Text version

UE

OE

M/G 400A/3P

M/G 400A/3P

C

PC

R

TS

T

100/3

100/3/70

100/3/70/1

100/3/CB

PP

J

GF

OR

OR

OR

EPO

AM

VM

DM

ST

KK

GFR

M

SPD

R

CU

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL, TECHNOLOGY OR FIRE ALARM

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL REFERENCE

SECTION CUT DESIGNATION

ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)

LP1

A1

LIGHT FIXTURE, CEILING MOUNTED

a

LIGHTING TRACK WITH TRACK LIGHT FIXTURES

LIGHT FIXTURE, POLE MOUNTED

LIGHT FIXTURE, WALL MOUNTED

EMERGENCY BATTERY PACK LIGHT FIXTURE,

WALL MOUNTED

EMERGENCY BATTERY PACK LIGHT FIXTURE,

CEILING MOUNTED

EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED

EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED

EMERGENCY LIGHT FIXTURE, CEILING MOUNTED

A1E a

A1 a

A1

A1

X1E

X1E

Y1E

Y1E

HOMERUN TO PANELBOARD, ARROWS INDICATE

NUMBER OF CIRCUITS, TICK MARKS INDICATE

NUMBER OF CONDUCTORS. DESIGNATIONS ARE

PANELBOARD AND CIRCUIT NUMBERS.

UNSWITCHED HOT CONDUCTORS SHOWN LEADING

NEUTRAL CONDUCTOR

NEUTRAL CONDUCTOR

SWITCHED HOT CONDUCTORS SHOWN TRAILING

GROUND CONDUCTOR

EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY

ISOLATED GROUNDING CONDUCTOR IN RACEWAY

CONCEALED RACEWAY

EXPOSED RACEWAY

RACEWAY TURNING DOWN

RACEWAY TURNING UP

EQUIPMENT TERMINATION

LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)

LIGHT FIXTURE, BOLLARDA1

RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, SPECIAL PURPOSE

RECEPTACLE, TWIST-LOCK

RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO

RECEPTACLE, MOUNTED 6" ABOVE COUNTER,

TYPE AS INDICATED ABOVE

RECEPTACLE DESIGNATIONS AS FOLLOWS:

SWITCH, SINGLE POLE

SWITCH DESIGNATIONS AS FOLLOWS:

OCCUPANCY SENSOR, CEILING MOUNTED

POWER PACK FOR LIGHTING CONTROL

JUNCTION BOX

RECEPTACLE ON EMERGENCY POWER

RECEPTACLE, ISOLATED GROUND TYPE

MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,

NEMA 5-20R, UNO

SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION

PANELBOARD ON HOUSEKEEPING PAD

PANELBOARD, RECESS MOUNTED

PANELBOARD, SURFACE MOUNTED

TRANSFORMER

DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES

AMPERES/POLES, CB = CIRCUIT BREAKER TYPE

DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES

AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE

COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER

100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER

SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,

3-POLE, UNO

CONTACTOR

PHOTOCELL

RELAY

TIME SWITCH

LOW-VOLTAGE TRANSFORMER

PUSH BUTTON, TYPE AS NOTED

VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH

100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,

NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

UNDERGROUND ELECTRIC LINE

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

CABINET, RECESS MOUNTED

CABINET, SURFACE MOUNTED

RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT

INTERRUPTER, NEMA 5-20R, UNO

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

OVERHEAD ELECTRIC LINE

MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED

PLAN NOTE CALL OUT

TRANSFER SWITCH, RATINGS AS INDICATED

ATS = AUTOMATIC TRANSFER SWITCH

TX#

600AF

3P

500AT

400AS

3P

225AF

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, NON-SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

DRAWOUT CIRCUIT

BREAKER, RATINGS

AS INDICATED

600AF

3P

500AT

CIRCUIT BREAKER,

RATINGS AS

INDICATED

LPS-R

FUSED DISCONNECT

SWITCH, RATINGS

AS INDICATED

400AS

3P

225AF

LPS-R

COMBINATION FUSED

SWITCH AND STARTER,

RATINGS AS

PANELBOARD,

SINGLE-SECTION,

RATINGS PER

SCHEDULES

PANELBOARD,

MULTI-SECTION,

RATINGS PER

SCHEDULES

NEMA 1

AMMETER

VOLTMETER

COMBINATION DIGITAL

SHUNT-TRIP RELAY

KIRK-KEY INTERLOCK

GROUND-FAULT RELAY

UTILITY METER

RELAY

SURGE PROTECTION

AMMETER/VOLTMETER

DEVICE

AUTOMATIC TRANSFER SWITCH WITH BYPASS

TYPE AND RATINGS AS INDICATED

VARIABLE FREQUENCY

DRIVE WITH

DISCONNECT, RATINGS

GROUND CONNECTION

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

GROUND CONNECTION

WITH TEST WELL

CONTACT, OPEN

CONTACT, CLOSED

MOTOR

FEEDER TAGCAPACITOR

SURGE ARRESTER

HEATER

225A 3P

NEMA 1

INDICATED

COMBINATION CIRCUIT

BREAKER AND

STARTER, RATINGS AS

INDICATED AS INDICATED

225A 3P

200A 3P

ATS#

200A 3P

ATS#

TRANSFORMER

TX#

TRANSFORMER,

SHIELDED

200A DEAD-FRONT ELBOW

600A DEAD-FRONT ELBOW

DEAD-FRONT SPLITTER

FAULT INDICATOR

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CABLE CONNECTION

LIGHTNING PROTECTION GROUND ROD

LIGHTNING PROTECTION CONDUCTOR

MTS = MANUAL TRANSFER SWITCH

EP-101

EP-101

LIGHTNING PROTECTION SYMBOLS

ELECTRICAL ONE-LINE DIAGRAM SYMBOLS

M (CONT'D)

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

OS# = CEILING MOUNTED OCCUPANCY SENSOR,

REFER TO OCCUPANCY SENSOR SCHEDULE

2 = TWO-POLE WALL SWITCH

3 = THREE-WAY WALL SWITCH

4 = FOUR-WAY WALL SWITCH

D = DIMMER SWITCH

OS# = OCCUPANCY SENSOR WALL SWITCH, REFER

TO OCCUPANCY SENSOR SCHEDULE

P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT

WALL SWITCH

K = KEYED WALL SWITCH

M = MOTOR RATED SWITCH

WP = WEATHER PROOF SWITCH AND COVER

C = CLOCK HANGER

E = EMERGENCY POWER

GF = GROUND FAULT CIRCUIT INTERRUPTER

IG = ISOLATED GROUND

S = SWITCHED

TR = TAMPER RESISTANT

WP = WEATHER PROOF COVER

WR = WEATHER RESISTANT

XP = EXPLOSION PROOF

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULE

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULE

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

= ARROW INDICATES AIMING DIRECTION

LIGHTING SYMBOLS

POWER EQUIPMENT SYMBOLS

WIRING DEVICE SYMBOLS

AUDIBLE APPLIANCES (CENTERLINE) 84"

ALARMS (TOP) 48"

ANNUNCIATOR PANELS (TOP) 48"

CLOCK OUTLETS (CENTERLINE) 84"

CONTROLS (TOP) 48"

EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"

FIRE ALARM BELL (EXTERIOR) 120"

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"

INTERCOM (AFEA ONLY) 36"

INTERCOMS (TOP) 48"

PANELS & PANELBOARDS (TOP) 72"

PULL STATIONS (TOP) 48"

PHOTOCELLS 144"

RECEPTACLES (BOTTOM) 18"

RECEPTACLES, EXTERIOR (BOTTOM) 24"

RECEPTACLES, GARAGES (BOTTOM) 26"

RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"

RECEPTACLES ABOVE COUNTERTOPS (TOP) 44"

REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP) 48"

REMOTE INDICATING LIGHT, FINISHED AREAS (TOP) CEILING

SAFETY SWITCHES & STARTERS 48"

SWITCHES (TOP) 48"

TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"

VISIBLE APPLIANCES (CENTERLINE) 84"

X

W

V

U

T

S

R

CIRCUITING SYMBOLS

ANNOTATION STANDARD MOUNTING HEIGHTS

P

O

N

M

L

K

J

I

H

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

F

E

D

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

C

B

A

ABBREVIATIONS

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

JB JUNCTION BOX

J-BOX JUNCTION BOX

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT

INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

IC INSULATION CONTACT

ES EMERGENCY SHUNT RELAY

USB = DUPLEX RECEPTACLE WITH (2) USB OUTLETS

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL LEGEND

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-E-000

589-A5-19-116

BID DOCUMENTS

Revision # Date

A1

AREA OF DEMOLITION

1314 12 11 10 8 7 6 5.1 4.1

U

T

S

R

Q

P

O

N

M

9 5

A1

10 8 7 6

U

T

S

R

PROJECTS OFFICE

A107

CLEAN STORAGE

A138

DINING/ACTIVITY

A139

NURSE MANAGER

A105

ELEC. CLOSET

A139E

FIRE CLOSET

A139F

WOMEN'S STAFF RESTROOM

A104

CLOSET

A105A

UNIVERSAL WASTE STORAGE

A101A

LOBBY

A101

ENTRY

A100

CORRIDOR

A1-1

MECHANICAL

A140M

NURSE PRACTITIONER

A141

STAFF BREAKROOM

A142

REPORT ROOM

A143

CHART ROOM

A144

TUB ROOM

A170A

SHOWER

A170 RESTROOM

A170B

SOCIAL ROOM

A171

SUPPLY ROOM

A172

DOCK AREA

A173 TRAY DELIVERY

A174

CONFERENCE

A174A

HOUSEKEEPING

A179

MEN

A180

RECREATIONAL THERAPY

A178

SOILED LINEN

A175

STAIR 1

A175A

HOUSEKEEPING

A176

STORAGE

A178A

RESTROOM

A177B

WOMEN'S LOCKER ROOM

A176A

MEN'S LOCKER ROOM

A177

RESTROOM

A175B

CORRIDOR

A1-1

CORRIDOR

A1-1

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL LIGHTING

DEMOLITION PLAN - A WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-ELD101A

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL LIGHTING DEMOLITION PLAN - A WING

ELECTRICAL PLAN NOTES:

1 REMOVE ALL LIGHT FIXTURES, LIGHTING CONTROLS AND

CIRCUIT CONDUCTORS BACK TO THE PANELBOARDS WITHIN THE

AREA OF WORK.

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC AND BASED

OFF OF AVAILABLE INFORMATION AND MAY NOT REPRESENT ALL

DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY

ALL EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF

PROPOSAL.

GENERAL NOTES:

1/8" = 1'-0"2

ELECTRICAL LIGHTING DEMOLITION PLAN - BASEMENT

WING A

BASEMENT

DEDUCT ALTERNATE NOTES:

IF DEDUCT ALTERNATE IS ACCEPTED, OMIT DEMOLITION OF ALL

CIRCUITING, LIGHTING, AND LIGHTING CONTROLS OUTSIDE OF THE

AREA SHOWN. DEMOLISH ALL LIGHTING AND LIGHTING CONTROLS

WITHIN THE AREA SHOWN. TRACE CIRCUIT TO CLOSEST FIXTURE ON

CIRCUIT NOT BEING REMOVED. REMOVE ALL CIRCUITING BACK TO

THIS POINT. IF CIRCUIT ONLY FEEDS LIGHTS BEING DEMOLISHED,

DEMOLISH CIRCUITING BACK TO PANELBOARD AND UPDATE

PANELBOARD TO REFLECT "SPARE".

A1.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

OF WORK AS DEFINED ON ARCHITECTURAL SHEET 6-GI-105.

AREA OF DEMOLITION

12 11 10 8 7 6

L

K

J

H

G

F.1

F

E.1

E

D

C

B

A

5 4 3 2 1

MDS COORDINATOR

A137

HOUSEKEEPING SUPERVISOR

A136

SOCIAL WORKER

A135

DIETICIAN

A134

SUPPLY ROOM

A108

STORAGE

A108A

CORRIDOR

A1-3

PHYSICAL THERAPY

B129

RESTROOM

B126

STORAGE

B129A

KITCHEN

B128

STORAGE

B127

CORRIDOR

DCDR7

ENGINEERING SERVICE

B124

CHIEF ENG. ASSISTANT

B123C

ENGINEERING SERVICE CHIEF

B123B

ENGINEERING SERVICE MANAGER

B123A

ENGINEERING

B123

PROGRAM ANALYST

B122

ENGINEERING ADMINISTRATION

B121

STORAGE

B120

WOMEN STAFF RESTROOM

B118

ELEC. CLOSET

B119

STORAGE

B117

CLINICAL PHARMACIST

B116

OFFICE

B115

OFFICE

B114

OFFICE

B113

OSH MANAGER

B112C

SAFETY & EMERGENCY MGMT

B112B

GEMS COORDINATOR

B112A

PROGRAM SUPPORT ASSIST.

B112

WOMEN STAFF RESTROOM

B110

PALLIATIVE CARE COORD.

B109

PATIENT TRANSFER COORD.

B108C

OFFICE

B108B

ELEC. CLOSET

B108E

STORAGE

B130

STORAGE

B133

PROJECTS OFFICE

A107

CORRIDOR

B1-4

CORRIDOR

B1-4

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL LIGHTING

DEMOLITION PLAN - B WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-ELD101B

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL LIGHTING DEMOLITION PLAN - B WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC AND BASED

OFF OF AVAILABLE INFORMATION AND MAY NOT REPRESENT ALL

DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY

ALL DEMOLITION WORK PRIOR TO SUBMISSION OF PROPOSAL.

GENERAL NOTES:

ELECTRICAL PLAN NOTES:

1 REMOVE ALL LIGHT FIXTURES, LIGHTING CONTROLS, CIRCUIT

CONDUCTORS AND LIGHTING CIRCUIT CONDUIT BACK TO THE

PANELBOARDS WITHIN THE AREA OF WORK.

2 ELECTRICAL CLOSET TO REMAIN UNTIL LIGHTING POWER CAN

BE RELOCATED FOR THE EXISTING PHYSICAL THERAPY ROOM.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

EA

BLANKS

A1 & A2

(ETD)

(ETD)

(ETD)

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

A1

AREA OF DEMOLITION

6E (ETD) EMDB (ETR)

MSB (ETR)

B6S (ETR)

ES

BLANK

(ETD)

(ETD)

(ETD)

MTS

(ETR)

ATS (ETR)

FACP

(ETR)

F/O

(ETR)

EXISTING CONDENSER

WATER PUMP TO BE

DEMOLISHED.

(ETD)

B6

8, 10, 12

ES

(ETD)

EXISTING DOMESTIC WATER

HEATER TO BE DEMOLISHED.

EXISTING MED VACUUM

PUMP TO BE DEMOLISHED.

EXISTING AIR COMPRESSOR

TO BE DEMOLISHED.

EXISTING WATER SOFTENER

TO REMAIN

EXISTING CHILLER TO BE

ABANDONED IN PLACE.

ES

2, 4, 6

B6

20, 22, 24

ES

7, 9, 11

400/3

A1

10 8 7 6

U

T

S

R

CLEAN STORAGE

A138

DINING/ACTIVITY

A139

ELEC. CLOSET

A139E

FIRE CLOSET

A139F

ENG SERVICE

A139S

PROJECTS OFFICE

A107

LOBBY

A101

UNIVERSAL WASTE STORAGE

A101A

MEN

A180

WOMEN

A102

HOUSEKEEPING

A179

WOMEN'S STAFF RESTROOM

A104

MEN'S STAFF RESTROOM

A103

CONFERENCE

A174A

HOUSEKEEPING

A176

SOILED LINEN

A175

WOMEN'S LOCKER ROOM

A176A

MEN'S LOCKER ROOM

A177

CORRIDOR

A1-1

HOUSEKEEPING

A139A

TRAY DELIVERY

A174

DOCK AREA

A173

CLOSET

A105A

NURSE MANAGER

A105

SOCIAL ROOM

A171

STORAGE

A178A

RECREATIONAL THERAPY

A178

MECHANICAL

A140M

SHOWER

A170 RESTROOM

A170B

STAFF BREAKROOM

A142

REPORT ROOM

A143

CHART ROOM

A144

TUB ROOM

A170A

NURSE PRACTITIONER

A141

SUPPLY ROOM

A172

IT CLOSET

C149

RESTROOM

A175B

RESTROOM

A177B

CORRIDOR

A1-2

ENTRY

A100

STAIR 1

A175A

1314 12 11 10 8 7 6 5.1 4.1

U

T

S

R

Q

P

O

N

M

L

9 5

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL POWER DEMOLITION

PLAN - A WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-EPD101A

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL POWER DEMOLITION PLAN - A WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC AND BASED

OFF OF AVAILABLE INFORMATION AND MAY NOT REPRESENT ALL

DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY

ALL EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF

PROPOSAL.

GENERAL NOTES:

ELECTRICAL PLAN NOTES:

1 EXISTING IT ROOM AND EQUIPMENT TO REMAIN. THIS ROOM IS

TO REMAIN OPERATIONAL THROUGHOUT THE PERIOD OF WORK.

EXISTING INFRASTRUCTURE EXTENDING FROM THIS ROOM,

THROUGH B WING AND SERVING OTHER SPACES IS TO REMAIN

INTACT AND OPERATIONAL. PHASE DEMOLITION OF EXISTING

POWER AND PROVISION OF NEW POWER TO MINIMIZE DOWN

TIME. COORDINATE WITH VA COR AND VA OI&T.

2 REMOVE ALL EXISTING ELECTRICAL POWER DEVICES AND

CIRCUIT CONDUCTORS BACK TO THE PANELBOARDS WITHIN

THE AREA OF WORK.

3 REMOVE EXISTING PANELBOARD AND FEEDER BACK TO THE

UPSTREAM DISTRIBUTION EQUIPMENT.

4 EXISTING WALL MOUNTED BAS DATA SWITCH TO REMAIN.

PROTECT EQUIPMENT DURING CONSTRUCTION.

5 EXISTING WALL MOUNTED DATA ENCLOSURE TO REMAIN.

PROTECT EQUIPMENT DURING CONSTRUCTION.

6 EXISTING WALL MOUNTED CAMDEX SECURITY ENCLOSURE TO

REMAIN. PROTECT EQUIPMENT DURING CONSTRUCTION.

7 EXISTING WALL MOUNTED FIBER TERMINATION UNIT TO REMAIN.

PROTECT EQUIPMENT DURING CONSTRUCTION.

1/8" = 1'-0"2

ELECTRICAL POWER DEMOLITION PLAN - BASEMENT

DEDUCT ALTERNATE NOTES:

IF DEDUCT ALTERNATE IS ACCEPTED, OMIT DEMOLITION OF ALL

CIRCUITING, RECEPTACLES, AND OTHER ELECTRICAL DEVICES

OUTSIDE OF THE AREA SHOWN. DEMOLISH ALL CIRCUITS WITHIN

THE AREA SHOWN BACK TO PANELBOARD FED FROM. UPDATE

PANELBOARD SCHEDULE TO REFLECT "SPARE".

A1.

WING A

BASEMENT

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

B1 & B2

BLANKS

EB

EB-1

(ETD)

(ETD)

(ETD)

(ETD)

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD ETD ETD

ETD ETD ETD ETD ETD

ETD ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

AREA OF DEMOLITION

EM-TEMP

B-TEMP

6-E-401

MDS COORDINATOR

A137

HOUSEKEEPING SUPERVISOR

A136

STORAGE

A108A

SOCIAL WORKER

A135

DIETICIAN

A134

SUPPLY ROOM

A108

STORAGE

B133

STORAGE

B130

PHYSICAL THERAPY

B129

CORRIDOR

DCDR7

RESTROOM

B126

STORAGE

B129A

KITCHEN

B128

STORAGE

B127

ELEC. CLOSET

B119

WOMEN STAFF RESTROOM

B118

STORAGE

B120

ENGINEERING ADMINISTRATION

B121

ENGINEERING SERVICE

B124

CHIEF ENG. ASSISTANT

B123C

PROGRAM ANALYST

B122

ENGINEERING

B123

ENGINEERING SERVICE CHIEF

B123B

ENGINEERING SERVICE MANAGER

B123A

ELEC. CLOSET

B108E

FIRE CLOSET

B108F

OFFICE

B108B PATIENT TRANSFER COORD.

B108C PALLIATIVE CARE COORD.

B109

WOMEN STAFF RESTROOM

B110

PROGRAM SUPPORT ASSIST.

B112

GEMS COORDINATOR

B112A

SAFETY & EMERGENCY MGMT

B112B

OSH MANAGER

B112C

OFFICE

B113

OFFICE

B114

OFFICE

B115

CLINICAL PHARMACIST

B116

STORAGE

B117

CORRIDOR

B1-4

CORRIDOR

B1-5

PROJECTS OFFICE

A107

12 11 10 8 7 6

L

K

J

H

G

F.1

F

E.1

E

D

C

B

5 4 3 2

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL POWER DEMOLITION

PLAN - B WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-EPD101B

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL POWER DEMOLITION PLAN - B WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC AND BASED

OFF OF AVAILABLE INFORMATION AND MAY NOT REPRESENT ALL

DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY

ALL EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF

PROPOSAL.

GENERAL NOTES:

ELECTRICAL PLAN NOTES:

1 REMOVE ALL EXISTING ELECTRICAL POWER DEVICES, CIRCUIT

CONDUCTORS AND POWER CIRCUIT CONDUIT BACK TO THE

PANELBOARD WITHIN THE AREA OF WORK.

2 REMOVE EXISTING PANELBOARD AND FEEDER BACK TO THE

UPSTREAM DISTRIBUTION EQUIPMENT.

3 ELECTRICAL CLOSET TO REMAIN UNTIL POWER CAN BE

RELOCATED FOR THE EXISTING PHYSICAL THERAPY ROOM.

4 DISCONNECT AND REMOVE POWER TO PUBLIC ADDRESS

SYSTEM ENCLOSURE AFTER ENCLOSURE HAS BEEN

RELOCATED. REFER TO TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

5 DISONNECT AND REMOVE POWER TO NURSE CALL SYSTEM

PANEL AFTER PANEL HAS BEEN RELOCATED. REFER TO

TECHNOLOGY DRAWINGS FOR ADDITIONAL INFORMATION.

6 PROVIDE TEMPORARY PANELBOARD AS PART OF PHASE #2.

REFER TO 6-EP101B FOR ADDITIONAL INFORMATION.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

AREA OF DEMOLITION

ETD

ETD

ETD

A1

1314 12 11 10 8 7 6 5.1

U

T

S

R

Q

P

O

N

M

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL POWER DEMOLITION

ROOF PLAN - A WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-EPD102A

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL POWER DEMOLITION ROOF PLAN - A WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC AND BASED

OFF OF AVAILABLE INFORMATION AND MAY NOT REPRESENT ALL

DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY

ALL EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF

PROPOSAL.

GENERAL NOTES:

ELECTRICAL PLAN NOTES:

1 REMOVE ALL EXISTING ELECTRICAL POWER DEVICES AND

CIRCUIT CONDUCTORS BACK TO THE PANELBOARDS WITHIN

THE AREA OF WORK.

DEDUCT ALTERNATE NOTES:

IF THE ALTERNATE IS ELECTED, NO DEMOLITION WORK WILL BE

PERFORMED FOR THIS ROOF AREA.

A1.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

AREA OF DEMOLITION

ETD

12 11 10 8 7 6

L

K

J

H

G

F.1

F

E.1

E

D

C

B

A

5 4 3 2 1

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL POWER DEMOLITION

ROOF PLAN - B WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-EPD102B

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL POWER DEMOLITION ROOF PLAN - B WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC AND BASED

OFF OF AVAILABLE INFORMATION AND MAY NOT REPRESENT ALL

DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY

ALL EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF

PROPOSAL.

GENERAL NOTES:

ELECTRICAL PLAN NOTES:

1 REMOVE ALL EXISTING ELECTRICAL POWER DEVICES AND

CIRCUIT CONDUCTORS BACK TO THE PANELBOARDS WITHIN

THE AREA OF WORK.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

PP PP PP PP PP

PP

PP PP PP PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

ES

PP

PP

ES

ES

ES

PP

PPES

ES

A3D A3D

A3D A3D A3D A3D A3D

A3DE

A3D A3D A2D A2D

A2D A2D A2D A2D

A2D A2D

A2D A2D

A2D A2D

A2D A2D

A2D

A2D

A3D

A3D

A3D

A3D

A3DE

A3D

A3D

A3D A3DE

A3D A3DE

A3DE

A2D

A2D A2D

A3D

A3D

A3 A2D

STORAGE

A120

DIETICIAN

A121

LACTATION / PUMP

A122

REPORT ROOM

A119

HOSPICE APRN

A118

ACNS

A117

PHARM D

A124

ASST NURSE MNGR

A116

REC THERAPY OFFICE

A125

EXAM

A126

GEC PHYSICIAN

A129

REC THERAPY

A115

ELEC

A111

CONFERENCE

A130

LEARNER OFFICE

A131

STAIR

A135

BREAK ROOM

A132

TESTING

A134

EXAM

A136

NURSE MED

A137

EXAM, BARIATRIC

A138

FAMILY TLT

A102

ED SUPPLY ROOM

A139

BARIATRIC TLT

A103

RECEPTION

A101

STORAGE

A104

STAFF TOILET

A105

STAFF TOILET

A106

MDS / RESTOR OFFICE

A107

TESTING / INTERN

A108

GEROPSYCH

A109

CORRIDOR A

ACDR1

CORRIDOR A

ACDR3

EXAM

A135

PT/OT STOR

A128

SOCIAL WORK

A123

TOILET, BARIATRIC, SHOWER

A133

B1 B1E B1 B1 B1 B1E B1 B1 B1 B1E B1 B1

B1E

B1

B1

B1

B1E

B1

B1E

B1

B1

B1

B1E

B1

B1

B1

B1E

B1E

F1

F1

RC1

LVOD LVOD

PS

RC1

LVOD

PS

RC1

PS PS PS

PS PS PS PS

PS

PS

PS

PS

PS

PS

PS

PS

PS

PS

PS

RC1

LVOD LVOD

RC1 RC1

LVOD

RC1

LVOD

OS1

LVOD

RC1

LVOD

RC1

LVOD

RC1

LVOD

RC1

LVD

RC1

RC1

LVOD

RC1

LVOD

RC1

LVOD RC1

LVOD

RC1

LVD

OS1

D3

RC1

LV3

LVOD

RC1

RC1

OS1

OS1

D1 D1

D1 D1

OS1

D1 D1 a ab

OS2

OS2

OS2

OS2

OS2

OS2

OS2

OS2

OS2 OS2

OS2

OS2

OS2

ab

LVD

RC1

OS1

D1

D1

OS1

OS1

F1

A3DA3D

A2D

OS1

LV3

A3D

A2D

OS2

OS2

OS2

PS

PS

RC1

RC2

OS1

OS1

OS1

OS1

OS1

RC1

OS1

RC2

D2D D2D

OS1

OS1

RC1

OS1

A1

OS1

F2E

A2D A2D

A2D

A2D

F1E

F1E

D2D

D2D

PS

PS

D1D D1D

D1DE

D1D

D1D D1D

D1D

D1DE

D1DD1D

B1

B1D B1D

D1D

D1D D1D

D1D

D1DD1DD1D

D1D

D1

D1

D1

D1

LVD

LV1

W1E

OS1

OS1

LVD

LVD

X1E X1E

X1E

X1E

X1E

OS1

B1

PT / OT

A110

F1E

A2D

D1

D1

LVD

D1D

D1D

D1D

D1D

D1D

D1D

D1D

D1D

D1D

D1D

D1

D1

A3D

RC1

RC2

LVD LVD

HAC

A127

A1 & A2

A1 & A2

A1 & A2

PS

LS-A

A1 & A2

LVD

LVD

LVD

LVD

A1 & A2 (NEW)

EQ-A (NEW)

LS-A (NEW)

EQ-A-T (NEW)

X1E a b a

EQ-A

a a a a a a a a a a a a a a b b b b b b b b b b

(PART)

(PART)

VESTIBULE

A100

D1D D1D

D1D D1DE

b b a a a a b b a a a

RC2

A3D

OS1

X1E a

PS

A1

A1 & A2

A2D

OS1

RC1

IT

A114

PS

RM.

A126

EQ-A

RM.

A138

LVD

LVD

LVOD

LV1

LVD

LVD

PT / OT

A110

LV1

LVD

b

LV1

1314 12 11 10 8 7 6 5.1 4.1

U

T

S

R

Q

P

O

N

M

L

9 5

X1E

LVD

F2E F2 F2E

F2 F2E F2

F2E F2

F2 F2E

F2E

F2ESTAIRS

EQ-A

A1 & A2

MSB2 (NEW)

EMDB2 (NEW)EMDB (ETR)

ATS2 MSB (ETR)

ATS (ETR)

MTS2 (NEW)

MTS

(ETR)

FACP

(ETR)

F/O

(ETR)

(PART)

(PART)

400/3

Y1E

B6 (NEW)

S (ETR)

A1

10 8 7 6

U

T

S

R

AREA WAY

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL LIGHTING PLAN -

A WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-EL101A

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL LIGHTING PLAN - A WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

GENERAL NOTES:

ELECTRICAL PLAN NOTES:

1 REFER TO DETAIL 1, SHEET 6-E-701 FOR WIRING DIAGRAM OF

ALL TYPICAL ROOM CONTROLLERS WITH SWITCHES,

OCCUPANCY SENSORS AND DAYLIGHT SENSORS.

2 REFER TO DETAIL 2, SHEET 6-E-701 FOR WIRING DIAGRAM OF

TYPICAL OFFICE LIGHTS WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS.

3 REFER TO DETAIL 5, SHEET 6-E-701 FOR WIRING DIAGRAM OF

ALL EXAM ROOM LIGHTS WITH SWITCHES.

4 REFER TO DETAIL 6, SHEET 6-E-701 FOR WIRING DIAGRAM OF

CORRIDOR LIGHTS WITH SWITCHES, OCCUPANCY SENSORS

AND DAYLIGHT SENSORS.

5 REFER TO DETAIL 2, SHEET 6-E-702 FOR WIRING DIAGRAM OF

RECEPTION ROOM A101 AND VESTIBULE ROOM A100 LIGHTS

WITH SWITCHES, OCCUPANCY SENSORS AND DAYLIGHT

SENSORS.

6 REFER TO DETAIL 3, SHEET 6-E-702 FOR WIRING DIAGRAM OF

CONFERENCE ROOM A130 WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS.

7 REFER TO DETAIL 2, SHEET 6-E-701 FOR WIRING DIAGRAM OF

LACTATION/PUMP ROOM A122 WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS. LOCATE CONTROLLER IN

ADJACENT ACCESSIBLE CEILING.

8 REFER TO DETAIL 6, SHEET 6-E-702 FOR WIRING DIAGRAM OF

EXAM ROOM A138 LIGHTS WITH SWITCHES, OCCUPANCY

SENSORS, AND DAYLIGHT SENSORS.

9 REFER TO DETAIL 5, SHEET 6-E-702 FOR WIRING DIAGRAM OF

HAC ROOM 127, GEROPSYCH ROOM A109 AND ED SUPPLY ROOM

A139 WITH SWITCHES.

10 REFER TO DETAIL 4, SHEET 6-E-701 FOR WIRING DIAGRAM OF

PT/OT ROOM A110 CONTROLLERS WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS.

1/8" = 1'-0"2

ELECTRICAL LIGHTING PLAN - BASEMENT

WING A

BASEMENT

DEDUCT ALTERNATE NOTES:

IF DEDUCT ALTERNATE IS ACCEPTED, OMIT ALL CIRCUITING,

LIGHTING, AND LIGHTING CONTROLS OUTSIDE OF THE AREA SHOWN.

PROVIDE CIRCUITING, LIGHTING, AND LIGHTING CONTROLS WITHIN

THE AREA SHOWN. TIE NEW CIRCUITS INTO EXISTING PANELBOARD

A1 AND A2. PROVIDE NEW 20A BREAKERS AS REQUIRED.

A1.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

PP

PP

PP

PP

PP

PPPPPPPP

PPPP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

PP

ES

PP

PP

PP

PP

PP

PP

ES

PP ES

ES

PP

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

D2D D2D

REC THERAPY OFFICE

B132

RESIDENT

B135

RESIDENT

B131

RESIDENT

B137

RESIDENT

B136

RESIDENT

B124

RESIDENT

B125

HAC

B128

RESIDENT [BARIATRIC]

B119

RESIDENT

B120

RESIDENT

B121

RESIDENT

B122

SOCIAL WORKER

B113

NURSE MNGR

B112

STAFF BREAK

B115

GERIATRIC PSYCHIATRIST

B111

APRN

B110

SHARED OFFICE / REPORT

B129

RESIDENT

B123

COMPUTER LOUNGE

B118

TOILET [BARIATRIC]

B119A

RESIDENT

B126

KITCHEN

B109

NURSE STATION

B102

DINING & DAY ROOM

B108

STAFF TOILET

B116

CLINICAL NURSE LEADER

B114

CORRIDOR B

BCDR5

CORRIDOR B

BCDR2

CORRIDOR B

BCDR4

CORRIDOR B

BCDR3

CORRIDOR B

BCDR1

EXAM ROOM

B117

ELEC

B101

MEDS

B100

SOILED HOLDING

B106

LAUNDRY

B127

CLEAN SUPPLY

B104

RESIDENT

B130

TOILET

B130A

PS

B1

PS

PS

PS

PS

B1

B1E

B1

B1

B1

B1

B1

B1

B1E

B1

B1 B1

B1

B1 B1E B1 B1 B1 B1E B1 B1 B1 B1E B1

B1

B1

B1

B1

B1E

B1

D2D

D2D D2D

D2D

D2D D2D

D2D D2D D2D D2D

D3

D3

D1

D1

D1

D1

D1 D1

D1 D1

D3 D3

D1 D1

D1 D1

D3 D3

D1D1

D1 D1

D3D3D3

D1

D1

A3D

A3D

A1

B1B1E

A1

A1D

D1D D1D D1DE D1D D1D

D1DE D1D D1D D1D D1DE

D1DE

D1D

A3D A3D

A1

A1DA1D

A1D

PS

LVOD

RC1

LVOD

LVOD

LVOD

LVOD

LVOD

RC1

RC1

RC1

RC1

RC1

RC1

N1 a

LVD

RC2

a a a a c d c d c b c c d

LVD

a

RC2

N1b

N1b

RC2

LVD

a c d c d c c d c d c c d a a a a aa a a

RC2

a

N1 b a a a

RC2

LVD

a a a aa c d c d c c cc d d

LVD

a

N1

N1 b b

RC2

a a a a

OS1

RC1

D1D D1D D1D

D1D

D1DD1D

RC2

LVD

a a a a a d c d c c

F1E

OS1

aaa a a a a a a aa a d c c cc d a aa a

LVD

a

RC2

V1

V1

V1

V1 e e e e e e e

V1

V1 e e

D1

V1

V1 e e e e

N1 b

LVD

a

RC2

cde

V1

V1 e e cde

LVD

a

RC2

OS2

OS2

OS2

OS2

OS2

OS2 OS2 OS2 OS2

OS2

OS2

OS2

OS2

D3

D1

D1D1

W1E

W1E e e

OS1

OS1OS1

B1D B1DE

CLEAN LINEN

B107

D1D D1D

D1DD1D

D1DE

D1D

D1D

OS1 N1

b c d e N2 b

V1 e

D1 D1

D3cc d

D2D D2D

D2D D2D a a a a

LVD

a

OS1

OS1

OS1

D1

RC1

PS PS

OS1

LVD

RC1

LVD

RC1

B1

B1

OS1

PS

B1

LV1

OS1

OS1

STORAGE

B105

A1 A1

B1D B1D

A3D

A3D

A3D

A3D

A3D

A3D

SNOEZELEN

B134

X1E

X1E

X1E

X1E

X1E

X1E

X1E

RC1

RC2

LVD

a

N1 b 3 c e c c c c c

A3D A3D

A3D

D1

D1

D1

D1E

B1

B1D B1D

B1DB1D

B1

A3D A3DE

D2D D2D

D2DD2D

D3 D1 D1

V1

N2 e d c

N2

N2 b b

N2 b

V1 e

D3 dD1

D1 c c

N2 N2 b b

N2 N2b b

N2 N2b b

N2 b

N2 b b e d c c

LVD

a a a a a

LVD

a

D1

B1 & B2

N1 b

N1b

RC2

N1 b

REC THERAPY

B133

A3D

A3D

A3D

A3D

LED

F3

F3

F3

LVD

RC1

c d e

D2D D2Da a

RC2

N1 b

RC1

RC1

RC1LVD

LVD

LV1

b

LV1

b

LV1

b

LV1

b

LV1

b

LV1

b

LV1

b

LV1

b

LV1

b

LV1

b

B1 B1E B1 B1 B1

B1 & B2

B1 & B2

EQ-B

B1 & B2

TOILET

B135A

TOILET

B136A

TOILET

B137A

TOILET

B131A

TOILET

B126A

TOILET

B125A

TOILET

B124A

TOILET

B123A

TOILET

B122A

TOILET

B121A

TOILET

B120A

T

LS-B (NEW)

B1 & B2 (NEW)

LVD

a b c c c c c c c c c c b a a a a a a a a aa

LV1

b

LV1

bLV1 b

B1 & B2

3 3 3

RC1

RM. B117

RM. B102

LV1

LV1

LVOD

OS1

PS

OS1 PS

B1 & B2

LS-B

LVD

a

LVD

a

LVDa

LVD

a

LVD

a

LVD

LVD

a a

LVD

a

LVOD

LVD

a

LVD

a

LVD

LVD

a a

LVD

a

PS

DINING & DAY ROOM

B108

OS1

X1E

LVOD

LVD

LVOD

LVD

LVD

PS

12 11 10 8 7 6

L

K

J

H

G

F.1

F

E.1

E

D

C

B

A

5 4 3 2 1

X1EX1E

X1E

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL LIGHTING PLAN -

B WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-EL101B

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL LIGHTING PLAN - B WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

GENERAL NOTES:

ELECTRICAL PLAN NOTES:

1 REFER TO DETAIL 1, SHEET 6-E-701 FOR WIRING DIAGRAM OF

ALL TYPICAL ROOM CONTROLLERS WITH SWITCHES,

OCCUPANCY SENSORS AND DAYLIGHT SENSORS.

2 REFER TO DETAIL 2, SHEET 6-E-701 FOR WIRING DIAGRAM OF

TYPICAL OFFICE LIGHTS WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS.

3 REFER TO DETAIL 3, SHEET 6-E-701 FOR WIRING DIAGRAM OF

TYPICAL RESIDENT ROOM LIGHTS WITH SWITCHES.

4 REFER TO DETAIL 5, SHEET 6-E-701 FOR WIRING DIAGRAM OF

NURSE STATION B102 AND ALL EXAM ROOM LIGHTS WITH

SWITCHES.

5 REFER TO DETAIL 6, SHEET 6-E-701 FOR WIRING DIAGRAM OF

CORRIDOR LIGHTS WITH SWITCHES, OCCUPANCY SENSORS

AND DAYLIGHT SENSORS.

6 REFER TO DETAIL 4, SHEET 6-E-702 FOR WIRING DIAGRAM OF

DINING AND DAY ROOM B108 WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS. LOCATE CONTROLLER IN

ADJACENT ACCESSIBLE CEILING.

7 REFER TO DETAIL 1, SHEET 6-E-702 FOR WIRING DIAGRAM OF

DAY ROOM ENTRANCE WITH SWITCHES. LOCATE CONTROLLER

IN ADJACENT ACCESSIBLE CEILING.

8 REFER TO DETAIL 6, SHEET 6-E-702 FOR WIRING DIAGRAM OF

NURSE STATION WITH SWITCHES AND OCCUPANCY SENSORS.

DEDUCT ALTERNATE AND PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

J

J

J

STORAGE

A120

DIETICIAN

A121

LACTATION / PUMP

A122

REPORT ROOM

A119

HOSPICE APRN

A118

ACNS

A117

PHARM D

A124

ASST NURSE MNGR

A116

REC THERAPY OFFICE

A125

EXAM

A126

GEC PHYSICIAN

A129

REC THERAPY

A115

PT / OT

A110

ELEC

A111

CONFERENCE

A130

LEARNER OFFICE

A131

STAIR

A135

BREAK ROOM

A132

TESTING

A134

EXAM

A136

NURSE MED

A137

EXAM, BARIATRIC

A138

FAMILY TLT

A102

ED SUPPLY ROOM

A139

BARIATRIC TLT

A103

RECEPTION

A101

STORAGE

A104

STAFF TOILET

A105

STAFF TOILET

A106

MDS / RESTOR OFFICE

A107

TESTING / INTERN

A108

GEROPSYCH

A109

CORRIDOR A

ACDR1

CORRIDOR A

ACDR3

EXAM

A135

PT/OT STOR

A128

SOCIAL WORK

A123

TOILET, BARIATRIC, SHOWER

A133

IT

A114

+80"

LS-A (NEW)

EQ-A (NEW)

A1 & A2 (NEW)

+48"

+48"

EQ-A-T (NEW)

6-E-401

+48"WP/WR

WP/WR

HAC

A127

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

+60"

A1 & A2

A1 & A2

A1 & A2

A1 & A2

EQ-A

A1 & A2

EQ-A

A1 & A2

A1 & A2

EQ-A

A1 & A2

EQ-A

EQ-A

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

A1 & A2

VESTIBULE

A100

A1

6-E-401

A1 & A2

A1 & A2

A1 & A2

USBUSBUSBUSB

USB USB

USB USB

USB

A1 & A2

A1 & A2

A1 & A2

A1 & A2 19 A1 & A2

A1 & A2

A1 & A2

USB

USB

EXISTING

GENERATOR

NEW GENERATOR

A1 & A2

A1 & A2

A1 & A2

PT-01

A1 & A2

1314 12 11 10 8 7 6 5.1 4.1

U

T

S

R

Q

P

O

N

M

L

9 5

A1 & A2

A1 & A2

A1 & A2

A1 & A2

EMDB (ETR)

S (ETR) B6 (NEW)

MSB (ETR)

ATS (ETR)

ES (NEW)

ATS2

EMDB2 (NEW)

MSB2 (NEW)

MTS2 (NEW)

FACP

(ETR)

F/O

(ETR)

MTS

(ETR)

400/3

A1

REFER TO 6-EP101A FOR NEW

AND EXISTING GENERATORS.

10 8 7 6

U

T

S

R

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6ELECTRICAL POWER PLAN -

A WING

07/10/2019 BEN ABM

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-EP101A

589-A5-19-116

BID DOCUMENTS

1/8" = 1'-0"1

ELECTRICAL POWER PLAN - A WING

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE 24/7.

2. SEE SHEET 6-GI-102 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO

MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S

REPRESENTATIVE BEFORE THE START OF WORK.

4. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

5. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH CONTRACTING OFFICER’S REPRESENTATIVE.

GENERAL NOTES:

1/8" = 1'-0"2

ELECTRICAL POWER PLAN - BASEMENT

WING A

BASEMENT

DEDUCT ALTERNATE NOTES:

IF DEDUCT ALTERNATE IS ACCEPTED, OMIT ALL CIRCUITING,

RECEPTACLES, AND OTHER ELECTRICAL DEVICES OUTSIDE OF THE

AREA SHOWN. PROVIDE NEW CIRCUITING AND RECEPTACLES

WITHIN THE AREA SHOWN. TIE NEW CIRCUITS INTO EXISTING

PANELBOARD A1 AND A2. PROVIDE NEW 20A BREAKERS AS

REQUIRED.

A1.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE

OVERALL PROJECT PHASING SEQUENCE OUTLINED ON

ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN

WORK ON THIS SHEET IS ALSO SUBJECT TO THE REDUCED AREAS

OF WORK AS DEFINED ON ARCHITECTURAL SHEET 6-GI-105.

ELEC…