opportunity for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is soliciting proposals to replace windows in Building 1 at an unspecified location. The selected contractor will be responsible for fabricating and installing new windows, removing existing windows, conducting safety and infection control assessments, and coordinating work with the VA project team. The contractor must adhere to construction documents and codes and protect surfaces during the project, which has a period of performance of 730 calendar days from notice to proceed. The scope of work involves demolition, hazardous material abatement, and replacing exterior windows with a new energy efficient system while keeping the occupied building's operations unaffected.

View the file

Other files for this federal contract opportunity

Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LIMITED ASBESTOS AND LEAD SURVEY

Replace Windows, Building 1 VA Project Number 657-19-110JC

VA St. Louis Healthcare System, John Cochran Division 35% Hazardous Material Design Submittal

July 12, 2019

July 12, 2019

Ben Ramsey Project Manger Spur Design 312 SW 25th Street Oklahoma City, OK 73109

1.0 Introduction

Riverfront Safety & Health, LC (Riverfront), a Service Disabled Veteran Owned Small Business, has performed a limited asbestos and lead identification survey for the 35% Schematic Design (SD) phase of the Replace Windows, Building 1 Project (VA Project 657-19-110JC) at the John Cochran VA Medical Center in St. Louis, MO (The Project). The principal contacts for this project were Ben Ramsey of Spur Design and Michael Gomez of the VA Medical Center. The following report is provided for your review and for future design considerations related to asbestos and lead issues associated with demolition and reinstallation of exterior windows.

The limited asbestos and lead field survey was conducted by Justin Rhyneer, Zach Haselhorst and Gerald Reimer, all Missouri-licensed Asbestos Inspectors. The limited lead survey was conducted Zach Haselhorst, a Missouri-licensed Lead Risk Assessor.

The Building 1 exterior (perimeter) window inspections were conducted on April 29, 30; May 1, 2, 3, 6; and June 26, 2019 (A & B Wing Window Demolition Pilot Study), with the following limitations:

• The fully occupied and functioning hospital itself limited access into rooms due to daily hospital functions. At the time of the inspection, exam and inpatient rooms were not inspected if the room was occupied by a patient, current exam was taking place, or an employee meeting was in progress. Also, keys issued to personnel did not always function on every lock and therefore the area was not accessed.

• Select windows throughout the hospital have been covered up during renovations by drywall walls, etc. Windows in these areas were not accessible and therefore not thoroughly inspected.

• Exterior sampling throughout the hospital was very limited. Most windows are screwed shut limiting access to the exterior on floors higher than the basement and first floor levels.

Only a few windows throughout the hospital opened for inspectors to gain access to exterior window components above the basement and first floor levels. This effort was further enhanced by the Window Demolition Pilot Study (Pilot Study), which provided unlimited access to representative window systems.

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

35% Hazardous Material Design Submittal July 12, 2019

• In many situations, the inspector noted paint over interior window caulk. This ultimately changes the appearance of the material and makes it difficult for the inspector to classify the specific caulking material and color. This effort was further enhanced by the Window Demolition Pilot Study (Pilot Study), which provided unlimited access to representative window systems.

Prior to the survey, it was reported that 1,050 windows located in Wings A through E were to be considered for replacement. Wing A represents the original structure constructed in the 1950s with later additions B through E. Numerous rehabilitations have been constructed within the A, B, and C wings but a full history of window replacements was not available. Based on the age of the facility, prior survey results, and potential methodology of contract work, anticipated suspect materials included interior and exterior window caulks and seals, framing caulks, glazing, waterproofing, mastics, plaster, and Lead Based Paint (LBP) on window components or adjacent materials. Ceiling Grid systems and drywall material were deemed not to be ACM according to prior surveys. It was not well understood to what extent elevations above ceiling grid would be impacted by window removal, which shall be further defined during the ensuing design phases of The Project.

During assessment of existing field conditions (see 15% submittal) it was determined that a proper and adequate assessment of older windows systems must include an invasive/destructive inspection of concealed window systems, particularly in older building wings such as A & B Wings, whereby newer window system treatments (i.e. aluminum cladding) are commonly installed over remnants of original construction, including components those commonly exhibiting lead based paint and/or asbestos containing caulking/glazing components, leaving them concealed and otherwise undefined. While such a window system may already exhibit exposed environmental risk factors, thus requiring remediation prior to new construction to some extent, the existence of concealed lead/asbestos building materials is likely to present significant additional impacts to construction budget estimates and schedules. As such, the Riverfront inspection team, with substantial assistance from the VA, identified a representative set of window systems from both A Wing and B Wing for proper inspection, including destructive disassembly as necessary, to provide full access for visual assessment and additional bulk sampling. Such an inspection, also referred to herein as the Pilot Study, was carried out on June 26, 2019 under the direction of Riverfront representative Mr. Justin R. Rhyneer, CIH, with assistance from two Missouri Licensed asbestos abatement workers (see Attached for details).

This report summarizes the asbestos and lead-related issues identified with existing conditions for this project. The sampling results have been summarized in Tables 1 and 2, with the laboratory analytical report and sample chain of custody contained in Appendix A and B.

2.0 Scope of Work

Riverfront provided an AHERA/EPA trained Asbestos and Lead Inspector/Risk Assessor to perform the following:

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

- Perform an initial non-destructive survey to identify the presence, location, quantity, appearance, and condition of all suspect building materials within the VAJC Medical Center Building 1 in St. Louis, MO identified by the VA as likely to be impacted during removal and reinstallation of approximately 1,050 exterior/perimeter window units. Standard EPA/AHERA field sampling methods were employed to ensure representative sample collection during this initial assessment effort.

- Identify principal locations where ceiling grid will be removed to allow for project work and access hazardous material potential.

- Identify key windows for destructive inspection purposes to access potential presence of additional/concealed asbestos containing caulking, waterproofing, and lead containing materials inaccessible during the initial survey.

- Provide a Missouri Licensed Abatement Contractor (Talbert ICS, Inc.) to demolish and remediate window systems within a negative pressure mini containment (built by VA for use by A/E) to expose potentially concealed original window framing systems in A & B Wings (oldest wings with original window systems likely concealed). Windows selected for removal by the VA and Riverfront for this Pilot Study included one window each in Rooms A904 and B015, considered to be representative of all window systems/units within A & B Wings, respectively. During this Pilot Study, the inspector was to obtain a representative number of samples of concealed suspect building materials, if any, from A & B wing window units likely to be disturbed by future window replacement. Following removal, using manual wet methods only, ensure the Abatement Contractor shall properly dispose of window component waste as asbestos containing materials. Thoroughly clean containments that will be subject to asbestos (PCM) and lead air clearance sampling. Once clearance inspection and air sampling has been conducted and passed using EPA/MDNR/VA thresholds, the VA was to tear down containments.

3.0 Limited Inspection Results

Asbestos Containing Materials - Inspection Results

All suspect asbestos materials sampled were classified as a miscellaneous (e.g., adhesives, caulks, seals, and glazing) or surfacing material in the case of plaster skim coat wrap (unique to windows in stairwells). After classifying the suspect material, homogeneous materials (areas of uniform color, texture, and general appearance) were delineated. The number of samples collected from each area varied based on the classification of the material and increased as the potential for a non-uniform mixture of asbestos in the material increased. Typically, three samples per homogeneous area were collected, with less collected in the event of limited access to homogenous material areas. Sampling locations were chosen to be representative of the accessible materials and collected randomly from all accessible areas of the building where material was available without destructive collection procedures. All sampling procedures were conducted using guidelines established by the EPA. Samples were analyzed using polarized light microscopy (PLM) analysis with dispersion staining (DS) according to U.S. Environmental

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Protection Agency (EPA) Method 600 IR-93/116 which is presently recommended by the EPA.

Asbestos Containing Materials are defined by the EPA as having greater than 1% asbestos as measured by PLM methods.

Riverfront collected a total of 177 representative samples of suspected asbestos-containing materials related to proposed removal and reinstallation of windows in Building 1, A-E Wings.

All samples were transferred via written chain-of-custody, to EMSL, an AIHA & NVLAP accredited laboratory, for analysis. Sampled indoor and outdoor building materials included plaster wrap skim coat, sill adhesive, window seals, caulks, expansion caulks, glazing, and frame seals. The suspect materials, which were similar in general appearance and age of construction, were grouped into homogeneous material sets and sampled.

Eleven material groups tested positive as asbestos-containing materials (ACM) during this survey and will be affected by the project scope. The material groups are as follows:

• Black Textured Interior Window Caulk (exposed) bulk sample results were positive, containing 3-6% Chrysotile asbestos. The estimated quantity of known affected material was approximately 4,860 lineal feet (~ 18 LF per window x 270 windows). This black texture caulk was in good pliable condition and located at interior seams of some perimeter windows (wood to metal; wood to plaster; metal to metal).

The black textured caulk was used on numerous windows throughout (A.1, B.1, A.2, &, B.2 types) but appeared to be limited to Wings A and B. This window caulk is predominately located in Wing B with limited locations in Wing A, and not observed in Wings C-E whatsoever. Similar black textured caulk (newer black textured caulking) was sampled in Wing C and was “none-detected” (i.e. negative) for asbestos and should not be confused with that of A & B Wing as it had less texture and exhibited more of a “shiny finish” than the asbestos-containing homogenous material. An additional caulk is existing or co-existing in some locations and is recognized as shiny, pliable, nontextured black caulk that is non-detected for asbestos throughout.

The number of window locations where asbestos-containing black textured asbestos caulk exists is yet unknown. Many rooms with exterior windows were unavailable for inspection due to patient restrictions or covered by paint. It is unknown if this black textured caulk exists on wood window mouldings behind drywall surrounds in remolded areas (window types C & D) and/or orphaned windows behind new walls in the A & B wings, and cannot be reliably determined without room-by-room destructive inspections.

• Tan Exterior Caulk (concealed original construction) bulk sample results were positive, containing 6% Chrysotile asbestos. The estimated quantity of likely affected material is approximately 4,860 lineal feet (~ 18 LF per window x 270 windows). This concealed tan exterior caulk on window seams was discovered during the Pilot Study window removal process as being in very poor condition (due to historical weathering) and located at exterior seams (where wood/brick meet) of what should be presumed on all perimeter windows located in B Wing.

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

• Black/Brown Exterior Caulk on Aluminum Frame bulk sample results were positive, containing 3-5% Chrysotile asbestos. The estimated quantity of known affected material was approximately 4,860 lineal feet (~ 18 LF per window x 270 windows). This black exterior caulk on aluminum frames was discovered during the Pilot Study window removal process and was generally observed in good condition and located along the exterior aluminum/brick seams of what should be assumed on all perimeter windows located in B Wing.

• Brown Interior Caulk on Bottom Aluminum Trim (concealed original construction) bulk sample results were positive, containing 4% Chrysotile asbestos. The estimated quantity of known affected material was approximately 990 lineal feet (44” per window x 270 windows). This concealed brown interior caulk on bottom aluminum trim was discovered during the Pilot Study window removal processes in good condition and located along the aluminum to wood window sill interior seam and should be assumed present on all perimeter windows located in B Wing.

• Brown Interior Caulk on Aluminum Frame (concealed) bulk sample results were positive, containing 5% Chrysotile asbestos. The estimated quantity of known affected material was approximately 4,860 lineal feet (~ 18 LF per window x 270 windows). This brown interior frame caulk on aluminum framing was generally in good condition and located along the aluminum to wood interior seams of what should be assumed on all perimeter windows located in B Wing. The concealed brown interior frame caulk on aluminum framing was discovered during Pilot Study window removal processes.

• White Frame Caulk on Original Wood Window Framing bulk sample results were positive, containing 9% Chrysotile asbestos. The estimated quantity of known affected material was approximately 4,860 lineal feet (~ 18 LF per window x 270 windows). This white frame caulk on window was in good condition and located along the wood/brick interior seams of what should be assumed on all perimeter windows located in B Wing.

The concealed white frame caulk was discovered during window removal processes.

• Off-White Frame Caulk at Bottom Sill bulk sample results were positive, containing 6% Chrysotile asbestos. The estimated quantity of known affected material was approximately 990 lineal feet (44” per window x 270 windows). This off-white frame caulk was in good condition and located at the bottom of the window sill interior seams of what should be assumed on all perimeter windows located B Wing. The concealed off-white frame caulk was discovered during window removal processes.

• Beige Exterior Caulk (outer seam) bulk sample results were positive, containing 6-7%

11,700 lineal feet (18 LF per window x 650 units). This beige exterior caulk was in poor condition and located along the wood/brick exterior seams of what should be assumed on all perimeter windows located in A Wing. The concealed beige exterior caulk was discovered during window removal processes.

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

• Beige Exterior Caulk, Inner Bead, bulk sample results were positive, containing 7%

2,384 lineal feet (44” per window sill x 650 units). This beige exterior caulk, inner bead, was in poor condition and located along the original wood to stone window sill seams of what should be assumed on all perimeter windows located in A Wing. The concealed beige exterior caulk, inner bead, was discovered during window removal processes.

• Black Caulk Interior Wood Framing bulk sample results were positive, containing 6%

11,700 lineal feet (18 LF per window x 650 units). This black caulk on the interior wood sill was in generally good condition and located at window sill interior seams of what should be assumed on all perimeter windows located in A Wing. The concealed black caulk on the interior wood sill was discovered during window removal processes.

• Brown/Black Exterior Caulk bulk sample results were positive, containing 8% Chrysotile asbestos. The estimated quantity of known affected material was approximately 11,700 lineal feet (18 LF per window x 650 units). This brown exterior caulk was in poor condition and located along the aluminum to brick seams of what should be assumed on all perimeter windows located in A Wing. The brown/black exterior caulk was discovered during window removal processes.

Ceiling Tiles, brick, brick mortar, drywall, drywall joint compound, and general wall plaster were not sampled as a significant number of historic building samples from 1994 Roth Asbestos and Environmental Consultants, 2008 Altec Environmental Consultants & 2018 Riverfront Safety and Health Campus Surveys have shown these materials to be non-detect for asbestos.

It should also be noted that Riverfront utilized previous inspections, including the 2018 Riverfront Safety and Health Facility Re-Inspection, the 2008 Altec Asbestos Assessment as well as 1994 Roth Asbestos and Environmental Consultants Asbestos Survey, to identify ACM Thermal System Insulation above potentially impacted ceiling grids.

A summary of sampling efforts, including sample numbers, descriptions, locations, quantities, category (friable or non-friable) and analytical results are presented in the following Table 1.

The full laboratory analytical reports are included in Attachment A.

TABLE 1: ASBESTOS BULK SAMPLING SUMMARY

Field Sampling on April 30 thru May 6, 2019

Sample No.

Material Description

Sample Location

Category Homogenous Area

Condition Quantity Asbestos Content

Interior Window

Caulk-Brown Pliable

A012 Non- Friable

A Wing Basement Good - None

Detected

Interior Window

Caulk-Brown Pliable

A012 Non- Friable

A Wing Basement Good - None

Detected

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Interior Window

Caulk-Brown Pliable

A012 Non- Friable

A Wing Basement Good - None

Detected

Interior Window

Caulk- Gray Pliable

Near A285

Non- Friable

A Wing Floor 2 Addition Good - None

Detected

Interior Window

Caulk- Gray Pliable

Near A287

Non- Friable

A Wing Floor 2 Addition Good - None

Detected

Interior Window

Caulk- Gray Pliable

Near A287

Non- Friable

A Wing Floor 2 Addition Good - None

Detected

7 Interior Glazing- Foam A285 Non-

Friable A Wing Floor

2 Addition Good - None Detected

8 Interior Glazing- Foam A284 Non-

Friable A Wing Floor

2 Addition Good - None Detected

9 Interior Glazing- Foam A284 Non-

Friable A Wing Floor

2 Addition Good - None Detected

Interior Glazing

Seal- Black Rubbery

Near A287

Non- Friable

A Wing Floor 2 Addition Good - None

Detected

Interior Glazing

Seal- Black Rubbery

Near A285

Non- Friable

A Wing Floor 2 Addition Good - None

Detected

Interior Glazing

Seal- Black Rubbery

Near A285

Non- Friable

A Wing Floor 2 Addition Good - None

Detected

13 Plaster Skim Coat- White

Floor 2 Stairwell

Cat 2 Non-

Friable

A Wing Stairwell 1 Good - None

Detected

14 Plaster Skim Coat- White

Floor 5 Stairwell

Cat 2 Non-

Friable

A Wing Stairwell 1 Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

15 Plaster Skim Coat- White

Floor 8 Stairwell

Cat 2 Non-

Friable

A Wing Stairwell 1 Good - None

Detected

Interior Window

Caulk- White Pliable

Near A467

Non- Friable A Wing Good - None

Detected

Interior Window

Caulk- White Pliable

A400 Non- Friable A Wing Good - None

Detected

Interior Window

Caulk- White Pliable

A943A Non- Friable A Wing Good - None

Detected

Interior Glazing

Seal- Black Rubbery

A438 Non- Friable A Wing Good - None

Detected

Interior Glazing

Seal- Black Rubbery

Floor 5 Stairwell

Non- Friable A Wing Good - None

Detected

Interior Glazing

Seal- Black Rubbery

A543 Non- Friable A Wing Good - None

Detected

Interior Glazing

Seal- Black Rubbery

A623 Non- Friable A Wing Good - None

Detected

Interior Glazing

Seal- Black Rubbery

A727 Non- Friable A Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

A824 Non- Friable A Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

A634 Non- Friable A Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

A123 Non- Friable A Wing Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Interior Window

Caulk- Brown Pliable

A123 Non- Friable A Wing Good - None

Detected

Interior Window

Caulk- Brown Pliable

A540 Non- Friable A Wing Good - None

Detected

Interior Window

Caulk- Brown Pliable

A861 Non- Friable A Wing Good - None

Detected

Interior

Window Caulk- Black Textured

A921 Non- Friable A Wing Good - 3%

Chrysotile

Interior

Window Caulk- Black Textured

A019 Non- Friable A Wing Good - 4%

Chrysotile

Interior

Window Caulk- Black Textured

A436A Non- Friable A Wing Good - 3%

Chrysotile

Interior Window

Caulk- Brown Hard (Typical)

Near A167 Friable A Wing Good - None

Detected

Interior Window

Caulk- Brown Hard (Typical)

A210 Friable A Wing Good - None Detected

Interior Window

Caulk- Brown Hard (Typical)

A407 Friable A Wing Good - None Detected

Interior Window

Caulk- Brown Hard (Typical)

A543 Friable A Wing Good - None Detected

Interior Window

Caulk- Brown Hard (Typical)

A621 Friable A Wing Good - None Detected

Interior Window

Caulk- Brown Hard (Typical)

A763 Friable A Wing Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Interior Window

Caulk- Brown Hard (Typical)

A901 Friable A Wing Good - None Detected

Interior Window

Caulk- Brown Hard (Typical)

10th Floor Friable A Wing Good - None

Detected

Interior Window

Caulk- Brown Hard (Typical)

11th Floor Friable A Wing Good - None

Detected

Exterior Brick Lined Caulk- Brown Pliable

A338 Non- Friable

A Wing- Exterior Good - None

Detected

Exterior Brick Lined Caulk- Brown Pliable

A608 Non- Friable

A Wing- Exterior Good - None

Detected

Exterior Brick Lined Caulk- Brown Pliable

10th Floor

Non- Friable

A Wing- Exterior Good - None

Detected

Exterior Aluminum

Frame Seal- Black Pliable

A338 Non- Friable

A Wing- Exterior Good - None

Detected

Exterior Aluminum

Frame Seal- Black Pliable

A608 Non- Friable

A Wing- Exterior Good - None

Detected

Exterior Aluminum

Frame Seal- Black Pliable

10th Floor

Non- Friable

A Wing- Exterior Good - None

Detected

Exterior

Window Glaze- Black Pliable

A338 Non- Friable

A Wing- Exterior Good - None

Detected

Exterior

Window Glaze- Black Pliable

A608 Non- Friable

A Wing- Exterior Good - None

Detected

Exterior

Window Glaze- Black Pliable

10th Floor

Non- Friable

A Wing- Exterior Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Interior

Window Caulk- Black Textured

B719 Non- Friable B Wing Good ~ 2,000 LF 5%

Chrysotile

Interior

Window Caulk- Black Textured

B315 Non- Friable B Wing Good - 6%

Chrysotile

Interior

Window Caulk- Black Textured

B118 Non- Friable B Wing Good - 6%

Chrysotile

Interior Glazing

Seal- Black Rubbery

B902 Non- Friable B Wing Good - None

Detected

Interior Glazing

Seal- Black Rubbery

B821 Non- Friable B Wing Good - None

Detected

Interior Glazing

Seal- Black Rubbery

B303 Non- Friable B Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

B731 Non- Friable B Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

B320B Non- Friable B Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

B219 Non- Friable B Wing Good - None

Detected

Interior Window

Caulk- Brown Hard

B731 Friable B Wing Good - None Detected

Interior Window

Caulk- Brown Hard

B544 Friable B Wing Good - None Detected

Interior Window

Caulk- Brown Hard

B320 Friable B Wing Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Interior Glazing

Seal- Black Sticky

H109 Non- Friable H109 Good - None

Detected

Interior Glazing

Seal- Black Sticky

H109 Non- Friable H109 Good - None

Detected

Interior Glazing

Seal- Black Sticky

H109 Non- Friable H109 Good - None

Detected

66 Interior Window Caulk- White B534 Non-

Friable B Wing Good - None Detected

67 Interior Window Caulk- White B532 Non-

Friable B Wing Good - None Detected

68 Interior Window Caulk- White B533 Non-

Friable B Wing Good - None Detected

Interior Window

Caulk- Brown Pliable

B907 Non- Friable B Wing Good - None

Detected

Interior Window

Caulk- Brown Pliable

B907 Non- Friable B Wing Good - None

Detected

Interior Window

Caulk- Brown Pliable

B907 Non- Friable B Wing Good - None

Detected

Exterior Brick Lined (Window)

Caulk- Black Pliable

B315 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior Brick Lined (Window)

Caulk- Black Pliable

B537 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior Brick Lined (Window)

Caulk- Black Pliable

B620 Non- Friable

B Wing-

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Exterior

Window Glaze- Black Pliable

B620 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior

Window Glaze- Black Pliable

B537 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior

Window Glaze- Black Pliable

B315 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior Aluminum

Frame Seal- Black Pliable

B315 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior Aluminum

Frame Seal- Black Pliable

B537 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior Aluminum

Frame Seal- Black Pliable

B620 Non- Friable

B Wing- Exterior Good - None

Detected

Exterior Brick Lined

(Window)Caulk- Beige Pliable

B100 Non- Friable

B Wing- I Window Good - None

Detected

Exterior Brick Lined

(Window)Caulk- Beige Pliable

B100 Non- Friable

B Wing- I Window Good - None

Detected

Exterior Brick Lined

(Window)Caulk- Beige Pliable

B100 Non- Friable

B Wing- I Window Good - None

Detected

Interior Window

Caulk- Black Pliable

B410 Non- Friable

B Wing- Pharmacy Good - None

Detected

Interior Window

Caulk- Black Pliable

C614 Non- Friable C Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

C402 Non- Friable C Wing Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Interior Window

Caulk- Black Pliable

C204 Non- Friable C Wing Good - None

Detected

Interior Window Glazing- Black Pliable w/ Foam

C204 Non- Friable C Wing Good - None

Detected

Interior Window Glazing- Black Pliable w/ Foam

C402 Non- Friable C Wing Good - None

Detected

Interior Window Glazing- Black Pliable w/ Foam

C500A Non- Friable C Wing Good - None

Detected

Interior Window Sash Seal- Black

Rubbery C500A Non-

Friable C Wing Good - None Detected

Interior Window Sash Seal- Black

Rubbery C402 Non-

Friable C Wing Good - None Detected

Interior Window Sash Seal- Black

Rubbery C602 Non-

Friable C Wing Good - None Detected

Exterior Window Frame Caulk- Black

Pliable

C402 Non- Friable C Wing Good - None

Detected

Exterior Window Frame Caulk- Black

Pliable

C500A Non- Friable C Wing Good - None

Detected

Exterior Window Frame Caulk- Black

Pliable

C602 Non- Friable C Wing Good - None

Detected

Exterior Glazing

Seal- Black Pliable

C402 Non- Friable C Wing Good - None

Detected

Exterior Glazing

Seal- Black Pliable

C500A Non- Friable C Wing Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Exterior Glazing

Seal- Black Pliable

C602 Non- Friable C Wing Good - None

Detected

Exterior Brick Lined (Window)

Caulk- Dk Brown

C112 Non- Friable

C 112 (1 Window) Good - None

Detected

Exterior Glazing

Seal- Black Pliable

C112 Non- Friable

C 112 (1 Window) Good - None

Detected

Interior Window

Caulk- Black Textured

C112 Non- Friable

C 112 (1 Window) Good - None

Detected

Interior Window Glazing- Black

Rubbery w/foam D201 Non-

Friable D/E Wing Good - None Detected

Interior Window Glazing- Black

Rubbery w/foam H433 Non-

Friable D/E Wing Good - None Detected

Interior Window Glazing- Black

Rubbery w/foam H433 Non-

Friable D/E Wing Good - None Detected

Interior Window

Caulk- Black Pliable

D201 Non- Friable D/E Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

D238 Non- Friable D/E Wing Good - None

Detected

Interior Window

Caulk- Black Pliable

E110 Non- Friable D/E Wing Good - None

Detected

Interior Window Caulk- Black

Textured (newer)

D416 Non- Friable

D Wing- Room D416 Good - None

Detected

Interior Window Caulk- Black

Textured (newer)

D416 Non- Friable

D Wing- Room D416 Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Interior Window Caulk- Black

Textured (newer)

D416 Non- Friable

D Wing- Room D416 Good - None

Detected

Interior Window Sill Adhesive-

Beige D414 Non-

Friable D/E Wing Good - None Detected

Interior Window Sill Adhesive-

Beige D414 Non-

Friable D/E Wing Good - None Detected

Interior Window Sill Adhesive-

Beige D414 Non-

Friable D/E Wing Good - None Detected

Interior Window

Caulk- Clear Pliable

H433 Non- Friable D/E Wing Good - None

Detected

Interior Window

Caulk- Clear Pliable

H433 Non- Friable D/E Wing Good - None

Detected

Interior Window

Caulk- Clear Pliable

D201 Non- Friable D/E Wing Good - None

Detected

Exterior Glazing

Seal- Black Pliable

Northwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Glazing

Seal- Black Pliable

Southwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Glazing

Seal- Black Pliable

Southeast

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Expansion

Caulk, Conc.

Line- Black

Northwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Expansion

Caulk, Conc.

Line- Black

Northwest

Non- Friable

D/E Wing-

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Exterior Expansion

Caulk, Conc.

Line- Black

Northwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Frame Caulk- Black

Pliable

Southwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Frame Caulk- Black

Pliable

Southeast

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Frame Caulk- Black

Pliable

Northwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Expansion

Caulk, Conc.

Line- Gray

Southwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Expansion

Caulk, Conc.

Line- Gray

Southwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Expansion

Caulk, Conc.

Line- Gray

Southwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Window Caulk, Brick Line- Black

Northwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Window Caulk, Brick Line- Black

Southwest

Non- Friable

D/E Wing- Exterior Good - None

Detected

Exterior Window Caulk, Brick Line- Black

Southeast

Non- Friable

D/E Wing- Exterior Good - None

Detected

Notes:

1) Positive ACM samples are noted in bold type.

2) An asbestos-containing material is defined as a material that contains greater than 1% asbestos.

3) A friable asbestos-containing material is a material than can be pulverized, crumbled or reduced to powder by hand pressure. Likewise, a non-friable asbestos-containing material is a material than cannot be pulverized, crumbled or reduced to powder by hand pressure.

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

TABLE 2: ASBESTOS BULK SAMPLING SUMMARY

Pilot Study Window Removal Field Sampling 06/26/19 Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Tan Exterior Caulk on

Window Frame (Wood/Masonry)

B015 Window Friable B-Wing Damaged;

Friable - 6% Chrysotile

Tan Exterior Caulk on

Window Frame (Wood/Masonry)

B015 Window Friable B-Wing Damaged;

Friable - Positive Stop

Tan Exterior Caulk on

Window Frame (Wood/Masonry)

B015 Window Friable B-Wing Damaged;

Friable - Positive Stop

Black Exterior Caulk on

Aluminum Frame

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - 3% Chrysotile

Black Exterior Caulk on

Aluminum Frame

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

Black Exterior Caulk on

Aluminum Frame

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

Beige Caulk on Interior Quarter

Round

B015 Window

CAT1-

non-friable B-Wing Good - None

Detected

Beige Caulk on Interior Quarter

Round

B015 Window

CAT1-

non-friable B-Wing Good - None

Detected

Beige Caulk on Interior Quarter

Round

B015 Window

CAT1-

non-friable B-Wing Good - None

Detected

Brown Interior

Caulk on Bottom Aluminum Trim

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - 4% Chrysotile

Brown Interior Caulk on Bottom Aluminum Trim

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

Brown Interior Caulk on Bottom Aluminum Trim B015

Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Brown Interior Caulk on

Aluminum Frame

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - 5% Chrysotile

Brown Interior Caulk on

Aluminum Frame

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

Brown Interior Caulk on

Aluminum Frame

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

White Interior Frame Caulk on Original Wood

Windows

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - 9% Chrysotile

White Interior Frame Caulk on Original Wood

Windows

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

White Interior Frame Caulk on Original Wood

Windows

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

Off-white Frame Caulk on Bottom of Window

B015 Window

CAT1-

non-friable B-Wing Good; Non-

Friable - 6% Chrysotile

Off-white Frame Caulk on Bottom of Window B015

Window

CAT1-

nonfriable B-Wing Good; Non- Friable - Positive

Stop

Off-white Frame Caulk on Bottom of Window B015

Window

CAT1-

non-friable B-Wing Good; Non-

Friable - Positive Stop

White Interior

Frame Caulk on Bottom of Frame

B015 Window

CAT1-

non-friable B-Wing Good - None

Detected

White Interior Frame Caulk on Bottom of Frame

B015 Window

CAT1-

non-friable B-Wing Good - None

Detected

White Interior Frame Caulk on Bottom of Frame

B015 Window

CAT1-

non-friable B-Wing Good - None

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Beige Exterior Caulk on Exterior

Brick/Wood

B015 Window

CAT1-

non-friable B-Wing Damaged;

Friable - 7% Chrysotile

Beige Exterior Caulk on Exterior

Brick/Wood

B015 Window

CAT1-

non-friable B-Wing Damaged;

Friable - Positive Stop

Beige Exterior Caulk on Exterior

Brick/Wood

B015 Window

CAT1-

non-friable B-Wing Damaged;

Friable - Positive Stop

Black Caulk at Aluminum frame on Exterior

Wood/Brick

A904 Window

CAT1-

non-friable A Wing Good; Non-

Friable - 5% Chrysotile

Black Caulk at Aluminum frame on Exterior

Wood/Brick

A904 Window

CAT1-

non-friable A Wing Good; Non-

Friable - Positive Stop

Black Caulk at Aluminum frame on Exterior

Wood/Brick

A904 Window

CAT1-

non-friable A Wing Good; Non-

Friable - Positive Stop

Black Caulk

Interior Wood Framing

A904 Window

CAT1-

non-friable A Wing Good; Non-

Friable - 6% Chrysotile

Black Caulk

Interior Wood Framing

A904 Window

CAT1-

non-friable A Wing Good; Non-

Friable - Positive Stop

Black Caulk

Interior Wood Framing

A904 Window

CAT1-

non-friable A Wing Good; Non-

Friable - Positive Stop

Beige Outer Caulk on Exterior

Wood/Brick

A904 Window Friable A Wing

Significantly Damaged;

Friable

- 6%

Chrysotile

Beige Outer Caulk on Exterior

Wood/Brick

A904 Window Friable A Wing

Significantly Damaged;

Friable

- Positive

Stop

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Material

Description Sample

Location Category Homogenous

Area Condition Quantity Asbestos

Content

Beige Outer Caulk on Exterior

Wood/Brick

A904 Window Friable A Wing

Significantly Damaged;

Friable

- Positive

Stop

Beige (painted white) Exterior

Caulk Inner bead on Exterior

Wood/Brick

A904 Window Friable A Wing

Significantly Damaged;

Friable

- 7%

Chrysotile

Beige (painted white) Exterior

Caulk Inner bead on Exterior

Wood/Brick

A904 Window Friable A Wing

Significantly Damaged;

Friable

- Positive

Stop

Beige (painted white) Exterior

Caulk Inner bead on Exterior

Wood/Brick

A904 Window Friable A Wing

Significantly Damaged;

Friable

- Positive

Stop

40 Brown/Black Exterior Caulk

A904 Window Friable A Wing Damaged;

Friable - 8% Chrysotile

41 Brown/Black Exterior Caulk

A904 Window Friable A Wing Damaged;

Friable - Positive Stop

42 Brown/Black Exterior Caulk

A904 Window Friable A Wing Damaged;

Friable - Positive Stop

43 Black Flash Paper A904 Window

CAT1-

non-friable A Wing Good - None

Detected

44 Black Flash Paper A904 Window

CAT1-

non-friable A Wing Good - None

Detected

45 Black Flash Paper A904 Window

CAT1-

non-friable A Wing Good - None

Detected

Notes:

1) Positive ACM samples are noted in bold type.

2) An asbestos-containing material is defined as a material that contains greater than 1% asbestos.

3) A friable asbestos-containing material is a material than can be pulverized, crumbled or reduced to powder by hand pressure. Likewise, a non-friable asbestos-containing material is a material than cannot be pulverized, crumbled or reduced to powder by hand pressure.

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Lead Based Painted Window Components & Potential Associated Impacted Material Results

A targeted lead inspection was performed on representative indoor window assemblies to identify lead-based painted components and/or lead-based glazing on primary substrates potentially impacted by project work. Typical window trim, where existing, included sills, wood moulding, and quarter round. The typical window pieces had aluminum covering (black anodized) over stiles, rails, jambs, and sills. Primary adjacent substrates included painted plaster, drywall, historic metal moulding, glazed ceramic tiles, glazed ceramic blocks, and/or brick.

Window treatments which included window films on glass and valances were not surveyed.

Riverfront collected lead readings from window components and targeted surfaces to identify the presence of lead-based paint (LBP), which is defined by the EPA as greater than or equal to 1.0 mg/cm2 lead by surface loading (as tested by an XRF instrument). EPA/HUD compliant XRF (X- Ray Fluorescence) sampling methods, which are non-destructive, were employed for this project assessment. Note that lead glazing finishes on ceramic tiles and blocks have been tested in the same manner as painted surfaces, with results held to the same standard of lead mass loading of

1.0 mg/cm2.

It is stressed that this sampling was intended to identify the presence of lead-based paint and/or lead glazed tiles and blocks within readily accessible areas of the building likely to become disturbed during future window removal and associated with this particular project design, and not necessarily an EPA-HUD type “surface-by- surface” inspection. Readings were collected by an EPA-HUD trained Lead Inspector/Risk Assessor.

An attempt was made to sample each paint color on indoor wood window components, where accessible, in functional areas within the building Wings. Painted window components for a given window were generally the same color with a different color presented on the adjacent wall substrate. Wood trim was not observed outside, all surfaces appeared to be black metal covering over stiles, rails, jambs, and sills and readings were not collected.

Wing A

Indoor testing locations and XRF results are contained in Table 2. The primary type or assumed to be aged (Typical) window has wood vertical moulding, header moulding, quarter round, and slanted sill (A.1, A.2, B.1, B.2) where one or all of these components contain lead-based paint.

Within areas where floor spaces have been remodeled, some window types have visible lead-based wood moulding (A.3 & B.3). It was not apparent whether underlying lead based painted wood mouldings, sills, or ceramic tiles exist behind the new Faux Drywall surrounds at C.3 and D.3 locations. In approximately 12 locations, exterior painted steel cages were not accessible however should be assumed to be have a lead-based paint. Visual observation suggested that the lead paint film, where component readings were positive for lead, likely exists beneath the current paint color as suggested by multilayer paint observed in chipped locations. A total of 390 XRF measurements, including 13 measurements for QA/QC purposes were collected from painted surfaces and/or suspect lead-containing materials likely to be

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division impacted by project work. These measurements represent approximately 97 windows and 179 readings were considered to be lead based paint or ceramic glaze. Paint condition on window components were noted to be intact with the exceptions of Level 10 Mechanical Room, Hall near 837, A837, and A014 where the paint is deteriorated.

Additional sampling occurred during the Pilot Study window removal process that took place in Room A904. Remediation processes exposed original painted wood window components which were then tested for lead based paint using the same procedures and guidelines previously mentioned. Additional testing proved that interior concealed wood window components are considered lead-based paint containing and should be assumed present throughout A Wing for all window types.

Wing B

Indoor testing locations and XRF results are contained in Table 2. The primary type or assumed to be aged (Typical) window had wood vertical moulding, header moulding, quarter round, and slanted sill (A.1, A.2, B.1, B.2) where one or all of these components contain lead-based paint. Within areas where floor spaces have been remodeled, some window types have visible lead-based wood moulding (A.3 & B.3). It was not apparent whether underlying lead based painted wood mouldings, sills, or ceramic tiles exist behind the new Faux Drywall surrounds at C.3 and D.3 locations. Visual observation suggested that the lead paint film, where component readings were positive for lead, likely exists beneath the current paint color as suggested by multilayer paint observed in chipped locations. A total of 187 XRF measurements, including 18 measurements for QA/QC purposes were collected from painted surfaces and/or suspect lead-containing materials likely to be impacted by project work. These measurements represent approximately 44 windows and 95 readings were considered to be lead based paint or ceramic glaze.

Additional sampling occurred during the Pilot Study window removal process that took place in Room B015. Remediation processes exposed original painted wood window components which were then tested for lead based paint using the same procedures and guidelines previously mentioned. Additional testing proved that interior concealed wood window components are considered lead-based paint containing and should be assumed present throughout B Wing for all window types.

Wing C

Indoor testing locations and XRF results are contained in Table 2. The primary type or assumed to be aged (Typical) window was not observed in C Wing at the time of the inspection.

Limitations may have inhibited the observation of such typical windows that could contain lead based paint components. It was not apparent whether underlying lead based painted wood mouldings, sills, or ceramic tiles exist behind the new Faux Drywall surrounds at J.3, L.3, M.3 and N.3 locations. A total of 49 XRF measurements, including 15 measurements for QA/QC purposes were collected from painted surfaces and/or suspect lead-containing materials likely to be impacted by project work. These measurements represent approximately 11 windows and 0 readings were considered to be lead based paint or ceramic glaze.

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Wing D/E

Indoor testing locations and XRF results are contained in Table 2. The primary type or assumed to be aged (Typical) window was not observed in D/E Wing at the time of the inspection.

Limitations may have inhibited the observation of such typical windows that could contain lead based paint components. It was not apparent whether underlying lead based painted wood mouldings, sills, or ceramic tiles exist behind the new Faux Drywall surrounds at L.3, M.3 and H.3 locations. A total of 38 XRF measurements, including 15 measurements for QA/QC purposes were collected from painted surfaces and/or suspect lead-containing materials likely to be impacted by project work. These measurements represent approximately 8 windows and 0 readings were considered to be lead based paint or ceramic glaze.

A summary of lead results for each Wing of Building 1 is provided below:

TABLE 3: LEAD XRF SAMPLING SUMMARY

Field Sampling on April 30, thru May 3, 2019

Sample No.

Floor Area

Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

348 Calibration Calibration Standard 1.1

(acceptable)

349 11 Mechanical South Window Apron Wood Intact White 7.6

350 11 Mechanical South Molding Wood Intact White 7.5

351 11 Mechanical South Quarter Round Wood Intact White 5.2

352 11 Mechanical South Brick Wall Brick Intact White 0.3

353 11 Mechanical South Metal Jam Cover Metal Intact Brown 0.3

354 10 Mechanical West Window Apron Wood Det. Dark Gray 6.9

355 10 Mechanical West Molding Wood Det. Dark Gray 2.2

356 10 Mechanical West Quarter Round Wood Det. Dark Gray 4.5

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Floor Area

Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

357 10 Mechanical West Metal Sill Cover Metal Intact Brown 0.3

358 10 Mechanical West Brick Wall Brick Intact Sand Stone 0

359 10 Stairwell South Window Sill/Slanted Wood Intact White 2.2

360 10 Stairwell South Molding Wood Intact White 1.4

361 10 Stairwell South Quarter Round Wood Intact White 6.1

362 10 Stairwell South Wall Plaster Intact White 0

363 10 Mechanical South Window Apron Wood Intact Dark Gray 7.6

364 10 Mechanical South Molding Wood Intact Dark Gray 3.3

365 10 Mechanical South Quarter Round Wood Det. Dark Gray 5.4

366 9 A921 South Molding Wood Intact Aqua 1.1

367 9 A921 South Metal Frame/Sill Area Metal Intact Aqua 0.6

368 9 A921 South Metal Frame Metal Intact Aqua 2

369 9 A920 South Molding Wood Intact Gray 0.9

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Floor Area

Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

370 9 A920 South Metal

Frame/Horizontal Frame

Metal Intact Gray 0.7

371 9 A920 South Metal

Frame/Vertical Sill

Metal Intact Gray 0.4

372 9 Stairwell 1 South Molding Skim Coat Intact Gray 0

373 9 Stairwell 1 South Window Sill Skim Coat Intact Gray 0

374 9 Stairwell 1 South Wall Plaster Intact Gray -0.4

375 9 A912 West Window Sill Slanted Wood Det. White 1.7

376 9 A912 West Molding Wood Intact White 1.2

377 9 A912 West Quarter Round Wood Intact White 1.4

378 9 A912 West Wall Plaster Intact White 0.1

379 9 A909 West Wood Sill Wood Intact Off White 1.5

380 9 A909 West Molding Wood Intact Off White 1.5

381 9 A909 West Quarter Round Wood Intact Off White 1.8

382 9 A909 West Wall Plaster Intact Off White 0

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Floor Area

Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

383 9 A908B East Window Sill/Slanted Wood Intact Tan 2.1

384 9 A908B East Molding Wood Intact Tan 1.1

385 9 A908B East Quarter Round Wood Intact Tan 1.2

386 9 A908B East Wall Plaster Intact Tan 0

387 9 A901 East Window Sill/Slanted Wood Intact White 4.1

388 9 A901 East Molding Wood Intact White 1.3

389 9 A901 East Quarter Round Wood Intact White 1.9

390 9 A901 East Metal Casing Metal Intact Black, Wrap 0.2

391 9 A936B West Molding Wood Intact White 1.3

392 9 A936B West Window Sill Wood Intact White -0.1

393 9 A936B West Wall Drywall Intact White -0.1

394 9 A938B East Molding Wood Intact White 4

395 9 A938B East Window Sill Wood Intact White -0.2

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Floor Area

Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

396 9 A938B East Wall Drywall Intact White 0

397 9 A927 North Window Sill/Slanted Wood Intact Gray 1.9

398 9 A927 North Molding Wood Intact Gray 1.5

399 9 A927 North Quarter Round Wood Intact Gray 2

400 9 A926 North Window Sill Wood Intact Gray 0.5

401 9 A926 North Molding/Vertical Wood Intact Gray 1.2

402 9 A926 North Metal Frame/Vertical Metal Intact Gray -0.2

403 9 A926 North Metal

Frame/Vertical Sill

Metal Intact Gray 0.6

404 9 A926 West Window Sill Wood Intact Gray 0.6

405 9 A908A East Window Sill Drywall Intact White 0.1

406 9 A908A East Vertical Drywall Intact White -0.2

407 9 A908A East Metal Trim Metal Intact White 0.2

408 8 A832 South Metal Sill Metal Intact White 0.8

VA Project Number 657-19-110JC VA St. Louis Healthcare System, John Cochran Division

Sample

No.

Floor Area

Sample Location

Side Component Substrate Condition Color Result (mg/cm²)

409 8 A832 South Vertical Metal Frame Metal Intact White 1.7

410 8 A832 South Molding Wood Intact White 2.5

411 8 Hall North Metal Frame Metal Intact Brown 0.5

412 8 Hall North Metal Frame Vertical Metal Intact Brown 2.5

413 8 Hall North Molding Wood Intact Brown 1.3

414 8 Stair 1 South Vertical Skim Coat Plaster Intact Off White -0.1

415…