36C25518R0539 0001 Drawings Renovate Lobby-Vol 6.pdf

View the file

Other files

File Type Posted
36C25518C0223-000.docx DOCX document
36C25518R0539-0005000.docx DOCX document
36C25518R0539-0004001.pdf PDF
36C25518R0539-0004000.docx DOCX document
36C25518R0539-0003001.pdf PDF
36C25518R0539-0003000.docx DOCX document
36C25518R0539-0002002.pdf PDF
36C25518R0539-0002000.docx DOCX document
36C25518R0539-0002001.docx DOCX document
36C25518R0539-0001011.pdf PDF
36C25518R0539-0001003.pdf PDF
36C25518R0539-0001008.pdf PDF
36C25518R0539-0001009.pdf PDF
36C25518R0539-0001001.pdf PDF
36C25518R0539-0001005.pdf PDF
36C25518R0539-0001004.pdf PDF
36C25518R0539-0001014.pdf PDF
36C25518R0539-0001013.pdf PDF
36C25518R0539-0001002.pdf PDF
36C25518R0539-0001010.pdf PDF
36C25518R0539-0001015.pdf PDF
36C25518R0539-0001012.pdf PDF
36C25518R0539-0001007.pdf PDF
36C25518R0539-0001006.pdf PDF
36C25518R0539-0001000.docx DOCX document
36C25518R0539-008.pdf PDF
36C25518R0539-005.pdf PDF
36C25518R0539-001.docx DOCX document
36C25518R0539-003.pdf PDF
36C25518R0539-007.pdf PDF
36C25518R0539-006.pdf PDF
36C25518R0539-004.pdf PDF
36C25518R0539-002.pdf PDF
36C25518R0539-000.docx DOCX document
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PEN WEIGHT LEGEND

LIGHT FIXTURE TO BE REMOVED

EXISTING LIGHT FIXTURE TO REMAIN

NEW LIGHT FIXTURE

LINES ARE TO BE REMOVED.

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK DASHED

DUPLEX GROUNDED RECEPTACLE TO BE REMOVED

EXISTING DUPLEX GROUNDED RECEPTACLE TO REMAIN

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT SOLID

LINES ARE EXISTING TO REMAIN.

LINES ARE NEW TO BE INSTALLED.

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK SOLID

NEW DUPLEX GROUNDED RECEPTACLE

SYMBOL DESCRIPTION

SPECIAL OUTLET SCHEDULE

CR

W

E

T

W

H

'FACP'

FSD

FAAP

TS

x-x x-x

J

H

M

D

R

CH

T

K

P

'A'

K PSS

SS SS

S

A

F

A

CT

WP

U

WAP

CS

BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME

RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE

CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY

BE GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE

CIRCUITS ARE LOCATED IN THE SAME RACEWAY, JUNCTION

BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE

ASSOCIATED WITH. SEE SPECIFICATION SECTION "LOW

VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES"

FOR ADDITIONAL INFORMATION.

WHEN INCREASED CONDUCTOR SIZES ARE SHOWN ON THE

PLANS, THE LARGER CONDUCTOR SIZE SHALL BE USED

THROUGHOUT THE LENGTH OF THE CIRCUIT, INCLUDING

ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST

EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) &

SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED

WITH WIRING AND CONNECTION OF INTERLOCKING AND

CONDUIT RUN W/CONDUCTORS AS INDICATED & GROUND

WIRE SIZED PER N.E.C. 250.122. CONDUIT SIZE AS

"CT" INDICATED ADJACENT TO DEVICE INDICATES DEVICE

MOUNTED ABOVE BACKSPLASH OF COUNTER TOP. VERIFY

EXACT HEIGHT WITH ARCHITECTURAL PLANS AND ELEVATIONS.

REFER TO RELATED ARCHITECTURAL, MECHANICAL, AND

REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE

ALL MOUNTING HEIGHTS TO CENTERLINE OF ITEM UNLESS

OTHERWISE NOTED. VERIFY ALL OUTLET LOCATIONS ON

9.

THE AMERICANS WITH DISABILITIES ACT (ADA).

NEUTRAL AND GROUND.

TO MINIMIZE CUTTING OF BRICK OR BLOCK.

THE JOB PRIOR TO ROUGH-IN.

E.C. SHALL REFER TO MECHANICAL DRAWINGS AND

CONTROLS OF MECHANICAL UNITS AND THERMOSTAT

STRUCTURAL DRAWINGS FOR RELATED INFORMATION.

COORDINATE OUTLET BOX LOCATIONS WITH MASONRY

2.

1.

3.

4.

LOCATIONS.

DRAWINGS.

6.

7.

8.

REQUIRED.

T1.

5.

11.

EACH DATA, TELEPHONE, VIDEO, OR OTHER SYSTEMS

OUTLET REQUIRES 1-1/4"C. WITH PULL ROPE STUBBED 6"

ABOVE NEAREST ACCESSIBLE CEILING UNLESS OTHERWISE

NOTED ON PLANS. CONDUITS STUBBED UP ABOVE CEILINGS

SHALL BE TURNED OUT 90°. PROVIDE INSULATED BUSHINGS

ON ALL CONDUITS. LABEL CONDUIT TO IDENTIFY ITS

INTENDED USE (IE: TELEPHONE, DATA, ETC.).

10.

LOCATE CABLE TRAYS 6" ABOVE CEILING. OFFSET TRAY UP

AND OVER LIGHT FIXTURES AND DUCTWORK (FIELD VERIFY

AND PROVIDE AS REQUIRED). IF PHYSICALLY IMPOSSIBLE

TO RUN CABLE TRAY UP AND OVER, THEN PROVIDE CABLE

SUPPORT HOOKS FROM STRUCTURE ABOVE, SIZED AND

RATED FOR THE INSTALLED CABLES PLUS 25%.

14.

PROVIDE 18" LONG (MIN.) CONDUIT SLEEVES THRU ALL

WALLS WHERE CABLES ARE INDICATED OR REQUIRED TO

PASS THRU WALLS. PROVIDE BUSHINGS ON BOTH ENDS.

SIZE CONDUIT FOR CABLES INSTALLED. AT CABLE TRAYS,

PROVIDE ONE 4" CONDUIT SLEEVE FOR EACH 4" WIDTH OF

CABLE TRAY. MAXIMUMS SHALL BE:

2"C. = 10 CABLES

2 1/2"C. = 20 CABLES

3"C. = 30 CABLES

4"C. = 50 CABLES

13.

LABEL THE FRONT OF EACH RECEPTACLE COVERPLATE

WITH PANEL DESIGNATION AND CIRCUIT NUMBER USING

CLEAR THERMAL TRANSFER (ELECTRONIC DYMO) LABELS

WITH 1/8" HIGH BLACK LETTERS (OR CONTRASTING

COLOR IF PLATES ARE BLACK OR BROWN). LABELS

SHALL BE SUITABLE FOR INDOOR/OUTDOOR USE. LABEL

THE BACK OF EACH LIGHT SWITCH COVERPLATE WITH

PANEL DESIGNATION AND CIRCUIT NUMBER USING A FINE

BLACK PERMANENT MARKER.

JUNCTON BOX OR RECEPTACLE FOR DRINKING FOUNTAINS

SHALL BE LOCATED BEHIND THE EQUIPMENT SKIRT UNLESS

OTHERWISE NOTED. COORDINATE CONNECTION TYPE AND

12.

LOCATION WITH EQUIPMENT PROVIDED.

PROVIDE DIMMER PER THE SPECIFICATIONS. COORDINATE

DIMMER TYPE AND WIRING WITH ASSOCIATED LIGHT FIXTURE

DIMMING REQUIREMENTS (I.E. 3-WIRE, 0-10V, ELECTRONIC

OR MAGNETIC LOW-VOLTAGE, ETC.) OR WITH LIGHTING

CONTROL SYSTEM PROPRIETARY REQUIREMENTS (I.E. LUTRON,

nLIGHT, DALI, ETC.) AS NECESSARY. 3-WIRE DIMMERS SHALL

15.

BE PROVIDED WITH A DEDICATED NEUTRAL FOR EACH

CONTROL ZONE. 0-10V DIMMERS SHALL BE PROVIDED WITH

DIM/ON/OFF CONTROL. COORDINATE PHASE CONTROL OF

LED DRIVERS (I.E. REVERSE PHASE, FORWARD PHASE, ETC.)

WITH LIGHT FIXTURE MANUFACTURER'S RECOMMENDATIONS.

LOW-VOLTAGE CONTROL WIRING IS NOT SHOWN ON PLANS

FOR CLARITY, BUT SHALL BE PROVIDED AS REQUIRED.

F1.

F2.

F3.

FIELD VERIFY LOCATION OF AREA SMOKE DETECTORS AND

HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF A

HVAC DIFFUSER (SUPPLY OR RETURN), IN A DIRECT AIR

FLOW, WITHIN 36" OF A SPRINKLER HEAD, OR WITHIN

36" OF THE TIP OF A CEILING FAN BLADE. SMOKE

DETECTORS FOR DOOR RELEASE SHALL BE LOCATED ON THE

CENTER LINE OF THE DOOR AND A MAXIMUM OF 5 FEET

FROM THE DOOR. THE MINIMUM DISTANCE FROM THE DOOR

IS THE DEPTH OF THE WALL SECTION ABOVE THE DOOR,

BUT NOT LESS THAN 12".

T2. RUN CABLES CONTINUOUS FROM JACK TO ASSOCIATED

T3.

SYSTEM PATCH PANEL IN CONDUIT, CABLE TRAY, OR

J-HOOKS PER THE PLANS AND SPECIFICATIONS. NUMBER

BESIDE CABLE SYMBOL INDICATES QUANTITY OF CABLES

REQUIRED PER HOME RUN.

PROVIDE QUANTITY AND TYPE OF JACKS PER THE

SPECIFICATIONS AND DETAILS. PROVIDE JACK AND CABLE

LABELING PER THE SPECIFICATIONS.

FIRE ALARM DEVICES SHOWN INDICATE THE MINIMUM

REQUIRED. CONTRACTOR TO PROVIDE ALL ADDITIONAL

DEVICES REQUIRED BY CODE AND AUTHORITY HAVING

JURISDICTION.

INTERLOCK DELAYED EGRESS DEVICE WITH FIRE ALARM

SYSTEM TO ALLOW FREE EGRESS WHEN BUILDING IS IN ALARM

CONDITION.

16. CONNECT POWERED PLUMBING FIXTURE SENSOR AS

REQUIRED. COORDINATE ROUGH-IN AND CONNECTION

REQUIREMENTS WITH FIXTURE MANUFACTURER.

17. EXISTING TELEMETRY AND CELL PHONE REPEATER ANTENNAS

TO REMAIN . PROTECT DEVICE AND CABLING DURING

CONSTRUCTION AND REINSTALL IN EXISTING LOCATIONS.

18. DOOR HOLDER TO BE INTEGRATED INTO DOOR CLOSER.

REFERENCE DOOR HARDWARE SPECIFICATIONS.

N1. THE CONTRACTOR SHALL PROVIDE OUTLET BOXES AND 1"

CONDUIT TO ABOVE THE ACCESSIBLE CEILING FOR ALL NURSE

CALL DEVICE LOCATIONS. ALL NURSE CALL DEVICE LOCATIONS

SHALL BE COORDINATED WITH THE FINAL DRAWINGS FROM THE

NURSE CALL SYSTEM SUPPLIER. COORDINATE BACK BOX SIZES

AND ALL OTHER REQUIREMENTS WITH THE NURSE CALL SYSTEM

SUPPLIER PRIOR TO ROUGH-IN. MOUNTING HEIGHT FOR

EMERGENCY BATH STATIONS SHALL BE PER AIA GUIDELINES.

N2. A GASKET SHALL BE INCLUDED FOR DEVICES LOCATED

ADJACENT TO A SHOWER OR TUB. DEVICE MOUNTING HEIGHT

SHALL BE PER AIA GUIDELINES.

A

A

A

A

A

A

A

GENERAL NOTESFIRE ALARM NOTES

TELECOM NOTES

SYMBOL LIST SYMBOL LIST

NURSE CALL NOTES

DUPLEX GROUNDED RECEPTACLE

EMERGENCY CIRCUIT CEIL./WALL

SWITCH LEGS (#12 UON)

GROUND CONDUCTOR (#12 UON)

CONDUIT RUN PARTIAL CIRCUIT. 2#12

CONDUIT RUN 2#12 & 1#12 GRD.-

CONDUIT RUN 2#12 & 1#12 GRD.-

CONDUIT HOME RUN, 2 CIRCUITS

PHASE CONDUCTORS (#12 UON)

NEUTRAL CONDUCTOR (#12 UON)

CEIL./WALL

EARTH/FLOOR

ELECTRICAL DISTRIBUTION EQUIPMENT

BRANCH CIRCUIT PANEL & PANEL DESIG.

FEEDER DESIGNATION

SPECIAL DEVICE (AS NOTED)

FUSTAT BUSS #SSY

JUNCTION BOX

72" TO TOP

SPECIAL OUTLET (SEE SCHEDULE OR AS NOTED)

GROUND FAULT DUPLEX RECEPTACLE

DOUBLE DUPLEX GROUNDED RECEPTACLE

CLG-MTD DUPLEX GROUNDED RECEPT. CEILING MTD

DF

AFF

NL

a,b,c

SWITCHES (KEYED, PILOT)

SINGLE GROUNDED RECEPTACLE

INDICATES SWITCHING SCHEME

NIGHT LIGHT-WIRE AHEAD OF CONTROLS

ABOVE FINISHED FLOOR

DRINKING FOUNTAIN (SEE GEN NOTE 12)

WEATHERPROOF

SEE GENERAL NOTE 9

EXIT LIGHT (SHADING DENOTES EXIT FACE SIDE)

FIXTURE W/SHADED LAMP(S) ON EMERG. POWER

EMERGENCY BATTERY LIGHT FIXTURE

SWITCHES (1-POLE,2-POLE,3-WAY,4-WAY)

LIGHT FIXTURE & FIXTURE LETTER

46"AFF

46"AFF

CEIL./WALL

CEILING

CEIL./WALL

WALL

SYMBOL

LIGHT FIXTURE & FIXTURE LETTER

LIGHT FIXTURE & FIXTURE LETTER

LIGHT FIXTURE & FIXTURE LETTER

DESCRIPTION

CEILING

CEILING

WALL

CEILING

MOUNTING

UON UNLESS OTHERWISE NOTED

DUPLEX GRD. RECEPT. BOTTOM SWITCHED

CEIL./WALL

18"AFF

FLOOR/WALL

STRIP LIGHT FIXTURE & FIXTURE LETTER

EM LIGHT FIXTURE ON EMERGENCY POWER

18"AFF

18"AFF

18"AFF

18"AFF

CEILINGMASTER/SLAVE FIXTURE WHIP

1/2"C.

3/4"C.

GROUND FAULT DOUBLE DUPLEX RECEPTACLE 18"AFF

& 1#12 GRD. 1/2"C.

CEIL./WALL

CEIL./WALL

CONDUIT HOME RUN, 2 CIRCUITS. 4#12

& 1#12 GRD. 1/2"C.

CEIL./WALLCONDUIT HOME RUN, 1 CIRCUIT. 2#12

& 1#12 GRD. 1/2"C.

CEIL./WALLCONDUIT HOME RUN, 3 CIRCUITS. 6#12

& 1#12 GRD. 1/2"C.

CEIL./WALLCONDUIT HOME RUN, 1 CIRCUIT. 2 #10

& 1 #10 GRD. GEN. NOTE 7 & 8#10

EQUIPMENT - SEE EQUIPMENT

CONNECTION SCHEDULE

CONDUIT SLEEVE (GEN NOTE 13)

CABLE TRAY (GEN NOTE 14)

SYMBOL DESCRIPTION MOUNTING

1 RELAY WALL MTD PIR SENSOR 46"AFF

DUAL TECHNOLOGY SENSOR <1000SF CEILING

THERMOSTAT/TEMPERATURE SENSOR

HANDICAP DOOR RELEASE PUSHBUTTON

DIMMER SWITCH (GEN NOTE 15)

PLUGMOLD SURFACE RACEWAY

46"AFF

WALL

46"AFF

46"AFF

1-VOICE OUTLET & JACK (NOTE T1 & T3)

1-VOICE/1-DATA OUTLET & JACKS

1-DATA OUTLET & JACK (NOTE T1 & T3) 18"AFF

18"AFF

WALL 46"AFFW

18"AFF

VOICE UTP CABLE HOME RUN

DATA UTP CABLE HOME RUN

FIBER OPTIC CABLE HOME RUN (MULTI MODE)

GEN NOTE T2

GEN NOTE T2

GEN NOTE T2

(GEN NOTE T1 & T3)

1-VOICE/2-DATA OUTLETS & JACKS 18"AFF

(GEN NOTE T1 & T3)

SECURITY CARD READER

DOOR POSITION SWITCH

WALL

CLG

CCTV CAMERA - FIXED

CCTV CAMERA - FIXED

46"AFFFIRE ALARM MANUAL STATION

FIRE SPRINKLER TAMPER SWITCH

DUCT SMOKE DETECTOR & FIRE/SMOKE

ELECTROMAGNETIC DOOR HOLDER

FIRE SPRINKLER WATER FLOW SWITCH

FIRE ALARM VISUAL SIGNAL

FIRE ALARM SPEAKER

HEAT DETECTOR (GEN NOTE F1)

DUCT SMOKE DETECTOR (GEN NOTE F2)

PHOTO ELECTRIC AREA SMOKE DETECTOR (GEN NOTE F1)

F.A. RELAY (GEN NOTE F3)

CHIME

SPRINKLER RISER

SPRINKLER RISER

DUCTWORK

CEILING

CEILING

FIRE ALARM CONTROL PANEL WALL

80" TO BOTTOM

COMB. F.A. SPEAKER & VISUAL SIGNAL

80" TO BOTTOM

80" TO BOTTOM

DAMPER (GEN NOTE F2 & F4)

46"AFFHAND-WAVE DOOR OPERATOR

DELAYED EGRESS DEVICE (GEN NOTE F6)

ELECTRIC DOOR STRIKE

DE

E

MAGNETIC DOOR LOCKM

SENSOR TRANSFORMER (GEN NOTE 16)

FIRE ALARM ANNUNCIATOR PANEL

DOOR CONTROL SYSTEM KEYED SWITCH

PUBLIC ADDRESS SPEAKER CEILING

SYMBOL DESCRIPTION

120V. 20A. DUPLEX RECEPTACLE WITH TYPE A AND TYPE C USB

CHARGING PORTS. PROVIDE HUBBELL #USB8300AC5BK OR

APPROVED EQUAL TAMPER RESISTANT RECEPTACLE WITH BLACK

FINISH COLOR AND STAINLESS STEEL COVERPLATE. MOUNT AT 36"

AFF AND ROTATED 90 DEGREES TO BE MOUNTED HORIZONTALLY IN

COUNTERTOP BACK SPLASH.

WIRELESS ACCESS POINT. PROVIDE GREEN CAT-6 DROP WITH 10'-0"

EXCESS CABLE COILED ABOVE THE CEILING. TERMINATE TO 8P8C

CONNECTOR. WAP PROVIDED AND INSTALLED BY GOVERNMENT.

COORDINATE EXACT LOCATION WITH C.O.R.

GEN NOTE 18

VIDEO COAX CABLE HOME RUN GEN NOTE T22

N.C. EMERGENCY BATH STATION (GEN NOTE N1 & N2)

CLG/WALLN.C. VISUAL SIGNAL (GEN NOTE N1)

120V. 20A. DUPLEX RECEPTACLE WITH TYPE A AND TYPE C USB

CHARGING PORTS. PROVIDE HUBBELL #USB8300AC5BK OR

APPROVED EQUAL TAMPER RESISTANT RECEPTACLE WITH BLACK

FINISH COLOR AND STAINLESS STEEL COVERPLATE. MOUNT AT 36"

AFF AND ROTATED 90 DEGREES TO BE MOUNTED HORIZONTALLY IN

COUNTERTOP BACK SPLASH. PROVIDE CHARGETECH #CS8

CHARGING STATION OR APPROVED EQUAL MOUNTED AT OUTLET

LOCATION ON COUNTERTOP. PROVIDE ANTI-THEFT HARDWARE FOR

SECURING THE CHARGING STATION TO THE COUNTERTOP.

LOW VOLTAGE SWITCH 46"AFF

CABLE TV OR VIDEO OUTLET & CONNECTOR 18"AFF

(GEN NOTE T1 & T3)

46"AFFPUSH BUTTON DOOR OPERATOR

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

E-001

ELECTRICAL LEAD SHEET

RENOVATE MAIN LOBBY 589-334

04/03/2018 DLD JLW

ELECTRICAL SHEET INDEX

Sheet

Number Sheet Name

E-001 ELECTRICAL LEAD SHEET

ED101 ELECTRICAL FIRST FLOOR DEMO PLAN

EL101 ELECTRICAL FIRST FLOOR LIGHTING PLAN

EL501 ELECTRICAL LIGHTING DETAILS

EP101 ELECTRICAL FIRST FLOOR POWER PLAN

EP501 ELECTRICAL POWER DETAILS

EY101 ELECTRICAL FIRST FLOOR SYSTEMS PLAN

EY501 ELECTRICAL SYSTEMS DETAILS

M

MMM

D

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS

WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS

(MAXIMUM OF THREE PHASE CONDUCTORS) MAY BE GROUPED IN A

SINGLE CONDUIT. WHERE MULTIPLE CIRCUITS ARE LOCATED IN

THE SAME RACEWAY, JUNCTION BOX OR ENCLOSURE, NEUTRALS

SHALL BE MARKED OR LABELED TO INDICATE WHICH CIRCUIT THEY

ARE ASSOCIATED WITH. SEE SPECIFICATION SECTION "LOW

VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES" FOR

ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS

REQUIRED IN ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A

T-RATING OF ONE HOUR.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR

EXACT LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES

WITH ARCHITECT PRIOR TO ROUGH-IN.

S1 S1 S1

S1 S1 S1S1

S1

S1 S1

LP1-D6.3-277VE

E

E

E

E

EE

S1

S1S1

S1

S1

S1S1S1

S2

S2 S2

S2

S2

S2

S2

S2

S2

S2 S2 S2

S6

S2 S2

S2 S2

V1

V1

X1

S4S4S4S4S4S4S4S4S4

S6 S6 S6 S6 S6

S8S8S8S8S8 S8

S6

S6S6

S6S6

S6

S6

S6

S3S3S3S3S3

LP1-D10-277VN:14

LP1-D10-277VN:14

LP1-D10-277VN:14

LP1-D10-277VN:16

LP1-D10-277VN:18

EX1

L1

L2 L2

L2

L3L3L3L3L3L3L3L3L3

LP1-D10-277VN:14 L2

LP1-D10-277VN:14

L2

E

E

E

E

INFO. DESK

C1E35

PHARM. CARE

SVC.

A119ASILVER TEAM

CHECK IN

A119

ADMISSIONS

SUPERVISOR

E102H

ADMISSIONS

LEAD

E102I

KIOSK

E101

SUPPLY

E102J

HBA

E102F

ROI LEGAL

E102E

HBA

E102D

HBA

E102C

HBA

E102B

PRE-REG

E102A

WORK

E102G

WAITING

PERSONAL

EFFECTS

E102K

HALL

E102

CORR

C1A1

CORR

C1E6

LOBBY

C1E3

MEN TLT

E108

FAMILY TLT

E107

WOMEN TLT

E106

SOILED UTIL.

CHART

112A

CORR.

C1E8

HALL

CORR.

CORR.

TREAT. 1

X1

X1

L2

S4 S4 L3L3

L2

L5 L5 L5 L5 L5 L5

NOT IN SCOPE OF WORK

L6

L6 L7

L7

U2 U2 U2 U2

U2U2U2U2

U2

U2

U2 U2

U1

U1

U2U2

L7

EXISTING TO REMAIN

REMODEL AREA

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

EL101

ELECTRICAL FIRST FLOOR LIGHTING

PLAN

RENOVATE MAIN LOBBY 589-334

04/03/2018 DLD JLW

N

4' 8' 16'

1/8" = 1'-0"

0'

1/8" = 1'-0" A

PARTIAL ELECTRICAL FIRST FLOOR LIGHTING PLAN

N.T.S.

KEY PLAN FIRST FLOOR

N

KEYED NOTES:

L1 CONNECT TO NEAREST EXISTING LIFE SAFETY 277V. LIGHTING

CIRCUIT AND CONTROLS SERVING EXISTING SPACE.

L2 CONNECT TO EXISTING LIGHTING CIRCUIT AND CONTROLS

INDICATED. CIRCUIT SHOWN BASED ON AS BUILT DRAWINGS.

CONTRACTOR TO VERIFY EXISITNG CONDITIONS, AND RE-WORK

EXISTING CONDUIT AND CIRCUITING AS REQUIRED FOR

CONNECTION TO NEW LIGHTS. UPDATE PANEL SCHEDULE

ACCORDINGLY.

L3 LIGHT FIXTURE TO BE INSTALLED IN EXACT LOCATION OF

EXISTING FIXTURE BEING REMOVED. REPAIR EXISTING WALL AS

REQUIRED. CONNECT FIXTURE TO EXISITNG LIGHTING CIRCUIT

AND CONTROLS IN PLACE.

L5 PROVIDE COMBINATION OCCUPANCY SENSOR AND 0-10V DIMMING

SWITCH EQUAL TO WATTSTOPPER PW-311. PROVIDE DIMMING

POWER PACK AT FIXTURE AS REQUIRED FOR MANUAL ON/AUTO

OFF AS WELL AS 0-10V RAISE/LOWER CAPABILITIES.

L6 INTERLOCK OCCUPANCY SENSORS AS REQUIRED.

L7 CONNECT UNDERCABINET LIGHTING TO 120V NORMAL POWER

RECEPTACLE CIRCUIT BELOW.

DOWNLIGHT MOUNTING - GYPBOARD CEILINGLUMINAIRE MOUNTING - LAY-IN CEILINGLUMINAIRE MOUNTING - GYPBOARD CEILING

NO SCALENO SCALENO SCALE

LUMINAIRE SUSPENSION WIRES

(#10 MIN) ATTACHED TO

STRUCTURE

(TYP EA. CORNER)

3 TWIST MINIMUM (TYP)

FIXTURE WHIP FROM

JUNCTION BOX

(6FT. LONG MAX.)

CEILING MAIN BEAM

GYPSUM BOARD (TYP)

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE MANUFACTURER'S EARTHQUAKE

CLIP, (4) PER FIXTURE AT CORNERS. ATTACH

WITH SHEET METAL SCREW

CEILING CROSS BEAM

GYPSUM BOARD

CEILING CROSS BEAM

LUMINAIRE.

REFER TO

SCHEDULE

DRYWALL BORDER

LUMINAIRE SUSPENSION WIRES

(#10 MIN) ATTACHED TO

STRUCTURE

(TYP EA. CORNER)

3 TWIST MINIMUM (TYP)

FIXTURE WHIP FROM

JUNCTION BOX

(6FT. LONG MAX.)

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE MANUFACTURER'S EARTHQUAKE

CLIP, (4) PER FIXTURE AT CORNERS. ATTACH

WITH SHEET METAL SCREW

ACOUSTICAL CEILING TILE (TYP)

ARCHITECTURAL CEILING

GRID

LUMINAIRE.

REFER TO

SCHEDULE

CEILING HANGER WIRE, TYP.

RECESSED CAN

LUMINAIRE

CEILING MAIN BEAM

GYPSUM BOARD

(TYP)

WIRE TIE OR SCREW BAR

HANGER TO CROSS BEAM TYP.

LUMINAIRE

BAR HANGERS

12GA. HANGER WIRE AT DIAGONAL CORNER

ATTACHED TO STRUCTURE

CEILING CROSS

BEAM

RECESSED CAN LUMINAIRE

CEILING BEAM

LIGHTING FIXTURE SCHEDULE

MANUFACTURER

CATALOG NUMBER SEE NOTES VOLTS

LAMP TYPE

NO. REMARKS

DLWDESCRIPTION LENS\LOUVER\FINISH

CATALOG NUMBER

MANUFACTURERMANUFACTURER

CATALOG NUMBERCATALOG NUMBER

MANUFACTURER

LTR.

FIXT.

(P.E.C.)1 2 3 4

1 GENERAL CONTRACTOR SHALL PROVIDE FIREPROOFING AROUND RECESSED FIXTURES INSTALLED IN FIRE RATED CEILING PER U.L. REQUIREMENTS.

ELECTRICAL CONTRACTOR WILL COORDINATE.

PROVIDE ARROWS AND FACES AS INDICATED ON THE DRAWINGS.

MANUFACTURERS LISTED IN THIS SCHEDULE OR APPROVED BY WRITTEN ADDENDUM WILL BE THE ONLY APPROVED MANUFACTURERS TO BID THE LIGHTING FIXTURES FOR THIS PROJECT. CONTRACTORS AND SUPPLIERS USING PRICING FROM MANUFACTURERS NOT LISTED ON SCHEDULE OR BY

ADDENDUM DO SO AT THEIR OWN RISK.

LIGHT FIXTURE SELECTIONS ARE BASED ON THE MANUFACTURER IN THE LEFT MOST COLUMN AS LISTED IN THE SCHEDULE. FIXTURES APPROVED AS EQUALS IN THIS SCHEDULE OR BY ADDENDUM SHALL BE EQUAL TO THE UNIT SPECIFIED IN THE LEFT MOST COLUMN, IE: SPRING LOADED LATCHES, POST PAINTED FINISH, AND PHOTOMETRICS.

ALL LIGHT FIXTURES SHALL BE SECURED TO THE CEILING FRAMING SYSTEM BY MECHANICAL MEANS (SUCH AS BOLTS, SCREWS, OR RIVETS) OR BY CLIPS

IDENTIFIED FOR USE WITH THE TYPE OF CEILING FRAMING MEMBER AND LIGHT FIXTURE.

LIGHT OUTPUT. LED DRIVERS SHALL HAVE A DISCONNECTING MEANS MEETING THE REQUIREMENTS OF NEC SECTION 410.130(G), EXCEPT FOR THOSE LIGHT FIXTURES SHALL BE PROVIDED WITH 0-10V DIMMING DRIVERS. DRIVERS SHALL BE CAPABLE OF DIMMING TO A MINIMUM OF 10% OF TOTAL

INSTALLED IN CORD-AND-PLUG CONNECTED FIXTURES. WHERE APPLICABLE, WHEN DIMMING SWITCHES ARE NOT PROVIDED AS PART OF THE DESIGN, CONTRACTOR SHALL CAP OFF 0-10V DIMMING WIRES FOR FUTURE EXTENSION BY OWNER.

D EXISTING FIXTURE

TO BE REMOVED

E EXISTING FIXTURE

TO REMAIN

EX1 EXISTING FIXTURE

TO REMAIN

1 FACE/AC EXIT LED

RED W/O BATTERY

S1 CREE

ZR22-32L-40K-10V

OR EQUAL 2X2 LAY-IN 4000K LED

UNV

WHITE 2.0 2.0

3200 LUMEN, 35 WATTS, 80+ CRI6

PROVIDE WITH 0-10V DIMMING

S2 PORTFOLIO

LDRT6B-20-D010-EU6B1020-80

OR EQUAL DOWNLIGHT 4000K LED

UNV

SEMI-SPECULAR .5

2000 LUMEN, 24 WATTS, 80+ CRI6

PROVIDE WITH MEDIUM BEAM SPREAD, SELF FLANGED, SEMI SPECULAR FINISH

S3 LUMIERE LANTERRA

1002-S1-FL-4080-W-WT-36-RS

OR EQUAL WIDE FLOOD LED 4000K

UNV

WHITE

900 LUMENS, 12 WATTS, 80+ CRI

36" STEM, WALL MOUNTED ABOVE EMBLEM AND AIMED BACK DOWNWARD AT EMBLEM.

S4 CORELITE

DWI-WD-4-L40-1C-SU-WA-4-W

OR EQUAL WALL MOUNT LED 4000K

UNV

DIFFUSE/WHITE 4.0

3600 LUMENS, 36 WATTS, 80+ CRI

PROVIDE WITH DUST COVER

S6 LUMENWERX

VIA5RF-HLO-LED-80-750-40-6

OR EQUAL 6FT LINEAR 4000K LED

UNV

WHITE .5 6.0

4500 LUMEN, 39 WATTS, 80+ CRI6

PROVIDE WITH DRYWALL FLUSH TRIM, SINGLE CIRCUIT WITH 0-10V DIMMING

S8 LUMENWERX

VIA5R-ARO2-LED-80-500-40-8

OR EQUAL 8FT LINEAR 4000K LED

UNV

WHITE .5 8.0

4000 LUMENS, 32 WATTS, 80+ CRI6

ASYMMETRIC OPTIC. PROVIDE WITH DRYWALL FLUSH TRIM, SINGLE CIRCUIT WITH 0-10V DIMMING

V1 VISA LIGHTING

CB6456-L40K-L-SNA

OR EQUAL VANITY LIGHT LED 4000K

UNV

SATIN NICKEL 0.33 2.75

2000 LUMENS, 17 WATTS, 80+ CRI

WALL MOUTNED ABOVE VANITY MIRROR.

X1 LITHONIA

EDG-1-RMR

OR EQUAL 1 FACE/AC EXIT LED

UNV

CAST ALUMINUM .167 1.1 .7

RED W/O BATTERY5

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

EL501

ELECTRICAL LIGHTING DETAILS

RENOVATE MAIN LOBBY 589-334

04/03/2018 DLD JLW