ABBREVIATIONS
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
M METER, SI UNIT
M/s METERS PER SECOND
(OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN
(STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR)
L/m LITERS PER MINUTE (OR
LITERS/MINUTE)
L/s LITERS PER SECOND (OR
LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN
(CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
J INTENTIALLY LEFT BLANK
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
ABBREVIATIONS
E EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE
DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT
EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H HUMIDIFER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN
(STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY
(STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING)
PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
ABBREVIATIONS
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER
MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLER RECTIFIER
SCV STEAM CONDENSATE VENT
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND
DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT
EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING
VALVE
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT
EXCHANGER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER
(SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE)
STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH –
GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR
CONDITIONER
ABBREVIATIONS
YR YEAR
W WATTS
WAG WASTE ANETHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL
OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE)
RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
ABBREVIATIONS
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
DB DECIBELS
Db DRY-BULB TEMPERATURE
DD-1 DESIGN DEVELOPMENT
(SUBMISSION1)
DD-2 DESIGN DEVELOPMENT
(SUBMISSION2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
CD-2 CONSTRUCTION DOCUMENTS
(SUBMISSION2)
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL
DAMPER,MODULATING
ACD-TP AUTOMATIC CONTROL
DAMPER,TWO POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND
REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
C CENTIGRADE (CELCIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE
DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS
(SUBMISSION1)
GENERAL NOTES
1. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN A FURRED CHASE OR ABOVE THE HARD
SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION
OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS,
COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS
TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON
FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING
COILS SHALL BE MADE TO PROVIDE COUNTER FLOW
BETWEEN WATER AND AIR.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
9. SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE
NOTED.
10.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
11.THE CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL
COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 230511, 1.4 (G). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
12.TAB CONTRACTOR SHALL BALANCE EXISTING GRILLES
USING AIRFLOWS DETERMINED IN TAB PRE-BALANCE
REPORT (SEE DEMO DRAWINGS).
SEISMIC BRACING NOTES
SOME MECHANICAL AND PLUMBING COMPONENTS OF THIS
BUILDING REQUIRE SEISMIC BRACING. IT IS THE
RESPONSIBILITY OF THIS CONTRACTOR AND THE GC TO
ENGAGE A SEISMIC DESIGN ENGINEER TO DETERMINE AND
DESIGN THE REQUIRED BRACING FOR EACH SYSTEM.
SYSTEMS REQUIRING BRACING INCLUDE, BUT ARE NOT
LIMITED TO, THE FOLLOWING:
1. ALL LIFE-SAFETY COMPONENTS INCLUDING FIRE
PROTECTION SYSTEMS.
2. COMPONENTS WEIGHING MORE THAN 400 POUNDS.
3. COMPONENTS WITH A CENTER OF MASS GREATER
THAN 4 FEET ABOVE FLOOR LEVEL AND WEIGHING
MORE THAN 20 POUNDS. (E.G. TERMINAL UNITS).
4. DISTRIBUTION SYSTEMS WEIGHING MORE THAN 5
POUNDS PER FOOT. (E.G. 12x12, 22 GAUGE, SHEET
STEEL DUCTWORK AND CHILLED, HEATING,
DOMESTIC HOT, AND DOMESTIC COLD WATER PIPING
LARGER THAN 1 1/2".
FLEXIBLE CONNECTIONS ARE REQUIRED BETWEEN ALL
COMPONENTS AND ASSOCIATED DUCTWORK, PIPING, AND
CONDUITS.
THE FOLLOWING COMPONENTS ARE NOT REQUIRED TO BE
BRACED:
1. PLUMBING FIXTURES
THE CONTRACTOR SHALL PROVIDE ALL COMPONENT
SUBMITTALS WITH COMPONENT WEIGHTS TO SEISMIC
DESIGN ENGINEER FOR USE IN BRACING DESIGN.
BRACING SHALL BE DESIGNED TO MEET ASCE7 AND NFPA
13 BRACING REQUIREMENTS. REFER TO ASCE7 CHAPTER
13 FOR MORE INFORMATION ON SYSTEMS REQUIRED TO BE
BRACED.
TEST AND BALANCE NOTES
THE TEST AND BALANCE SCOPE OF WORK IS AS FOLLOWS:
1. OBTAIN PRE-BALANCE READINGS AS INDICATED ON DEMO
DRAWINGS. PROVIDE EXHAUST AND SUPPLY READINGS.
2. ALL HYDRONIC SYSTEMS SERVING 1-AHU1 INCLUDING:
A. HEATING WATER PIPING SERVING THE
HEATING COIL.
B. LOW PRESSURE STEAM PIPING SERVING THE
HUMIDIFIER.
C. CHILLED WATER PIPING SERVING THE COOLING
COIL.
3. HEATING WATER PIPING SERVING ALL NEW TERMINAL UNITS.
4. ALL COMPONENTS OF THE AIR SYSTEM SERVED BY 1-AHU1
INCLUDING:
A. TERMINAL UNITS.
B. SUPPLY AIR BRANCH DUCTWORK TO DIFFUSERS.
C. RETURN AIR BRANCH DUCTWORK FROM GRILLES.
5. NEW TERMINAL UNITS (AND BRANCH DUCTWORK)
CONNECTED TO EXISING MEDIUM PRESSURE DUCTWORK
SERVED BY (E)AHU-1, 2 AND 3.
6. ALL COMPONENTS OF ALL EXHAUST SYSTEMS INCLUDING:
A. NEW EXHAUST MAINS CONNECTED TO EXISTING
MAINS.
B. NEW EXHAUST BRANCHES AND ASSOCIATED GRILLES.
7. ALL NEW CIRCUIT SETTERS IN DOMESTIC HOT WATER
LOOP. REFER TO PLUMBING SHEETS FOR QUANTITY AND
LOCATION.
NOTE: THIS LIST IS NOT INTENDED TO BE ALL INCLUSIVE. REFER
TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
MECHANICAL COVER SHEET
COLUMBIA, MO
BOH FLB04/03/2018
MM001
MECHANICAL SHEET INDEX
MM001 MECHANICAL COVER SHEET
MM002 MECHANICAL COVER SHEET
MD101 FIRST FLOOR HVAC DEMOLITION PLAN
MD102 SECOND FLOOR HVAC DEMOLITION PLAN
MD111 FIRST FLOOR HYDRONICS DEMOLITION PLAN
MD112 SECOND FLOOR HYDRONICS DEMOLITION PLAN
MH101 FIRST FLOOR HVAC PLAN
MH101.2 FIRST FLOOR HVAC PLAN - BID DEDUCT #2
MH102 SECOND FLOOR HVAC PLAN
MH102.1 SECOND FLOOR HVAC PLAN - BID DEDUCT #1
MH103 ROOF HVAC PLAN
MH301 MECHANICAL SECTIONS
MP101 FIRST FLOOR HYDRONICS PLAN
MP101.2 FIRST FLOOR HYDRONICS PLAN - BID DEDUCT #2
MP102 SECOND FLOOR HYDRONICS PLAN
MP201 SNOW MELT PLAN
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-505 MECHANICAL DETAILS
M-511 MECHANICAL CONTROL DIAGRAMS
M-512 MECHANICAL CONTROL DIAGRAMS
M-513 MECHANICAL CONTROL DIAGRAMS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-701 HVAC AIRFLOW BALANCE PLANS
M-702 ROOM AIR BALANCE SCHEDULE
04/04/2018
OVERFLOW
RH
SCH
SH
TH
PS
RC
WB
CSH
SS
LC
M
PIPING SYMBOLS
VACUUM CONDENSATE RETURN
CONDENSATE TRANSFER PUMP SUCTION
CONDENSATE TRANSFER PUMP DISCHARGE
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
VR
CTPS
CTPD
FWPS
FWPD
FEEDWATER SAMPLE (FROM DEAERATOR)
BOILER WATER SAMPLE
CONTINUOUS BLOWDOWN
CF
FWS
BWS
CBD
BO
CHEMICAL FEED
BOILER BLOWOFF
TUBE CLEANER WATER SUPPLYTC
A
OFL
COMPRESSED AIR
COLD WATER (CITY WATER)
LIQUEFIED PETROLEUM GAS IGNITER FUEL
NATURAL GAS IGNITER FUEL
NATURAL GAS MAIN FUEL
HW
SW
CW
FOR
FOS
LPG(I)
G(I)
G
HOT WATER
SOFTENED WATER
FUEL OIL RETURN
FUEL OIL SUPPLY
RISER CLAMP (TYPE 42)*
FLOOR-SUPPORTED PIPE STAND
CLEVIS-TYPE HANGER
VARIABLE SPRING-TYPE HANGER (TYPE 51)*
ROLLER-TYPE HANGER
TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)
TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT
SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*
STANDARD PRACTICE SP-58
SLIDING SUPPORTS (TYPE 35)*
CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*
WALL BRACKET (TYPE 31, 32, 33)*
* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY
DRAWING SYMBOLS
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
AIR TERMINAL SYMBOLS
FAN POWERED VARIABLE VOLUME
TERMINAL UNIT WITH HEATING COIL.
MB
DOUBLE DUCT MIXING BOX.
TERMINAL UNIT WITH REHEAT COIL
PIPING SYMBOLS
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HOT WATER HEATING SUPPLY
CONDENSATE PUMP DISCHARGE
LOW PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
VENT LINE
SOLAR WATER RETURN
SOLAR WATER SUPPLY
GLYCOL-WATER HEATING RETURN
GLYCOL-WATER HEATING SUPPLY
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
REFRIGERANT LIQUID
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRAIN LINE
MAKE-UP WATER
CONDENSER WATER RETURN (TO TOWER)
CHILLED GLYCOL-WATER RETURN
CHILLED GLYCOL-WATER SUPPLY
CONDENSER WATER SUPPLY (FROM TOWER)
HOT WATER HEATING RETURN
HPS
HPR
MPS
MPR
LPS
LPR
PC
HWS
HWR
GHS
GHR
V
SWS
SWR
CWR
CHR
GCR
RL
RS
RHG
CWS
CHS
GCS
MW
D
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURNGRR
GRS
X EXISTING PIPE TO BE REMOVED
GENERAL PIPING SYMBOLS
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PRESSURE GAGE
THERMOMETER
FLOW ELEMENT
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
PIPING ACCESSORIES SEE DETAIL
INVERTED BUCKET TRAP SET INCLUDING
FE
PIPE UP
PIPE DOWN
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
AV
MANUAL AIR VENT
MV
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
QUICK-COUPLE HOSE CONNECTOR
VALVE SYMBOLS
BALL VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC BALANCING CONTROL VALVE
PRESSURE SAFETY VALVE
GATE VALVE - THREADED/FLANGED
GLOBE VALVE - THREADED/FLANGED
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE CONNECTION
WATER BALANCE DEVICE
MODULATING CONTROL BUTTERFLY VALVE
CIRCUIT SETTER VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
HOSE CONNECTOR
WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE
WATER LEVEL CONTROLLER
FLOW METER
DUCTWORK SYMBOLS
LIMIT OF DEMOLITION
(WALL TYPE)
(WALL TYPE)
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER OR TOP GRILLE
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
DNUP RETURN DUCT (UP & DOWN)
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SQUARE 1-WAY CEILING DIFFUSERS
DUCTWORK SYMBOLS
BACK DRAFT DAMPER
BDD
SECTION.)
FC
10x8
FLEXIBLE CONNECTION, EQUIPMENT,
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
FIRE DAMPER
FD
VD
DUCT WITH SOUND LINING
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED
VIBRATION, OR SEISMIC
DUCTWORK SYMBOLS
DUCT MOUNTED COIL
DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)
SUPPLY
RETURN45°
RETURN, NO SPLITTER (45° TAP)
STANDARD BRANCH SUPPLY OR
MANUAL SPLITTER DAMPER
45°
N
2 1
POINT OF CHANGE IN DUCT CONSTRUCTION BY
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
PRESSURE CLASS (IN. OF WATER) WHICH WILL
ACCOMMODATE MAXIMUM OPERATING PRESSURE
COMBINATION FIRE/SMOKE DAMPER
1/24 IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
STAINLESS STEEL DUCT
(ELECTRIC)
F/S DPR
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
TERMINAL UNIT SYMBOLS
2'x4' RADIANT CEILING PANEL
2'x2' RADIANT CEILING PANEL
AIR CURTAIN
A
PTAC
A TWU
THRU WALL AIR CONDITIONING UNIT.
UNIT. LETTER INDICATES UNIT SIZE.
WINDOW TYPE AIR CONDITIONING
LETTER INDICATES UNIT SIZE.
UNIT HEATER (VERTICAL)
UNIT HEATER (HORIZONTAL)
CONVECTOR OR RADIATOR (RECESSED)
LETTER INDICATES UNIT SIZE.
FLOOR MOUNTED VERTICAL CABINET FAN COIL UNIT.
FLOOR MOUNTED VERTICAL RECESSED FAN COIL UNIT.
LETTER INDICATES UNIT SIZE.
CONVECTOR OR RADIATOR (WALL HUNG)
A
FCU
FCU
A
INDICATES UNIT SIZE.
FLOOR MOUNTED HEAT PUMP. LETTER
PTACA
(E)10x8
FIRE PROTECTION RISER LOCATION
H4
H7
A
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
MECHANICAL COVER SHEET
COLUMBIA, MO
BOH FLB04/03/2018
MM002
ACA
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
ACA
ACA
11.5
ACA
ACA
10.6
ACA
ACA
ACA
D.8
D.1
(E)-150
(E)-275
(E X
)1 x
(E)-275(E)-275(E)-275
(EX)12x10
(E X
)1 x
(EX)14x10
(E)-130
(E)-130
(E X)1
0x
(E)-130
(E)-130
(E)-130
(E X
)8 "ø
(E X
)8 "ø
(E X
)1 x
(E)-255
(E)-255
(E)-255
(E X
)1 x
(E)-130
(EX)12x12
(E X
)8 "ø
(EX)8"ø
(EX)10"ø
(EX)12x12
(E X
)1 x
(E)-130
(E)-130
(E X
)1 x
(E)-115
(E)-115 (E)-115
(E)-115
(E X
)1 x
(E X
)2 x
(E)-200
(E)-135
(E X
)1 x
(E)-135
(E)-135
(E)-200 (E)-200
(E X
)1 x
EXISTING PROJECT
AREAS
GENERAL NOTES
1. TAB CONTRACTOR TO PROVIDE TAB PRE-BALANCE REPORT
FOR ALL EXISTING VAV BOXES, AIR HANDLER UNITS,
EXHAUST FANS OR OTHER AIR MOVING SYSTEM(S)
AFFECTED IN REMODEL AREA. PRE-BALANCE REPORT TO
INCLUDE AIRFLOW FROM ALL TERMINAL UNITS, SUPPLY
DIFFUSERS, RETURN GRILLES AND EXHAUST GRILLES.
2. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN A FURRED CHASE OR ABOVE THE HARD
SUSPENDED CEILING.
3. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF
FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE
DIMENSIONS.
4. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
5. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS, COILS,
ETC.
6. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO
EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
7. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON FLOOR
PLANS ARE NECK SIZES.
8. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING
COILS SHALL BE MADE TO PROVIDE COUNTER FLOW
BETWEEN WATER AND AIR.
9. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
10.SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED.
11.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
12.THIS CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL
COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 230511, 1.4 (G). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
DEMOLITION PLAN NOTES
1. REMOVE EXISTING DIFFUSERS/GRILLES.
2. REMOVE EXISTING DUCTWORK.
3. REMOVE EXISTING TERMINAL UNITS.
4. REMOVE EXISTING FIRE ALARM CONTROL PANEL.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR HVAC DEMOLITION PLAN
COLUMBIA, MO
BOH FLB04/03/2018
MD101
1/8" = 1'-0"
HVAC DEMOLITION PLAN - FIRST FLOOR
4' 8' 16'
1/8" = 1'-0"
0'
N
1" = 80'-0"
KEY PLAN - EXISTINGN
(EX)14x10 (EX)14x10
(EX)16x10
(EX)12x10
(E X
)1 x
(EX)16x6
(EX)16x12
(E X
)1 x
(E)-270
(E)-240
(E)-200
(E)-240
(E)-200
(E)-250
(E)-250
(EX)12x12
(EX)8"ø
(E X
)1 "ø
(E)-270
(E)-380 (E)-310
(E)-380 (E)-310 (E)-310
(E)-310
(E)-310
(E)-310
(E X
)2 x
(EX)16x16
(E X
)1 x
(E X
)1 x
(E X
)4 x
(E X)4
0x
(E X
)1 x
(EX)20x16
(E X
)1 x
(EX)8x12
(EX)12x14
(E X
)6 "ø
(E X
)6 "ø
(E X
)6 "ø
(E X
)6 "ø
(E X
)8 "ø
(E X
)8 x
(EX)16x14
(E X
)3 x
(E X
)3 x
(E X
)1 x
(E X
)8 "ø
(EX)8"ø
(E X
)8 "ø
(E X
)1 x
(EX)12x6
(EX)14x8
(E X
)1 x
ACA
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
ACA
ACA
11.5
ACA
ACA
10.6
ACA
ACA
ACA
ACA
D.8
D.1
C.3
B.8
(EX)6x6
(E X
)6 x
(EX)6x6
(E X
)6 x
(E X
)6 x 6 (E
X )8 x
(E)-250
(E)-150 (E)-150
(E)-200
(E)-380
(E)-250
(E)-250
(E)-200
(E)-150
(E)-150
(E)-200
(E)-200
(E)-150
(E)-150
(E)-150
(E)-200
(E)-150
(E)-150
(E)-300
(E)-125
(E)-125
(E)-250
(E)-250
(E)-250
T1.9
200 CFM
5 5 5
T
GENERAL NOTES
1. TAB CONTRACTOR TO PROVIDE TAB PRE-BALANCE REPORT
FOR ALL EXISTING VAV BOXES, AIR HANDLER UNITS,
EXHAUST FANS OR OTHER AIR MOVING SYSTEM(S)
AFFECTED IN REMODEL AREA. PRE-BALANCE REPORT TO
INCLUDE AIRFLOW FROM ALL TERMINAL UNITS, SUPPLY
DIFFUSERS, RETURN GRILLES AND EXHAUST GRILLES.
2. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN A FURRED CHASE OR ABOVE THE HARD
SUSPENDED CEILING.
3. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF
FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE
DIMENSIONS.
4. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
5. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS, COILS,
ETC.
6. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO
EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
7. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON FLOOR
PLANS ARE NECK SIZES.
8. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING
COILS SHALL BE MADE TO PROVIDE COUNTER FLOW
BETWEEN WATER AND AIR.
9. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
10.SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED.
11.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
12.THIS CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL
COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 230511, 1.4 (G). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
EXISTING PROJECT
AREAS
DEMOLITION PLAN NOTES
1. REMOVE EXISTING DIFFUSERS/GRILLES.
2. REMOVE EXISTING DUCTWORK.
3. REMOVE EXISTING TERMINAL UNITS.
4. (NOT USED)
5. RELOCATE EXISTING DIFFUSER/GRILLE TO MATCH
ARCHITECTURAL RCP. EXTEND DUCTWORK AS REQUIRED.
A MAXIMUM LENGTH OF 5' (EXISTING AND NEW OF FLEX
DUCTWORK MAYBE USED FOR SUPPLY.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
SECOND FLOOR HVAC DEMOLITION PLAN
COLUMBIA, MO
BOH FLB04/03/2018
MD102
1/8" = 1'-0"
HVAC DEMOLITION PLAN - SECOND FLOOR
4' 8' 16'
1/8" = 1'-0"
0'
N
1" = 80'-0"
E 1
H
G
Ea
E
D
ACA
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
D.8
D.1
(EX)1" HWS
(EX)1" HWR
(EX)3/4" HWR
(EX)3/4" HWS
(EX)3/4" HWS
(EX)3/4" HWR
(EX)3/4" HWR
(EX)3/4" HWS
(EX)2" HWR
(EX)2" HWS
(EX)3/4" HWS
(EX)3/4" HWR
(EX)1" HWS
(EX)1" HWR
(EX)2" HWR
(EX)2" HWS
(EX)1 1/2" HWR
(EX)1 1/2" HWS
(EX)3/4" HWS
(EX)3/4" HWR
(EX)1" HWR
(EX)1" HWS
(EX)3/4" HWS
(EX)3/4" HWR
(EX)3/4" HWR
(EX)3/4" HWS
(EX)2" HWS
(EX)2" HWR
T
T
T
3H
T
T
EXISTING PROJECT
AREAS
GENERAL NOTES
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES
SHALL BE CONCEALED IN A FURRED CHASE OR ABOVE
THE HARD SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION
OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS,
COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS
TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON
FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND
COOLING COILS SHALL BE MADE TO PROVIDE COUNTER
FLOW BETWEEN WATER AND AIR.
8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON
DRAWINGS ARE TO BE INSTALLED WITH BOTTOM
ELEVATION OF REGISTER AT 7" [175mm] ABOVE FINISHED
FLOOR.
9. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
10.SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE
NOTED.
11.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
12.THIS CONTRACTOR IS RESPONSIBLE FOR SUBMITTING
FULL COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 220511, 1.4 (I). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
13.THERE IS ASBESTOS ON THIS PROJECT. REFER TO
DEMOLITION SPECIFICATIONS FOR PROPER REMOVAL
PROCEDURES.
DEMOLITION PLAN NOTES
1. REMOVE EXISTING THERMOSTAT, CONTROL WIRING AND
BRANCH HWS & HWR PIPING ASSOCIATED WITH TERMINAL
UNIT TO BE REMOVED IN REMODEL AREA.
2. REMOVE EXISTING HUMIDITY CONTROLLER & ASSOCIATED
CONTROL WIRING.
3. EXISTING HOT WATER UNIT HEATER TO BE REMOVED.
DEMO PIPING TO ABOVE CEILING VALVE AND CAP. REMOVE
ASSOCIATED THERMOSTAT AND CONTROL WIRING.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR HYDRONICS DEMOLITION
PLAN
COLUMBIA, MO
BOH FLB04/03/2018
MD111
1/8" = 1'-0"
HYDRONICS DEMOLITION PLAN - FIRST FLOOR
N
4' 8' 16'
1/8" = 1'-0"
0'
1" = 80'-0"
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
D.8
D.1
(EX)1" HWR
(EX)1" HWS
(EX)1 1/4" HWS
(EX)1 1/4" HWR
(EX)3/4" HWR
(EX)3/4" HWS
(EX)1" HWS
(EX)1" HWR
(EX)2" HWS
(EX)2" HWS
(EX)2" HWR
(EX)3/4" HWS
(EX)3/4" HWR
(EX)2" HWS
(EX)2" HWR
(EX)2" HWS
(EX)2" HWR
(EX)3/4" HWS
(EX)3/4" HWR
(EX)2" HWS
(EX)2" HWR
(EX)2" HWS
(EX)2" HWR
(EX)3/4" HWS
(EX)3/4" HWR
(EX)1 1/2" HWR
(EX)1 1/2" HWS
(EX)1" HWR
(EX)1" HWS
(EX)3/4" HWR
(EX)3/4" HWS
(EX)3/4" HWS
(EX)3/4" HWR
(EX)1 1/4" HWS
(EX)1 1/4" HWR
(EX)3/4" HWS
(EX)3/4" HWR
(EX)3/4" HWS
(EX)3/4" HWR
(EX)5"HWR/S RISER
(EX)2" HWR
T
T
T
T
T
T
T
T
T
T
EXISTING PROJECT
AREAS
GENERAL NOTES
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES
SHALL BE CONCEALED IN A FURRED CHASE OR ABOVE
THE HARD SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION
OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS,
COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS
TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON
FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND
COOLING COILS SHALL BE MADE TO PROVIDE COUNTER
FLOW BETWEEN WATER AND AIR.
8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON
DRAWINGS ARE TO BE INSTALLED WITH BOTTOM
ELEVATION OF REGISTER AT 7" [175mm] ABOVE FINISHED
FLOOR.
9. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
10.SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE
NOTED.
11.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
12.THIS CONTRACTOR IS RESPONSIBLE FOR SUBMITTING
FULL COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 220511, 1.4 (I). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
13.THERE IS ASBESTOS ON THIS PROJECT. REFER TO
DEMOLITION SPECIFICATIONS FOR PROPER REMOVAL
PROCEDURES.
DEMOLITION PLAN NOTES
1. DISCONNECT EXISTING 3/4" HWS/HWR PIPING FROM
TERMINAL BOX BEING REMOVED. EXISTING PIPING TO
REMAIN FOR CONNECTION TO NEW BOX.
2. REMOVE EXISTING THERMOSTAT AND CONTROL WIRING
ASSOCIATED WITH TERMINAL UNIT TO BE REMOVED IN
REMODEL AREA.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
SECOND FLOOR HYDRONICS DEMOLITION
PLAN
COLUMBIA, MO
BOH FLB04/03/2018
MD112
1/8" = 1'-0"
HYDRONICS DEMOLITION PLAN - SECOND FLOOR
4' 8' 16'
1/8" = 1'-0"
0'
N
1" = 80'-0"
KEY PLAN - EXISTING
N
DN
(EX)12x8
(E X
)1 x 8 (EX)8"ø (EX)8"ø
(EX)12x12
(E X
)6 x
(E X
)1 x
(EX)6"ø
(E X
)1 x
(EX)10"ø
(EX)16x12 (EX)10"ø
(E X
)8 "ø
(EX)14"ø
(E X
)5 x
(E X
)3 x
(EX)36x12
(E X
)2 x
(E X
)1 x
(E X
)1 x
(E X
)1 x
(EX)12x12
(EX)12"ø
(E X
)1 x
(EX)6x6
(EX)6x6
(EX)6x6
(E X
)1 x
(EX)12x12 (EX)8"ø
(E X
)1 x 0 (E
X )8
"ø (E
X )8
"ø
(EX)6"ø
(EX)6"ø
(EX)10"ø
(EX)12x10
(E X)1
0x
(E X
)8 "ø
(E X
)8 "ø
(EX)12x12
(EX)8"ø
(EX)10"ø
(E X
)1 x
(E X
)1 x
(EX)22x10
(E X
)1 x 0(E
X )8
"ø (E
X )8
"ø
(E X
)1 x
(E X
)1 x
(EX)10"ø
(EX)8"ø
(EX)6"ø (E X
)8 "ø
(E X
)8 "ø
(EX)8"ø
(EX)10x12
(EX)10x12
(EX)28x14
(E X
)1 x
(EX)8"ø
(E X
)8 "ø
(EX)8"ø (EX)8"ø
(EX)12x8
(EX)12x12 (EX)12x8
(EX)8"ø
(EX)12x12
(E X
)6 x
(E X
)1 x
(EX)6"ø
(E X
)1 x
(EX)10"ø
(EX)16x12 (EX)10"ø
(E X
)8 "ø
(EX)14"ø
(E X
)5 x
(E X
)3 x
(EX)36x12
(E X
)2 x
(E X
)1 x
(E X
)1 x
(E X
)1 x
(EX)12x12
(EX)12"ø
(E X
)1 x
(EX)12x8
(EX)12x12
(E X
)1 x
(EX)6x6
(EX)6x6
(EX)6x6
(E X
)1 x
(EX)12x12 (EX)8"ø
(E X
)1 x 0 (E
X )8
"ø (E
X )8
"ø
(EX)6"ø
(E X
)1 x
(E X
)1 "ø
(EX)12x10
(E X
)1 x
(E X
)1 x
(EX)14x10
(EX)16"ø
(E X
)1 "ø
(E X
)8 "ø
(E X)1
0x
(E X
)8 "ø
(E X
)8 "ø
(E X
)8 "ø
(EX)12x12
(EX)8"ø (EX)6"ø
(EX)8"ø
(E X
)1 x
(EX)22x10
(E X
)1 x 0(E
X )8
"ø (E
X )8
"ø
(E X
)1 x
(EX)12x12
(E X
)1 x
(EX)10"ø
(EX)8"ø
(EX)6"ø
(EX)6"ø
(E X
)8 "ø
(EX)8"ø
(EX)10x12
(EX)10x12
(EX)28x14
(E X
)1 x
(EX)8"ø
(E X
)8 "ø
(EX)8"ø (EX)8"ø
ACA
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
ACA
ACA
11.5
ACA
ACA
10.6
ACA
ACA
D.8
D.1
STORAGE
F179
WAITING
F174
CONSULT 1
F174A
CONSULT 2
F174B
CONSULT 3
F174C
AGENT CASHIER
E142
SWAMP
F176
STAIR #11
F173
F.M.S. ENG.
F170
PINPOINT TRAVEL
E144
VAULT
F178
OFFICE
F175
OFFICE
F164
OFFICE
F162
OFFICE
F161
OFFICE
F160
OFFICE
F159
MED ADMIN
E141
LOBBY
C1E3
CORR
F1F21
F177B
PHARMACY WORK
F177
DISPENSING
F177A
VALET
C1E34
INFO. DESK
C1E35
VESTIBULE
C1E32
ENTRY
C1E31
W.C. STOR
E101
LOBBY
C1E3
32x24 RA UP
"ø
"ø x
12"ø x x
32x24
24x20 x x
12"ø 12"ø1
"ø
8"ø
"ø x
"ø
10"ø
12"ø
12"ø 12"ø
12"ø
12"ø
12"ø
12"ø
"ø
8"ø
"ø
SD-15
SD-13
SD-12
SD-12
SD-12
SD-13
SD-12
SD-12
RR-52
14"ø
RR-52
RR-54
SD-13
RR-51 350
RR-53
1-T1.11
125 CFM
1-T1.12
650 CFM
1-T1.13
375 CFM
1-T1.14
250 CFM
1-T1.15
400 CFM
1-T1.16
2700 CFM
1-T1.17
750 CFM
1-T1.18
400 CFM
MH301
MH301
MH301
MH301
24x20 x x
14"ø
26x22
RR-54 750
RR-54
x
10"ø
SD-16
SD-13
RR-51
28x24 24x18
8"ø
24x24 SA UP
RG-63
SD-62
(TYP. OF 4)
(TYP. OF 2)
CORRIDOR
F1F23
TRAVEL
E140
(TYP. OF 5)
(TYP. OF 6)
1-UH-1
1-FD-1
1-FD-2
1-FCU-1
12x12
"ø
10"ø
SD-12
1-T2.18
200 CFM
PROVIDE
TRANSFER
AIR DUCT
RR-51
RR-51
SD-12
SD-12
SD-12
1-T2.16
375 CFM 1
"ø
8"ø
8"ø
"ø
RR-51
RR-53
1-T2.17
450 CFM
SD-12
SD-12
SA-12
S
1-FD-3
1-FD-4
"ø
GENERAL NOTES
1. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN A FURRED CHASE OR ABOVE THE HARD
SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION
OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS,
COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS
TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON
FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING
COILS SHALL BE MADE TO PROVIDE COUNTER FLOW
BETWEEN WATER AND AIR.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
9. SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE
NOTED.
10.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
11.THE CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL
COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 230511, 1.4 (G). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
12.TAB CONTRACTOR SHALL BALANCE EXISTING GRILLES
USING AIRFLOWS DETERMINED IN TAB PRE-BALANCE
REPORT (SEE DEMO DRAWINGS).
ADDITION
REMODEL
AREAS
PLAN NOTES
1. RE-BALANCE EXISITING VAV TERMINAL UNITS TO AIRFLOW
MEASURED IN TAB PRE-BALANCE REPORT (SEE DEMO
DRAWINGS, GENERAL NOTE #1).
2. DUCTWORK PASSING THROUGH AGENT CASHIER SHALL BE
PROTECTED WITH SECURITY BARS. PROVIDE 1/2 INCH (12.7
MM) DIAMETER STEEL WELDED BARS VERTICALLY AND
HORIZONTALLY SIX INCHES (150 MM) ON CENTER.
3. INSTALL HORIZONTAL FIRE DAMPER IN DUCT AT 2ND FLOOR.
PER SPECS, PROVIDE ACCESS PANEL IN DUCT FOR DAMPER
MAINTENANCE.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR HVAC PLAN
COLUMBIA, MO
BOH FLB04/03/2018
MH101
1/8" = 1'-0"
HVAC PLAN - FIRST FLOOR
N
4' 8' 16'
1/8" = 1'-0"
0'
N 1" = 80'-0"
KEY PLAN LEVEL 1
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
ACA
ACA
11.5
ACA
ACA
10.6
ACA
ACA
ACA
D.1
MH301
(EX)12x8
(E X
)1 x
(EX)8"ø (EX)8"ø
(EX)12x12
(E X
)6 x
(E X
)1 x
(EX)6"ø
(E X
)1 x
(EX)10"ø
(EX)16x12 (EX)10"ø
(E X
)8 "ø
(EX)14"ø
(E X
)3 x
(EX)36x12
(E X
)2 x
(E X
)1 x
(E X
)1 x
(E X
)1 x
(EX)12x12
(EX)12"ø
(E X
)1 x
(EX)6x6
(EX)6x6
(EX)6x6
(EX)12x12 (EX)8"ø
(E X
)8 "ø
(E X
)8 "ø
(EX)6"ø
(EX)6"ø
(E X
)1 "ø
(EX)10"ø
(EX)12x10
(EX)16"ø
(E X
)8 "ø
(E X)1
0x
(E X
)8 "ø
(E X
)8 "ø
(E X
)8 "ø
(EX)12x12
(EX)8"ø
(EX)6"ø
(EX)8"ø
(EX)10"ø
(E X
)1 x
(E X
)1 x
(EX)22x10
(E X
)1 x 0(E
X )8
"ø (E
X )8
"ø
(E X
)1 x
(E X
)1 x
(EX)10"ø
(EX)8"ø
(EX)6"ø (E X
)8 "ø
(E X
)8 "ø
(EX)8"ø
(EX)10x12
(EX)10x12
(EX)28x14
(EX)8"ø
(E X
)8 "ø
(EX)8"ø (EX)8"ø
(EX)12x8
(E X
)1 x
(EX)12x12 (EX)12x8
(EX)8"ø (EX)8"ø
(EX)12x12
(E X
)6 x
(E X
)1 x
(EX)6"ø
(E X
)1 x
(EX)10"ø
(EX)16x12 (EX)10"ø
(E X
)8 "ø
(EX)14"ø
(E X
)3 x
(EX)36x12
(E X
)2 x
(E X
)1 x
(E X
)1 x
(E X
)1 x
(EX)12x12
(EX)12"ø
(E X
)1 x
(EX)12x8
(E X
)1 x
(EX)6x6
(EX)6x6
(EX)6x6
(EX)12x12 (EX)8"ø
(E X
)8 "ø
(E X
)8 "ø
(EX)6"ø
(EX)6"ø
(E X
)1 x
(E X
)1 "ø
(EX)10"ø
(EX)12x10
(E X
)1 x 4(E
X )1 x
(EX)16"ø
(E X
)1 "ø
(E X )8
"ø
(E X)1
0x
(E X
)8 "ø
(E X
)8 "ø
(E X
)8 "ø
(EX)12x12
(EX)8"ø
(EX)6"ø
(EX)8"ø
(EX)10"ø
(E X
)1 x
(E X
)1 x
(EX)22x10
(E X
)1 x 0(E
X )8
"ø (E
X )8
"ø
(E X
)1 x
(E X
)1 x
(EX)10"ø
(EX)8"ø
(EX)6"ø
(EX)6"ø (E X
)8 "ø
(E X
)8 "ø
(EX)8"ø
(EX)10x12
(EX)10x12
(EX)28x14
(EX)8"ø
(E X
)8 "ø
(EX)8"ø (EX)8"ø
LOBBY
C1E3
CORR
F1F21
VALET
C1E34
INFO. DESK
C1E35
VESTIBULE
C1E32
ENTRY
C1E31
W.C. STOR
E101
LOBBY
C1E3
ENTR. VEST.
E1100
32x24 RA UP
24x24 SA UP x
32x24
24x20
SD-12
RR-52
SD-13
1-T1.15
400 CFM
1-T1.16
2700 CFM
24x20 x x
26x22
28x24 24x18 20x18
1-T1.19
2300 CFM
SD-63
(TYP. OF 10)
(TYP. OF 7)
(TYP. OF 2)
(TYP. OF 10)
12x12 16x14 18x16 16x14
12x12
22x18 14x14
RG-64
SD-63
18x14
12"ø
SD-62
1-UH-1
PROVIDE
TRANSFER AIR DUCT
1-T2.18
200 CFM
1-T2.17
450 CFM100
SA-12
RR-51
RR-51
RR-51
SD-12
10"ø
SD-12
SD-12
RR-51
"ø
8"ø
AGENT CASHIER
E142
CORRIDOR
F1F23
TRAVEL
E140
"ø
GENERAL NOTES
1. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN A FURRED CHASE OR ABOVE THE HARD
SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION
OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS,
COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS
TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON
FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING
COILS SHALL BE MADE TO PROVIDE COUNTER FLOW
BETWEEN WATER AND AIR.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
9. SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE
NOTED.
10.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
11.THE CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL
COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 230511, 1.4 (G). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
12.TAB CONTRACTOR SHALL BALANCE EXISTING GRILLES
USING AIRFLOWS DETERMINED IN TAB PRE-BALANCE
REPORT (SEE DEMO DRAWINGS).
ADDITION
REMODEL
AREAS
PLAN NOTES
1. RE-BALANCE EXISITING VAV TERMINAL UNITS TO AIRFLOW
MEASURED IN TAB PRE-BALANCE REPORT (SEE DEMO
DRAWINGS, GENERAL NOTE #1).
2. DUCTWORK PASSING THROUGH AGENT CASHIER SHALL BE
PROTECTED WITH SECURITY BARS. PROVIDE 1/2 INCH (12.7
MM) DIAMETER STEEL WELDED BARS VERTICALLY AND
HORIZONTALLY SIX INCHES (150 MM) ON CENTER.
3. INSTALL HORIZONTAL FIRE DAMPER IN DUCT AT 2ND FLOOR.
PER SPECS, PROVIDE ACCESS PANEL IN DUCT FOR DAMPER
MAINTENANCE.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR HVAC PLAN - BID DEDUCT #2
COLUMBIA, MO
BOH FLB04/03/2018
MH101.2
1/8" = 1'-0"
FIRST FLOOR HVAC PLAN - BID DEDUCT #2
4' 8' 16'
1/8" = 1'-0"
0'
N 1" = 80'-0"
EXAM 17
F265
EXAM 16
F266
EXAM 15
F267
CORR
C2F23
CORR
C2F22
WAITING
F263
NURSE
F264
WAITING
F268
EXAM 14
F269
EXAM 18
F262
EXAM 13
F270
EXAM 19
F261
EXAM 20
F260
EXAM 12
F271
EXAM 11
F272
EXAM 21
F259
EXAM 10
F273
EXAM 22
F258
WAITING DILATION
F257
WAITING / DILATION
E209
DIRTY
E253
ELEC
F252
SWAMP
E215
LASER
E255
TLT
F253
EXAM 1
E226
EXAM 2
E225
EXAM 3
E223
EXAM 4
E222
EXAM 5
E221
EXAM 6
E219
EXAM 7
E218
EXAM 8
E217
FUNDUS
E216
VISUAL FIELDS
E211
VISUAL FIELDS
E212
REFRAC
E212A
PROCEDURE
E213
EXAM 9
E220
JAN
E205
EQUIP
E205A
N.S.
E211AWORK RM.
E224A
REFRAC
E210
IMAGING
F256
WAITING
E206
CORR
C2E3
CORR
C2E2
CORR
C2E1
CORR
C2F21
STAIR #11
F248
CORR
C2F24
PRE- CATARACT
E214
CLEAN
E254
ADMIN OFFICE
F255
(EX)12x10 (EX)16x6
(E X
)9 "ø
(E X
)2 x
(EX)12x6
(EX)6x6
(EX)12x10
(EX)20x16(EX)32x16
(E X
)3 x
(E X
)3 x
(E X
)2 x
(E X
)6 "ø
(E X
)6 "ø
(E X
)1 "ø
(E X
)6 "ø
(EX)6"ø
(E X
)1 x
(E X
)6 x
(EX)14x14
(EX)8"ø
(EX)12x10
(EX)12x10
(E X
)8 "ø
(E X
)1 "ø
(E X
)2 x
(EX)14x8 (EX)14x8
(EX)10"ø
(E X
)1 "ø
(E X
)1 "ø
(E X
)1 x
(EX)8x8
(E X
)8 x
(E X
)6 x
(E X
)8 "ø
(EX)8"ø
(E X
)1 x
(E X
)1 x 6 (E
X )8
"ø
(E X
)8 "ø
(EX)20x16(EX)16x14
(E X
)8 "ø (EX)8"ø
(EX)10"ø
(EX)16x6
(EX)16x10
(EX)14x10 (EX)14x10
(E X
)1 x
(E X )6
"ø
(E X
)6 x
(E X
)1 "ø
(EX)10"ø (EX)10"ø
(EX)6"ø
(E)-240
(E)-240
(E)-270
(E)-250
(E)-250
(E)-200
(E)-380 (E)-380 (E)-310
(E)-310 (E)-310
(E)-310
(E)-310
(E)-310
(E X
)2 x
(EX)12x6
(EX)6x6
(EX)12x10
(EX)20x16(EX)32x16
(E X
)3 x
(E X
)4 x
(E X
)6 "ø
(E X
)6 "ø
(E X
)1 "ø
(E X
)6 "ø
(EX)6"ø
(E X
)1 x
(E X
)6 x
(EX)14x14
(EX)8"ø
(EX)12x10
(EX)12x10
(E X
)8 "ø
(EX)12x10
(E X
)1 "ø
(E X
)2 x
(EX)14x8 (EX)14x8
(EX)10"ø
(E X
)1 "ø
(E X
)1 "ø
(E X
)1 x
(EX)8x8
(EX)8"ø
(E X
)8 "ø
(E X
)1 x
(E X
)1 x 6 (E
X )8
"ø
(EX)20x16(EX)16x14
(EX)12x12 (EX)10"ø
(E X
)1 x
(E X )6
"ø
(E X
)6 x
(E X
)1 "ø
(EX)10"ø (EX)10"ø
(EX)6"ø
(E)-200
(E)-240
(E)-270
(E)-380
RELOCATE
(E) DIFFUSER
SD-12
SD-12
SD-12
SD-12
SD-12
ACA
B
ACA
B
ACA
C
ACA
C
ACA
D
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E
ACA
E.1
ACA
F
ACA
F
ACA
G
ACA
G
ACA
H
ACA
H
ACA
ACA
11.5
ACA
10.6
ACA
ACA
32x20
40x22
20x16
24x24 SA DN 32x24 RA DN
"ø
12"ø x
"ø
SD-13
SD-13
SD-13
SD-12
RR-51
RR-51
RR-51
SD-12
SD-12
SD-12
"ø
10"ø
SD-12
SD-13
SD-14
RR-51
SD-12
20x16 x x
12"ø
10"ø x x
12"ø
12"ø
"ø
10"ø
8"ø
10"ø
"ø
"ø
8"ø
"ø 8"ø 8"ø
8"ø
10"ø
8"ø
12"ø
"ø
1-T1.01
100 CFM
1-T1.02
650 CFM
1-T1.04
350 CFM
1-T1.03
300 CFM
1-T1.05
800 CFM
1-T1.07
375 CFM
1-T1.06
500 CFM
1-T1.10
600 CFM
1-T1.08
400 CFM
1-SAS1
1-SAS2
1-SAR1
1-SAR2
EG-51
SD-11
EG-51
EG-51
1-T2.15
675 CFM
SD-12
SD-12
1-T2.01
400 CFM
1-T2.02
100 CFM
1-T2.04
150 CFM
1-T2.10
300 CFM
1-T2.11
930 CFM
1-T2.09
600 CFM
1-T2.08
600 CFM
1-T2.07
200 CFM
1-T2.13
710 CFM
1-T2.12
380 CFM
1-T2.06
375 CFM
1-T2.05
600 CFM
1-T2.03
200 CFM
1-T2.14
250 CFM
SD-12
SD-12
SD-12
SD-12
SD-12
SD-12
10"ø x
RELOCATE
(E) DIFFUSER
SD-12
SD-12
SD-12
SD-12
SD-13
SD-15
SD-12
32x24
14x14
MH301
MH301
MH301
MH301
MH301
34x20
14x14
8"ø
12"ø 10"ø 8"ø
14"ø12"ø
"ø x
20x14
RR-52
SD-12
10x10
UP TO
1-EF-1
"ø
RR-54
x
"ø x
RR-52
RR-53
12x10
RR-54
12"ø
14x12
RR-54
"ø x
MH301
RR-52200
RR-52
RR-54
RR-54
SD-15
RR-51
SD-15
RR-51
RR-53
RR-53
MH301
RR-53
RR-53
"ø
"ø
40x24
RR-51
SD-12
1-T1.09
500 CFM
(TYP. OF 2)
(TYP. OF 2)
S
S S
(EX)10"ø
"ø
"ø
"ø
"ø
GENERAL NOTES
1. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN A FURRED CHASE OR ABOVE THE HARD
SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION
OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS,
COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS
TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON
FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING
COILS SHALL BE MADE TO PROVIDE COUNTER FLOW
BETWEEN WATER AND AIR.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
9. SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE
NOTED.
10.SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS
CAN BE FOUND ON THE EQUIPMENT SCHEDULES.
11.THE CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL
COORDINATION AND LAYOUT DRAWINGS PER
SPECIFICATIONS SECTION 230511, 1.4 (G). COORDINATION
SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.
CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION
DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
COR.
12.TAB CONTRACTOR SHALL BALANCE EXISTING GRILLES
USING AIRFLOWS DETERMINED IN TAB PRE-BALANCE
REPORT (SEE DEMO DRAWINGS).
ADDITION
REMODEL
AREA
PLAN NOTES
1. CLEAN AND RELOCATE EXISTING DIFFUSER. EXTEND
DUCTWORK AS REQUIRED TO LOCATE DIFFUSER AS
SHOWN ON ARCHITECTURAL RCP. COORDINATE WITH
OTHER TRADES.
2. TYP., ALL NEW EXAM ROOMS.
3. DUCT UP TO 1-AHU-1. SEE 1/M-505 FOR DUCT/AHU
ACOUSTICAL REQUIREMENTS.
4. STEAM HUMIDIFIER, SEE SHEET MP102.
5. ALL DUCTWORK 10'-0" DOWNSTREAM OF STEAM
HUMIDIFIER TO BE ALUMINUM CONSTRUCTION. SLOPE
DUCT BACK TO HUMIDIFIER.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
SECOND FLOOR HVAC PLAN
COLUMBIA, MO
BOH FLB04/03/2018
MH102
1/8" = 1'-0"
HVAC PLAN - SECOND FLOOR
4' 8' 16'
1/8" = 1'-0"
0'
N
N 1" = 80'-0"
KEY PLAN LEVEL 2
GENERAL NOTES
1. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN A FURRED CHASE OR ABOVE THE HARD
SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION
OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE
REQUIRED FOR ALL VALVES, TRAPS, DAMPERS,
CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL
SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES
INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS,
COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS
TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON
FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING
COILS SHALL BE MADE TO PROVIDE COUNTER FLOW
BETWEEN WATER AND AIR.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS OF CEILING DIFFUSERS,
REGISTERS, AND GRILLES.
9. SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES
LISTED ARE GAGE PRESSURE UNLESS OTHERWISE
NOTED.
10.SIZES…