F E
C
S
S S S S
S
GENERAL FIRE PROTECTION NOTES
1. EXISTING PIPING AND FIRE PROTECTION ZONES ARE SHOWN FOR
REFERENCE ONLY.
2. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR
THE FOLLOWING:
a. REMOVE DISTRIBUTION PIPING BACK TO MAIN. REDISTRIBUTE
AS REQUIRED TO ACCOMMODATE NEW FLOOR PLAN. (E)
BRANCH PIPING MAY BE USED IF SIZE MATCHES CALCULATION
REQUIREMENTS.
b. PROVIDE NEW HEADS AS REQUIRED TO ACCOMMODATE NEW
FLOOR PLAN. REMOVED HEADS SHALL NOT BE REINSTALLED.
ALL NEW HEADS ARE TO BE FM-APPROVED, QUICK RESPONSE
TYPE. ALL HEADS WITHIN SMOKE COMPARTMENT SHALL
MATCH. CONTRACTOR TO CONFIRM AND REPLACE HEADS IF
NECESSARY TO ALL QUICK-RESPONSE TYPE.
c. FIRE SPRINKLER HEADS SHALL BE LOCATED IN CENTER OF
TILE IN BOTH DIRECTIONS WHEN LOCATED IN LAY-IN CEILINGS.
FIRE SPRINKLER HEADS SHALL BE LOCATED IN SYMMETRICAL
PATTERNS IN ROOMS WITH HARD CEILINGS.
d. COORDINATE SPRINKLER HEAD LOCATIONS WITH ALL
CEILING COMPONENTS INCLUDING ELECTRICAL &
MECHANICAL COMPONENTS.
3. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR
THE SPRINKLER HEAD LAYOUTS, CALCULATIONS, AND SEALED
ENGINEERING DRAWINGS AS FOLLOWS:
a. DELEGATED DESIGN: DESIGN SPRINKLER SYSTEM (S), INCLUDING COMPREHENSIVE ENGINEERING ANALYSIS BY A
QUALIFIED PROFESSIONAL ENGINEER, USING PERFORMANCE
REQUIREMENTS AND DESIGN CRITERIA OF NFPA 13.
b. OBTAIN COPY OF FIRE-HYDRANT OR RISER FLOW TEST
RECORDS OR CONTACT LOCAL WATER AND/OR FIRE
DEPARTMENTS TO PERFORM A FIRE-HYDRANT FLOW TEST.
INCLUDE FLOW TEST RESULTS FOR EACH RISER WITH
HYDRAULIC CALCULATIONS. INCLUDE A 10% SAFETY FACTOR
IN HYDRAULIC CALCULATIONS.
c. SPRINKLER SYSTEM SHALL BE APPROVED BY AUTHORITIES
HAVING JURISDICTION.
d. SHOP DRAWINGS: FOR WET-PIPE SPRINKLER SYSTEMS.
INCLUDE PLANS, ELEVATIONS, SECTIONS, DETAILS, AND
ATTACHMENTS TO OTHER WORK.
e. DELEGATED DESIGN SUBMITTAL: FOR ALL SPRINKLER
SYSTEMS, INCLUDING ANALYSIS DATA SIGNED AND SEALED BY
THE QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR
THEIR PREPARATION. ENGINEER SHALL BE LICENSED IN THE
STATE OF MISSOURI.
f. COORDINATION DRAWINGS: SPRINKLER SYSTEMS, DRAWN TO
SCALE, ON WHICH THE ELECTRICAL, PLUMBING, HVAC,
STRUCTURAL AND OTHER BUILDING SYSTEMS ARE SHOWN
AND COORDINATED WITH EACH OTHER, USING INPUT FROM
INSTALLERS OF THE ITEMS INVOLVED.
g. APPROVED SPRINKLER PIPING DRAWINGS: WORKING PLANS, PREPARED ACCORDING TO NFPA 13, THAT HAVE BEEN
APPROVED BY AUTHORITIES HAVING JURISDICTION,
INCLUDING HYDRAULIC CALCULATIONS.
4. EXISTING FIRE PROTECTION PIPING ARE BASED ON BEST
AVAILABLE EXISTING DRAWINGS AND ARE SHOWN FOR
INFORMATION ONLY. FP CONTRACTOR RESPONSIBLE FOR
VERIFYING EXISTING CONDITIONS BEFORE BEGINNING WORK.
5. THIS CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL
COORDINATION AND LAYOUT DRAWINGS PER FIRE PROTECTION
SPEC SECTION. COORDINATION SHOULD BE COMPLETED WITH
ALL TRADES INCLUDED. CONSTRUCTION SHALL NOT BEGIN
UNTIL COORDINATION DRAWINGS HAVE BEEN REVIEWED BY THE
ENGINEER AND COR.
HATCH KEY PLAN
ORDINARY HAZARD GROUP 2
LIGHT HAZARDNO
HATCH
ORDINARY HAZARD GROUP 1
EXISTING TO REMAIN
REMODEL AREA
E 1
ACA
B
ACA
B.2
ACA
C
ACA
ACA
ACA
ACA
ACA
6.3
ACA
ACA
5.6
0.8
LOBBY
C1E3
INFO. DESK
C1E35
W.C. STOR
E101
LOBBY
C1E3
AREA
NOT IN
SCOPE
AREA NOT IN SCOPE
ADMISSIONS SUPERVISOR
E102H
ADMISSIONS LEAD
E102I
KIOSK
E101
SUPPLY
E102J
HBA
E102F
ROI LEGAL
E102E
HBA
E102D HBA
E102C
HBA
E102B
PRE-REG
E102A
WORK
E102G
WAITING
PERSONAL EFFECTS
E102K
HALL
E102
CORR
C1E6
MEN TLT
E108
PAT. REP.
E108B
DETAILS CLERK
E108C
FAMILY TLT
E107
WOMEN TLT
E106
CL.
E103
CL.
E104
CL.
E105
CHECK-IN
A119
PHARM. CARE SVC.
A119A
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
FP101
FIRE PROTECTION PLAN FIRST FLOOR
RENOVATE MAIN LOBBY 589-334
04/03/2018 BOH AR
N 4' 8' 16'
1/8" = 1'-0"
0'
FP SHEET INDEX
FP101 FIRE PROTECTION PLAN FIRST FLOOR
N 1" = 80'-0"
KEY PLAN LEVEL 1
1/8" = 1'-0"
FIRE PROTECTION PLAN - FIRST FLOOR
NOTES:
1. REARRANGE HEAD LOCATIONS AS
REQUIRED IN PROJECT AREA TO
COORDINATE WITH NEW FLOOR
PLAN LAYOUT.
2. ADJUST SPRINKLER HEAD HEIGHT
AS REQUIRED WITH GYP BOARD
INSTALLATION IN SLOPED CEILING.
CO
DRAWING SYMBOLS
26-P 3
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
PUMP NO.3 IN BUILDING NO.26
EQUIPMENT ABBREVIATION (PUMP)
DRAWING NUMBER WHERE DRAWN
GENERAL PLUMBING SYMBOLS
LIMIT OF DEMOLITION
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
AND EXISTING WORK
POINT OF CONNECTION BETWEEN NEW
PRESSURE GAGE
THERMOMETER
STRAINER
PIPE UP
PIPE DOWN
WALL CLEAN OUT
PLUMBING PIPING SYMBOLS
DOMESTIC HOT WATER, HOT WATER
DOMESTIC COLD WATER, COLD WATER
MEDICAL VACUUM
MEDICAL AIR
DOMESTIC HOT WATER CIRC., HOT WATER RETURN
STORM WATER
DRAIN
MA
MV MV MV
D D D
SD SD SD
SANITARY SEWER
OXYGENO2
PLUMBING VENT
PLUMBING VALVE SYMBOLS
BALL VALVE
BUTTERFLY VALVE
AUTOMATIC FLOW CONTROL VALVE
PLUMBING ABBREVIATIONS
WASTE
WATER CLOSET
WALL CLEANOUT
WATER HAMMER ARRESTER
WATER SUPPLY FIXTURE UNITS
VENT
VACUUM
VENT STACK
VENT THROUGH ROOF
TRENCH DRAIN
TEMPERATURE
THERMOSTATIC MIXING VALVE
TYPICAL
SANITARY SEWER
STAINLESS STEEL
ROOF DRAIN
ROOF LEADER
PLUMBING AND DRAINAGE INSTITUTE
POUNDS PER SQUARE INCH
OXYGEN
OUTSIDE DIAMETER
OVERFLOW DRAIN
NOT TO SCALE
MEDICAL AIR
MEDICAL
MEDICAL VACUUM
LAVATORY
POUNDS PER HOUR
INSIDE DIAMETER
INTERNATIONAL PLUMBING CODE
INDIRECT WASTE
HOT AND COLD WATER
HOSE BIBB
HUB DRAIN
HORSEPOWER
GAL
GPH
GPM
F
FD
FS
FU
EL
EWS
EX
CW
DFU
DN
DOE
DW
DWG
DWV
CI
CO
BFP
BTU
BTUH
ARCHITECT / ENGINEER
AREA DRAIN/ACCESS DOOR
ABOVE FINISH FLOOR
AIR GAP
ACCESS PANEL
AMERICAN SOCIETY OF HEATING,
REFRIGERATION, AIR CONDITIONING
ENGINEERS
AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AMERICAN SOCIETY OF PLUMBING
ENGINEERS
W
WC
WCO
WHA
WSFU
V
VAC
VS
VTR
TD
TEMP
TMV
TYP
SAN
SS
RD
RL
PDI
PSI
GALLON
GALLONS PER HOUR
GALLONS PER MINUTE
H&CW
HB
HD
HP
ID
IPC
IW
O2
OD
OFD
NTS
MA
MED
MV
LAV
LBS/HR
A/E
AD
AFF
AG
AP
ASHRAE
ASME
ASPE
REDUCED PRESSURE BACKFLOW
PREVENTER
BRITISH THERMAL UNIT
BRITISH THERMAL UNIT PER HOUR
CAST IRON
CLEANOUT
COLD WATER
DRAINAGE FIXTURE UNITS
DOWN
DEPARTMENT OF ENERGY
DISHWASHER
DRAWING
DRAIN WASTE VENT
ELEVATION
EYE WASH STATION
EXISTING
FAHRENHEIT
FLOOR DRAIN
FLOOR SINK
FIXTURE UNITS
CONTRACTING OFFICER'S REPRESENTATIVECOR
HW
HWC
DOMESTIC HOT WATER
DOMESTIC HOT WATER CIRC
CIRCUIT SETTER
HWCP DOMESTIC HOT WATER CIRCULATION PUMP
CONDENSATE DRAINCD
RAINLEADERRL
FLOOR CLEANOUT
FLOOR CLEANOUTFCO
HYD HYDRANT
WH WALL HYDRANT
ORL OVERFLOW RAIN LEADER
SW STORM WATER
OVERFLOW RAINLEADERORL
PLUMBING PIPING TO BE REMOVED
PL105
A
PL105
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
PP001
PLUMBING COVER SHEET
RENOVATE MAIN LOBBY 589-334
04/03/2018 JAC JGA
1. VERIFY JOB SITE CONDITIONS AND DIMENSIONS BEFORE BEGINNING WORK. PLANS ARE
SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST AVAILABLE INFORMATION.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS.
2. NO PIPING, DUCTWORK, ETC. SHALL PENETRATE STRUCTURAL MEMBERS.
3. PROVIDE MISCELLANEOUS CUTTING, PATCHING AND REPAIRING OF FINISHES, ROOF,
WALLS, ETC., AS REQUIRED TO ACCOMMODATE THE NEW WORK.
4. G.C. IS TO PATCH ANY OPENINGS IN CORRIDORS REQUIRED TO BE CONSTRUCTED TO LIMIT
THE TRANSFER OF SMOKE AND IN SMOKE BARRIERS AS REQUIRED TO MEET CODE
REQUIREMENTS. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY EXACT LOCATION,
CONFIGURATION AND ROUTING OF EXISTING SYSTEMS REQUIRED TO REMAIN IN
OPERATION DURING THE PROJECT TO PREVENT DAMAGE DURING DEMOLITION AND
PHASING.
6. REMOVE ALL EXISTING EQUIPMENT, DUCTWORK AND PIPING THAT IS NOT REQUIRED FOR A
WORKING INSTALLATION.
7. COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO INSTALLATION.
8. ALL CUTTING AND PATCHING SHALL BE CLOSELY COORDINATED WITH THE G.C.
9. COORDINATE ROUTING OF PLUMBING, AND HVAC PIPING WITH DUCTWORK, LIGHTS,
ARCHITECTURAL CEILING AND STRUCTURAL ELEMENTS. PIPING SHALL RISE AND DROP,
JOG OR OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL TAKE
PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE MUST BE MAINTAINED FOR
DRAINAGE. REWORK OF INSTALLED WORK TO RESOLVE CONFLICTS RISING FROM LACK OF
COORDINATION SHALL NOT JUSTIFY AN INCREASE IN THE CONTRACT AMOUNT.
10.ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE FIRE STOPPED BY THE
TRADE MAKING THE PENETRATION. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR REQUIREMENTS.
11.DO NOT ROUTE PIPING OR DUCTWORK OVER ELECTRICAL PANELS OR EQUIPMENT. PIPING
OR DUCTWORK SHALL NOT BE ROUTED THROUGH ELECTRICAL ROOMS, TELECOM ROOMS,
OR ELEVATOR EQUIPMENT ROOMS UNLESS SPECIFICALLY SERVING THAT ROOM.
COORDINATE WITH E.C. PROVIDE WATERTIGHT DRIP PAN WITH DRAIN TO NEAREST
APPROVED RECEPTOR WHERE REQUIRED.
12.COORDINATE SIZE AND LOCATION OF ACCESS DOORS IN CONSTRUCTION REQUIRED FOR
ACCESS TO MECHANICAL EQUIPMENT WITH G.C.
13.ALL WORK IS TO CONFORM WITH APPLICABLE CODES AND STANDARDS.
14.COORDINATE ACCESS TO EQUIPMENT AND VALVES INSTALLED ABOVE 'HARD' CEILINGS
AND IN MASONRY CHASES WITH GENERAL CONTRACTOR. PROVIDE LOCKING ACCESS
DOORS FOR INSTALLATION BY CONTRACTOR AS REQUIRED TO SERVICE CONCEALED
DAMPERS, VALVES AND EQUIPMENT.
15.REFER TO ARCH FOR PHASING PLAN AND ALLOWABLE WORK HOURS.
16.THESE DRAWINGS ARE ACCOMPANIED BY SPECIFICATIONS. REFER TO SPECIFICATIONS
FOR FURTHER INFORMATION.
17.COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED BY PARAGRAPH
"SUBMITTAL" IN SPECIFICATION SECTION 220511. CONSTRUCTION SHALL NOT START ON
ANY SYSTEM UNTIL THE COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
18.THIS IS A LIFE SAFETY BUILDING WHICH MEANS IT SHALL REMAIN REASONABLY
OPERATIONAL IN THE CASE OF A SEISMIC EVENT. THEREFORE ALL STATIONARY
EQUIPMENT ON THE FLOOR SHALL BE FIXED RIGIDLY TO THE STRUCTURE. ALL HANGING
PIPING SHALL BE BRACED TO THE STRUCTURE. REFER TO SPECIFICATION SECTION 130541.
1. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY
DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ARCHITECT IMMEDIATELY.
MINOR CHANGES IN THE SCOPE OF THE DEMOLITION WORK SHALL NOT JUSTIFY AN
ADDITIONAL COST.
2. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATING THE PIPING
RISERS OR MAINS VIA SHUT-OFF VALVES. INSTALL NEW ISOLATION VALVES WHERE
REQUIRED FOR COMPLETION OF WORK.
3. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT, ETC. WILL REQUIRE
CAPPING AND SEALING EXISTING MAINS OR BRANCHES AS NECESSARY AND REQUIRED TO
ALLOW THE REMAINING SYSTEMS TO FULLY OPERATE WITHOUT DEGRADATION.
CONTRACTOR SHALL PROVIDE PROTECTIVE PLASTIC DROP CLOTHS TO PROTECT THE
EXISTING OCCUPIED AREAS AND EQUIPMENT FROM DUST AND DEBRIS DURING THE
CONSTRUCTION WORK, AND SHALL CLEAN THE AREAS OF ALL CONSTRUCTION DIRT DAILY,
AND UPON COMPLETION OF THE WORK. REFER TO GENERAL CONDITIONS AND DIVISION 1
SECTIONS IN THE SPECIFICATIONS.
4. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED WITH PROPER FLUID AND
PROPERLY VENTED BY THIS CONTRACTOR, ONCE NEW WORK HAS BEEN INSTALLED.
5. COORDINATE WITH GENERAL CONTRACTOR THE REMOVAL AND REPLACEMENT OF ALL
EXISTING CEILINGS, WALLS, ETC. AS REQUIRED FOR MECHANICAL DEMOLITION WORK.
6. EXISTING PIPING AND EQUIPMENT, ETC., NOT TO BE UTILIZED IN THE COMPLETED
BUILDING SHALL BE DISCONTINUED OR REMOVED AS REQUIRED. ALL ENDS OF
DISCONTINUED PIPING SHALL BE CAPPED IN THE NEAREST WALL, CEILING OR FLOOR SO
THAT THEY ARE COMPLETELY CONCEALED. OPENINGS LEFT IN WALLS, CEILINGS, ETC.,
WHERE EQUIPMENT AND PIPE, ETC., ARE REMOVED AND NOT REPLACED, SHALL BE
PATCHED NEATLY WITH SIMILAR MATERIAL TO ADJACENT CONSTRUCTION. REFER TO
DRAWINGS DELINEATING NEW WORK FOR ADDITIONAL INFORMATION REGARDING
SYSTEMS OR PORTIONS OF SYSTEMS WHERE USE IS TO BE DISCONTINUED.
7. EXISTING PIPING, FIXTURES AND EQUIPMENT THAT ARE NOT TO BE REUSED SHALL BE
REMOVED AND SHALL REMAIN THE PROPERTY OF THE OWNER IF THEY WISH TO RETAIN
OWNERSHIP OF SAME. IF NOT, EQUIPMENT SHALL BECOME THE PROPERTY OF THIS
CONTRACTOR AND SHALL BE REMOVED FROM THE SITE AS SOON AS PRACTICAL AND
DISPOSED OF IN ACCORDANCE WITH APPLICABLE LAWS AND REGULATIONS.
8. ALL CUTTING AND CHANNELING OF EXISTING BUILDING SHALL BE ACCOMPLISHED IN A
NEAT AND WORKMANLIKE MANNER WITHOUT REMOVAL OF EXCESS MATERIALS. THIS
CONTRACTOR SHALL PATCH AND REPLACE WITH MATERIAL SIMILAR TO ADJACENT
CONSTRUCTION.
9. WHERE EXISTING PIPING AND EQUIPMENT, ETC., THAT ARE TO BE UTILIZED IN THE
COMPLETED PROGRAM CONFLICT WITH NEW CONSTRUCTION AND THE REQUIRED
DEMOLITION, THEY SHALL BE RELOCATED AND RECONNECTED TO MAINTAIN THE DESIRED
SERVICE.
10.PORTIONS OF EXISTING SYSTEMS MAY BE SHOWN FOR CLARITY EVEN THOUGH IT MAY
NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN
BASED ON ORIGINAL OR REMODEL BUILDING DRAWINGS. CONTRACTOR TO VERIFY ALL
EXISTING CONDITIONS.
11.ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE OWNER AND OCCUPANTS
OF THIS BUILDING SO AS TO PROVIDE THE LEAST AMOUNT OF DISRUPTION OF BUILDING
ACTIVITIES AS POSSIBLE.
12.ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND
PROPERLY DISPOSED OF.
GENERAL NOTES GENERAL DEMOLITION NOTES
PLUMBING SHEET INDEX
PP001 PLUMBING COVER SHEET
PD101 BASEMENT AND FIRST FLOOR PLUMBING DEMOLITION PLANS
PL101 BASEMENT AND FIRST FLOOR PLUMBING PLANS
PL301 PLUMBING RISER DIAGRAMS
PL501 PLUMBING SCHEDULES
FEC
FE
FEC
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND
THE REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. ALL PIPING TO BE REMOVED SHALL BE CAPPED AT THE MAINS,
AND HANGERS REMOVED, UNLESS OTHERWISE NOTED.
4. ALL ACCESSIBLE ABANDONED PIPING SHALL BE REMOVED.
5. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS
ARE 100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY
WITH OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION TO
BE AS LEAST DISRUPTIVE AS POSSIBLE.
6. ALL DEMO WORK ON SHALL BE DONE AT NIGHT AND/OR
WEEKENDS,OR AS DIRECTED BY THE COR.
7. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED
BY PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
EXISTING TO REMAIN
REMODEL AREA
E 1
K Jb Ja J H G Ea
ACA
B
ACA
B.2
ACA
C
ACA
ACA
ACA
ACA
6.3
ACA
ACA
5.6
0.8
(E X
)2
(E X
)3 /4
(EX)4"
(EX)1/2"
(EX)1/2"
(E X
)4
(EX)3" W(EX)4" W
(EX)3"
(EX)3"
(EX)3/4" (EX)1 1/2"
(EX)2 1/2"
(E X
)4
(E X
)2
/2
(E X
)1
(E X
)3 /4
HARD CEILINGS WITH ACCESS PANELS AS INDICATED (TYP)
LAY IN CEILING
LAY IN CEILING
RL
E 1
K JbJa J H G Ea
ACA
B
ACA
B.2
ACA
C
ACA
ACA
0.8
(EX)2"
(EX)1 1/2"
(EX)1 1/4"
(EX)2"
(EX)2"
REMOVE (EX) 3/4"HW& CW, (EX)3"W DOWN
REMOVE (EX)1 1/2"V
(EX)3"VTR TO REMAIN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
PD101
BASEMENT AND FIRST FLOOR
PLUMBING DEMOLITION PLANS
RENOVATE MAIN LOBBY 589-334
04/03/2018 JAC JGA
N 4' 8' 16'
1/8" = 1'-0"
0'
N
PLAN NOTES
1 REMOVE WATER AND WASTE LINE UP TO FIXTURE BEING
REMOVED. CAP AT MAIN.
2 REMOVE (EX) FLOOR DRAIN AND WASTE PIPING.
3 REMOVE (EX) PLUMBING FIXTURE AND ASSOCIATED PIPING.
4 REMOVE (EX) DRINKING FOUNTAIN. LEAVE PIPING ROUGH-INS
FOR RECONNECTION.
N 4' 8' 16'
1/8" = 1'-0"
0' 1" = 80'-0"
KEY PLAN LEVEL 1
1/8" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN
1/8" = 1'-0"
FIRST FLOOR PLUMBING DEMOLITION PLAN
GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST
AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AND DIMENSIONS.
2. ALL CUTTING, PATCHING AND DEMOLITION WORK SHALL BE
CLOSELY COORDINATED WITH THE EXISTING CONDITIONS AND THE
REQUIRED NEW WORK. G.C. SHALL PATCH AND FINISH
PENETRATIONS OF EXISTING SURFACES TO MATCH ADJACENT
SURFACES.
3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND DUCTWORK.
COORDINATE WITH EXISTING EQUIPMENT, PIPING AND DUCTWORK.
NEW PIPING SHALL RISE AND DROP, JOG OR OFFSET AS REQUIRED
TO AVOID CONFLICTS. DUCTWORK SHALL TAKE PRECEDENCE
OVER ALL PIPING, EXCEPT WHERE GRADE MUST BE MAINTAINED
FOR DRAINAGE. ANY EXPENSES RISING FROM LACK OF
COORDINATION SHALL BE MADE AT THE CONTRACTOR’S EXPENSE.
4. REFER TO ARCHITECTURAL SPECIFICATIONS AND PLANS FOR
PHASING OF DEMOLITION AND NEW WORK. ADJACENT AREAS ARE
100% OCCUPIED AND CONTRACTOR SHALL WORK CLOSELY WITH
OWNER TO SCHEDULE DEMOLITION AND CONSTRUCTION TO BE AS
LEAST DISRUPTIVE AS POSSIBLE.
5. ALL WORK SHALL BE DONE AT NIGHT AND/OR WEEKENDS, OR AS
DIRECTED BY THE COR.
6. PIPE LENGTH FROM RECIRCULATED HOT WATER MAIN TO
LAVATORY HOT WATER STOP SHALL BE NO MORE THAN 15'-6".
7. PIPE LENGTH FROM COLD WATER MAIN TO WATER CLOSET FLUSH
VALVE SHALL BE NO MORE THAN 19'-6".
8. COMPLETE COORDINATION OF DRAWINGS SHALL BE REQUIRED BY
PARAGRAPH "SUBMITTAL" IN SPECIFICATION SECTION 220511.
CONSTRUCTION SHALL NOT START ON ANY SYSTEM UNTIL THE
COORDINATION DRAWINGS HAVE BEEN APPROVED BY VA.
EXISTING TO REMAIN
REMODEL AREA
E 1
K Jb Ja J H G Ea
ACA
B
ACA
B.2
ACA
C
ACA
ACA
0.8
2"CW UP INTO WALL
CONNECT 2"CW & 3/4"HW TO (EX)2"CW & 3/4"HW
1/2"HW UP
1/2"HW & 2"W UP
1/2"HW & 2"W UP
CONNECT 4"W TO (EX)4"W ABV. CLG.
(EX)4" W
4"W UP INTO CHASE ABV.
2"W UP TO FD
CONNECT 4"W TO (EX)4"W ABV. CLG.
CONNECT 2"W TO (EX)3"W ABV. CLG.
2"W UP TO FD
(EX)2 1/2"
(EX)1 1/2"(EX)3/4"
(E X
)1
(E X
)2
/2
(E X
)4
4"W UP INTO CHASE ABV.
1/2"CW UP
A
B
D
B
B
C
A
A
1/2"CW UP
(EX)8" RL
(EX)3" W
WAITING
LOBBY
C1E3
W.C. STOR
E101
LOBBY
C1E3
E 1
K Jb Ja J H G Ea
ACA
B
ACA
B.2
ACA
C
ACA
ACA
0.8 P-121 P-122 P-204
P-203
P-422
P-422
P-121 P-122P-121
P-422
P-122
(E)3"VTR
2"CW DOWN
WOMEN TLT
E106
FAMILY TLT
E107
ROI LEGAL
E102E
HBA
E102D
HBA
E102C
HBA
E102C
PRE-REG
E102A
KIOSK
E101
PL101
PL101
P-604
CONNECT NEW DRINKING
FOUNTAIN TO (EX) ROUGH-INS IF
POSSIBLE, OR TO EXISTING RISERS
(EX)3"W, 2"V & 3/4"CW RISERS
1 1/2" 2"V
"V
P-121 P-122 P-204 P-203 P-422
2" FD-C
WHA-B
2"W IN CHASE
4"W DOWN
1 1/4" 1 1/2" 1 1/2"1 1/2"
1/2"HW FROM BELOW
2"V
1/2"CW DOWN
TRAP PRIMER ABV. CLG.
P-422
P-121 P-122
P-121
P-422
P-122
2" FD-C
WHA-A
WHA-B
1 1/2"
/2
1 1/4"
1 1/2"
"V
2"V
2"V
2"V
1 1/2"V
1/2"HW FROM BELOW
1/2"HW
FROM
BELOW
4"W DOWN
TRAP PRIMER
ABV. CLG.
1/2"CW DOWN
4"W IN CHASE
E
PLAN NOTES
HARD CEILING WITH ACCESS PANELS.
LAY IN CEILING.
NO CEILING.
EXISTING FOUNDATION WALL. REUSE
EXISTING OPENINGS FOR
PENETRATIONS WHERE POSSIBLE.
SUPPORT COUNTERTOP USING
FLOOR MOUNTED CARRIER EQUAL
TO WADE 510-02.
A
B
C
D
E
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
PL101
BASEMENT AND FIRST FLOOR
PLUMBING PLANS
RENOVATE MAIN LOBBY 589-334
04/03/2018 JAC JGA
N
1" = 80'-0"
KEY PLAN LEVEL 1
N
4' 8' 16'
1/8" = 1'-0"
0'
N
4' 8' 16'
1/8" = 1'-0"
0'
1/8" = 1'-0"
BASEMENT FLOOR PLUMBING PLAN
1/8" = 1'-0"
FIRST FLOOR PLUMBING PLAN
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - MEN TLT.
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - FAMILY & WOMEN TLT.
2' 4' 8'0'
1/4" = 1'-0"
2' 4' 8'0'
1/4" = 1'-0"
P-422
P-121
P-122
P-121
P-121
P-122
P-204
P-203
P-422
2"V
2"V
1 1/2"V
2"V
1 1/2"V 2"V
2"V
2"V
3"V
(E)3"VTR
3"W
2"W
3"W
2"W
4"W
(EX)4" W
(EX)3" W
2"W
2"W
3"W
4"W
4"W3"W
P-122
P-422
(EX)4" W
2"W
(EX)3" W
3"W
4"W
2"V
2"V
1 1/2"V
1 1/2"V
1 1/2"V
2"FD-C
2"FD-C
3"W
2"W
P-121
P-122
P-204
P-203
P-422
P-422
P-121
P-122
P-122
P-121
P-422
1 1/2"CW
1/2"HW
2"CW
2"CW
1 1/2"CW
1/2"CW
1"CW
1"CW
1 1/4"CW
1/2"CW
1 1/4"CW
1/2"CW
1/2"CW1/2"CW
1 1/4"CW
1/2"CW
1/2"HW 1 1/4"CW
1/2"HW
(EX)3/4" HW
(EX)2" CW
1 1/4"CW
1 1/2"CW
1 1/4"CW
1 1/4"CW
1/2"HW
TRAP PRIMER ABV. CLG.
WHA-B
WHA-A
WHA-B
1 1/4"CW
1 1/4"CW
1 1/2"CW
TRAP PRIMER ABV. CLG.
CONNECT TO 2"FD-C
SHUT-OFF VALVE
3/4"HW
CONNECT TO 2"FD-C
1/2"HW
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
PL301
PLUMBING RISER DIAGRAMS
RENOVATE MAIN LOBBY 589-334
04/03/2018 JAC JGA
SANITARY WASTE AND VENT RISER DIAGRAM
DOMESTIC WATER RISER DIAGRAM
NOT TO SCALENOT TO SCALE
MARK
P-121
DESCRIPTION
WATER CLOSET
FLOOR MTD
WASTE
PIPE IN
VENT
PIPE IN
COLD
WATER IN
HOT
WATER IN
WASTE
FIXTURE
UNITS
WATER
FIXTURE
UNITS
WRIST
BLADE
N/A
HANDLES
ELECTRIC
SENSOR
YES
REMARKS
P-122
PLUMBING FIXTURE SCHEDULE
P-203
P-204
COMPLETE LAYOUT DRAWINGS SHALL BE REQUIRED BY SPECIFICATION
PARAGRAPH, SUBMITTALS. CONSTRUCTION WORK SHALL NOT START ON ANY
SYSTEM UNTIL THE LAYOUT DRAWINGS HAVE BEEN APPROVED BY VA.
FLOOR MTD BACK OUTLET 1.28 GPF, WHEELCHAIR ACCESSIBLE
PLUMBING FIXTURE DESCRIPTION
P-121: WATER CLOSET:
BASED ON AMERICAN STANDARD 3312.001 “HURON” FLOOR MOUNTED, BACK OUTLET ELONGATED VITREOUS CHINA WATER CLOSET WITH
TOP SPUD, ANGLE BACK AND BASE, 17-1/8” RIM, BOLT CAPS - SLOAN ECOS 111-1.28 HARD WIRED SENSOR OPERATED FLUSH VALVE WITH
VACUUM BREAKER, TAILPIECE, DUAL FILTERED BYPASS, METAL COVER, OVERRIDE BUTTON - SUPPLY ONE TRANSFORMER FOR EACH
GROUP OF WATER CLOSETS OR URINALS - WHITE SOLID PLASTIC ELONGATED OPEN FRONT SEAT, LESS COVER. SET WATER CLOSET SO
THAT CENTERLINE IS 16”-18” FROM NEAREST WALL.
P-122: WATER CLOSET:
BASED ON AMERICAN STANDARD 3312.001 “HURON” FLOOR MOUNTED, BACK OUTLET ELONGATED VITREOUS CHINA WATER CLOSET WITH
TOP SPUD, ANGLE BACK AND BASE, 17-1/8” RIM, BOLT CAPS - SLOAN ECOS 111-1.28 HARD WIRED SENSOR OPERATED FLUSH VALVE WITH
VACUUM BREAKER, TAILPIECE, DUAL FILTERED BYPASS, METAL COVER, OVERRIDE BUTTON - WHITE SOLID PLASTIC ELONGATED OPEN
FRONT SEAT, LESS COVER.
P-203: URINAL:
BASED ON KOHLER K-4991-ET “BARDON” 1.0 GPF WALL HUNG VITREOUS CHINA WASHOUT ACTION URINAL WITH 3/4” TOP SPUD, 2” OUTLET, AND WALL BOLTS - SLOAN ECOS 186-0.125 HARD WIRED, SENSOR OPERATED FLUSH VALVE WITH VACUUM BREAKER, METAL COVER, DUAL
FILTERED BYPASS DIAPHRAGM - FLOOR MOUNTED WALL CARRIER.
P-204: URINAL:
BASED ON KOHLER K-4991-ET “BARDON” 1.0 GPF WALL HUNG VITREOUS CHINA WASHOUT ACTION URINAL WITH 3/4” TOP SPUD, 2” OUTLET, AND WALL BOLTS - SLOAN ECOS 186-0.125 HARD WIRED, SENSOR OPERATED FLUSH VALVE WITH VACUUM BREAKER, METAL COVER, DUAL
FILTERED BYPASS DIAPHRAGM - FLOOR MOUNTED WALL CARRIER. MOUNT RIM AT 17” A.F.F.
P-422: LAVATORY:
LAVATORY BOWL INTEGRAL TO COUNTERTOP. FAUCET BASED ON CHICAGO FAUCET 116.706.AB.1 DECK MOUNTED, SINGLE HOLE, SENSOR
OPERATED FAUCET WITH 0.5 GPM VANDAL PROOF NON-AERATING OUTLET, 12 VOLT TRANSFORMER, THERMOSTATIC MIXING VALVE, STAINLESS STEEL BRAIDED HOSES - GRID DRAIN - WALL SUPPLIES WITH LOOSE KEY STOPS - CAST BRASS “P” TRAP. INSTALL PIPING TO FIT
WITHIN ARCHITECTURAL ENCLOSURE.
P-604: ELECTRIC WATER COOLER WITH BOTTLE FILLER:
BASED ON ELKAY EZSG8WSSK WALL HUNG, WHEELCHAIR ACCESSIBLE, WATER COOLER WITH SENSOR ACTIVATED BOTTLE FILLING
STATION, SIDE AND FRONT PUSHBAR ACTIVATED BUBBLER, STAINLESS STEEL FINISH, CAPACITY OF 8 GPH OF 50 DEGREE WATER AT ARI
CONDITIONS.
URINAL 2 1.5 .75 -- 2 3 NO YES
URINAL 2 1.5 .75 -- 2 3 NO YES
LAVATORY 1.5 .375 .375 1 2P-422
WATER CLOSET
FLOOR MTD
3 2 1 -- 4 10 N/A YES FLOOR MTD BACK OUTLET 1.28 GPF
WHEELCHAIR ACCESSIBLE
NO YES1.5 WHEELCHAIR ACCESSIBLE
1.5 .5 - 1 1P-604 N/A NO2 WHEELCHAIR ACCESSIBLE
ELEC.
WATER COOLER
COLD WATER
DISTRIBUTION LINE - 1-1/2"
OR SMALLER
TAP OFF TOP OF LINE
1/2" BALL
VALVE
ADJUSTABLE TRAP PRIMER WITH
INTEGRAL VACUUM BREAKER. LOCATE
ABOVE ACCESSIBLE CEILING.
NOTE: AVOID IMBEDDING CW LINE TO
TRAP IN CONCRETE IF LINE MUST BE
IMBEDDED IN SLAB, INSULATE WITH MIN.
3/8" THICK ARMAFLEX INSULATION.
FLOOR
WHERE TUBING PENETRATES SLAB,
INSULATE WITH MIN. 3/8" THICK ARMAFLEX
INSULATION.
NO JOINTS IN OR BELOW SLAB
DEEP SEAL "P" TRAP W/ TRAP
PRIMER CONNECTION.
PREFERRED METHOD.
PITCH
DN
1/2"CW
PITCH
DN
1/2"CW
FLOOR DRAIN WITH TRAP
PRIMER CONNECTION.
ALTERNATE METHOD.
"M
IN
CAULK OR SEALANT AT
FLOOR DRAIN TRANSITION
TO FLOOR
NICKLE BRONZE ADJUSTABLE STRAINER
(FLUSH WITH FINISHED FLOOR)
CEMENT BED
TILE FLOOR
CONCRETE FILL
STRUCTURAL SLAB
FLASHING CLAMP WITH WEEP HOLES
THREADED, CAULKED OR NO-HUB CONNECTION
LOOSE GRAVEL AT WEEP HOLES 3mm to 6mm SIZE
WATERPROOF MEMBRANE
PROVIDE A METAL SUPPORT PLATE WHEN DRAIN IS INSTALLED IN AN
EXISTING FLOOR. CAULK AROUND DRAIN PRIOR TO RE-GROUTING
CLAMP WATERPROOF MEMBRANE INSIDE
OF DRAIN BODY TO DRAIN TO WEEP HOLES
NOTE:
SLOPE MEMBRANE LINER 2% TO DRAIN.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
PL501
PLUMBING SCHEDULES
RENOVATE MAIN LOBBY 589-334
04/03/2018 JAC JGA
NO SCALE
TRAP PRIMER DETAIL
NO SCALE
TYPE "C" FLOOR DRAIN DETAIL
File details come from the government source that posted it.