TYPICAL RECEPTACLE MOUNTING DETAIL
NO SCALE
METAL STUD
CONDUITS
RECEPTACLE
EQUIPMENT GROUND
CONDUCTOR
GROUND SCREW ON
WIRING DEVICE
GROUND SCREW IN
OUTLET BOX
CONDUIT
4 SQUARE OUTLET BOX
DRYWALL
PLASTER RING
PLASTER RING
RECEPTACLE
OUTLET BOX SECURED
TO BOX SUPPORT
GROUND SCREW IN
OUTLET BOX
WIRE NUT (TYP.)
STUD TO STUD BOX
SUPPORT, B-LINE #BB2
SERIES OR EQUAL.
NEUTRAL
CONDUCTORS
HOT CONDUCTORS
TYPICAL TRANSFORMER GROUNDING DETAILTYPICAL HEALTHCARE NAME PLATES
SERIES RATED
BRANCH CIRCUIT/DISTRIBUTION PANELBRANCH CIRCUIT/DISTRIBUTION PANEL
DISCONNECT SWITCH
CONTROL CENTER BREAKER/SWITCH
SWITCHBOARD/DISTRIBUTION PANEL/MOTOR
NO SCALENO SCALE
NOTE: SEE SPECIFICATION SECTION 260500 FOR NAME PLATE
COLOR REQUIREMENTS.
NOTE:
WHERE DEVICES ARE INDICATED TO BE INSTALLED IN
EXISTING WALLS, WALLS SHALL BE CUT AND PATCHED AS
REQUIRED TO INSTALL STUD-TO-STUD SUPPORTS.
PANEL
TYPICAL TRANSFORMER
SYSTEM BONDING JUMPER
H2 X0
X2
X1
H3
H1 X3
MAIN CIRCUIT BREAKER
EQUIPMENT GROUND BUS
BONDED TO CAN
GROUNDING ELECTRODE
CONDUCTOR IN CONDUIT.
SIZE SAME AS BONDING
JUMPER.
FLEXIBLE METAL CONDUIT,
FEEDER, AND EQUIPMENT
ELECTROSTATIC
SHIELDING ON
TRANSFORMER
(IF SPECIFIED)
NEUTRAL BUS (200%
WHEN SPECIFIED)
ISOLATED EQUIPMENT GROUNDING CONDUCTOR
(IF SPECIFIED OR REQUIRED)
FLEXIBLE METAL CONDUIT, FEEDER, AND
SUPPLY SIDE BONDING JUMPER
FROM TRANSFORMER TO PANEL
ISOLATED GROUND BUS (IF SPECIFIED). CONNECT THE
ISOLATED EQUIPMENT GROUNDING CONDUCTOR FROM EACH
CIRCUIT AS SHOWN ON THE DRAWINGS TO THIS BUS.
(ALL OTHER EQUIPMENT GROUNDING CONDUCTORS SHALL BE
CONNECTED TO THE EQUIPMENT GROUND BUS.)
WHERE METAL WATER PIPING OR BUILDING STEEL IS
UNAVAILABLE, GROUND TO ANY OF THE OTHER ELECTRODES
IDENTIFIED IN NEC SECTION 250.52(A).
NOTE:
AT THE TRANSFORMER
LOCATION, GROUND TO THE
NEAREST OF; METAL WATER
PIPE OR BUILDING STEEL.
SUPPLY SIDE BONDING JUMPER PER FEEDER
SCHEDULE (NEC SECTION 250.102(C))
GROUNDING CONDUCTOR
PANEL K
PHASE B: RED
PHASE C: BLUE
PHASE A: BLACK
42,000 A.I.C. WITH
120/208V.,3∅,4W.
1/4"
1/8"
1/8" 1/8"
1/4"
3/8"
GROUND: GREEN
NEUTRAL: WHITE
ISO.GRD.: GRN/YEL
22KA BREAKERS AND1/4"
CLASS 'J' FUSES1/4"
CAUTION - SERIES1/4"
RATED SYSTEM.1/4"
FED FROM DP:**1/4"
1/8"
1/4"
1/4"
PANEL K
PHASE B: RED
PHASE C: BLUE
PHASE A: BLACK
10,000 A.I.C.
120/208V.,3∅,4W.
1/4"
1/8"
1/8" 1/8"
1/4"
3/8"
GROUND: GREEN
NEUTRAL: WHITE
RTU #1
LPJ 200AMP
SERVES
1/8"
1/4" RTU-1
SERVES
ISO.GRD.: GRN/YEL
FED FROM DP:**1/4"
FED FROM DP:**1/4"
CRITICAL BRANCH1/4"
1/4" CRITICAL BRANCH
CRITICAL BRANCH1/4"
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
OFFEROR:
EXPAND PHARMACY AND LOBBY 589-334
ELECTRICAL POWER DETAILS
COLUMBIA, MO
DLD JLW04/04/2018