GENERAL:

1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE DESIGN CRITERIA,

THESE DRAWINGS, AND THE PROJECT SPECIFICATIONS FOR IMPORTANT

QUALIFICATION, DEFINITION, SUBMITTAL, PRODUCT, INSTALLATION, AND TESTING

REQUIREMENTS.

2. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE COMPLETED IN A NEAT,

WORKMAN-LIKE MANNER.

3. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE APPROACHES AND/OR

SUBSTITUTIONS WILL BE CONSIDERED BY THE ENGINEER IF THE CONTRACTOR

PROVIDES WRITTEN, WELL-DOCUMENTED, ENGINEERING-BASED SUBSTANTIATION

FOR PROPOSED ALTERNATIVE.

APPLICABLE CODES AND STANDARDS:

1. INTERNATIONAL BUILDING CODE (2018)

2. NFPA 70 NATIONAL ELECTRIC CODE (2017)

3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2019)

AUDIBILITY DESIGN:

1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT CONDITIONS,

THE AUDIBILITY DESIGN GOALS SHALL BE CONFIRMED BY MEASUREMENT WITH

CALIBRATED TEST EQUIPMENT. IF RESULTS INDICATE THAT ADDITIONAL

NOTIFICATION APPLIANCES, THE CONTRACTOR SHALL ADD THEM AT NO ADDITIONAL

COST.

2. THE EXPECTED AMBIENT SOUND PRESSURE LEVELS ARE AS FOLLOWS:

A. OFFICES, RESTROOMS, RESIDENT ROOMS, CIRCULATION AREAS: 55 dBA B. MECHANICAL EQUIPMENT AREAS: 85 dBA

3. THE DESIGN GOAL IS FOR THE ALERT TONE PRECEDING THE VOICE MESSAGE TO

REACH THE FOLLOWING SOUND PRESSURE LEVELS (PUBLIC MODE):

A. OFFICES, RESTROOMS, RESIDENT ROOMS, CIRCULATION AREAS: 70 dBA B. MECHANICAL EQUIPMENT AREAS: 100 dBA

4. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION INDICATED ON THE

APPROVED DESIGN WITHOUT CONSULTING THE ENGINEER.

VISUAL NOTIFICATION DESIGN:

1. CLEAR STROBES SHALL BE PROVIDED WHERE INDICATED ON THE APPROVED

DESIGN.

2. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION INDICATED ON THE

APPROVED DESIGN WITHOUT CONSULTING THE ENGINEER. CONSULT WITH

ENGINEER PRIOR TO RELOCATING STROBES MORE THAN 3 FT.

INITIATING DEVICES:

1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION

INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE ENGINEER.

CONSULT WITH ENGINEER PRIOR TO RELOCATING INITIATING DEVICES MORE THAN 3

FT.

CIRCUITS AND CONDUIT:

1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE WITH NFPA 70 AND

THE CONDUIT LISTING.

2. NEW SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE CIRCUITS SHALL BE

ARRANGED SO THAT A SINGLE FAULT DOES NOT CAUSE THE LOSS OF ADDRESSABLE

DEVICES ON MORE THAN ONE SMOKE COMPARTMENT.

INSTALLATION:

1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING STRUCTURE AND

SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO THE BUILDING STRUCTURE

UNLESS NOTED OTHERWISE.

2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE APPROVED DESIGN

WITHOUT WRITTEN APPROVAL FROM THE ENGINEER.

TESTING:

1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL PERFORM ALL

ACCEPTANCE TESTING IN ACCORDANCE WITH THE APPLICABLE DESIGN CRITERIA

AND THE EQUIPMENT MANUFACTURER'S INSTRUCTIONS.

2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL PERFORM

TESTING AND PROVIDE DOCUMENTATION PRIOR TO REQUESTING ENGINEER'S

PRESENCE TO WITNESS TESTING.

FIRE ALARM GENERAL NOTES

FACP

F

WF

EXISTING SIMPLEX 4100ES FIRE ALARM CONTROL PANEL

FIRE ALARM LEGEND

SPD SURGE PROTECTIVE DEVICE

FIRE ALARM PULL STATION

AIM ADDRESSABLE INPUT MODULE

AOM ADDRESSABLE OUTPUT MODULE

WATERFLOW SWITCH

WALL MOUNTED STROBE

s SMOKE DETECTOR - SPOT TYPE

S SPEAKER

SPEAKER STROBE

SYMBOL MODIFIERS

C ncd nW

WP

CEILING MOUNTED

CANDELA RATING

WATT TAP

WEATHER PROOF

DH DOOR HOLDERS

LFSB LOW FREQUENCY SOUNDER BASE

VS VALVE SUPERVISORY SWITCH

LF LOW FREQUENCY SPEAKER

DH DOOR HOLD RELEASE

MANUAL PULL STATION 1 • • • • • • • • 1

SPRINKLER WATERFLOW SWITCH 2 • • • • • • • • 2

SMOKE DETECTOR - SPOT TYPE (OTHER THAN SPECIFIC DETECTORS BELOW) 3 • • • • • • • • 3

RESIDENT ROOM SMOKE DETECTORS (ANY TYPE) 4 • • • • 4

SMOKE DETECTOR - DUCT TYPE 5 • • • • 5

VALVE SUPERVISORY SWITCH 6 • • • 6

FACU AC POWER FAILURE 7 • • • 7

FACU LOW BATTERY 8 • • • 8

OPEN CIRCUIT 9 • • • 9

GROUND FAULT 10 • • • 10

NOTIFICATION APPLIANCE CIRCUIT SHORT 11 • • • 11

ALL OTHER TROUBLES 12 • • • 12

A B C D E F G H I J K L M N O P

NOTE: THIS MATRIX IS ONLY INTENDED TO SHOW THE MAJOR SYSTEM FUNCTIONS, SYSTEM SHALL ALSO PERFORM INPUTS/OUTPUTS REQUIRED BY

NFPA 72 AND THE PRODUCTS' LISTING.

OUTPUTS

NOTIFICATION INTERFACE

AC

TI

VA

TE

C

LE

AR

S

TR

O

BE

S

TH

R

O U

G H

O U

T

BU

IL

D

IN

G

AC

TI

VA

TE

P R

E- R

EC

O

R D

ED

F

IR

E

EV

AC

U

AT

IO

N

M

ES

SA

G

E

TH

R O

U G

H O

U T

BU

IL

D

IN

G

D

IS

PL

AY

A

LA

R M

C O

N D

IT

IO

N A

T

FI

R E

AL

AR

M C

O N

TR

O

L U

N

IT

D

IS

PL

AY

A

LA

R M

C O

N D

IT

IO

N A

T

FI

R E

AL

AR

M A

N N

U N

C

IA

TO

R

P

AN

EL

TR

AN

SM

IT

A

LA

R M

S

IG

N

AL

T O

S U

PE

R

VI

SI

N G

S

TA

TI

O

N

D

IS

PL

AY

S U

PE

R

VI

SO

R Y

C O

N D

IT

IO

N A

T

FI

R E

AL

AR

M C

O N

TR

O

L U

N

IT

D

IS

PL

AY

S U

PE

R

VI

SO

R Y

C O

N D

IT

IO

N A

T

FI

R E

AL

AR

M A

N N

U N

C

IA

TO

R

P

AN

EL

TR

AN

SM

IT

S U

PE

R

VI

SO

R Y

SI

G

N

AL

T O

S U

PE

R

VI

SI

N G

S

TA

TI

O

N

D

IS

PL

AY

T R

O U

BL

E

C O

N D

IT

IO

N A

T

FI

R E

AL

AR

M C

O N

TR

O

L U

N

IT

D

IS

PL

AY

T R

O U

BL

E

C O

N D

IT

IO

N A

T

FI

R E

AL

AR

M A

N N

U N

C

IA

TO

R

P

AN

EL

TR

AN

SM

IT

T R

O U

BL

E

SI

G

N

AL

T O

S U

PE

R

VI

SI

N G

S

TA

TI

O

N

R

EL

EA

SE

M

AG

N

ET

IC

AL

LY

H

EL

D

D O

O R

S

AC

TI

VA

TE

IN

D

IV

ID

U

AL

R O

O M

S M

O

KE

D

ET

EC

TO

R S

O U

N D

ER

B

AS

E

SH

U

TD

O

W N

A

SS

O C

IA

TE

D A

IR

H

AN

D

LI

N

G U

N

IT

AC

TI

VA

TE

S

PE

AK

ER

S

TH

R O

U G

H O

U T

BU

IL

D

IN

G

AC

TI

VA

TE

S

TR

O

BE

S

TH

R O

U G

H O

U T

BU

IL

D

IN

G

INPUTS A B C D E F G H I J K L M N O P

FACP

WF VS

S

SPD

S

FIRST FLOOR

BASEMENT

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING SIMPLEX 4100ES FIRE ALARM CONTROL PANEL IS LOCATED IN BASEMENT

EQUIPMENT ROOM A175B.

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT,

PANEL CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT

QUANTITIES AND TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS

ARE NOT INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL

SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION OF THE PROJECT.

s AIM AIM F s

LFSB

DH

AOMs

DH

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

PLAN NORTH

W E

S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of Andrew W. Morris

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6FIRE ALARM GENERAL NOTES,

LEGEND AND MATRIX

07/10/2019 KAB SAB

2200 SW GAGE BLVD.

TOPEKA, KS 66622

6-FA001

589A5-18-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

SCALE: NONE1 FIRE ALARM INPUT/OUTPUT MATRIX

SCALE: NONE2 FIRE ALARM RISER DIAGRAM

Revision # Date

F

F

15cd

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.

W cd

S 0.25W

C

S 0.25W

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C S 0.25W

C S 0.25W

C S 0.25W

C S 0.25W

C 0.25W

15cd

C

0.

W cd 0.

W cd

0.25W 15cd

C

0.25W 30cd

C 0.25W

30cd

C

0.25W 30cd

C

0.5W 30cd

C

0.25W 15cd

C 0.25W

15cd

C 0.25W

15cd

C 0.25W

15cd

C

0.25W 15cd

C

0.25W15cd

0.25W 15cd

C 0.25W

15cd

C 0.25W

15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

S 0.25W

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

WP

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

0.25W 15cd

0.25W15cd

15cd1W 15cd

F

6.1 7 7.1 8 7.2

V

W

S

Q

D.7

A134

TESTING

A134

A135

EXAM

A135

A136

EXAM

A136

A137

NURSE

MED

A137

A138

EXAM,

BARIATRIC

A138

A139

ED

SUPPLY

ROOM

A139

A102

FAMILY

TLT

A102

A101

RECEPTION

A101

ACDR1

CORRIDOR

A

ACDR1

ACDR2

CORRIDOR

ACDR2

A133

TOILET,

BARIATRIC,

SHOWER

A133

A132

BREAK

ROOM

A132

A131

LEARNER

OFFICE

A131

A135

STAIR

A135

A130

CONFERENCE

A130

A129

GEC

PHYSICIAN

A129

A103

BARIATRIC

TLT

A103

A104

STORAGE

A104

A105

STAFF

TOILET

A105

A106

STAFF

TOILET

A106

A107

MDS /

RESTOR

OFFICE

A107

A108

TESTING /

INTERN

A108

A109

GEROPSYCH

A109

A110

PT / OT

A110

A114

IT

A114

A114.1

EXISTING

IT

A114.1

A115

REC

THERAPY

A115

A127

HAC

A127

A126

EXAM

A126 A125

REC

THERAPY

OFFICE

A125 A124

PHARM D

A124A123

SOCIAL

WORK

A123A122

LACTATION

/ PUMP

A122A121

DIETICIAN

A121A120

STORAGE

A120

A119

REPORT

ROOM

A119 A118

HOSPICE

APRN

A118 A117

ACNS

A117

A116

ASST

NURSE

MNGR

A116

A113

ENG SERV

A113

ACDR3

CORRIDOR

A

ACDR3

A100

VESTIBULE

A100

A128

PT/OT

STOR

A128

A110

PT / OT

A110

VS

W

F s

DH

DH

DH

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

PLAN NORTH

W E

S N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of Andrew W. Morris

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6FIRE ALARM FLOOR PLAN - WING A

07/10/2019 KAB SAB

2200 SW GAGE BLVD.

TOPEKA, KS 66622

6-FA101

589A5-18-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

SCALE = 1/8" = 1'-0"1 FIRE ALARM FLOOR PLAN - WING A

Revision # Date

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.25W15cd

WP

0.25W15cd

WP

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.25W15cd

WP

0.25W 15cd

WP

0.25W 177cd

C

LF

0.25W 15cd

C

0.25W 30cd

C

0.25W 15cd

C

0.25W15cd

WP

0.25W 15cd

C

S 0.25W

C

S 0.25W

C

0.25W 15cd

C S 0.25W

C

0.25W 15cd

C

0.25W 30cd

C 0.25W

15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 30cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

CS

0.25W

CS

0.25W

CS

0.25W

C

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.

W cd W

P

0.

W cd W

P

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.25W 177cd

C

LF

0.

W cd W

P

0.

W cd W

P

0.

W cd W

P

0.

W cd W

P

0.25W 15cd

WP 0.

W cd

W P

0.25W 15cd

C

0.5W 30cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C0.25W 15cd

C

0.25W 15cd

C

0.25W 15cd

C

F

0.25W 30cd

C

0.5W 30cd

C

0.25W 30cd

C 0.25W

15cd

C

A

D

C.1

F

6.1 7 7.1 8 7.2

Q

D.7

A109

GEROPSYCH

A109

B114

CLINICAL

NURSE

LEADER

B114

B113

SOCIAL

WORKER

B113

B112

NURSE

MNGR

B112

B115

STAFF

BREAK

B115

BCDR5

CORRIDOR

B

BCDR5

B111

GERIATRIC

PSYCHIATRIST

B111

B110

APRN

B110

B108

DINING &

DAY

ROOM

B108

B106

SOILED

HOLDING

B106 B107

CLEAN

LINEN

B107

B105

STORAGE

B105

B104

CLEAN

SUPPLY

B104

BCDR1

CORRIDOR

B

BCDR1

B137

RESIDENT

B137

B137A

TOILET

B137A

B136A

TOILET

B136A

B136

RESIDENT

B136

B135

RESIDENT

B135

BCDR2

CORRIDOR

B

BCDR2

B133

REC

THERAPY

B133

B132

REC

THERAPY

OFFICE

B132

B131

RESIDENT

B131

B131A

TOILET

B131A

B130A

TOILET

B130A

BCDR3

CORRIDOR

B

BCDR3

B130

RESIDENT

B130

B129

SHARED

OFFICE /

REPORT

B129

B109

KITCHEN

B109

B128

HAC

B128

B127

LAUNDRY

B127

B126

RESIDENT

B126

B126A

TOILET

B126A B125A

TOILET

B125A

B125

RESIDENT

B125 B124

RESIDENT

B124

B124A

TOILET

B124A B123A

TOILET

B123A

B123

RESIDENT

B123

BCDR4

CORRIDOR

B

BCDR4

B122

RESIDENT

B122

B122A

TOILET

B122AB121A

TOILET

B121A

B121

RESIDENT

B121B120

RESIDENT

B120

B120A

TOILET

B120A

B119A

TOILET

[BARIATRIC]

B119A

B119

RESIDENT

[BARIATRIC]

B119

B118

COMPUTER

LOUNGE

B118

B117

EXAM

ROOM

B117

B116

STAFF

TOILET

B116

B102

NURSE

STATION

B102

B100

MEDS

B100 B101

ELEC

B101 s

LFSB

s

LFSB

s

LFSB

s

LFSB

s

LFSB

B134

SNOEZELEN

B134 s

LFSB

s

LFSB

s

LFSB

s

LFSB

s

LFSB

B135A

TOILET

B135A

B108

DINING &

DAY

ROOM

B108 s

LFSB

s

LFSB

s

LFSB

s s s s s s s s s s s ss

WF

VS

s

DH

s

DH

DH

DH

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

PLAN NORTH

W E

S N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of Andrew W. Morris

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6FIRE ALARM FLOOR PLAN - WING B

07/10/2019 KAB SAB

2200 SW GAGE BLVD.

TOPEKA, KS 66622

6-FA102

589A5-18-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

SCALE = 1/8" = 1'-0"1 FIRE ALARM FLOOR PLAN - WING B

Revision # Date

1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION,

FIRE SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH

U.S. DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION

DESIGN MANUAL, SEVENTH EDITION, DECEMBER 2015; NFPA 13:

STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS,

2019 EDITION; AND NFPA 291: RECOMMENDED PRACTICE FOR

FIRE FLOW TESTING AND MARKING OF HYDRANTS, 2019

EDITION.

2. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE

GUIDANCE FOR BIDDING. THE CONTRACTOR SHALL BE THE

ENGINEER OF RECORD. THE FIRE PROTECTION CONTRACTOR

SHALL BE FULLY RESPONSIBLE FOR PROVIDING A COMPLETE

AND FULLY OPERABLE SYSTEM WHICH SHALL BE IN STRICT

ACCORDANCE WITH PROJECT SPECIFICATIONS AND

APPLICABLE CODES AND STANDARDS. THE WORK THAT IS

INDICATED IN THIS DOCUMENT IS AN OVERVIEW OF THE

PROJECT, INTENDED TO ESTABLISH THE MINIMUM SCOPE

REQUIREMENTS FOR THE PROJECT AS WELL AS THE

CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL

SUBMIT A COMPLETE SET OF WORKING DRAWINGS,

EQUIPMENT, AND CALCULATIONS TO THE OWNER’S

REPRESENTATIVE AND AHJ FOR REVIEW AND APPROVAL PRIOR

TO FABRICATION AND INSTALLATION WITH THEIR ENGINEERS

SEAL.

3. PRIOR TO BEGINNING ANY CONSTRUCTION, THE CONTRACTOR

SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL

DIMENSIONS, MEASUREMENTS AND LOCATIONS OF EXISTING

FACILITIES, UTILITIES, EQUIPMENT AND OTHER EXISTING

CONDITIONS WHICH MAY AFFECT CONSTRUCTION. BASE CIVIL

ENGINEERING HAS MADE EVERY ATTEMPT TO VERIFY THIS

INFORMATION. HOWEVER, IN THE EVENT OF DISCREPANCIES

BETWEEN THE DRAWINGS AND ACTUAL FIELD CONDITIONS,

CONTACT THE CONTRACTING OFFICER IMMEDIATELY.

4. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF

FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,

DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL

ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE

SHALL BE CONSIDERED DURING INSTALLATION. DO NOT

INSTALL SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN

CLEARANCE SPACES FOR MECHANICAL AND ELECTRICAL

EQUIPMENT. SPRINKLERS SHALL BE INSTALLED UNDER

OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13.

5. THE SPRINKLER SYSTEM MUST BE ZONED BY SMOKE

COMPARTMENT. THE SPRINKLER RISER LOCATED IN WING A

MUST ONLY FEED WING A AND THE SPRINKLER RISER LOCATED

IN WING B MUST ONLY FEED WING B.

6. THE EXISTING 4-INCH FEED MAIN THAT SUPPLIES WING D MUST

REMAIN IN SERVICE DURING THIS CONSTRUCTION PROJECT.

7. MATERIALS AND ACCESSORIES NECESSARY MUST BE

INSTALLED IN ACCORDANCE WITH THE APPLICABLE NFPA

CODES AND STANDARDS, PROJECT SPECIFICATIONS, AND BE

UL LISTED OR FM APPROVED FOR FIRE PROTECTION USE,

UNLESS OTHERWISE NOTED.

8. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC

TAMPER SWITCHES WIRED TO THE FACU. VALVES IN NORMAL

CLOSED POSITION SHALL BE PROVIDED WITH TAMPER TO

ACTIVATE IN THREE TURNS OR LESS. ALL VALVES OUTSIDE TO

BE SUPERVISED WITH LOCK AND CHAIN.

9. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN

ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.

10. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,

VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE

REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING

REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS.

11. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE

THAN 7 FEET AFF.

12. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL

BE USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY

SPRINKLER PIPING.

13. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE

IDENTIFIED AS REQUIRED BY NFPA 13.

14. PIPING MUST BE ARRANGED FOR FLUSHING. READILY

REMOVABLE FITTINGS MUST BE PROVIDED AT THE END OF ALL

CROSS MAINS.

15. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE

CENTER OF THE CEILING TILES.

16. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN

ACCORDANCE WITH NFPA 13. ALL DRAINS AND TEST

CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF THE

BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND SHALL

NOT DISCHARGE ACROSS PATHS OF EGRESS.

17. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY

DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.

18. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT

WORK TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.

19. A LISTED RELIEF VALVE MUST BE PROVIDED IN ACCORDANCE

WITH NFPA 13, SECTION 8.1.2 FOR THE SPRINKLER SYSTEM.

20. AN AIR VENT MUST BE PROVIDED IN ACCORDANCE WITH NFPA

13, SECTION 8.1.5 AND SECTION 16.7 FOR THE SPRINKLER

SYSTEM.

21. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER

SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO

BE MAINTAINED ABOVE 40 DEGREES F.

22. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE

CONCEALED SPACES.

23. DEMOLISH THE SPRINKLER SYSTEM IN ALL AREAS OF WING A

AND B FROM THE SPRINKLERS BACK TO THE SPRINKLER RISER

BUTTERFLY VALVES. ALL DEMOLISHED EQUIPMENT AND

MATERIALS MUST BE PROPERLY DISPOSED OF BY THE

CONTRACTOR.

24. INSTALL NEW CHECK VALVES, WATERFLOW SWITCHES, AND

INSPECTOR'S TEST CONNECTIONS WITH PRESSURE RELIEF

VALVE.

FIRE SUPPRESSION GENERAL NOTES

BUTTERFLY VALVE

3" PIPE

4" PIPE

INSPECTOR'S TEST

CONNECTION AND

MAIN DRAIN

TO SPRINKLER

SYSTEM

WATERFLOW

SWITCH

DEMO EVERYTHING

ABOVE CONTROL

VALVE

BUTTERFLY VALVE

3" PIPE

4" PIPE

INSPECTOR'S TEST

CONNECTION AND

MAIN DRAIN

4" PIPE TO WING D

WATERFLOW

SWITCH

TO SPRINKLER

SYSTEM

DEMO EVERYTHING

AFTER CONTROL

VALVE

BUTTERFLY VALVE

3" PIPE

4" PIPE

EXISTING INSPECTOR'S

TEST CONNECTION AND

MAIN DRAIN.

CONTRACTOR CAN

REUSE EXISTING TEST

AND DRAIN PIPING

TO SPRINKLER

SYSTEM

WATERFLOW SWITCH

INSPECTOR'S TEST

CONNECTION AND

DRAIN WITH PRESSURE

RELIEF VALVE

PRESSURE GAUGE

BUTTERFLY VALVE

3" PIPE

4" PIPE

EXISTING INSPECTOR'S

TEST CONNECTION AND

MAIN DRAIN.

CONTRACTOR CAN

REUSE EXISTING TEST

AND DRAIN PIPING

4" PIPE TO WING D

WATERFLOW SWITCH

TO SPRINKLER

SYSTEM

PRESSURE GAUGE

INSPECTOR'S TEST

CONNECTION AND

DRAIN WITH PRESSURE

RELIEF VALVE

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

PLAN NORTH

W E

S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of Andrew W. Morris

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6FIRE SUPPRESSION GENERAL

NOTES

07/10/2019 KAB DRF

2200 SW GAGE BLVD.

TOPEKA, KS 66622

6-FX001

589A5-18-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

SCALE = 1/2" = 1'-0"1,3 EXISTING SPRINKLER RISER ROOM A110

SCALE = 1/2" = 1'-0"2,4 EXISTING SPRINKLER RISER ROOM B102

SCALE = 1/2" = 1'-0"3 NEW SPRINKLER RISER ROOM A110

SCALE = 1/2" = 1'-0"4 NEW SPRINKLER RISER ROOM B102

Revision # Date

A134

TESTING

A134

A135

EXAM

A135

A136

EXAM

A136

A137

NURSE

MED

A137

A138

EXAM,

BARIATRIC

A138

A139

ED

SUPPLY

ROOM

A139

A102

FAMILY

TLT

A102

A101

RECEPTION

A101

ACDR1

CORRIDOR

A

ACDR1

ACDR2

CORRIDOR

ACDR2

A133

TOILET,

BARIATRIC,

SHOWER

A133

A132

BREAK

ROOM

A132

A131

LEARNER

OFFICE

A131

A135

STAIR

A135

A130

CONFERENCE

A130

A129

GEC

PHYSICIAN

A129

A103

BARIATRIC

TLT

A103

A104

STORAGE

A104

A105

STAFF

TOILET

A105

A106

STAFF

TOILET

A106

A107

MDS /

RESTOR

OFFICE

A107

A108

TESTING /

INTERN

A108

A109

GEROPSYCH

A109

B114

CLINICAL

NURSE

LEADER

B114 B113

SOCIAL

WORKER

B113

ACDR3

CORRIDOR

A

ACDR3

A110

PT / OT

A110

A114

IT

A114 A114.1

EXISTING

IT

A114.1

A115

REC

THERAPY

A115

A127

HAC

A127A126

EXAM

A126A125

REC

THERAPY

OFFICE

A125A124

PHARM D

A124A123

SOCIAL

WORK

A123A122

LACTATION

/ PUMP

A122A121

DIETICIAN

A121A120

STORAGE

A120

A119

REPORT

ROOM

A119 A118

HOSPICE

APRN

A118 A117

ACNS

A117 A116

ASST

NURSE

MNGR

A116

A113

ENG SERV

A113

6.1 7 7.1 8 7.2

V

W

S

Q

D.7

A128

PT/OT

STOR

A128

A111

ELEC

A111

A112

STOR

A112

1,3

FX001

HAZARD CLASSIFICATION LEGEND

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD GROUP 2

(0.20 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD GROUP 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

EXISTING FIRE SUPPRESSION RISER

FIRE SUPPRESSION LEGEND

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

PLAN NORTH

W E

S N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of Andrew W. Morris

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6FIRE SUPPRESSION HAZARD

CLASSIFICATION FLOOR PLAN -

WING A

07/10/2019 KAB DRF

2200 SW GAGE BLVD.

TOPEKA, KS 66622

6-FX101

589A5-18-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

SCALE = 1/8" = 1'-0"1 FIRE SUPPRESSION HAZARD CLASSIFICATION FLOOR PLAN - WING A

Revision # Date

A

D

C.1

F

A109

GEROPSYCH

A109

B114

CLINICAL

NURSE

LEADER

B114 B113

SOCIAL

WORKER

B113

ACDR3

CORRIDOR

A

ACDR3

B112

NURSE

MNGR

B112

B115

STAFF

BREAK

B115

BCDR5

CORRIDOR

B

BCDR5

B111

GERIATRIC

PSYCHIATRIST

B111

B110

APRN

B110

B108

DINING &

DAY

ROOM

B108

B106

SOILED

HOLDING

B106 B107

CLEAN

LINEN

B107

B105

STORAGE

B105

B104

CLEAN

SUPPLY

B104

BCDR1

CORRIDOR

B

BCDR1

B137

RESIDENT

B137

B137A

TOILET

B137A

B136A

TOILET

B136A

B136

RESIDENT

B136

B135

RESIDENT

B135

BCDR2

CORRIDOR

B

BCDR2

B133

REC

THERAPY

B133

B132

REC

THERAPY

OFFICE

B132

B131

RESIDENT

B131

B131A

TOILET

B131A

B130A

TOILET

B130A

BCDR3

CORRIDOR

B

BCDR3

B130

RESIDENT

B130

B129

SHARED

OFFICE /

REPORT

B129

B109

KITCHEN

B109

B128

HAC

B128

B127

LAUNDRY

B127

B126

RESIDENT

B126

B126A

TOILET

B126A B125A

TOILET

B125A

B125

RESIDENT

B125 B124

RESIDENT

B124

B124A

TOILET

B124A B123A

TOILET

B123A

B123

RESIDENT

B123

BCDR4

CORRIDOR

B

BCDR4

B122

RESIDENT

B122

B122A

TOILET

B122AB121A

TOILET

B121A

B121

RESIDENT

B121B120

RESIDENT

B120

B120A

TOILET

B120A

B119A

TOILET

[BARIATRIC]

B119A

B119

RESIDENT

[BARIATRIC]

B119

B118

COMPUTER

LOUNGE

B118

B117

EXAM

ROOM

B117

B116

STAFF

TOILET

B116

B102

NURSE

STATION

B102

B100

MEDS

B100 B101

ELEC

B101

6.1 7 7.1 8 7.2

Q

D.7

A110

PT / OT

A110

B135A

TOILET

B135A

B134

SNOEZELEN

B134

2,4

FX001

HAZARD CLASSIFICATION LEGEND

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD GROUP 2

(0.20 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD GROUP 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

EXISTING FIRE SUPPRESSION RISER

FIRE SUPPRESSION LEGEND

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

PLAN NORTH

W E

S N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of Andrew W. Morris

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BLDG 6FIRE SUPPRESSION HAZARD

CLASSIFICATION FLOOR PLAN -

WING B

07/10/2019 KAB DRF

2200 SW GAGE BLVD.

TOPEKA, KS 66622

6-FX102

589A5-18-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

SCALE = 1/8" = 1'-0"1 FIRE SUPPRESSION HAZARD CLASSIFICATION FLOOR PLAN - WING B

Revision # Date

MA

MV

CO

EV

VE

AI

FOV

FOR

FOS

FP

LPG

NPW

NO

O

N

G

MPG

G

MPG

CA

CD

ACD

V

VBG

VBF

AV

AW

AW

ST

OST

GW

GW

S

W

ID

SPD

T

T

SCW

WS

140°

S

W

ST

CAP

AV

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT

PUMP NO.3 IN BUILDING NO.26

EQUIPMENT ABBREVIATION (PUMP)

IS LOCATED.

ORAL EVACUATION

LABORATORY VACUUM

LABORATORY AIR

TEMPERED WATER RETURN

TEMPERED WATER SUPPLY

INDUSTRIAL AIR

LA

LV

OA

IA

TWR

TWS

FILTERED COLD WATERFCW

FUEL OIL DISCHARGEFOD

ANCHOR

CONNECTION - SIDE

ECCENTRIC REDUCER

CONNECTION - BOTTOM, 45° OR 90°

CONNECTION - TOP, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

RISE OR DROP IN PIPE

STRAINER

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES

PIPING ACCESSORIES

INVERTED BUCKET TRAP SET INCLUDING

FLOOR DRAIN (FD), SIZE & TYPE

ROOF DRAIN (RD), SIZE & TYPE

FLOOR SINK (FS), SIZE & TYPE

NATURAL GAS BELOW GRADE (G)

SUMP OR SEWAGE PUMP DISCHARGE (SPD)

CONDENSATE DRAIN (CD)

INDIRECT DRAIN (ID)

NATURAL GAS (G)

NITROUS OXIDE (NO)

LIQUIFIED PETROLEUM GAS (LPG)

FIRE PROTECTION (FP)

WATER SERVICE (WS)

COMPRESSED AIR (CA)

NITROGEN (N)

MEDICAL AIR (MA)

OXYGEN (O)

DOMESTIC HOT WATER RECIRC.

SOIL PIPING - ABOVE FLOOR (S)

SOIL PIPING - BELOW FLOOR (S)

STORM DRAIN - ABOVE FLOOR (ST)

STORM DRAIN - BELOW FLOOR (ST)

ACID WASTE - ABOVE FLOOR (AW)

ACID WASTE - BELOW FLOOR (AW)

DOMESTIC COLD WATER

DOMESTIC HOT WATER

140° DOMESTIC HOT WATER (140°)

WASTE PIPING - ABOVE FLOOR (W)

WASTE PIPING - BELOW FLOOR (W)

GREASE WASTE - ABOVE FLOOR (GW)

GREASE WASTE - BELOW FLOOR (GW)

SOFTENED COLD WATER (SCW)

ACID VENT (AV)

VENT PIPING (V)

HOSE BIBB (HB)

NONFREEZE WALL HYDRANT (NW)

WALL CLEANOUT (WCO)

FLOOR CLEANOUT (FCO)

EXTERIOR CLEANOUT (ECO)

THERMOSTATIC MIXING VALVE

BACKFLOW PREVENTER

OVERFLOW STORM DRAIN - ABOVE FLOOR (OST)

NON POTABLE WATER (NPW)

FUEL OIL SUPPLY (FOS)

FUEL OIL RETURN (FOR)

FUEL OIL VENT (FOV)

AUXILIARY CONDENSATE DRAIN (ACD)

VENT BELOW GRADE (VBG)

VENT BELOW FLOOR (VBF)

CARBON DIOXIDE (CO)

MEDICAL VACUUM (MV)

EVACUATION (EV)

MEDICAL VACUUM EXHAUST (VE)

MEDICAL AIR INTAKE (AI)

TRAP PRIMER LINE (T)

WATER METER

MEDIUM PRESSURE NATURAL GAS (MPG)

MEDIUM PRESSURE NATURAL GAS ON ROOF (MPG)

ELBOW DOWN WITH SHUT-OFF VALVE (SOV)

TEE DOWN WITH SHUT-OFF VALVE (SOV)

TEE UP WITH SHUT-OFF VALVE (SOV)

RECIRCULATION PUMP

DIRECTION OF FLOW

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE REMOVED

FLANGE CONNECTION

CLEANOUT

ELBOW DOWN

ELBOW UP

TEE DOWN

ELBOW UP WITH SHUT-OFF VALVE (SOV)

TEE UP

UNION

THERMOMETER

PRESSURE GAUGE

PRESSURE REDUCING VALVE

REDUCER

SHOWER HEADS

JANITORS SINK

DRINKING FOUNTAIN & TYPE

SHOWER

BATHTUB

TANK TYPE WATER CLOSET

COUNTER TOP LAVATORY & TYPE

WALL MOUNTED LAVATORY & TYPE

URINAL SINK & TYPE

BALL VALVE

GATE VALVE WITH 3/4 " HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC FLOW CONTROL VALVE

PRESSURE RELIEF VALVE

GATE VALVE

MANUAL AIR VENT

TEST PLUG (PRESSURE/TEMPERATURE)

GLOBE VALVE

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

AUTOMATIC AIR VENT

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL OR FIRE ALARM PLAN NOTE CALL OUT

TECHNOLOGY PLAN NOTE CALL OUT

PLUMBING EQUIPMENT DESIGNATION

MECHANICAL EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL NUMBER

SHEET NUMBER

LIMIT OF DEMOLITION

TRAP PRIMER LINE - BELOW SLAB (T)

CO

DOUBLE EXTERIOR CLEANOUT (ECO)

CLEANOUTS

DRAINS AND TRAPS

EQUIPMENT

FITTINGS AND ACCESSORIES

SHEET NUMBER

SECTION NUMBER

JANITORS SINK - CORNER

MEDICAL GAS OUTLET (TYPE)

EXISTING TO REMAIN

A

A/E ARCHITECT / ENGINEER

AD AREA DRAIN/ACCESS DOOR

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISH GRADE

AG AIR GAP

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATION, AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY OF ECHANICAL

ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

B

BFP REDUCED PRESSURE BACKFLOW

PREVENTER

BHP BREAK HORSEPOWER

BSP BLACK STEEL PIPE

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C CELSIUS

CA COMPRESSED AIR

CGA COMPRESSED GAS ASSOCIATION

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CO CLEANOUT

CS CLINICAL SINK

CV CONTROL VALVE

D

DCW DOMESTIC COLD WATER

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DHWS DOMESTIC HOT WATER SUPPLY

DI DEIONIZED WATER

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

E

EL ELEVATION

EMCS ENERGY MONOSERRAT

AND CENTRAL SYSTEM

EPA ENVIROMENTAL PROTECTION AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

EWS EYE WASH STATION

EWS/SH EYE WASH/DRENCH SHOWER

EX EXISTING

F

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT (HOSE) CONNECTION

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

G

GAL GALLON

GCO GRADE CLEANOUTS

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED WATER HEATER

H

H&CW HOT AND COLD WATER

HB HOSE BIBB

HD HUB DRAIN

HEX HEAT EXCHANGER

HP HORSEPOWER

HS HAND SINK

HST HOT WATER STORAGE TANK (DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HYD HYDRANT

I

ID INSIDE DIAMETER

IE INVERT ELEVATION

ICW INDUSTRIAL COLD WATER

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

K

KW KILOWATT

KWH KILOWATT-HOUR

L

L/S LITER PER SECOND

LA LABORATORY AIR

LAV LAVATORY

LBS/HR POUNDS PER HOUR

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

MED MEDICAL

MER MECHANICAL EQUIPMENT

ROOM

MH MANHOLE

MOU MEMORANDUM OF

UNDERSTADING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N

N2 NITROGEN

N20 NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM. NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

O

O OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OR OPERATING ROOM

OVFL OVERFLOW

P

PA PASCAL

PD PRESSURE DROP OR DIFFERENCE

PDI PLUMBING AND DRAINAGE

INSTITUTE

PG PRESSURE GAGE

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH

ATMOSPHERE

PSIG POUNDS PER SQUARE INCH

GAGE

PTRV PRESSURE TEMPERATURE RELIEF

VALVE

PW POTABLE WATER

R

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RP RECIRCULATION PUMP

RO REVERSE OSMOSIS WATER

RWL RAIN WATER LEADER

S

SAN SANITARY SEWER

SMACNA SHEET METAL AND AIR

CONDITIONING CONTRACTORS

NATIONAL ASSOCIATION

SCFM STANDARD CUBIC FOOT/MINUTE

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SMH SANITARY MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT/SF SQUARE FEET

SS STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

T

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

V

V VENT

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM PUMP

VS VENT STACK

VSD VARIABLE SPEED DRIVE

VTR VENT THROUGH ROOF

W

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAGE

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

WSFU WATER SUPPLY FIXTURE UNITS

Y

YCO YARD CLEANOUT

YH YARD HYDRANT

26-P 3

PIPING SYMBOLS

ANNOTATION

XX-1

xx

X100

X100

GENERAL PLUMBING SYMBOLS

DENTAL

MEDICAL GASES

STORM

FUEL

EXISTING PIPING

WATER

WASTE

VALVE SYMBOLS

GENERAL EQUIPMENT

FLOOR MOUNTED FLUSH VALVE

WATER

CLOSET

WALL MOUNTED FLUSH VALVE

WATER

CLOSET

ETR

ABBREVIATIONS

ETR EXISTING TO REMAIN

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

FFA FROM FLOOR ABOVE

FFB FROM FLOOR BELOW

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of John E. Sommers, P.E. 22162

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BUILDING 6PLUMBING LEGEND

07/10/2019 JES RLC

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-P-000

589-A5-19-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

Revision # Date

7/10/2019

5" ST (ETR)

5" ST (ETR)

6" ST (ETR)

6" ST (ETR)

6" ST (ETR)

S T

E

T R

6" ST (ETR)

5" ST (ETR)

5" ST (ETR)

S T

E

T R

4" ST (ETR

4" ST (ETR)

5" ST (ETR)

2" ST (ETR)

3" S (ETR)

3" S (ETR)

S

E T

R

3" S (ETR

S T

S T

3" ST

4" ST

S T

4" S

T

S T

4" S

T

4" ST

WATER

SOFTENER

(ETR)

FD (ETR)

FD (ETR)

FD (ETR)

3" x2"

REDUCER

(ETR)

FCO (ETR)

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

4" ST FFA

3" ST FFA

3" ST FFA

6-PLD100B

6-PLD100A

1314 12 11 10 8 7 6 5.1 4.1

U

T

S

R

Q

P

O

N

M

L

9 5 4

A1

A1

A1

A1

A1A1

A1

A1

3" S (ETR)

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of John E. Sommers, P.E. 22162

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BUILDING 6PLUMBING WASTE DEMO PLAN -

BASEMENT WING A FLOOR PLAN

07/10/2019 JES RLC

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-PLD100A

589-A5-19-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

1/8" = 1'-0"1

PLUMBING WASTE DEMO PLAN - BASEMENT WING A FLOOR PLAN

GENERAL NOTES:

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST REMAIN

IN SERVICE 24/7.

2. SEE SHEET GI-001 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE (COR)

BEFORE THE START OF WORK.

4. COORDINATE PLUMBING WORK WITH OTHER TRADES AND CONTRACTORS. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

5. COORDINATE TEMPORARY ROOF DRAINAGE DURING CONSTRUCTION AND REPLACEMENT OF

STORM PIPE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC. CONTRACTOR RESPONSIBLE FOR FIELD

VERIFYING EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF PROPOSAL.

7. ALL PLUMBING FIXTURES SHOWN ON THIS SHEET ARE EXISTING TO BE DEMOLISHED UNLESS

NOTED OTHERWISE.

GENERAL NOTES:

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST REMAIN

IN SERVICE 24/7.

2. SEE SHEET GI-001 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE (COR)

BEFORE THE START OF WORK.

4. COORDINATE PLUMBING WORK WITH OTHER TRADES AND CONTRACTORS. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

5. COORDINATE TEMPORARY ROOF DRAINAGE DURING CONSTRUCTION AND REPLACEMENT OF

STORM PIPE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC. CONTRACTOR RESPONSIBLE FOR FIELD

VERIFYING EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF PROPOSAL.

7. ALL PLUMBING FIXTURES SHOWN ON THIS SHEET ARE EXISTING TO BE DEMOLISHED UNLESS

NOTED OTHERWISE.

PLUMBING DEMO PLAN NOTES:

1 DEMOLISH EXISTING STORM PIPING TO DEMARCATION POINT SHOWN.

Revision # Date

DEDUCT ALTERNATE NOTES:

A1. IF DEDUCT ALTERNATE IS ACCEPTED, DO NOT DEMOLISH EXISTING STORM PIPING.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE OVERALL PROJECT PHASING

SEQUENCE OUTLINED ON ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN WORK ON THIS SHEET IS ALSO

SUBJECT TO THE REDUCED AREAS OF WORK AS DEFINED ON ARCHITECTURAL SHEET 6-GI-105.

S T

E

T R

S T

E

T R

S T

E

T R

5" ST (ETR) 5" ST (ETR) 4" ST (ETR)

4" ST (ETR)

5" ST (ETR)

5" ST (ETR)

S T

E

T R

S T

E

T R

10" ST (ETR)

4" ST

S T

4" S

T

S T

4" ST

4" ST

5" ST4" ST

1 1 1

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

3" ST FFA

4" ST FFA

4" ST FFA

6-PLD100B

6-PLD100A

12 11 10 8 7 6

L

K

J

H

G

F.1

F

E.1

E

D

C

B

A

5 4 3 2 1

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of John E. Sommers, P.E. 22162

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BUILDING 6PLUMBING WASTE DEMO PLAN -

BASEMENT WING B FLOOR PLAN

07/10/2019 JES RLC

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-PLD100B

589-A5-19-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

1/8" = 1'-0"1

PLUMBING WASTE DEMO PLAN - BASEMENT WING B FLOOR PLAN

GENERAL NOTES:

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST REMAIN

IN SERVICE 24/7.

2. SEE SHEET GI-001 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE (COR)

BEFORE THE START OF WORK.

4. COORDINATE PLUMBING WORK WITH OTHER TRADES AND CONTRACTORS. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

5. COORDINATE TEMPORARY ROOF DRAINAGE DURING CONSTRUCTION AND REPLACEMENT OF

STORM PIPE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC. CONTRACTOR RESPONSIBLE FOR FIELD

VERIFYING EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF PROPOSAL.

7. ALL PLUMBING FIXTURES SHOWN ON THIS SHEET ARE EXISTING TO BE DEMOLISHED UNLESS

NOTED OTHERWISE.

PLUMBING DEMO PLAN NOTES:

1 DEMOLISH EXISTING STORM PIPING TO DEMARCATION POINT SHOWN.

Revision # Date

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE OVERALL PROJECT PHASING

SEQUENCE OUTLINED ON ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN WORK ON THIS SHEET IS ALSO

SUBJECT TO THE REDUCED AREAS OF WORK AS DEFINED ON ARCHITECTURAL SHEET 6-GI-105.

4" S (ETR)

S

E T

R

S

E T

R

5" S (ETR)5" S (ETR)4" S (ETR)4" S (ETR) 4" S (ETR)

3" ST

3" ST

3" ST3" ST

3" ST

3" ST

3" ST

4" ST

3" ST

4 (TYP)

(TYP)

(TYP)

(TYP)

1 2 (TYP)

12(TYP)

1 2 (TYP)

3" ST

DRINKING

FOUNTAIN

(ETR)

6-PLD101B

6-PLD101A

1314 12 11 10 8 7 6 5.1 4.1

U

T

S

R

Q

P

O

N

M

L

9 5 4

S

E T

R

2" S FROM

SUMP PUMP

IN BASEMENT

FLOOR

2" V 2" S

S

2" V

4" S (ETR) 4" S (ETR)

2" V

S

S

V

S

2" V 2

S

S

S

2" V

5" S (ETR)

4" S

3" S

2" V

4" S

S

2" V

2" S

V

2" S

S

2" S

2" V

3" S

S 4" S

3" S

3" S

S

2" V

2" S

A1 A2

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of John E. Sommers, P.E. 22162

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BUILDING 6PLUMBING WASTE DEMO PLAN -

LEVEL 1 WING A FLOOR PLAN

07/10/2019 JES RLC

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-PLD101A

589-A5-19-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

1/8" = 1'-0"1

PLUMBING WASTE DEMO PLAN - LEVEL 1 WING A FLOOR PLAN

GENERAL NOTES:

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST REMAIN

IN SERVICE 24/7.

2. SEE SHEET GI-001 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE (COR)

BEFORE THE START OF WORK.

4. COORDINATE PLUMBING WORK WITH OTHER TRADES AND CONTRACTORS. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

5. COORDINATE TEMPORARY ROOF DRAINAGE DURING CONSTRUCTION AND REPLACEMENT OF

STORM PIPE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC. CONTRACTOR RESPONSIBLE FOR FIELD

VERIFYING EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF PROPOSAL.

7. ALL PLUMBING FIXTURES SHOWN ON THIS SHEET ARE EXISTING TO BE DEMOLISHED UNLESS

NOTED OTHERWISE.

PLUMBING DEMO PLAN NOTES:

1 DEMOLISH EXISTING FIXTURES AND ASSOCIATED SANITARY WASTE PIPING BACK TO MAIN IN

CRAWL SPACE. ALL PLUMBING FIXTURES SHOWN ON THIS SHEET ARE EXISTING TO BE

DEMOLISHED UNLESS NOTED OTHERWISE.

2 DEMOLISH EXISTING SANITARY VENT PIPING BACK TO VENT THROUGH ROOF (VTR). VTR TO

REMAIN UNLESS NOTED OTHERWISE.

3 DEMOLISH EXISTING SANITARY WASTE PIPING TO DEMARCATION POINT SHOWN.

4 DEMOLISH EXISTING STORM PIPING FROM CONNECTION AT ROOF DRAIN TO MAIN IN CRAWL

SPACE.

5 CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS.

Revision # Date

DEDUCT ALTERNATE NOTES:

A1. IF DEDUCT ALTERNATE IS ACCEPTED, DO NOT DEMOLISH EXISTING STORM PIPING.

A2. IF DEDUCT ALTERNATE IS ACCEPTED, DO NOT DEMOLISH EXISTING PLUMBING FIXTURES AND

ASSOCIATED SANITARY WASTE AND VENT PIPING.

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE OVERALL PROJECT PHASING

SEQUENCE OUTLINED ON ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN WORK ON THIS SHEET IS ALSO

SUBJECT TO THE REDUCED AREAS OF WORK AS DEFINED ON ARCHITECTURAL SHEET 6-GI-105.

4" S (ETR)4" S (ETR) 4" S (ETR)

4" S

(E

TR

4" S (ETR)

S

E T

R

S

E T

R

4" ST4" ST

3" ST 3" ST

3" ST3" ST

3" ST

3" ST

3" ST

(TYP)

(TYP)

(TYP)

1 2

1 2

12(TYP)

(TYP)

(TYP)

6-PLD101B

6-PLD101A

12 11 10 8 7 6

L

K

J

H

G

F.1

F

E.1

E

D

C

B

A

5 4 3 2 1

V

4" S

2" V

S

2" S

S

S

4" S

V

3" S

3" S

2" S

2" S

3" S

2" S

2" V

S

3" S

S

4" S

3" S

S

S

S

2" V 2" V

S 2" S

V

S

S

S

2" V

2" V

3" V

S

2" S

2" V

V

2" S2" S

V

5 5

5 5

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

FIRE PROTECTION

ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATH, KS 66062

(913) 829-8650

This Document is released for the purpose of interim review under the authority of John E. Sommers, P.E. 22162

WING A

WING B

WING C

WING D

KS ARCH REG. NO. A-1139, EXP. 12/31/2019

KS ENGR REG. NO. E-2586, EXP. 12/31/2019

RENOVATE A & B WING BUILDING 6PLUMBING WASTE DEMO PLAN -

LEVEL 1 WING B FLOOR PLAN

07/10/2019 JES RLC

2200 SW GAGE BLVD

TOPEKA, KS 66622

6-PLD101B

589-A5-19-116

BID DOCUMENTS

on 07/10/2019.

It is not to be used for construction purposes.

1/8" = 1'-0"1

PLUMBING WASTE DEMO PLAN - LEVEL 1 WING B FLOOR PLAN

GENERAL NOTES:

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST REMAIN

IN SERVICE 24/7.

2. SEE SHEET GI-001 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

3. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE (COR)

BEFORE THE START OF WORK.

4. COORDINATE PLUMBING WORK WITH OTHER TRADES AND CONTRACTORS. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

5. COORDINATE TEMPORARY ROOF DRAINAGE DURING CONSTRUCTION AND REPLACEMENT OF

STORM PIPE.

6. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC. CONTRACTOR RESPONSIBLE FOR FIELD

VERIFYING EXISTING DEMOLITION WORK PRIOR TO SUBMISSION OF PROPOSAL.

7. ALL PLUMBING FIXTURES SHOWN ON THIS SHEET ARE EXISTING TO BE DEMOLISHED UNLESS

NOTED OTHERWISE.

PLUMBING DEMO PLAN NOTES:

1 DEMOLISH EXISTING FIXTURES AND ASSOCIATED SANITARY WASTE PIPING BACK TO MAIN IN

CRAWL SPACE. ALL PLUMBING FIXTURES SHOWN ON THIS SHEET ARE EXISTING TO BE

DEMOLISHED UNLESS NOTED OTHERWISE.

2 DEMOLISH EXISTING SANITARY VENT PIPING BACK TO VENT THROUGH ROOF (VTR). VTR TO

REMAIN UNLESS NOTED OTHERWISE.

3 DEMOLISH EXISTING SANITARY WASTE PIPING TO DEMARCATION POINT SHOWN.

4 DEMOLISH EXISTING STORM PIPING FROM CONNECTION AT ROOF DRAIN TO MAIN IN CRAWL

SPACE.

5 CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS.

Revision # Date

DEDUCT ALTERNATE & PHASING:

ALL PLAN WORK SHOWN ON THIS SHEET IS SUBJECT TO THE OVERALL PROJECT PHASING

SEQUENCE OUTLINED ON ARCHITECTURAL SHEET 6-GI-102.

IN ADDITION, IF THE DEDUCT ALTERNATE IS ELECTED, ALL PLAN WORK ON THIS SHEET IS ALSO

3" CW (ETR)

3/4" HWR (ETR)

3" CW (ETR)

1 1/4" HW (ETR)

3/4" HWR (ETR)

/2

IW

S /2

IW

R

C W

/4

H W

/4

H

W R

1/2" IWS

/2

IW

S

1/2" IWS

/2

IW

S

/4

IW

S /4

IW

R

/2

C W

/2

H W

H W

R

3 1/2" CW

1" HWR

1 1/2" HW

/2

C W

/2

H W

H W

R

1/2" IWR

1/2" IWS

1/2" IWR

1/2" IWS

(TYP)

(TYP)

(TYP)

(TYP)

WATER

SOFTNER

(ETR)

3 1/2" CW

6-PPD100B

6-PPD100A

1314 12 11 10 8 7 6 5.1 4.1

U

T

S

R

Q

P

O

N

M

L

9 5 4

3/4" HW

3/4" CW

/4

C

W /4

H

W

3/4" HW

3/4" CW 1" HW

1 1/4" CW

1/2" IWS

2" CW

3/4" HW

3/4" HW

1" CW

3/4" CW

3/4" CW

3/4" HW

1" CW

1" HW 3/4" CW

3/4" HW

/2

H

W

1" CW

3/4" HW

3/4" CW

3/4" CW

/4

C

W

/2

C W

/4

H

W

/4

C

W

1" HW

1 1/2" CW

3/4" CW

3/4" HW

1" CW

1" HW

2" CW

3/4" CW

1/2" IWS TFA 5

1/2" IWS TFA5

3/4" CW

3/4" HW

A2

A1

A3

N W

E S

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL /

CIVIL ENGINEER

F

STAND STRUCTURAL ENGINEERING

11827 W. 112TH STREET, SUITE 200

OVERLAND PARK, KS 66210

(913) 214-2169

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

SPUR DESIGN

11020…