CO
DRAWING SYMBOLS
26-P 3
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
PUMP NO.3 IN BUILDING NO.26
EQUIPMENT ABBREVIATION (PUMP)
DRAWING NUMBER WHERE DRAWN
GENERAL PLUMBING SYMBOLS
LIMIT OF DEMOLITION
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
AND EXISTING WORK
POINT OF CONNECTION BETWEEN NEW
PRESSURE GAGE
THERMOMETER
STRAINER
PIPE UP
PIPE DOWN
WALL CLEAN OUT
PLUMBING PIPING SYMBOLS
DOMESTIC HOT WATER, HOT WATER
DOMESTIC COLD WATER, COLD WATER
MEDICAL VACUUM
MEDICAL AIR
DOMESTIC HOT WATER CIRC., HOT WATER RETURN
STORM WATER
DRAIN
MA
MV MV MV
D D D
SD SD SD
SANITARY SEWER
OXYGENO2
PLUMBING VENT
PLUMBING VALVE SYMBOLS
BALL VALVE
BUTTERFLY VALVE
AUTOMATIC FLOW CONTROL VALVE
PLUMBING ABBREVIATIONS
WASTE
WATER CLOSET
WALL CLEANOUT
WATER HAMMER ARRESTER
WATER SUPPLY FIXTURE UNITS
VENT
VACUUM
VENT STACK
VENT THROUGH ROOF
TRENCH DRAIN
TEMPERATURE
THERMOSTATIC MIXING VALVE
TYPICAL
SANITARY SEWER
STAINLESS STEEL
ROOF DRAIN
ROOF LEADER
PLUMBING AND DRAINAGE INSTITUTE
POUNDS PER SQUARE INCH
OXYGEN
OUTSIDE DIAMETER
OVERFLOW DRAIN
NOT TO SCALE
MEDICAL AIR
MEDICAL
MEDICAL VACUUM
LAVATORY
POUNDS PER HOUR
INSIDE DIAMETER
INTERNATIONAL PLUMBING CODE
INDIRECT WASTE
HOT AND COLD WATER
HOSE BIBB
HUB DRAIN
HORSEPOWER
GAL
GPH
GPM
F
FD
FS
FU
EL
EWS
EX
CW
DFU
DN
DOE
DW
DWG
DWV
CI
CO
BFP
BTU
BTUH
ARCHITECT / ENGINEER
AREA DRAIN/ACCESS DOOR
ABOVE FINISH FLOOR
AIR GAP
ACCESS PANEL
AMERICAN SOCIETY OF HEATING,
REFRIGERATION, AIR CONDITIONING
ENGINEERS
AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AMERICAN SOCIETY OF PLUMBING
ENGINEERS
W
WC
WCO
WHA
WSFU
V
VAC
VS
VTR
TD
TEMP
TMV
TYP
SAN
SS
RD
RL
PDI
PSI
GALLON
GALLONS PER HOUR
GALLONS PER MINUTE
H&CW
HB
HD
HP
ID
IPC
IW
O2
OD
OFD
NTS
MA
MED
MV
LAV
LBS/HR
A/E
AD
AFF
AG
AP
ASHRAE
ASME
ASPE
REDUCED PRESSURE BACKFLOW
PREVENTER
BRITISH THERMAL UNIT
BRITISH THERMAL UNIT PER HOUR
CAST IRON
CLEANOUT
COLD WATER
DRAINAGE FIXTURE UNITS
DOWN
DEPARTMENT OF ENERGY
DISHWASHER
DRAWING
DRAIN WASTE VENT
ELEVATION
EYE WASH STATION
EXISTING
FAHRENHEIT
FLOOR DRAIN
FLOOR SINK
FIXTURE UNITS
CONTRACTING OFFICER'S REPRESENTATIVECOR
HW
HWC
DOMESTIC HOT WATER
DOMESTIC HOT WATER CIRC
CIRCUIT SETTER
HWCP DOMESTIC HOT WATER CIRCULATION PUMP
CONDENSATE DRAINCD
RAINLEADERRL
FLOOR CLEANOUT
FLOOR CLEANOUTFCO
HYD HYDRANT
WH WALL HYDRANT
ORL OVERFLOW RAIN LEADER
SW STORM WATER
OVERFLOW RAINLEADERORL
PLUMBING PIPING TO BE REMOVED
PL105
A
PL105
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
PLUMBING COVER SHEET
COLUMBIA, MO
JAM DBB04/03/2018
PP001
1. VERIFY JOB SITE CONDITIONS AND DIMENSIONS BEFORE BEGINNING WORK. PLANS ARE
SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST AVAILABLE INFORMATION.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS.
2. NO PIPING, DUCTWORK, ETC. SHALL PENETRATE STRUCTURAL MEMBERS.
3. PROVIDE MISCELLANEOUS CUTTING, PATCHING AND REPAIRING OF FINISHES, ROOF,
WALLS, ETC., AS REQUIRED TO ACCOMMODATE THE NEW WORK.
4. G.C. IS TO PATCH ANY OPENINGS IN CORRIDORS REQUIRED TO BE CONSTRUCTED TO LIMIT
THE TRANSFER OF SMOKE AND IN SMOKE BARRIERS AS REQUIRED TO MEET CODE
REQUIREMENTS. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY EXACT LOCATION,
CONFIGURATION AND ROUTING OF EXISTING SYSTEMS REQUIRED TO REMAIN IN
OPERATION DURING THE PROJECT TO PREVENT DAMAGE DURING DEMOLITION AND
PHASING.
6. REMOVE ALL EXISTING EQUIPMENT, DUCTWORK AND PIPING THAT IS NOT REQUIRED FOR A
WORKING INSTALLATION.
7. COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO INSTALLATION.
8. ALL CUTTING AND PATCHING SHALL BE CLOSELY COORDINATED WITH THE G.C.
9. COORDINATE ROUTING OF PLUMBING, AND HVAC PIPING WITH DUCTWORK, LIGHTS,
ARCHITECTURAL CEILING AND STRUCTURAL ELEMENTS. PIPING SHALL RISE AND DROP,
JOG OR OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL TAKE
PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE MUST BE MAINTAINED FOR
DRAINAGE. REWORK OF INSTALLED WORK TO RESOLVE CONFLICTS RISING FROM LACK OF
COORDINATION SHALL NOT JUSTIFY AN INCREASE IN THE CONTRACT AMOUNT.
10.ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE FIRE STOPPED BY THE
TRADE MAKING THE PENETRATION. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR REQUIREMENTS.
11.DO NOT ROUTE PIPING OR DUCTWORK OVER ELECTRICAL PANELS OR EQUIPMENT. PIPING
OR DUCTWORK SHALL NOT BE ROUTED THROUGH ELECTRICAL ROOMS, TELECOM ROOMS,
OR ELEVATOR EQUIPMENT ROOMS UNLESS SPECIFICALLY SERVING THAT ROOM.
COORDINATE WITH E.C. PROVIDE WATERTIGHT DRIP PAN WITH DRAIN TO NEAREST
APPROVED RECEPTOR WHERE REQUIRED.
12.COORDINATE SIZE AND LOCATION OF ACCESS DOORS IN CONSTRUCTION REQUIRED FOR
ACCESS TO MECHANICAL EQUIPMENT WITH G.C.
13.ALL WORK IS TO CONFORM WITH APPLICABLE CODES AND STANDARDS.
14.COORDINATE ACCESS TO EQUIPMENT AND VALVES INSTALLED ABOVE 'HARD' CEILINGS
AND IN MASONRY CHASES WITH GENERAL CONTRACTOR. PROVIDE LOCKING ACCESS
DOORS FOR INSTALLATION BY CONTRACTOR AS REQUIRED TO SERVICE CONCEALED
DAMPERS, VALVES AND EQUIPMENT.
15.REFER TO ARCH FOR PHASING PLAN AND ALLOWABLE WORK HOURS.
16.THESE DRAWINGS ARE ACCOMPANIED BY SPECIFICATIONS. REFER TO SPECIFICATIONS
FOR FURTHER INFORMATION.
17.COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED BY PARAGRAPH
"SUBMITTAL" IN SPECIFICATION SECTION 220511. CONSTRUCTION SHALL NOT START ON
ANY SYSTEM UNTIL THE COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
18.THIS IS A LIFE SAFETY BUILDING WHICH MEANS IT SHALL REMAIN REASONABLY
OPERATIONAL IN THE CASE OF A SEISMIC EVENT. THEREFORE ALL STATIONARY
EQUIPMENT ON THE FLOOR SHALL BE FIXED RIGIDLY TO THE STRUCTURE. ALL HANGING
PIPING SHALL BE BRACED TO THE STRUCTURE. REFER TO SPECIFICATION SECTION 130541.
1. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY
DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ARCHITECT IMMEDIATELY.
MINOR CHANGES IN THE SCOPE OF THE DEMOLITION WORK SHALL NOT JUSTIFY AN
ADDITIONAL COST.
2. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATING THE PIPING
RISERS OR MAINS VIA SHUT-OFF VALVES. INSTALL NEW ISOLATION VALVES WHERE
REQUIRED FOR COMPLETION OF WORK.
3. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT, ETC. WILL REQUIRE
CAPPING AND SEALING EXISTING MAINS OR BRANCHES AS NECESSARY AND REQUIRED TO
ALLOW THE REMAINING SYSTEMS TO FULLY OPERATE WITHOUT DEGRADATION.
CONTRACTOR SHALL PROVIDE PROTECTIVE PLASTIC DROP CLOTHS TO PROTECT THE
EXISTING OCCUPIED AREAS AND EQUIPMENT FROM DUST AND DEBRIS DURING THE
CONSTRUCTION WORK, AND SHALL CLEAN THE AREAS OF ALL CONSTRUCTION DIRT DAILY,
AND UPON COMPLETION OF THE WORK. REFER TO GENERAL CONDITIONS AND DIVISION 1
SECTIONS IN THE SPECIFICATIONS.
4. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED WITH PROPER FLUID AND
PROPERLY VENTED BY THIS CONTRACTOR, ONCE NEW WORK HAS BEEN INSTALLED.
5. COORDINATE WITH GENERAL CONTRACTOR THE REMOVAL AND REPLACEMENT OF ALL
EXISTING CEILINGS, WALLS, ETC. AS REQUIRED FOR MECHANICAL DEMOLITION WORK.
6. EXISTING PIPING AND EQUIPMENT, ETC., NOT TO BE UTILIZED IN THE COMPLETED BUILDING
SHALL BE DISCONTINUED OR REMOVED AS REQUIRED. ALL ENDS OF DISCONTINUED PIPING
SHALL BE CAPPED IN THE NEAREST WALL, CEILING OR FLOOR SO THAT THEY ARE
COMPLETELY CONCEALED. OPENINGS LEFT IN WALLS, CEILINGS, ETC., WHERE
EQUIPMENT AND PIPE, ETC., ARE REMOVED AND NOT REPLACED, SHALL BE PATCHED
NEATLY WITH SIMILAR MATERIAL TO ADJACENT CONSTRUCTION. REFER TO DRAWINGS
DELINEATING NEW WORK FOR ADDITIONAL INFORMATION REGARDING SYSTEMS OR
PORTIONS OF SYSTEMS WHERE USE IS TO BE DISCONTINUED.
7. EXISTING PIPING, FIXTURES AND EQUIPMENT THAT ARE NOT TO BE REUSED SHALL BE
REMOVED AND SHALL REMAIN THE PROPERTY OF THE OWNER IF THEY WISH TO RETAIN
OWNERSHIP OF SAME. IF NOT, EQUIPMENT SHALL BECOME THE PROPERTY OF THIS
CONTRACTOR AND SHALL BE REMOVED FROM THE SITE AS SOON AS PRACTICAL AND
DISPOSED OF IN ACCORDANCE WITH APPLICABLE LAWS AND REGULATIONS.
8. ALL CUTTING AND CHANNELING OF EXISTING BUILDING SHALL BE ACCOMPLISHED IN A NEAT
AND WORKMANLIKE MANNER WITHOUT REMOVAL OF EXCESS MATERIALS. THIS
CONTRACTOR SHALL PATCH AND REPLACE WITH MATERIAL SIMILAR TO ADJACENT
CONSTRUCTION.
9. WHERE EXISTING PIPING AND EQUIPMENT, ETC., THAT ARE TO BE UTILIZED IN THE
COMPLETED PROGRAM CONFLICT WITH NEW CONSTRUCTION AND THE REQUIRED
DEMOLITION, THEY SHALL BE RELOCATED AND RECONNECTED TO MAINTAIN THE DESIRED
SERVICE.
10.PORTIONS OF EXISTING SYSTEMS MAY BE SHOWN FOR CLARITY EVEN THOUGH IT MAY NOT
BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED
ON ORIGINAL OR REMODEL BUILDING DRAWINGS. CONTRACTOR TO VERIFY ALL EXISTING
CONDITIONS.
11.ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE OWNER AND OCCUPANTS
OF THIS BUILDING SO AS TO PROVIDE THE LEAST AMOUNT OF DISRUPTION OF BUILDING
ACTIVITIES AS POSSIBLE.
12.ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY
DISPOSED OF.
GENERAL NOTES GENERAL DEMOLITION NOTES
PLUMBING SHEET INDEX
PP001 PLUMBING COVER SHEET
PD100 BASEMENT PLUMBING DEMOLITION PLAN
PD100.2 BASEMENT PLUMBING DEMOLITION PLAN - BID DEDUCT #2
PD101 FIRST FLOOR PLUMBING DEMOLITION PLAN
PD101.2 FIRST FLOOR PLUMBING DEMOLITION - BID DEDUCT #2
PD102 SECOND FLOOR PLUMBING DEMOLITION PLAN
PL100 BASEMENT PLUMBING PLAN
PL101 FIRST FLOOR PLUMBING PLAN
PL101.1 FIRST FLOOR PLUMBING - BID DEDUCT #1
PL101.2 FIRST FLOOR PLUMBING - BID DEDUCT #2
PL102 SECOND FLOOR PLUMBING PLAN
PL102.1 SECOND FLOOR PLUMBING - BID DEDUCT #1
PL401 PLUMBING DETAILS
PL501 PLUMBING SCHEDULES
04/04/2018
REMOVE (EX)10"
STORM SEWER
BELOW GRADE
(EX)10" RL ABOVE
CEILING
(EX)4" W, 3" V, 3/4" HWC,
1 1/2" HW, & 2 1/2" CW UP
R L
RL
(EX)8" RL
(EX)8" RL
(EX)4" W
REMOVE (EX)2" W UP
TO DEMO'D LAVATORY.
CAP AT MAIN.
SEE CIVIL DRAWINGS
FOR EXTENT OF
REMOVAL
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. ALL PIPING TO BE REMOVED SHALL BE CAPPED AT THE MAINS,
AND HANGERS REMOVED, UNLESS OTHERWISE NOTED.
4. ALL ACCESSIBLE ABANDONED PIPING SHALL BE REMOVED.
5. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION TO
BE AS LEAST DISRUPTIVE AS POSSIBLE.
6. ALL DEMO WORK ON SHALL BE DONE AT NIGHT AND/OR
WEEKENDS,OR AS DIRECTED BY THE COR.
7. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
EXISTING PROJECT
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
BASEMENT PLUMBING DEMOLITION PLAN
COLUMBIA, MO
JAM DBB04/03/2018
PD100
1/8" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN
N
4' 8' 16'
1/8" = 1'-0"
0'
N 1" = 80'-0"
KEY PLAN - EXISTING
REMOVE (EX)10"
STORM SEWER
BELOW GRADE
(EX)10" RL ABOVE
CEILING
(EX)4" W, 3" V, 3/4" HWC,
1 1/2" HW, & 2 1/2" CW UP
R L
RL
(EX)8" RL
(EX)8" RL
(EX)4" W
(EX)2" W UP
SEE CIVIL DRAWINGS
FOR EXTENT OF
REMOVAL
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. ALL PIPING TO BE REMOVED SHALL BE CAPPED AT THE MAINS,
AND HANGERS REMOVED, UNLESS OTHERWISE NOTED.
4. ALL ACCESSIBLE ABANDONED PIPING SHALL BE REMOVED.
5. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION TO
BE AS LEAST DISRUPTIVE AS POSSIBLE.
6. ALL DEMO WORK ON SHALL BE DONE AT NIGHT AND/OR
WEEKENDS,OR AS DIRECTED BY THE COR.
7. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
EXISTING PROJECT
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
BASEMENT PLUMBING DEMOLITION PLAN -
BID DEDUCT #2
COLUMBIA, MO
JAM DBB04/03/2018
PD100.2
1/8" = 1'-0"
BID DEDUCT #2 - BASEMENT PLUMBING DEMOLITION PLANN
4' 8' 16'
1/8" = 1'-0"
0'
N 1" = 80'-0"
(EX)4" W ABOVE CEILING
R L
(EX)8" RL ABOVE CEILING
(EX)3" W ABOVE CEILING
RL
R L
(EX) WALL HYDRANT -
REMOVE CW BACK
TO MAIN AND CAP.
(EX)4" W UP INTO CHASE
(EX) 2" CW, 1 1/4" HW
& 3/4" HWC VALVED
AND CAPPED ABOVE
CEILING.
RELOCATE (EX) 8" RL, 2 1/2" CW,
1 1/2" HW, 3/4" HW, 3" V, & 4" W RISERS
INTO NEW CHASE ABOVE
REMOVE (EX)2" V
ABOVE CEILING
REMOVE (EX) LAVATORY
AND ASSOCIATED PIPING.
CAP AT MAINS.
H
G
Ea
E
D
D.8
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. ALL PIPING TO BE REMOVED SHALL BE CAPPED AT THE MAINS,
AND HANGERS REMOVED, UNLESS OTHERWISE NOTED.
4. ALL ACCESSIBLE ABANDONED PIPING SHALL BE REMOVED.
5. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION TO
BE AS LEAST DISRUPTIVE AS POSSIBLE.
6. ALL DEMO WORK ON SHALL BE DONE AT NIGHT AND/OR
WEEKENDS,OR AS DIRECTED BY THE COR.
7. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
EXISTING PROJECT
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR PLUMBING DEMOLITION PLAN
COLUMBIA, MO
JAM DBB04/03/2018
PD101
1/8" = 1'-0"
FIRST FLOOR PLUMBING DEMOLITION PLANN
4' 8' 16'
1/8" = 1'-0"
0'
N
PLAN NOTES
1 REMOVE WATER AND WASTE LINE UP TO FIXTURE BEING
REMOVED. CAP AT MAIN.
2 REMOVE (EX) FLOOR DRAIN AND WASTE PIPING.
3 REMOVE (EX) PLUMBING FIXTURE AND ASSOCIATED PIPING.
1" = 80'-0"
H
G
Ea
E
D
D.8
(EX)4" W ABOVE CEILING
R L
(EX)8" RL ABOVE CEILING
(EX)3" W ABOVE CEILING
RL
R L
(EX) WALL HYDRANT -
REMOVE CW BACK
TO MAIN AND CAP.
(EX)4" W UP INTO CHASE
(EX) 2" CW, 1 1/4" HW
& 3/4" HWC VALVED
AND CAPPED ABOVE
CEILING.
RELOCATE (EX) 8" RL, 2 1/2" CW,
1 1/2" HW, 3/4" HW, 3" V, & 4" W RISERS
INTO NEW CHASE ABOVE
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. ALL PIPING TO BE REMOVED SHALL BE CAPPED AT THE MAINS,
AND HANGERS REMOVED, UNLESS OTHERWISE NOTED.
4. ALL ACCESSIBLE ABANDONED PIPING SHALL BE REMOVED.
5. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION TO
BE AS LEAST DISRUPTIVE AS POSSIBLE.
6. ALL DEMO WORK ON SHALL BE DONE AT NIGHT AND/OR
WEEKENDS,OR AS DIRECTED BY THE COR.
7. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
EXISTING PROJECT
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR PLUMBING DEMOLITION - BID
DEDUCT #2
COLUMBIA, MO
JAM DBB04/03/2018
PD101.2
1/8" = 1'-0"
BID DEDUCT #2 - FIRST FLOOR PLUMBING DEMOLITION PLANN
4' 8' 16'
1/8" = 1'-0"
0'
N
PLAN NOTES
1 REMOVE WATER AND WASTE LINE UP TO FIXTURE BEING
REMOVED. CAP AT MAIN.
2 REMOVE (EX) FLOOR DRAIN AND WASTE PIPING.
3 REMOVE (EX) PLUMBING FIXTURE AND ASSOCIATED PIPING.
1" = 80'-0"
REMOVE (EX) SINKS AND ASSOCIATED
PIPING BACK TO MAINS AND CAP.
REMOVE (EX) SINKS AND ASSOCIATED
PIPING BACK TO MAINS AND CAP.
REMOVE (EX) SINKS AND ASSOCIATED
PIPING BACK TO MAINS AND CAP.
REMOVE (EX) SINKS AND ASSOCIATED
PIPING BACK TO MAINS AND CAP.
REMOVE (EX) MEDICAL
GAS ZONE BOX
REMOVE (EX) WATER CLOSET &
LAVATORY, AND ASSOCIATED
PIPING BACK TO MAINS AND CAP.
RELOCATE (EX) 8"
RL, 4" W, 3" V, 3/4"
HWC, 1 1/2" HW,
1/2" CW DOWN.
R L
H
G
Ea
E
D
C
D.8
D.1
C.3
B.8
0.2
(EX)3/4" HWC, 4" W,
1 1/4" HW, 4" V & 2"
CW UP
RL
(EX)8" RL UP
(EX)6" RL UP
(EX)6" RL ABV CLG
(EX)6" RL UP
(EX)8" RL
ABV CLG
REMOVE (EX) VACUUM,
OXYGEN AND MED AIR
BACK TO (EX) VALVES
AND CAP
REMOVE (EX)
VACUUM, OXYGEN
AND MED AIR
PIPING ABOVE
CEILING
REMOVE (EX)
VACUUM, OXYGEN
AND MED AIR
PIPING ABOVE
CEILING
REMOVE (EX)
MED GAS
OUTLETS
REMOVE (EX)
MED GAS
ALARM PANEL
(EX) SINKS AND
ASSOCIATED PIPING TO
REMAIN (TYP 8 PLACES)
REMOVE (EX)
FLOOR DRAIN
REMOVE (EX) MOP
BASIN AND
EMERGENCY
EYEWASH AND
ASSOCIATED PIPING.
(EX)4" VTR
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. ALL PIPING TO BE REMOVED SHALL BE CAPPED AT THE MAINS,
AND HANGERS REMOVED, UNLESS OTHERWISE NOTED.
4. ALL ACCESSIBLE ABANDONED PIPING SHALL BE REMOVED.
5. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION TO
BE AS LEAST DISRUPTIVE AS POSSIBLE.
6. ALL DEMO WORK ON SHALL BE DONE AT NIGHT AND/OR
WEEKENDS,OR AS DIRECTED BY THE COR.
7. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
ADDITION
REMODEL
AREA
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
SECOND FLOOR PLUMBING DEMOLITION
PLAN
COLUMBIA, MO
JAM DBB04/03/2018
PD102
1/8" = 1'-0"
SECOND FLOOR PLUMBING DEMOLITION PLAN
4' 8' 16'
1/8" = 1'-0"
0'
N
N 1" = 80'-0"
KEY PLAN LEVEL 2
2" W UP INTO
WALL ABOVE
4" W UP INTO
WALL ABOVE
2" W UP INTO
WALL ABOVE
4" W ABV CLG
CONNECT NEW 4" W
TO (EX) 4" W ABV CLG
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
ACA
10.6
ACA
ACA
ACA
ACA
D.1
5" RL FROM
ABOVE
10" STORM SEWER
BELOW GRADE - SEE
CIVIL FOR CONTIN
SEE DTL 2/PL401 FOR DETAIL
OF PIPE PENETRATION
RL
CONNECT NEW 10"
STORM SEWER TO
(EX) STORM SEWER
(EST. FLOWLINE 4'
BELOW FIN. FLOOR)
10" STORM
SEWER BELOW
FLOOR
RL
(EX)10" RL
ABOVE CEILING
COORDINATE ROUTING OF
10" STORM SEWER TO
AVOID STRUCTURE
SLOPE 10" STORM SEWER
SO THAT IT PASSES BELOW
GRADE BEAM (SEE 4/S502)
TERMINATE 5" ORL
ABOVE GRADE WITH
DOWNSPOUT NOZZLE
5" ORL FROM
ABOVE
5" ORL BELOW RAMP
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND DUCTWORK.
COORDINATE WITH EXISTING EQUIPMENT, PIPING AND
DUCTWORK. NEW PIPING SHALL RISE AND DROP, JOG OR
OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL
TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE
MUST BE MAINTAINED FOR DRAINAGE. ANY EXPENSES RISING
FROM LACK OF COORDINATION SHALL BE MADE AT THE
CONTRACTOR’S EXPENSE.
4. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION
TO BE AS LEAST DISRUPTIVE AS POSSIBLE.
5. ALL WORK SHALL BE DONE AT NIGHT AND/OR WEEKENDS, OR AS
DIRECTED BY THE COR.
6. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION
220511. CONSTRUCTION SHALL NOT START ON ANY SYSTEM
UNTIL THE COORDINATION DRAWINGS HAVE BEEN APPROVED
BY VA.
ADDITION
REMODEL
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
BASEMENT PLUMBING PLAN
COLUMBIA, MO
JAM DBB04/03/2018
PL100
1/8" = 1'-0"
BASEMENT PLUMBING PLAN
4' 8' 16'
1/8" = 1'-0"
0'
N
N 1" = 80'-0"
KEY PLAN LEVEL 1
(EX)3/4"
(EX)8" RL
(EX)4" W
(EX)8" RL
(E X
)2
(EX)2"
(EX)3" W
STORAGE
F179
WAITING
F174
CONSULT 1
F174A
CONSULT 2
F174B
CONSULT 3
F174C
TRAVEL
E140
AGENT CASHIER
E142
SWAMP
F176
CORRIDOR
F1F23
CORRIDOR
F1F22
STAIR #11
F173
F.M.S. ENG.
F170
PINPOINT TRAVEL
E144
VAULT
F178
OFFICE
F175
OFFICE
F164
OFFICE
F162
OFFICE
F161 OFFICE
F160
OFFICE
F159
MED ADMIN
E141
LOBBY
C1E3
CORR
F1F21
F177B
PHARMACY WORK
F177
DISPENSING
F177A
VALET
C1E34
INFO. DESK
C1E35
VESTIBULE
C1E32
W.C. STOR
E101
LOBBY
C1E3
ENTR. VEST.
E1100
P-414
1 1/2" V UP INTO
WALL ABOVE
3" W DOWN IN CHASE
TO BELOW FLOOR W/
4"CO AT BASE
2" W DOWN TO BELOW
FLOOR W/CO AT BASE
P-801
H
G
Ea
E
D
C
ACA
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
D.8
D.1
0.8
5" RL & ORL DOWN
TO BELOW FLOOR
2" W UP INTO
WALL ABOVE (TYP)
RL
R L
2" W UP INTO
WALL ABOVE
3" W & 2" V UP
TO MOP BASIN
2" W UP INTO
WALL ABOVE
3" W UP INTO
CHASE ABOVE
CONNECT NEW 3" W
TO (EX) 4" W ABV
CLG
CONNECT
NEW LINES
TO EXISTING
NEW 8" RL, 4" W, 3" V,
2 1/2" CW, 1 1/2" HW, &
3/4" HWC UP INTO
CHASE ABOVE
CONNECT NEW 3/4"
HWC, 1" HW & 1 1/4"
CW TO (EX) 3/4" HWC,
1 1/4" HW & 2" CW
ABOVE CEILING
1" HW & 1 1/4"
CW UP INTO
WALL ABOVE
3/4" HW UP INTO
WALL ABOVE
3" CO
2" W UP INTO
WALL ABOVE
(TYP)
3" CO
2" W ABOVE
CEILING LEVEL
2" CO
2" W UP
INTO WALL
ABOVE
2" W UP
INTO WALL
ABOVE
2" W UP INTO
WALL ABOVE
CONNECT NEW 2" W
TO (EX) 4" W ABV CLG
1 1/4" CW, 1" HW
& 3/4" HWC
ABOVE CEILING
3/4"
5" RL & ORL UP TO
CHASE ABOVE
CIRCUIT SETTER
BALANCE VALVE,
SET AT 3 GPM
3" CO
3"W
2" CO
3/4"
HOLD TIGHT TO
STRUCTURE TO
AVOID RAISED
CEILINGS
3"CO
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND DUCTWORK.
COORDINATE WITH EXISTING EQUIPMENT, PIPING AND
DUCTWORK. NEW PIPING SHALL RISE AND DROP, JOG OR
OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL
TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE
MUST BE MAINTAINED FOR DRAINAGE. ANY EXPENSES RISING
FROM LACK OF COORDINATION SHALL BE MADE AT THE
CONTRACTOR’S EXPENSE.
4. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION
TO BE AS LEAST DISRUPTIVE AS POSSIBLE.
5. ALL WORK SHALL BE DONE AT NIGHT AND/OR WEEKENDS, OR AS
DIRECTED BY THE COR.
6. PIPE LENGTH FROM RECIRCULATED HOT WATER MAIN TO
LAVATORY HOT WATER STOP SHALL BE NO MORE THAN 18'-0".
7. PIPE LENGTH FROM COLD WATER MAIN TO WATER CLOSET
FLUSH VALVE SHALL BE NO MORE THAN 19'-6".
8. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
ADDITION
REMODEL
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR PLUMBING PLAN
COLUMBIA, MO
JAM DBB04/03/2018
PL101
1/8" = 1'-0"
FIRST FLOOR PLUMBING PLAN
N
4' 8' 16'
1/8" = 1'-0"
0'
N 1" = 80'-0"
KEY PLAN LEVEL 1
Ea
E
D
C
ACA
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
D.8
D.1
0.8
(EX)3/4"
(EX)8" RL
(EX)4" W
(EX)8" RL
(E X
)2
(EX)2"
(EX)3" W
STORAGE
F179
WAITING
F174
CONSULT 1
F174A
CONSULT 2
F174B
CONSULT 3
F174C
TRAVEL
E140
AGENT CASHIER
E142
SWAMP
F176
CORRIDOR
F1F23
CORRIDOR
F1F22
STAIR #11
F173
F.M.S. ENG.
F170
PINPOINT TRAVEL
E144
VAULT
F178
OFFICE
F175
OFFICE
F164
OFFICE
F162
OFFICE
F161
OFFICE
F160
OFFICE
F159
MED ADMIN
E141
LOBBY
C1E3
CORR
F1F21
F177B
PHARMACY WORK
F177
DISPENSING
F177A
VALET
C1E34
INFO. DESK
C1E35
VESTIBULE
C1E32
W.C. STOR
E101
LOBBY
C1E3
ENTR. VEST.
E1100
P-414
1 1/2" V UP INTO
WALL ABOVE
3" W DOWN IN
CHASE TO
BELOW FLOOR
W/ 4"CO AT BASE
CAP 2" WASTE LINE
ABOVE CEILING LEVEL
FOR FUTURE
P-801
5" RL & ORL DOWN
TO BELOW FLOOR
RL
R L
2" W UP INTO
WALL ABOVE
3" W & 2" V UP
TO MOP BASIN
2" W UP INTO
WALL ABOVE
3" W UP INTO
CHASE ABOVE
CONNECT NEW 3" W
TO (EX)4" W ABV CLG
CONNECT
NEW LINES
TO EXISTING
NEW 8" RL, 4" W, 3" V,
2 1/2" CW, 1 1/2" HW, &
3/4" HWC UP INTO
CHASE ABOVE
CONNECT NEW 3/4"
HWC, 1" HW & 1 1/4"
CW TO (EX) 3/4" HWC,
1 1/4" HW & 2" CW
ABOVE CEILING
1" HW & 1 1/4"
CW UP INTO
WALL ABOVE
3/4" HW UP INTO
WALL ABOVE
3" CO
2" W UP INTO
WALL ABOVE
(TYP)
3"CO
2" CO
2" W UP INTO
WALL ABOVE
2" W UP INTO
WALL ABOVE
2" W UP INTO
WALL ABOVE
CONNECT NEW 2" W
TO (EX)4" W ABV CLG
1 1/4" CW, 1" HW
& 3/4" HWC
ABOVE CEILING
3/4"
5" RL & ORL UP
TO CHASE ABOVE
CIRCUIT SETTER
BALANCE VALVE
3"W
3" CO
2" W DOWN TO BELOW
FLOOR W/ CO AT BASE
3" CO
3/4"CW
HOLD TIGHT TO
STRUCTURE TO
AVOID RAISED
CEILINGS
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND DUCTWORK.
COORDINATE WITH EXISTING EQUIPMENT, PIPING AND
DUCTWORK. NEW PIPING SHALL RISE AND DROP, JOG OR
OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL
TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE
MUST BE MAINTAINED FOR DRAINAGE. ANY EXPENSES RISING
FROM LACK OF COORDINATION SHALL BE MADE AT THE
CONTRACTOR’S EXPENSE.
4. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION
TO BE AS LEAST DISRUPTIVE AS POSSIBLE.
5. ALL WORK SHALL BE DONE AT NIGHT AND/OR WEEKENDS, OR AS
DIRECTED BY THE COR.
6. PIPE LENGTH FROM RECIRCULATED HOT WATER MAIN TO
LAVATORY HOT WATER STOP SHALL BE NO MORE THAN 18'-0".
7. PIPE LENGTH FROM COLD WATER MAIN TO WATER CLOSET
FLUSH VALVE SHALL BE NO MORE THAN 19'-6".
8. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
ADDITION
REMODEL
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR PLUMBING - BID DEDUCT #1
COLUMBIA, MO
JAM DBB04/03/2018
PL101.1
1/8" = 1'-0"
FIRST FLOOR PLUMBING PLAN - BID DEDUCT #1
N
4' 8' 16'
1/8" = 1'-0"
0'
1" = 80'-0"
KEY PLAN LEVEL 1
N
Ea
E
D
C
ACA
B
ACA
C
ACA
D
ACA
D.7
ACA
D.8
ACA
E
ACA
E.1
ACA
F
ACA
G
ACA
H
D.8
D.1
0.8
(EX)3/4"
(EX)8" RL
(EX)4" W
(EX)8" RL
(E X
)2
(EX)2"
(EX)3" W
OFFICE
F164
OFFICE
F162
OFFICE
F161
OFFICE
F160
OFFICE
F159
LOBBY
C1E3
CORR
F1F21
VALET
C1E34
INFO. DESK
C1E35
VESTIBULE
C1E32
W.C. STOR
E101
LOBBY
C1E3
1 1/2" V UP INTO
WALL ABOVE
3" W DOWN TO BELOW
FLOOR W/ 4" CO AT BASE
P-801
5" RL & ORL DOWN
TO BELOW FLOOR
RL
R L
2" W UP
INTO WALL
ABOVE
3" W & 2" V UP
TO MOP BASIN
2" W UP INTO
WALL ABOVE
3" W UP INTO
CHASE ABOVE
CONNECT NEW 3" W
TO (EX)4" W ABV
CLG
CONNECT
NEW LINES
TO EXISTING
NEW 8" RL, 4" W, 3" V,
2 1/2" CW, 1 1/2" HW, &
3/4" HWC UP INTO
CHASE ABOVE
CONNECT NEW 3/4"
HWC, 1" HW & 1 1/4" CW
TO (EX) 3/4" HWC,
1 1/4" HW & 2" CW
ABOVE CEILING
1" HW & 1 1/4"
CW UP INTO
WALL ABOVE
3/4" HW UP INTO
WALL ABOVE
3" CO
2" W UP INTO
WALL ABOVE
(TYP)
3" CO
2" CO
2" W UP INTO
WALL ABOVE
2" W UP INTO
WALL ABOVE
2" W UP
INTO WALL
ABOVE
CONNECT NEW 2" W
TO (EX)4" W ABV CLG
1 1/4" CW, 1" HW
& 3/4" HWC
ABOVE CEILING
3/4"
5" RL & ORL UP TO
CHASE ABOVE
CIRCUIT SETTER
BALANCE VALVE,
SET AT 3 GPM
CAP 2" WASTE LINE
ABOVE CEILING LEVEL
FOR FUTURE
ROUGH IN WATER
WASTE AND VENT
FOR FUTURE SINK
3"W
3" CO 2" W DOWN TO BELOW
FLOOR W/ CO AT BASE.
3"CO
3/4"CW
HOLD TIGHT TO
STRUCTURE TO
AVOID FUTURE
RAISED CEILING
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND DUCTWORK.
COORDINATE WITH EXISTING EQUIPMENT, PIPING AND
DUCTWORK. NEW PIPING SHALL RISE AND DROP, JOG OR
OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL
TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE
MUST BE MAINTAINED FOR DRAINAGE. ANY EXPENSES RISING
FROM LACK OF COORDINATION SHALL BE MADE AT THE
CONTRACTOR’S EXPENSE.
4. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION
TO BE AS LEAST DISRUPTIVE AS POSSIBLE.
5. ALL WORK SHALL BE DONE AT NIGHT AND/OR WEEKENDS, OR AS
DIRECTED BY THE COR.
6. PIPE LENGTH FROM RECIRCULATED HOT WATER MAIN TO
LAVATORY HOT WATER STOP SHALL BE NO MORE THAN 18'-0".
7. PIPE LENGTH FROM COLD WATER MAIN TO WATER CLOSET
FLUSH VALVE SHALL BE NO MORE THAN 19'-6".
8. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
ADDITION
REMODEL
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
FIRST FLOOR PLUMBING - BID DEDUCT #2
COLUMBIA, MO
JAM DBB04/03/2018
PL101.2
1/8" = 1'-0"
BID DEDUCT #2 - FIRST FLOOR PLUMBING PLANN
4' 8' 16'
1/8" = 1'-0"
0'
1" = 80'-0"
KEY PLAN LEVEL 1
(E X
)3 /4
(E X
)3 /4
(E X
)2
(E X
)8
(EX)5"
(E X
)5
(EX)8"
(E X
)2
(E X
)1
/4
(E X
)1
(E X
)1
(EX)1"
(EX)1 1/4"
(EX)1"
(EX)2"
(EX)3/4" (EX)3/4"
(E X
)2
(EX)3/4"
(E X
)2
WAITING / DILATION
E209
DIRTY
E253
ELEC
F252
SWAMP
E215
LASER
E255
TLT
F253
EXAM 1
E226
EXAM 2
E225
EXAM 3
E223
EXAM 4
E222
EXAM 5
E221
EXAM 6
E219
EXAM 7
E218
EXAM 8
E217
FUNDUS
E216
VISUAL FIELDS
E211
VISUAL FIELDS
E212
REFRAC
E212A
PROCEDURE
E213
EXAM 9
E220
JAN
E205
EQUIP
E205A
N.S.
E211A
WORK RM.
E224A
REFRAC
E210
IMAGING
F256
EXAM 10
F273
EXAM 22
F258
EXAM 21
F259
EXAM 11
F272
EXAM 12
F271
EXAM 13
F270
EXAM 14
F269
EXAM 18
F262
EXAM 19
F261
EXAM 20
F260
EXAM 15
F267
EXAM 16
F266
EXAM 17
F265
WAITING DILATION
F257
WAITING
E206
CORR
C2E3
CORR
C2E2
CORR
C2E1
CORR
C2F21
STAIR #11
F248
CORR
C2F22
CORR
C2F24
CORR
C2F23
WAITING
F263
NURSE
F264
WAITING
F268
PRE- CATARACT
E214
CLEAN
E254
ADMIN OFFICE
F255
ADMIT
E224
HALL
C2E4
EXAM
F247
EXAM
F244
EXAM
F243
EXAM
F241
EXAM
F240
CORR
C2F20
NEW 8" RL, 4" W, 3" V, 3/4"
HWC,1 1/2" HW,& 2 1/2"
CW DOWN IN CHASE.
P-414
P-414 P-414 P-414
P-414
P-414 P-414 P-414 P-414 P-414
P-414
P-414
P-414
P-414
P-414
P-502
P-115
3" VTR
D.8
D.1
C.3
B.8
0.2
5" RL & ORL
DOWN IN CHASE
5" RD
(3246 SQ FT)
5" ORD
(3246 SQ FT)
P-414 P-414
1 1/2"V
2"V
2"V
1 1/2"V
3/4" HW DOWN
IN WALL
1 1/2" V DOWN
1" HW & 1 1/4" CW
DOWN IN WALL
3/4"
1" P-710
3/4"
P-414
P-414P-414
P-804
CONNECT 2" V
TO (EX)4" V
1 1/2" COND
DRAIN UP TO
RTU
CD
C D
2"V
1/2" DRAIN AND 1" CW
UP TO P-813 ON ROOF
SEE DTL 1/PL401
1 1/2" COND
DRAIN ABOVE
CEILING
CD
DRAIN DOWN IN WALL
AND TERMINATE
ABOVE MOP BASIN
VALVE & CAP 1 1/4" CW
& 1" HW FOR FUTURE
(EX) LAVATORY TO
REMAIN (TYP 8
PLACES)
VALVE AND CONNECT 1/2"
HW & CW TO (EX)1" HW &
1" CW
CONNECT 1 1/2"
VENT LINE TO
(EX) VENT THIS
AREA
VALVE & CONNECT 1 1/4" CW
AND 1/2" HW TO (EX) 2" CW AND
(EX) 1 1/4" HW ABOVE CEILING
(E X
)2
VALVE & CAP 1/2"
HW FOR FUTURE
VALVE AND
CONNECT 3/4"
HW & CW TO (EX)
1" HW & CW
LINES.
VALVE AND
CONNECT 1/2"
HW & CW TO (EX)
1" HW & CW
LINES.
/2
"1 /2
WHA-A
1"
RL
ORL
D
D
D
INSTALL DRAIN COOLER ON
WALL ABOVE MOP BASIN.
VALVE & CONNECT 1/2"CW
TO DRAIN COOLER. RUN
DRAIN COOLER DRAIN LINE
TO ABOVE MOP BASIN.
3/4" DRAIN LINE
ABOVE CEILING. RUN
TO DRAIN COOLER.
1/2" DRAIN LINE FROM
HUMIDIFER (TYP 2 PLACES)
D
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND DUCTWORK.
COORDINATE WITH EXISTING EQUIPMENT, PIPING AND
DUCTWORK. NEW PIPING SHALL RISE AND DROP, JOG OR
OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL
TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE
MUST BE MAINTAINED FOR DRAINAGE. ANY EXPENSES RISING
FROM LACK OF COORDINATION SHALL BE MADE AT THE
CONTRACTOR’S EXPENSE.
4. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION
TO BE AS LEAST DISRUPTIVE AS POSSIBLE.
5. ALL WORK SHALL BE DONE AT NIGHT AND/OR WEEKENDS, OR AS
DIRECTED BY THE COR.
6. PIPE LENGTH FROM RECIRCULATED HOT WATER MAIN TO
LAVATORY HOT WATER STOP SHALL BE NO MORE THAN 18'-0".
7. PIPE LENGTH FROM COLD WATER MAIN TO WATER CLOSET
FLUSH VALVE SHALL BE NO MORE THAN 19'-6".
8. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
ADDITION
REMODEL
AREA
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
SECOND FLOOR PLUMBING PLAN
COLUMBIA, MO
JAM DBB04/03/2018
PL102
1/8" = 1'-0"
PLUMBING PLAN - SECOND FLOOR
4' 8' 16'
1/8" = 1'-0"
0'
N
1" = 80'-0"
KEY PLAN LEVEL 2
D.8
D.1
C.3
B.8
0.2
(E X
)3 /4
(E X
)3 /4
(E X
)2
(E X
)8
(EX)5"
(E
X )5
(EX)8"
(E X
)2
(E X
)1
/4
(E X
)1
(E X
)1
(EX)1"
(EX)1 1/4"
(EX)1"
(EX)2"
(EX)3/4" (EX)3/4"
(E X
)2
(EX)2"(EX)3/4"
(E X
)2
WAITING / DILATION
E209
DIRTY
E253
ELEC
F252
SWAMP
E215
LASER
E255
TLT
F253
EXAM 1
E226
EXAM 2
E225
EXAM 3
E223
EXAM 4
E222
EXAM 5
E221
EXAM 6
E219
EXAM 7
E218
EXAM 8
E217
FUNDUS
E216
VISUAL FIELDS
E211
VISUAL FIELDS
E212
REFRAC
E212A
PROCEDURE
E213
EXAM 9
E220
JAN
E205
EQUIP
E205A
N.S.
E211A
WORK RM.
E224A
REFRAC
E210
IMAGING
F256
EXAM 10
F273
EXAM 22
F258
EXAM 21
F259
EXAM 11
F272
EXAM 12
F271
EXAM 13
F270
EXAM 14
F269
EXAM 18
F262
EXAM 19
F261
EXAM 20
F260
WAITING DILATION
F257
WAITING
E206
CORR
C2E3
CORR
C2E2
CORR
C2E1
CORR
C2F21
STAIR #11
F248
CORR
C2F22
CORR
C2F24
CORR
C2F23
WAITING
F263
NURSE
F264
WAITING
F268
PRE- CATARACT
E214
CLEAN
E254
ADMIN OFFICE
F255
ADMIT
E224
HALL
C2E4
EXAM
F247
EXAM
F244
EXAM
F243
EXAM
F241
EXAM
F240
CORR
C2F20
NEW 8" RL, 4" W, 3" V, 3/4"
HWC,1 1/2" HW,& 2 1/2"
CW DOWN IN CHASE.
P-414
P-414 P-414 P-414
P-414
P-414 P-414 P-414 P-414 P-414
P-414
P-414
P-502
P-115
3"VTR
5" RL & ORL
DOWN IN CHASE
5" RD
(3246 SQFT)
5" ORD
(3246 SQ FT)
P-414 P-414
1 1/2"V
2"V
3/4" HW DOWN IN WALL
1 1/2" V DOWN
1" HW & 1 1/4" CW
DOWN IN WALL
1" P-710
P-414
P-414P-414
P-804
CONNECT 2" V
TO (EX)4" V
1 1/2" COND DRAIN UP
TO RTU
CD
C D
1/2" DRAIN AND 1" CW UP
TO P-813 ON ROOF SEE
DTL 1/PL401
1 1/2" COND
DRAIN ABOVE
CEILING
CD
1 1/2" COND DRAIN
DOWN IN WALL
AND TERMINATE
ABOVE MOP BASIN
VALVE & CAP 1 1/4" CW
& 1" HW FOR FUTURE
(EX) LAVATORY TO
REMAIN (TYP 8
PLACES)
VALVE AND CONNECT 1/2"
HW & CW TO (EX)1" HW &
1" CW
CONNECT 1 1/2"
VENT LINE TO (EX)
VENT THIS AREA
VALVE & CAP 1/2" HWC
FOR FUTURE
VALVE & CAP 3/4" CW &
3/4" HW FOR FUTURE
CAP 2" V ABOVE
CEILING FOR FUTURE
VALVE & CONNECT 1 1/4" CW
AND 1/2" HW TO (EX) 2" CW AND
(EX) 1 1/4" HW ABOVE CEILING
VALVE AND
CONNECT 3/4"
HW & CW TO (EX)
1" HW & CW
LINES.
VALVE AND
CONNECT 1/2"
HW & CW TO (EX)
1" HW & CW
LINES.
/2
"1 /2
WHA-A
RL
ORL
1"
INSTALL DRAIN COOLER ON
WALL ABOVE MOP BASIN.
VALVE & CONNECT 1/2"CW
TO DRAIN COOLER. RUN
DRAIN COOLER DRAIN LINE
TO ABOVE MOP BASIN.
3/4" DRAIN LINE
ABOVE CEILING. RUN
TO DRAIN COOLER.
1/2" DRAIN LINE FROM
HUMIDIFER (TYP 2 PLACES)
D D
DD
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND DUCTWORK.
COORDINATE WITH EXISTING EQUIPMENT, PIPING AND
DUCTWORK. NEW PIPING SHALL RISE AND DROP, JOG OR
OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL
TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE
MUST BE MAINTAINED FOR DRAINAGE. ANY EXPENSES RISING
FROM LACK OF COORDINATION SHALL BE MADE AT THE
CONTRACTOR’S EXPENSE.
4. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION
TO BE AS LEAST DISRUPTIVE AS POSSIBLE.
5. ALL WORK SHALL BE DONE AT NIGHT AND/OR WEEKENDS, OR AS
DIRECTED BY THE COR.
6. PIPE LENGTH FROM RECIRCULATED HOT WATER MAIN TO
LAVATORY HOT WATER STOP SHALL BE NO MORE THAN 18'-0".
7. PIPE LENGTH FROM COLD WATER MAIN TO WATER CLOSET
FLUSH VALVE SHALL BE NO MORE THAN 19'-6".
8. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
ADDITION
REMODEL
AREA
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
SECOND FLOOR PLUMBING - BID DEDUCT
#1
COLUMBIA, MO
JAM DBB04/03/2018
PL102.1
1/8" = 1'-0"
SECOND FLOOR PLUMBING PLAN - BID DEDUCT #1
4' 8' 16'
1/8" = 1'-0"
0'
N
1" = 80'-0"
KEY PLAN LEVEL 2
ROOF HYDRANT DETAIL (P-813)
SCALE: NONE
PIPE PENETRATION THROUGH WALLS BELOW GRADE
SCALE: NONE
ROOF DECKING.
INSULATION.
CAST IRON HYDRANT
SUPPORT ASSEMBLY.
DIVERTER ASSEMBLY.
GALVANIZED STEEL
PIPE CASING.
LEVER OPERATOR
BRASS BACKFLOW
PREVENTER WITH
3/4" MALE HOSE
THREAD OUTLET. ADJUSTABLE LINK
VALVE BODY FOR AUTOMATIC
DRAIN-DOWN OF HYDRANT.
TRANSITION FROM BRANCH
PIPING SIZE TO HYDRANT
INLET SIZE AS REQUIRED.
INSULATED BRANCH COLD
ROOFING, THE GENERAL
CONTRACTOR SHALL FLASH/
SEAL HYDRANT PENETRATION.
EPDM BOOT AND WELL SEAL.
MOUNTING SYSTEM
PROVIDED BY HYDRANT
MANUFACTURER.
INSULATED 1/2" COPPER DRAIN
LINE, PIPE WITH SLOPE TO
APPROVED LOCATION OR
AS INDICATED ON THE
PLUMBING FLOOR PLANS.
WATER PIPING.
[5 0m m
FLEXIBLE EXPANSION JOINT MIN.
DEFLECTION 15" [375mm] MIN. EXPANSION 4" [100mm]
RESILIENT WATERPROOF
CAULKING
5/8" [16mm] ROD
WELD
PIPE CENTERED IN
SLEEVE
1/4"x1/4" [6x6mm] IRON
PIPE CLAMP
STANDARD WEIGHT GAL. STEEL
PIPE SLEEVE
1/4"x1/4" [6x6mm] IRON
PIPE STRAP
MODULAR TYPE WALL
PENETRATION SEAL
FLANGED CONNECTION
[1 m m
INTERIOR SIDE OF
EXISTING WALL
EXTERIOR SIDE OF EXISTING CONCRETE WALL
1/4" [6MM] STEEL PLATE WATER STOP & ANCHOR COLLAR
STAINLESS STEEL BOLTS, NUTS, & WASHERS
1 1/2"V
2"V1 1/2"V
1 1/2"V
1 1/2"V
1 1/2"V
2"V
1 1/2"V
2"V
3"W
3"W
3"W
3"W
4"W
3" VTR
P-414
P-414
P-414
3"CO
3"CO
P-414
CONNECT 4"W
TO (EX)4"W
ABOVE CEILING
P-414
ABOVE FIRST
FLOOR CEILING
P-414
2"W BELOW
FLOOR
P-414
P-414
P-414
3"W DOWN
IN WALL
4" WALL CO
2"CO
2"W BELOW
FLOOR
2"W DOWN
IN WALL
2" WALL CO
P-414
4"W BELOW
FLOOR
PENETRATION
OF (EX) WALL
1/2" DRAIN LINE UP
TO HUMIDIFIER
(TYP 2 PLACES)
3/4" DRAIN LINE
ABOVE CEILING
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
PLUMBING DETAILS
COLUMBIA, MO
JAM DBB04/03/2018
PL401
PLUMBING VENT & RISER DETAIL
SCALE: NONE
MARK
P-115
DESCRIPTION
WATER CLOSET
FLOOR MTD
WASTE
PIPE IN
VENT
PIPE IN
COLD
WATER IN
1.25
HOT
WATER IN
WASTE
FIXTURE
UNITS
WATER
FIXTURE
UNITS
WRIST
BLADE
N/A
HANDLES
ELECTRIC
SENSOR
YES
REMARKS
P-414 LAVATORY 2 1.5 .5 .5 2 2 YES NO
PLUMBING FIXTURE SCHEDULE
P-502 3 2 .75 .75 3 4 N/A NO
SERVICE SINK
P-710 -- -- .5 .5 0 0 NO NO
EMERGENCY
EYE AND FACEWASH
P-801 WALL HYDRANT .75 N/A N/A-- -- -- -- 5
P-804 HOSE BIBB .75 N/A N/A-- -- -- -- --
COMPLETE LAYOUT DRAWINGS SHALL BE REQUIRED BY SPECIFICATION PARAGRAPH, SUBMITTALS.
CONSTRUCTION WORK SHALL NOT START ON ANY SYSTEM UNTIL THE LAYOUT DRAWINGS HAVE
BEEN APPROVED BY VA.
P-813 ROOF HYDRANT 1.0 N/A N/A-- -- -- -- --
FLOOR MTD BACK OUTLET 1.28 GPF
PLUMBING FIXTURE DESCRIPTION
P-115: WATER CLOSET:
BASED ON AMERICAN STANDARD 3312.001 “HURON” FLOOR MOUNTED, BACK OUTLET ELONGATED VITREOUS CHINA WATER CLOSET WITH
TOP SPUD, ANGLE BACK AND BASE, 17-1/8” RIM, BOLT CAPS - SLOAN OPTIMA 111-1.28 ES-S TMO HARD-WIRED SENSOR OPERATED FLUSH
VALVE WITH VACUUM BREAKER, TAILPIECE, DUAL FILTERED BYPASS, TRUE MECHANICAL OVERRIDE - FLOOR MOUNTED CARRIER - WHITE
SOLID PLASTIC ELONGATED OPEN FRONT SEAT, LESS COVER. SET WATER CLOSET SO THAT CENTERLINE IS 16”-18” FROM NEAREST WALL.
P-414: LAVATORY:
BASED ON KOHLER K-2005 “KINGSTON” 20”X18” WALL HUNG VITREOUS CHINA LAVATORY WITH 4” CENTERS, FRONT OVERFLOW, DRILLED FOR
CONCEALED ARM CARRIER - CHICAGO FAUCET 895-317FCXKCP DECK MOUNTED LAVATORY FAUCET WITH GOOSENECK SPOUT, 1.5 GPM
LAMINAR FLOW DEVICE IN SPOUT, WRISTBLADE HANDLES, CERAMIC DISC CARTIDGES - PROVIDE DRAIN WITH GRID STRAINER - CHROME
PLATED WALL SUPPLIES WITH LOOSE KEY STOPS - 1-1/4” CHROME PLATED CAST BRASS “P” TRAP - FLOOR MOUNTED CONCEALED ARM
CARRIER - INSULATE “P” TRAP AND HOT WATER SUPPLY.
P-502: SERVICE SINK, FLOOR MOUNTED:
BASED ON STERN WILLIAMS SB-1700 24”X24”X12” DEEP TERRAZZO MOP BASIN WITH DROP FRONT AND STAINLESS STEEL CAP - CAST BRASS
DRAIN WITH STAINLESS STEEL STRAINER - CHICAGO FAUCET 540-LD897SWXFXKCP SERVICE SINK FAUCET WITH INTEGRAL CHECKSTOPS, SPOUT WITH BUCKET HOOK, 3/4" HOSE THREAD END, VACUUM BREAKER, ADJUSTABLE TOP BRACE, CERAMIC DISC CARTRIDGE - STAINLESS
STEEL BACKSPLASH PANELS ON ADJACENT WALLS - 3” CAST IRON “P” TRAP.
P-710: EMERGENCY EYE AND FACE WASH:
BASED ON BRADLEY S19-270JW WALL MOUNT, SWING DOWN EYE/FACEWASH - BRADLEY S19-2000 THERMOSTATIC MIXING VALVE WITH
TEMPERATURE GAUGE ABOVE CEILING - INSTALL PRESSURE REDUCING VALVE WITH 3-VALVE BYPASS BEFORE TMV. INSTALL
EYE/FACEWASH SO THAT IT CAN SWING DOWN OVER SINK WITHOUT INTERFERING WITH FAUCET OPERATION.
P-801: WALL HYDRANT:
BASED ON WOODFORD MODEL 65 AUTOMATIC DRAINING, FREEZELESS WALL HYDRANT WITH ASSE 1011 APPROVED VACUUM BREAKER.
P804: HOSE BIBB:
BASED ON CHICAGO FAUCET 387-XKCP HOSE BIBB WITH CERAMIC CARTRIDGE, 3/4" HOSE THREAD OUTLET.
P-813: ROOF HYDRANT:
BASED ON WOODFORD RHY2-MS FREEZELESS ROOF HYDRANT WITH ROOF MOUNTING SYSTEM, 3/4” BRASS HOSE NOZZLE WITH BACKFLOW
PREVENTER.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
PLUMBING SCHEDULES
COLUMBIA, MO
JAM DBB04/03/2018
PL501