NOT IN SCOPE OF
WORK
NOT IN SCOPE OF WORK
3 3 3 3
3' - 4"
AD1022
26 2728
FEC
DO NOT REMOVE
FLOORING
BEYOND THIS
POINT
18 26
DO NOT REMOVE
FLOORING BEYOND
THIS POINT
GENERAL DEMOLITION NOTES
A. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO WORK
BEGINNING.THE CONTRACTOR IS RESPONSIBLE FOR INFORMING THE ARCHITECT OF
ANY CONDITIONS THAT DIFFER FROM INFORMATION INDICATED IN THE DRAWINGS.
B. PROTECT ALL EXISTING BUILDING COMPONENTS TO REMAIN. REPAIR ANY DAMAGE
AREAS AS REQUIRED TO RETURN THEM TO THEIR ORIGINAL CONDITION.
C. VERIFY EXTENT OF DEMOLITION WORK w/ INFO SHOW IN THE DRAWINGS AND WORK
THAT IS NOT SHOWN AND MAY BE REQUIRED TO COMPLETE THE INTENDED WORK.
D. ALL WORK SHALL COMPLY w/ REQUIRED LOCAL CODES. CONTRACTOR IS
RESPONSIBLE FOR OBTAINING REQUIRED PERMITS & INSPECTIONS FOR ALL WORK
ASSOCIATED w/ HIS CONTRACT.
E. CONTRACTOR SHALL REPAIR ALL DISTURBED AREAS AS REQUIRED TO MATCH THE
ORIGINAL STATE OF ADJACENT FINISHES.
F. TYPES OF FLOOR, WALL & CEILING FINISHES INDICATED FOR REMOVAL BY
DEMOLITION NOTES IS FOR CONTRACTOR'S INFORMATION AND HAS BEEN OBTAINED
FROM EXISTING PLANS AND OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY
MATERIAL TYPES ONSITE PRIOR TO BID AND INCLUDE NECESSARY WORK IN HIS BID.
G. ALL APPLIANCES, FURNITURE AND EQUIPMENT TO REMAIN THE PROPERTY OF THE
OWNER. CONTRACTOR TO COORDINATE REMOVAL, RELOCATION AND STORAGE OF
EQUIPMENT FROM DEMO AREAS WITH OWNER.
H. MISCELLANEOUS FLOOR PENETRATIONS & DEMO FOR NEW MECHANICAL &
ELECTRICAL WORK SHALL BE COORDINATED FROM ARCHITECTURAL, MECHANICAL &
ELECTRICAL PLANS.
I. REFER TO MECHANICAL, PLUMBING & ELECTRICAL DEMO PLANS FOR DEMOLITION,
SALVAGE AND REUSE OF EXISTING ITEMS.
J. PATCH FLOOR AT REMOVED WALLS & CASEWORK. PREPARE FLOOR TO RECEIVE
NEW FLOORING AS REQUIRED.
K. ALL HOLES IN EXISTING SLAB LEFT FROM REMOVAL OF FIXTURES TO RECEIVE INFILL
PER STRUCTURAL DETAILS.
L. REMOVE ALL STAINLESS STEEL CORNER GUARDS CAREFULLY AND GIVE TO THE
OWNER.
M. ALL SIGNAGE TO BE RETURNED TO THE VA IF NOT RELOCATED OR REUSED
N. SAVE ANY EXISTING DOME MIRRORS FOR USE IN REMODELED SPACE OR RETURN TO
VA
DEMOLITION PLAN INDICATES ASSUMED
ASBESTOS CONTAINING MATERIAL (ACM)
WHERE OBSERVED. REFER TO ASBESTOS
ABATEMENT SPECIFICATION SECTION FOR
FURTHER INFORMATION REGARDING REMOVAL
OF ACM AND SPECIFIC TYPES AND LOCATIONS.
ABATEMENT ACTIVITIES WILL REQUIRE TO BE
PHASED ACCORDING TO THE PHASING PLAN
FOR THE PROJECT.
ASBESTOS DEMOLITION NOTES
DEMOLITION LEGEND
DOOR & FRAME TO BE REMOVED
WALL TO BE REMOVED
WALL TO REMAIN
DOOR & FRAME TO REMAIN
AREA FOR SELECTIVE WOOD
PANEL, BASE RAIL, OR WALL
GUARD REMOVAL
R.O.I.R.O.I.
TRANSCRIPTION
OFF.
E144
OFFICE
F159
OFFICE
F160
OFFICE
F161
OFFICE
F162
OFFICE
F164
OFFICE
F165
HOME
TELEHEALTH
N.
ENVIRO.
MGT.
OFFICE
OFFICE
BLDG.
MGT.
LKR./
LNGE./
TLT. TLT.
OFFICE
EXAM
ST. LNGE.
TLT.
TLT.
CORR.
CORR.
CORR.
BLDG.
MGT.
LKR./
LNGE./
TLT.
PHARMACY
CASHIER
E142
TELEHEALTH
IMAGING
E143
TRAVEL
E140
STAIR #11
F173
F.M.S.
ENG.
F170
SIGNAL
F172
CORR.
C1F22
CASHIER
WINDOWS
C1E2
ENTR.
VEST.
TUBE
STATION
TUBE
STATION ELEV #12
PHARMACYCORR.
ADDITION
REMODEL
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AD101
FIRST FLOOR PLAN - DEMOLITION
589-334
04/03/2018
1/8" = 1'-0" A
FIRST FLOOR PLAN - DEMOLITION
DEMO SCHEDULE
# DESCRIPTION
1 REMOVE EXISTING WALL OR PORTION OF WALL AS INDICATED - PATCH ADJ. EXIST. WALL AS REQ.
2 REMOVE EXISTING DOOR & FRAME
3 REMOVE EXISTING WINDOW
4 REMOVE EXISTING PLUMBING FIXTURE & ANY ASSOCIATED PLUMBING (REF. PLUMBING). REPAIR FLOOR/ WALL/ CEILING AS REQUIRED
5 REMOVE CASEWORK
6 REMOVE CORNER GUARD OR END GUARD; REPAIR WALL AS REQUIRED
7 REMOVE EXISTING EXTERIOR WALL OR PORTION OF WALL AS INDICATED, INCLUDING VENEER AND BACKUP
8 REMOVE EXISTING FLOORING, BASE & GLUE RESIDUE USING MECHANICAL MEANS. PREP SUB-FLOORING FOR NEW FLOOR COVERING
9 REMOVE EXISTING FIRE EXTINGUISHER CABINET
10 REMOVE EXISTING WOOD PANEL, METAL FILLER, AND METAL BASE AS REQUIRED; PATCH WALL AS REQUIRED
11 REMOVE EXISTING PASS-THROUGH DRAWER - PATCH WALL ON BOTH SIDES TO MATCH EXISTING - BASE BID ONLY
12 REF. CIVIL DRAWINGS FOR SCOPE OF SITE DEMOLITION; REVIEW ONSITE WITH COR WHICH DEMO ITEMS SHALL BE RETURNED TO OWNER
13 REMOVE ALL EXISTING METAL BASE & SAVE FOR REUSE IN REMODELED SPACE; RETURN ANY EXTRA MATERIAL TO THE VA
14 REMOVE PORTION OF WALL FOR NEW DOOR OPENING
15 REMOVE EXISTING STONE VENEER COVERING STRUCTURAL BEAM - REF. STRUCTURAL
16 REMOVE EXISTING DUMBWAITER AND ALL ASSOCIATED HARDWARE
17 REMOVE LIFT SYSTEM; RETURN TO VA
18 REMOVE WALL-ATTACHED MODULAR FURNITURE; RETURN TO VA. PATCH WALLS, PREPARE TO RECEIVE NEW FINISH
19 REMOVE WALL GUARDS AND CORNER GUARDS; REPAIR WALL AS REQ'D
20 REMOVE CHAIR RAILS; REPAIR WALL AS REQ'D
21 REMOVE CUBICLE CURTAIN AND TRACKS
22 REMOVE EXISTING BASE RAIL; REPAIR WALL AS REQ'D
23 REMOVE EXISTING OUTLET & HOSE BIB, REF. CIVIL & ELEC
24 REMOVE LIGHT FIXTURE, REF. ELEC.
25 REMOVE EXISTING KNOX BOX AND SAVE FOR USE IN REMODELED SPACE
26 REMOVE EXISTING SECURITY CAMERA AND RETURN TO OWNER, REF. ELEC.
27 REMOVE MECHANICAL UNIT, LIGHT FIXTURE & EXIT SIGNAGE, REF. ELEC & MECH.
28 REMOVE EXISTING FIRE ALARM & HUMIDITY CONTROL & RELOCATE; REF. MECH.
29 PRESERVE PNEUMATIC TUBE STATION. - RETURN TO VA
30 REMOVE EXISTING BLOCK WALL OR PORTION OF WALL AS INDICATED - PATCH ADJ. EXIST. WALL AS REQ.
31 REMOVE PHARMACY WINDOW & PHARMACY PASS-THROUGH DRAWER IN BASE BID ONLY
32 VA TO REMOVE/RELOCATE SAFE PRIOR TO CONSTRUCTION
33 RELOCATE T-STAT AS REQ'D FOR NEW CONSTRUCTION; REF. MECHANICAL
34 REMOVE EXISTING MED GAS ZONE BOX, OUTLET, OR ALARM PANEL & ANY ASSOCIATED PIPING - REF. MECH; PATCH & REPAIR
WALLS/CEILING AS REQ'D
35 REMOVE EXISTING BRICK VENEER WHERE INDICATED -REF ELEVATIONS FOR ADDITIONAL INFO
4' 8' 16'
1/8" = 1'-0"
0'
N 1" = 80'-0"
KEY PLAN FIRST FLOOR
N
3 3 3 3 3
NOT IN SCOPE OF
WORK
OPEN TO
BELOW
181818
AD1022
5' - 11"
F
IE
L D
V E
R
IF
Y E
X
IS
T
IN
G F
L O
O R
IN
G
8 8
KEEP
FLOORIN
G
3' - 10"
3' - 10"6' - 7"
EXTENT OF
FLOORING
DEMOLITION
3' - 10"
DEMOLITION LEGEND
DOOR & FRAME TO BE REMOVED
WALL TO BE REMOVED
WALL TO REMAIN
DOOR & FRAME TO REMAIN
AREA FOR SELECTIVE WOOD
PANEL, BASE RAIL, OR WALL
GUARD REMOVAL
GENERAL DEMOLITION NOTES
A. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO WORK
BEGINNING.THE CONTRACTOR IS RESPONSIBLE FOR INFORMING THE ARCHITECT OF
ANY CONDITIONS THAT DIFFER FROM INFORMATION INDICATED IN THE DRAWINGS.
B. PROTECT ALL EXISTING BUILDING COMPONENTS TO REMAIN. REPAIR ANY DAMAGE
AREAS AS REQUIRED TO RETURN THEM TO THEIR ORIGINAL CONDITION.
C. VERIFY EXTENT OF DEMOLITION WORK w/ INFO SHOW IN THE DRAWINGS AND WORK
THAT IS NOT SHOWN AND MAY BE REQUIRED TO COMPLETE THE INTENDED WORK.
D. ALL WORK SHALL COMPLY w/ REQUIRED LOCAL CODES. CONTRACTOR IS
RESPONSIBLE FOR OBTAINING REQUIRED PERMITS & INSPECTIONS FOR ALL WORK
ASSOCIATED w/ HIS CONTRACT.
E. CONTRACTOR SHALL REPAIR ALL DISTURBED AREAS AS REQUIRED TO MATCH THE
ORIGINAL STATE OF ADJACENT FINISHES.
F. TYPES OF FLOOR, WALL & CEILING FINISHES INDICATED FOR REMOVAL BY
DEMOLITION NOTES IS FOR CONTRACTOR'S INFORMATION AND HAS BEEN OBTAINED
FROM EXISTING PLANS AND OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY
MATERIAL TYPES ONSITE PRIOR TO BID AND INCLUDE NECESSARY WORK IN HIS BID.
G. ALL APPLIANCES, FURNITURE AND EQUIPMENT TO REMAIN THE PROPERTY OF THE
OWNER. CONTRACTOR TO COORDINATE REMOVAL, RELOCATION AND STORAGE OF
EQUIPMENT FROM DEMO AREAS WITH OWNER.
H. MISCELLANEOUS FLOOR PENETRATIONS & DEMO FOR NEW MECHANICAL &
ELECTRICAL WORK SHALL BE COORDINATED FROM ARCHITECTURAL, MECHANICAL &
ELECTRICAL PLANS.
I. REFER TO MECHANICAL, PLUMBING & ELECTRICAL DEMO PLANS FOR DEMOLITION,
SALVAGE AND REUSE OF EXISTING ITEMS.
J. PATCH FLOOR AT REMOVED WALLS & CASEWORK. PREPARE FLOOR TO RECEIVE
NEW FLOORING AS REQUIRED.
K. ALL HOLES IN EXISTING SLAB LEFT FROM REMOVAL OF FIXTURES TO RECEIVE INFILL
PER STRUCTURAL DETAILS.
L. REMOVE ALL STAINLESS STEEL CORNER GUARDS CAREFULLY AND GIVE TO THE
OWNER.
M. ALL SIGNAGE TO BE RETURNED TO THE VA IF NOT RELOCATED OR REUSED
N. SAVE ANY EXISTING DOME MIRRORS FOR USE IN REMODELED SPACE OR RETURN TO
VA
DEMOLITION PLAN INDICATES ASSUMED
ASBESTOS CONTAINING MATERIAL (ACM)
WHERE OBSERVED. REFER TO ASBESTOS
ABATEMENT SPECIFICATION SECTION FOR
FURTHER INFORMATION REGARDING REMOVAL
OF ACM AND SPECIFIC TYPES AND LOCATIONS.
ABATEMENT ACTIVITIES WILL REQUIRE TO BE
PHASED ACCORDING TO THE PHASING PLAN
FOR THE PROJECT.
ASBESTOS DEMOLITION NOTES
STAIR #4
A250
FIRE CL.
A250A
HOOD
ROOM
CHEMO.
OFFICE
EXAM
EXAM
F240
TLT.
SOILED
UTIL.
EXAM
ALCOVE
C2F17
CORR.
EXAM
EXAM 10
F241
EXAM 11
F243
EXAM 12
F244
EXAM 16
PHYS.
OFFICE
PROCEDURE
& EXAM 1
MICROSCOPE
ROOM
ST. TLT.
EXAM 15
OFFICE
EXAM 17
EXAM 14
F248
EXAM 13
F247
EXAM 5
TLT.
E207
TLT.
E208
ELECTRICAL
E202
TELE/
DATA
E203
OFFICE
E204
OFFICE
E204A
CORR.
C2F20
FAM.
COUNSELING
E209
JAN.
E210A
SOILED
UTIL.
E210
EXAM
E211
STG.
F253
EXAM
E212
WK. RM.
E215A
CLEAN
UTIL.
E214
N. STN.
E213
CORR.
C2F18
CORR.
RECEPT.
N. STN.
DWTR.
RM.
E206
TLT.
E205
EXAM
E226
ATTENDING
OFFICE./
EXAM
E225
EXAM
E223
EXAM
E222
PROCS.
RM.
E220
CORR.
C2E3
CORR.
C2E2
CHECK
IN/OUT
E224A
WAITING
AREA
E224
CORR.
C2E4
CORR.
C2E1
ELECT.
CLOSET
F252
EXAM
E219
EXAM
E218
EXAM
E217
EXAM RM.
E216
INTERN/
RES.
SWAMP
E215
STAIR #11
F248
EXAM/
OFFICE
E221
CORR.
C2E6
CORR.
CORR.
CORR.
C2E7
OFFICE
F255
CLEAN
DISPATCH
EXAM 18
736 -0 FIN. FLOOR
0' - 0"
749-9 1/4 SECOND
FLOOR
13' - 9 1/4"
762-5 1/4 THIRD
FLOOR
26' - 5 1/4"
ACA
ACA
10.6
ACA
ACA
11.5
ACA
REMOVE EXISTING
STOREFRONT
WINDOW
REMOVE EXISTING
STONE PARAPET &
PARAPET STONE
CAP
REMOVE EXISTING
DOOR &
STOREFRONT
WINDOWS
REMOVE EXISTING BRICK
WHERE INDICATED - REF.
STRUCT.
736 -0 FIN. FLOOR
0' - 0"
749-9 1/4 SECOND
FLOOR
13' - 9 1/4"
762-5 1/4 THIRD
FLOOR
26' - 5 1/4"
ACA
H
ACA
G
ACA
E
ACA
D
ACA
E.1
ACA
F
ACA
D.8
ACA
D.7
F.2 F.9 G.5E.5 F.1
REMOVE EXISTING
STOREFRONT
WINDOW
REMOVE
EXISTING
BRICK - REF.
STRUCT.
REMOVE BRICK
& MTL STUDS -
REF. STRUCT.
ADDITION
REMODEL
AREA
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AD102
SECOND FLOOR PLAN - DEMOLITION
589-334
04/03/2018
1/8" = 1'-0" A
SECOND FLOOR PLAN - DEMO
DEMO SCHEDULE
# DESCRIPTION
1 REMOVE EXISTING WALL OR PORTION OF WALL AS INDICATED - PATCH ADJ. EXIST. WALL AS REQ.
2 REMOVE EXISTING DOOR & FRAME
3 REMOVE EXISTING WINDOW
4 REMOVE EXISTING PLUMBING FIXTURE & ANY ASSOCIATED PLUMBING (REF. PLUMBING). REPAIR FLOOR/ WALL/ CEILING AS REQUIRED
5 REMOVE CASEWORK
6 REMOVE CORNER GUARD OR END GUARD; REPAIR WALL AS REQUIRED
7 REMOVE EXISTING EXTERIOR WALL OR PORTION OF WALL AS INDICATED, INCLUDING VENEER AND BACKUP
8 REMOVE EXISTING FLOORING, BASE & GLUE RESIDUE USING MECHANICAL MEANS. PREP SUB-FLOORING FOR NEW FLOOR COVERING
9 REMOVE EXISTING FIRE EXTINGUISHER CABINET
10 REMOVE EXISTING WOOD PANEL, METAL FILLER, AND METAL BASE AS REQUIRED; PATCH WALL AS REQUIRED
11 REMOVE EXISTING PASS-THROUGH DRAWER - PATCH WALL ON BOTH SIDES TO MATCH EXISTING - BASE BID ONLY
12 REF. CIVIL DRAWINGS FOR SCOPE OF SITE DEMOLITION; REVIEW ONSITE WITH COR WHICH DEMO ITEMS SHALL BE RETURNED TO OWNER
13 REMOVE ALL EXISTING METAL BASE & SAVE FOR REUSE IN REMODELED SPACE; RETURN ANY EXTRA MATERIAL TO THE VA
14 REMOVE PORTION OF WALL FOR NEW DOOR OPENING
15 REMOVE EXISTING STONE VENEER COVERING STRUCTURAL BEAM - REF. STRUCTURAL
16 REMOVE EXISTING DUMBWAITER AND ALL ASSOCIATED HARDWARE
17 REMOVE LIFT SYSTEM; RETURN TO VA
18 REMOVE WALL-ATTACHED MODULAR FURNITURE; RETURN TO VA. PATCH WALLS, PREPARE TO RECEIVE NEW FINISH
19 REMOVE WALL GUARDS AND CORNER GUARDS; REPAIR WALL AS REQ'D
20 REMOVE CHAIR RAILS; REPAIR WALL AS REQ'D
21 REMOVE CUBICLE CURTAIN AND TRACKS
22 REMOVE EXISTING BASE RAIL; REPAIR WALL AS REQ'D
23 REMOVE EXISTING OUTLET & HOSE BIB, REF. CIVIL & ELEC
24 REMOVE LIGHT FIXTURE, REF. ELEC.
25 REMOVE EXISTING KNOX BOX AND SAVE FOR USE IN REMODELED SPACE
26 REMOVE EXISTING SECURITY CAMERA AND RETURN TO OWNER, REF. ELEC.
27 REMOVE MECHANICAL UNIT, LIGHT FIXTURE & EXIT SIGNAGE, REF. ELEC & MECH.
28 REMOVE EXISTING FIRE ALARM & HUMIDITY CONTROL & RELOCATE; REF. MECH.
29 PRESERVE PNEUMATIC TUBE STATION. - RETURN TO VA
30 REMOVE EXISTING BLOCK WALL OR PORTION OF WALL AS INDICATED - PATCH ADJ. EXIST. WALL AS REQ.
31 REMOVE PHARMACY WINDOW & PHARMACY PASS-THROUGH DRAWER IN BASE BID ONLY
32 VA TO REMOVE/RELOCATE SAFE PRIOR TO CONSTRUCTION
33 RELOCATE T-STAT AS REQ'D FOR NEW CONSTRUCTION; REF. MECHANICAL
34 REMOVE EXISTING MED GAS ZONE BOX, OUTLET, OR ALARM PANEL & ANY ASSOCIATED PIPING - REF. MECH; PATCH & REPAIR
WALLS/CEILING AS REQ'D
35 REMOVE EXISTING BRICK VENEER WHERE INDICATED -REF ELEVATIONS FOR ADDITIONAL INFO
N
4' 8' 16'
1/8" = 1'-0"
0'
3/32" = 1'-0"
NORTH DEMO ELEVATION
3/32" = 1'-0"
WEST DEMO ELEVATION
1" = 80'-0"
KEY PLAN SECOND FLOOR
1 2
1 2
1 2
1 2
1 2
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF
WORK
E146E145
E144
C1F14
F159F160F161F162F164F165F166 F169
F142
F155
F156
F157
F158
F142*
F154
F153F152
F145 F144F146
F149
F148
F147
F168 F171A
F163A
F171
F150
F151
F151A
F151B
C1F17*
C1F19
C1F18
C1F17
C1F20
F1F21
F167
E141
E142
E143
E140
C1E9
E138 E139
E147A
F173
F170F172
C1F22
E137
E107
E106
C1E7
C1E2
E1100
E102C
E102D
E102E
A119A
A121
A123
E102A
E102B
E102
E102GE102F
C1E5
C1E6
C1E3
E101
E102IE102H
A125
A129B
A129B
A130
A131
E105
E104
E103
C1A1
C1E8
C1A3
A119
E102J
F150A
E141A E141B
F163
E147B
ADDITION
REMODEL
AREAS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AD103
FIRST FLOOR - REFLECTED CEILING PLAN
- DEMOLITION
589-334
04/03/2018
1/8" = 1'-0" A
FIRST FLOOR - REFLECTED CEILING
PLAN - DEMOLITIONN
4' 8' 16'
1/8" = 1'-0"
0'
DEMO PLAN NOTES - RCP
# DESCRIPTION
1 REMOVE EXISTING CEILING
2 REMOVE EXISTING MECHANICAL AND ELECTRICAL FIXTURES, REF. MECH. & ELEC DRAWINGS
3 REMOVE EXISTING EXTERIOR LIGHT FIXTURE, REF. ELEC
4 REMOVE EXISTING PATIENT LIFT SYSTEM & RETURN TO OWNER; REF. ELEC.
5 RELOCATE EXISTING SECURITY CAMERA AS REQUIRED FOR ADDITION; REF. ELEC.
6 EXISTING CEILING TO REMAIN, SPLICE GRID AT NEW CONSTRUCTION
7 EXISTING CONCRETE STUCCO SOFFIT TO REMAIN
8 EXISTING DOME MIRROR TO REMAIN
1" = 80'-0"
KEY PLAN FIRST FLOOR
E206
1 1
2 2
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF
WORK
A250
A250A
F236
F237A
F239
F240
F238
F233
F237
C2F17
C2F16
F242
F241F243F244
F245
F230
F231 F232
F250
F246
F251
F249
F248 F247
F234
E207 E208
E202
E203
E204E204A
C2F20
E209
E210A
E210
E211
F253
E212
E215A
E214
E213
C2F18
C2F19
F228
F229
E206
E205
E226
E225
E223
E222 E220
C2E3
C2E2
E224A
E224
C2E4
C2E1
F252
E219 E218 E217 E216
E215
F248
E221
C2E6
C2F14
C2F15
C2E7
F255
F257
F256
ADDITION
REMODEL
AREA
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AD104
SECOND FLOOR - REFLECTED CEILING
PLAN - DEMOLITION
589-334
04/03/2018
1/8" = 1'-0" A
SECOND FLOOR - REFLECTED CEILING
PLAN - DEMOLITION
4' 8' 16'
1/8" = 1'-0"
0'
N
DEMO PLAN NOTES - RCP
# DESCRIPTION
1 REMOVE EXISTING CEILING
2 REMOVE EXISTING MECHANICAL AND ELECTRICAL FIXTURES, REF. MECH. & ELEC DRAWINGS
3 REMOVE EXISTING EXTERIOR LIGHT FIXTURE, REF. ELEC
4 REMOVE EXISTING PATIENT LIFT SYSTEM & RETURN TO OWNER; REF. ELEC.
5 RELOCATE EXISTING SECURITY CAMERA AS REQUIRED FOR ADDITION; REF. ELEC.
6 EXISTING CEILING TO REMAIN, SPLICE GRID AT NEW CONSTRUCTION
7 EXISTING CONCRETE STUCCO SOFFIT TO REMAIN
8 EXISTING DOME MIRROR TO REMAIN
1" = 80'-0"
KEY PLAN SECOND FLOOR
DN
ADDITION
REMODEL
AREAS
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF WORK
AS301
AGENT
CASHIER
E142
TRAVEL
E140
WAITING
F174
CONSULT
F174A
CONSULT
F174B
CONSULT
F174C
STORAGE
F179
SWAMP
F176
CORRIDOR
F1F23
CORRIDOR
F1F22
STAIR #11
F173
F.M.S.
ENG.
F170
SAFE
CAROUSEL
SCRIPT PRO
PINPOINT
TRAVEL
E144
VAULT
F178
OFFICE
F175
AS401
AS401
AS401
A3
AI402
AI402
AI402 6
AI402
A2
BID DEDUCT #2
F174CF174BF174A
F176
F175
F177 F179
A1A1
F1F23
E144
OFFICE
F164
OFFICE
F162
OFFICE
F161
OFFICE
F160
OFFICE
F159
MED
ADMIN
E141
LOBBY
C1E3
AS502
CORR
F1F21
AI402
CAROUSEL
F178A
F178B
PHARMACY
WORK
F177
DISPENSING
F177A
F177B
AS105
AS101
AS101
E142
AS601
AS105
AS105
AS105
AS105
F1F22
A2
AS105
AS105
AS105
AS105
AS101
AS105
AS105
SE140
SE142
SF177A
AI402
AI402
FEC
A3
1AS101
ELEC
F180
F180
F173
PROTECTIVE WIRE MESH
AI4025
AS502
AS601
AS601
PROTECTIV
E WIRE
MESH
AS3011
ACA
F.9
DOOR AS
SCHEDULED
NEW TUBE STATION TO
BE PURCHASED AND
INSTALLED BY
CONTRACTOR; EXISTING
TUBE STATION TO BE
RETURNED TO VA
5/8" TYPE X GYP
ON 3 5/8" MTL
STUDS
5/8" TYPE X GYP
BD. ON 3 5/8" MTL.
STUDS @ 16" O.C.
5/8" TYPE X GYP BD ON 7/8" MTL.
HAT CHANNEL @ 16" O.C. ON
CMU - REF. SPEC.
CAULK - TYP.
2HR COLUMN WRAP - UL DESIGN X528 - REF. SPECS.
WIRE MESH REINFORCING
8' CMU WALL - REF.
STRUCT.
5/8" GYP BD. ON 7/8"
HAT CHANNEL @ 16"
O.C.
5/8" TYPE "X" GYP
BD. ON 3 5/8" MTL.
STUDS @ 16" O.C.
5/8" TYPE "X" GYP BD.
ON 1 5/8" MTL. STUDS
BATT. INSUL.
F177B
VAULT
F178
WIRE MESH REINFORCING
10.1
G.5
5/8" GYP BD. ON 7/8" MTL.
HAT CHANNEL ON CMU -
REF. SPEC.
5/8" TYPE X GYP
BD. ON 3 5/8" MTL
STUDS @ 16" 0.C.
5/8" TYPE X GYP BD.
ON 3 5/8" MTL.
STUDS @ 16" O.C.
5/8" TYPE XGYP BD.
ON 2 1/2" MTL.
STUDS
5/8" TYPE X GYP BD.
ON 7/8" MTL. HAT
CHANNEL
CAULK - TYP.
2HR COLUMN
WRAP - UL
DESIGN X528 -
REF. SPECS.
COLUMN, REF.
STRUCTURAL
WIRE MESH REINFORCING
WIRE MESH REINFORCING
6' - 6"
GYP CONTROL JOINT
@ SEAM OF
REMOVABLE WALL
PANEL - EXTEND TO
TOP OF WALL
GYP CONTROL JOINT
@ SEAM OF
REMOVABLE WALL
PANEL - EXTEND TO
TOP OF WALL
5/8" TYPE X GYP. BD. ON 3
5/8" MTL STUDS @ 16"
O.C.
MEDCAROUSEL; REF.
EQUIPMENT PLAN
WIRE MESH
REINFORCING
ACA
ACA
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS101
FIRST FLOOR - FLOOR PLAN
589-334
04/03/2018
N
4' 8' 16'
1/8" = 1'-0"
0'
1" = 80'-0"
KEY PLAN FIRST FLOOR
PLAN NOTES - FLOOR PLAN
# DESCRIPTION
1 REMOVEABLE PORTION OF WALL FOR INSTALLATION OF MEDCAROUSEL
2 RELOCATED KNOX BOX
3 PROVIDE A RAMP AND HANDRAIL, REF. CIVIL
4 ALIGN WALLS
5 ALIGN FACE OF GYP WITH EXIST ADJ. FACE OF GYP
6 PATCH FLOOR AS REQ'D WHERE METAL BASE WAS REMOVED
1/8" = 1'-0" A
FIRST FLOOR PLAN
1 1/2" = 1'-0"
PNEUMATIC TUBE STATION PLAN
DETAIL
1 1/2" = 1'-0"
PLAN DETAIL - VAULT CONNECTION
1 1/2" = 1'-0"
COLUMN WRAP DETAIL
1 1/2" = 1'-0"
REMOVEABLE WALL PANEL DETAIL
DN
ADDITION
REMODEL
AREAS
AS301
AI402
CORRIDOR
F1F23
STORAGE
F177
ACA
ACA
ACA
ACA
10.6
ACA
ACA
11.5
ACA
ACA
H
ACA
G
ACA
E
ACA
D
ACA
C
ACA
E.1
ACA
F
ACA
B.2
ACA
D.8
ACA
D.7
BD177A BD177B
F1F23
A3
A2
AS502
ACA
10.1
11.8
F.2 F.9 G.5
12.1
E.5 F.1
BID DEDUCT #2
AS105
AS105
AS105
AS105
AS105
AS105
AS105
AS105
STAIR #11
F173
OFFICE
F159
OFFICE
F160
OFFICE
F161
OFFICE
F162
OFFICE
F164
ELEC
F180
F180
F173
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF WORK
TRAVEL
E140
SAFE
PINPOINT
TRAVEL
E144
A1A1
FEC
E144
E142
F1F22
CORRIDOR
F1F22
AGENT
CASHIER
E142
F.M.S.
ENG.
F170
AS601
CORR
F1F21
AS105
SE140 SE142
AS502
AS601
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS101.2
FIRST FLOOR - FLOOR PLAN - BID DEDUCT
#2
589-334
04/03/2018
1" = 80'-0"
KEY PLAN FIRST FLOOR
1/8" = 1'-0" A
FIRST FLOOR PLAN - BID DEDUCT #2
N
4' 8' 16'
1/8" = 1'-0"
0'
PLAN NOTES - FLOOR PLAN
# DESCRIPTION
1 REMOVEABLE PORTION OF WALL FOR INSTALLATION OF MEDCAROUSEL
2 RELOCATED KNOX BOX
3 PROVIDE A RAMP AND HANDRAIL, REF. CIVIL
4 ALIGN WALLS
5 ALIGN FACE OF GYP WITH EXIST ADJ. FACE OF GYP
6 PATCH FLOOR AS REQ'D WHERE METAL BASE WAS REMOVED
AS301
WAITING /
DILATION
E209
DIRTY
E253
ELEC
F252
SWAMP
E215
LASER
E255
TLT
F253
EXAM 1
E226
EXAM 2
E225
EXAM 3
E223
EXAM 4
E222
EXAM 5
E221
EXAM 6
E219
EXAM 7
E218
EXAM 8
E217 FUNDUS
E216
VISUAL
FIELDS
E211
VISUAL
FIELDS
E212
REFRAC
E212A
PROCEDURE
E213
EXAM 9
E220
JAN
E205
EQUIP
E205A
N.S.
E211AWORK RM.
E224A
REFRAC
E210
IMAGING
F256
EXAM 10
F273
EXAM 22
F258
EXAM 21
F259
EXAM 11
F272
EXAM 12
F271
EXAM 13
F270
EXAM 14
F269
EXAM 18
F262
EXAM 19
F261
EXAM 20
F260
EXAM 15
F267
EXAM 16
F266
EXAM 17
F265
WAITING
DILATION
F257
WAITING
E206
NOT IN SCOPE OF
WORK
OPEN TO
BELOW
CORR
C2E3
CORR
C2E2
CORR
C2E1
CORR
C2F21
STAIR #11
F248
CORR
C2F22
CORR
C2F24
PRE-
CATARACT
E214 CLEAN
E254
ADMIN
OFFICE
F255
NURSE
F264
WAITING
F268
WAITING
F263
AS102
B
AS401
AS401
AS401
C2F20
E216
E224
E205
E215
F256
C2F22 F267
F266
F265
F259 F260 F261 F262
F269F270F271F272F273
E220
F248
E211
E212
E253
E254
A4 A5
A6
A7
AI401
AI401
AI4018
A5
BID DEDUCT #1
E213 E255
F258
AS502
ADMIT
E224
HALL
C2E4
EXAM
F247
EXAM
F244
EXAM
F243
EXAM
F241
EXAM
F240
CORR
C2F20
CORR
C2F23
AI401 10
AI401 56
AI401
C2F21
INFILL FLOOR SLAB
- REF. STRUCTURAL
AI401 7
AI4019
AS102
E209
AS504
Sim
AS102
AS105
AS105
15AS105
AS105
AS105
AS105
AS105
AS105
AS105
AS105
AI401
AI401 10 AI401 10 AI401 10 AI401 10
AI40110
AI40110
AI40110AI40110
AI40110
11 11 11 11
11 11 11
AI401 20
AS3011
C2E2
AI501
AI401
19 20
AI401
19 20
AI40112
AI40112
AI40112
AI401 12
AI401
AI401 12
AI401
AI401
AI401
SIM
SIM
SIM
SIM
SIM
REV
SIM SIM
FEC
AS105
11"
AS502
AI40122
AI40122
ADDITION
REMODEL
AREA
TLT
F253
AI40115
F253
AI401 21
DIRTY
E253
E253
SPANDREL GLASS - REF. SPECS.
ANODIZED ALUM. STOREFRONT
SYSTEM W/ 1" INSUL GLAZING -
REF SPEC
5/8" GYP BD. ON 2 1/2"
MTL. STUDS @ 16"
O.C.
5/8" GYP BD. ON
3 5/8" MTL.
STUDS @ 16"
O.C.
SS SILL - REF. FINISH SCHED.
WOOD BLOCKING
SS SILL - REF. FINISH
SCHED.
A7
BATT. INSUL.
5/8" GYP BD. ON 2 1/2"
MTL. STUDS @ 16"
O.C.
CAULK TO STOREFRONT
CAULK TO STOREFRONT
BREAK MTL. WALL CAP -
FINISH TO MATCH
STOREFRONT
ANODIZED ALUM
STOREFRONT SYSTEM W/
1" INSUL GLAZING -REF.
SPECS
5/8" TYPE "X" GYP. BD.
ON 3 5/8" MTL. STUDS
@ 16" 0.C.
EXAM 17
F265
EXAM 16
F266
SS SILL - REF. FINISH
SCHEDULE
SS SILL - REF. FINISH
SCHEDULE
ACA
H
ACA
H
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS102
SECOND FLOOR - FLOOR PLAN
589-334
04/03/2018
1/8" = 1'-0" A
SECOND FLOOR PLAN
1" = 80'-0"
KEY PLAN SECOND FLOOR
1/4" = 1'-0" B
ENLARGED PLAN - F253 TLT
N
4' 8' 16'
1/8" = 1'-0"
0'
1 1/2" = 1'-0"
PLAN DETAIL - WINDOW A7
1 1/2" = 1'-0"
PLAN DETAIL - WALL CAP
AS301
AS401
AS401
AS401
AI401
AI401
AI4018
A6
A6
BD265
STORAGE
BD265
E 1
ACA
ACA
ACA
ACA
ACA
10.6
ACA
ACA
11.5
ACA
ACA
H
ACA
G
ACA
E
ACA
D
ACA
C
ACA
B
ACA
E.1
ACA
F
ACA
B.2
ACA
D.8
ACA
D.7
AS502
ACA
10.1
11.8
F.2 F.9 G.5
12.1
AI401 10
AI401 56
AI401
E.5
AI401 7
AI4019
F.1
AS3011
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF WORK
AI401
WAITING /
DILATION
E209
DIRTY
E253
ELEC
F252
SWAMP
E215LASER
E255
TLT
F253
EXAM 1
E226
EXAM 2
E225
EXAM 3
E223
EXAM 4
E222
EXAM 5
E221
EXAM 6
E219
EXAM 7
E218 EXAM 8
E217
FUNDUS
E216
VISUAL
FIELDS
E211
VISUAL
FIELDS
E212
REFRAC
E212A
PROCEDURE
E213
EXAM 9
E220
JAN
E205
EQUIP
E205A
N.S.
E211AWORK RM.
E224A
REFRAC
E210
IMAGING
F256
EXAM 10
F273
EXAM 22
F258
EXAM 21
F259
EXAM 11
F272
EXAM 12
F271
EXAM 13
F270
EXAM 14
F269
EXAM 18
F262
EXAM 19
F261
EXAM 20
F260
WAITING
DILATION
F257
WAITING
E206
CORR
C2E3
CORR
C2E2
CORR
C2E1
CORR
C2F21
STAIR #11
F248
CORR
C2F22
CORR
C2F24
CORR
C2F23
WAITING
F263
NURSE
F264
WAITING
F268
PRE-
CATARACT
E214
CLEAN
E254
ADMIN
OFFICE
F255
ADMIT
E224
HALL
C2E4
EXAM
F247
EXAM
F244
EXAM
F243
EXAM
F241
EXAM
F240
CORR
C2F20
BID DEDUCT #1
AI401 10 AI401 10 AI401 10 AI401 10
AI40110AI40110AI40110AI40110AI40110
11 11 11 11
11 11 11 11
AS105
AS105
AS105
AS105
AS105
AS105
F273 F272 F271 F270 F269
F262F261F260F259F258
AS504
A4A5
E216 F256
E215
E255E213
E220
E205
E211
E212
E254
E253
E209
C2F20
C2F21
F248
INFILL FLOOR SLAB
- REF. STRUCTURAL
AS105
AS105
AS105
AS105
AS102
B
AI40112
AS502
AI40122
AI40122
AI40112
AI40112
AI401 12
AI401
AI401 12
AI401
AI401
AI401
/2
11 1/2"
A5
AI501
E224
C2F22
AS105
ADDITION
REMODEL
AREA
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS102.1
SECOND FLOOR - FLOOR PLAN - BID
DEDUCT #1
589-334
04/03/2018
1/8" = 1'-0" A
SECOND FLOOR PLAN - BID DEDUCT #1
1" = 80'-0"
KEY PLAN SECOND FLOORN
4' 8' 16'
1/8" = 1'-0"
0'
WALL MATERIALS
LEGEND FOR WALL TAGS
MATERIAL
WIDTH
S - STRUCTURAL METAL STUDS, 20 ga. OR
HEAVIER, (REF. STRUCT.)
L - LIGHT GAUGE METAL STUDS, 20 ga. INTERIOR, 16 ga.
EXTERIOR (REF. SPECS.)
B - CONCRETE MASONRY UNIT, STANDARD
WEIGHTS FOR EXTERIOR & INTERIOR, UNLESS
NOTED OTHERWISE (REF. STRUCT.)
WALL WIDTHS
0 - 7/8" HAT CHANNEL
1 - 1 5/8" HAT CHANNEL/ STUDS
4 - 4" METAL STUD FRAMING
6 - 6" METAL STUD FRAMING OR CONCRETE MASONRY UNIT
8 - 8" METAL STUD FRAMING OR CONCRETE MASONRY
UNIT
NOTES:
PROVIDE ACCOUSTICAL SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS OF WALLS WITH SOUND BATT.
ALL STUD FRAMING TO BE 16" O.C., TYP.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL PENETRATIONS OF
SMOKE PARTITION WALLS AS REQUIRED BY CODE.
PROVIDE ALL NEW WALLS THAT GO TO STRUCTURE w/ 1 1/2"
MTL. DEFLECTION TRACK - REF STRUCT.
N - NONE
A - ACC0USTICAL
XXXX
INSULATION
WALL INSULATION
WALL HEIGHT
SHADED WALLS INDICATES WALLS
THAT EXTEND TO DECK
INSTALL 5/8" TYPE X GYP BD ON ONE SIDE OF FURRING,
TYP. INSTALL 5/8" TYPE X GYP BD ON BOTH SIDES OF
STUD FRAMING, TYP., UNLESS NOTED OTHERWISE.
EXTEND GYP BD TO 6" ABOVE CEILING UNLESS REQUIRED
OTHERWISE. PROVIDE ACCOUSTICAL SEALANT AT TOP
AND BOTTOM OF ALL PENETRATIONS OF WALL WITH
SOUND BATT.
WALLS TO RECEIVE GYPSUM BOARD PRODUCT ON BOTH
FACES OF METAL STUD AND WALLS THAT REQUIRE
ACOUSTICAL SOUND BATT INSULATION SHALL BE
CONSTRUCTED TO MEET A MINIMUM 45 STC UNLESS
OTHERWISE NOTED.
FIRE TAPE AND/OR FILL VOIDS AT TOP OF WALL - FIRE
RATED WALL AS REQUIRED BY CODE - REF. SPEC.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS ON ONE SIDE OF SMOKE PARTITION
WALLS AS REQUIRED BY CODE - REF. SPECS
INSTALL FIRE RATED SEAL/CLOSURE @ ALL OPENINGS,
GAPS AND TOP & BOTTOM OF FRAMING AS SPECIFIED.
BRACE ALL STUD WALLS TO STRUCTURE ABOVE @ 4'-0" O.C.
OR EXTEND ALL STUDS TO DECK ABOVE, TYP.
T - THERMAL
RATING
R - RATED INDICATES WALL IS RATED FOR FIRE,
OCCUPANCY, AND/ OR SMOKE - REF. LIFE SAFETY
SHEETS
RATED
INDICATES WALL THAT EXTEND 6"
ABOVE CEILING
M - WIRE MESH REINFORCEMENT (REF. SPECS.)
3 - 3 5/8" METAL STUD FRAMING
PROVIDE COATED GLASS MAT TILE BACKER BOARD AT ALL
SHOWER & WET AREAS AND AS BACKER FOR CERAMIC WALL TILE.
TOILET & SINK AREAS TO RECEIVE MOISTURE-RESISTANT GYP
BOARD. PROVIDE 20GA. STUDS AS REQUIRED IN TCNA AND GA-216.
ADDITION
REMODEL
AREAS
TRAVEL
E140 AGENT
CASHIER
E142
CORRIDOR
F1F22
WAITING
F174
C O
N S
U L T
F
A
C O
N S
U L T
F
B
C O
N S
U L T
F
C
VAULT
F178
SWAMP
F176
STORAGE
F179
CORRIDOR
F1F23
12' - 6" ±17' - 6"
L3A
L3AMR
B6N
L3A
L3AM
L3A
L3T
L1N
L1N
STAIR #11
F173
F.M.S.
ENG.
F170
PINPOINT
TRAVEL
E144
L3A
B4NR
14' - 10"9' - 4"25' - 3"5' - 11"6' - 7"6' - 10"2' - 6" ±6' - 6"
9' - 6"5' - 5"
2' - 0"
4' - 11"5' - 4"3' - 6"17' - 8"7' - 4"13' - 2"
ACA
ACA
ACA
ACA
10.6
ACA
ACA
11.5
ACA
ACA
H
ACA
G
ACA
E
ACA
D
ACA
C
ACA
E.1
ACA
F
ACA
D.8
ACA
D.7
BID DEDUCT #2
1' - 0"51' - 8"1' - 0"15' - 3"
L3A
L3A
L3N
L3A
L3N
L3AM
L3AM L3AMR
L3N
L1NL3A
L3AR
L1N L0N
L3AR L3AR L3AR
L1N
OFFICE
F175
OFFICE
F164
OFFICE
F162
OFFICE
F161
OFFICE
F160
OFFICE
F159
ACA
10.1
11.8
F.2 F.9 G.5
12.1
/2
/2
CLEAR
4' - 0"
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF WORK
16' - 9" 52' - 8"
E.5
L3AR
B8N
L3AMR
/2
L3NL3N
PHARMACY
WORK
F177
L0N
4' - 6"
L3A
L3N
3' - 7" 15' - 0" 3' - 7"
L3AR
F.1
L3T
L3N L3N L3N
CLEAR
4' - 3 1/2"
L1N
L1N
B8N
B8NR
B8N
L0N
L1N
L3N
L3NL3N
5 555
L3NR
L3NR
L1N
L1N
ELEC
F180
L3NRL3NR
PROTECTIVE WIRE MESH
PROTECTIVE WIRE MESH
L3N
PROTECTIV
E WIRE
MESH
6' - 3 1/2"
L3A L3A L3A L3A
L0N L1N
L3N L3A L3AM L6A B4NR B8N
WIRE MESH
REINFORCEMEN
T
ACOUST. BATT
INSUL.ACOUST. BATT INSUL. ACOUST. BATT INSUL.
7/8" HAT CHANNEL
5/8" TYPE X GYP BD. 1 5/8" MTL. STUD
5/8" TYPE X GYP BD.
5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD.
7/8" HAT CHANNEL
6" CMU
8" CMU
3 5/8" MTL. STUD 3 5/8" MTL. STUD 3 5/8" MTL.
STUD
6" MTL. STUD
L3AR
ACOUST. BATT INSUL.
2X 5/8" TYPE X
GYP BD.
3 5/8" MTL. STUD
SUBSTRATE
T Y
P
T Y
P
T Y
P
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
B.O. DECK
FIRE RESISTIVE
JOINT SYSTEM
T Y
P
SUBSTRATE
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
CLG. - REF.
CLG. PLANS
B.O. DECK B.O. DECK
B.O. DECKB.O. DECK
B.O. DECKB.O. DECKB.O. DECK
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
DEFLECTIO
N TRACK
DEFLECTION TRACK
DEFLECTION TRACKDEFLECTION TRACK
DEFLECTION TRACK
ACOUST. SEALANT
L1NR
1 5/8" MTL.
STUD
3X 5/8" TYPE
X GYP BD.
CLG. - REF. CLG.
PLANS
B.O. DECK
FINISHED FLOOR
FIRE RESISTIVE
JOINT SYSTEM
DEFLECTION TRACK
ACOUSTICAL
SEALANT
2 HOUR
UL U411
METAL SECURITY
MESH
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS103
FIRST FLOOR - DIMENSIONS PLAN
589-334
04/03/2018
4' 8' 16'
1/8" = 1'-0"
0'
1" = 80'-0"
KEY PLAN FIRST FLOOR
1/8" = 1'-0" A
FIRST FLOOR PLAN - DIMENSIONSN
PLAN NOTES - FLOOR PLAN
# DESCRIPTION
1 REMOVEABLE PORTION OF WALL FOR INSTALLATION OF MEDCAROUSEL
2 RELOCATED KNOX BOX
3 PROVIDE A RAMP AND HANDRAIL, REF. CIVIL
4 ALIGN WALLS
5 ALIGN FACE OF GYP WITH EXIST ADJ. FACE OF GYP
6 PATCH FLOOR AS REQ'D WHERE METAL BASE WAS REMOVED
1 1/2" = 1'-0"
WALL TYPES
ACA
ACA
ACA
ACA
10.6
ACA
ACA
11.5
ACA
ACA
H
ACA
G
ACA
E
ACA
D
ACA
C
ACA
E.1
ACA
F
ACA
D.8
ACA
D.7
ACA
10.1
11.8
F.2 F.9 G.5
12.1
E.5 F.1
CORRIDOR
F1F23
STORAGE
F177
L1N
L1N
L3T
L3T
L1N
L3NR
L1N
BID DEDUCT #2
STAIR #11
F173
1' - 0"51' - 8"1' - 0"15' - 3"
16' - 9" 52' - 8"
L1NL1N
5 555
OFFICE
F164
OFFICE
F162
OFFICE
F161
OFFICE
F160
OFFICE
F159
L3AR L3AR L3AR L3AR
NOT IN SCOPE OF
WORK
NOT IN SCOPE OF WORK
CORRIDOR
F1F22
F.M.S.
ENG.
F170
AGENT
CASHIER
E142
TRAVEL
E140
PINPOINT
TRAVEL
E144
L3A
L3A
L3N
L3AR
B6N
L3A
L3NRL3NR
L3NR
L3NR
L3AR
3' - 7" 15' - 0" 3' - 7"
4' - 6"
12' - 6"17' - 6"
4' - 7" 54' - 8" 2' - 7"
2' - 1"
3' - 10"
L1NRL1NR
L1NR L1NR
L3N 6' - 3 1/2"
L3A
L3A
L3A L3A
L3A L3A
ADDITION
REMODEL
AREAS
WALL MATERIALS
LEGEND FOR WALL TAGS
MATERIAL
WIDTH
S - STRUCTURAL METAL STUDS, 20 ga. OR
HEAVIER, (REF. STRUCT.)
L - LIGHT GAUGE METAL STUDS, 20 ga. INTERIOR, 16 ga.
EXTERIOR (REF. SPECS.)
B - CONCRETE MASONRY UNIT, STANDARD
WEIGHTS FOR EXTERIOR & INTERIOR, UNLESS
NOTED OTHERWISE (REF. STRUCT.)
WALL WIDTHS
0 - 7/8" HAT CHANNEL
1 - 1 5/8" HAT CHANNEL/ STUDS
4 - 4" METAL STUD FRAMING
6 - 6" METAL STUD FRAMING OR CONCRETE MASONRY UNIT
8 - 8" METAL STUD FRAMING OR CONCRETE MASONRY
UNIT
NOTES:
PROVIDE ACCOUSTICAL SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS OF WALLS WITH SOUND BATT.
ALL STUD FRAMING TO BE 16" O.C., TYP.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL PENETRATIONS OF
SMOKE PARTITION WALLS AS REQUIRED BY CODE.
PROVIDE ALL NEW WALLS THAT GO TO STRUCTURE w/ 1 1/2"
MTL. DEFLECTION TRACK - REF STRUCT.
N - NONE
A - ACC0USTICAL
XXXX
INSULATION
WALL INSULATION
WALL HEIGHT
SHADED WALLS INDICATES WALLS
THAT EXTEND TO DECK
INSTALL 5/8" TYPE X GYP BD ON ONE SIDE OF FURRING,
TYP. INSTALL 5/8" TYPE X GYP BD ON BOTH SIDES OF
STUD FRAMING, TYP., UNLESS NOTED OTHERWISE.
EXTEND GYP BD TO 6" ABOVE CEILING UNLESS REQUIRED
OTHERWISE. PROVIDE ACCOUSTICAL SEALANT AT TOP
AND BOTTOM OF ALL PENETRATIONS OF WALL WITH
SOUND BATT.
WALLS TO RECEIVE GYPSUM BOARD PRODUCT ON BOTH
FACES OF METAL STUD AND WALLS THAT REQUIRE
ACOUSTICAL SOUND BATT INSULATION SHALL BE
CONSTRUCTED TO MEET A MINIMUM 45 STC UNLESS
OTHERWISE NOTED.
FIRE TAPE AND/OR FILL VOIDS AT TOP OF WALL - FIRE
RATED WALL AS REQUIRED BY CODE - REF. SPEC.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS ON ONE SIDE OF SMOKE PARTITION
WALLS AS REQUIRED BY CODE - REF. SPECS
INSTALL FIRE RATED SEAL/CLOSURE @ ALL OPENINGS,
GAPS AND TOP & BOTTOM OF FRAMING AS SPECIFIED.
BRACE ALL STUD WALLS TO STRUCTURE ABOVE @ 4'-0" O.C.
OR EXTEND ALL STUDS TO DECK ABOVE, TYP.
T - THERMAL
RATING
R - RATED INDICATES WALL IS RATED FOR FIRE,
OCCUPANCY, AND/ OR SMOKE - REF. LIFE SAFETY
SHEETS
RATED
INDICATES WALL THAT EXTEND 6"
ABOVE CEILING
M - WIRE MESH REINFORCEMENT (REF. SPECS.)
3 - 3 5/8" METAL STUD FRAMING
PROVIDE COATED GLASS MAT TILE BACKER BOARD AT ALL
SHOWER & WET AREAS AND AS BACKER FOR CERAMIC WALL TILE.
TOILET & SINK AREAS TO RECEIVE MOISTURE-RESISTANT GYP
BOARD. PROVIDE 20GA. STUDS AS REQUIRED IN TCNA AND GA-216.
L0N L1N
L3N L3A L3AM L6A B4NR B8N
WIRE MESH
REINFORCEMEN
T
ACOUST. BATT
INSUL.ACOUST. BATT INSUL. ACOUST. BATT INSUL.
7/8" HAT CHANNEL
5/8" TYPE X GYP BD. 1 5/8" MTL. STUD
5/8" TYPE X GYP BD.
5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD.
7/8" HAT CHANNEL
6" CMU
8" CMU
3 5/8" MTL. STUD 3 5/8" MTL. STUD 3 5/8" MTL.
STUD
6" MTL. STUD
L3AR
ACOUST. BATT INSUL.
2X 5/8" TYPE X
GYP BD.
3 5/8" MTL. STUD
SUBSTRATE
T Y
P
T Y
P
T Y
P
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
B.O. DECK
FIRE RESISTIVE
JOINT SYSTEM
T Y
P
SUBSTRATE
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
CLG. - REF.
CLG. PLANS
B.O. DECK B.O. DECK
B.O. DECKB.O. DECK
B.O. DECKB.O. DECKB.O. DECK
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
DEFLECTIO
N TRACK
DEFLECTION TRACK
DEFLECTION TRACKDEFLECTION TRACK
DEFLECTION TRACK
ACOUST. SEALANT
L1NR
1 5/8" MTL.
STUD
3X 5/8" TYPE
X GYP BD.
CLG. - REF. CLG.
PLANS
B.O. DECK
FINISHED FLOOR
FIRE RESISTIVE
JOINT SYSTEM
DEFLECTION TRACK
ACOUSTICAL
SEALANT
2 HOUR
UL U411
METAL SECURITY
MESH
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS103.2
FIRST FLOOR - DIMENSIONS PLAN - BID
DEDUCT #2
589-334
04/03/2018
1/8" = 1'-0" A
FIRST FLOOR PLAN - DIMENSIONS BID
DEDUCT #2
N
4' 8' 16'
1/8" = 1'-0"
0'
1" = 80'-0"
KEY PLAN FIRST FLOOR
PLAN NOTES - FLOOR PLAN
# DESCRIPTION
1 REMOVEABLE PORTION OF WALL FOR INSTALLATION OF MEDCAROUSEL
2 RELOCATED KNOX BOX
3 PROVIDE A RAMP AND HANDRAIL, REF. CIVIL
4 ALIGN WALLS
5 ALIGN FACE OF GYP WITH EXIST ADJ. FACE OF GYP
6 PATCH FLOOR AS REQ'D WHERE METAL BASE WAS REMOVED
1 1/2" = 1'-0"
WAITING /
DILATION
E209
DIRTY
E253
ELEC
F252
SWAMP
E215
LASER
E255
TLT
F253
EXAM 1
E226
EXAM 2
E225
EXAM 3
E223
EXAM 4
E222
EXAM 5
E221
EXAM 6
E219
EXAM 7
E218 EXAM 8
E217
FUNDUS
E216
VISUAL
FIELDS
E211
VISUAL
FIELDS
E212
REFRAC
E212A
PROCEDURE
E213
EXAM 9
E220
JAN
E205
EQUIP
E205A
N.S.
E211A
WORK RM.
E224A
REFRAC
E210
IMAGING
F256
EXAM 10
F273
EXAM 22
F258
EXAM 21
F259
EXAM 11
F272
EXAM 12
F271
EXAM 13
F270
EXAM 14
F269
EXAM 18
F262
EXAM 19
F261
EXAM 20
F260
EXAM 15
F267
EXAM 16
F266
EXAM 17
F265
NOT IN SCOPE OF
WORK
OPEN TO
BELOW
3' - 1" ±2' - 5"5' - 6"1' - 11"6' - 3"6' - 3"5' - 0"6' - 4" ±
11' - 4"9' - 9"6' - 5" ±10' - 4"6"6' - 6" ±13' - 0"
CLEAR, TYP
4' - 0"
4' - 10" ±
1' - 9"
8' - 0"
L3N
L3AR
L3A
L3AR
L3A
L3AR
L3A
L3A
L3N
L3A
L3A
L3A
L3A
L3A
L3A L3N
L3A
L3A
L3A
L3N
L3A
L3A
L3N
L3A
L3N
L3N
L3N
L3N
L3A
L3A
L3A
L3N
L3A L3A
L3A
L3A
L3A
L3A
L3A
L3A L3A L3A L3A
L3A
L3A
L3A
L3AR
L
N
L0N
L1N
L3N
CORR
C2E3
CORR
C2E2
CORR
C2E1
CORR
C2F21
WAITING
DILATION
F257
CORR
C2F24
CORR
C2F22
CORR
C2F23
STAIR #11
F248
3 1/2"8' - 3 1/2"5' - 10"7' - 3"9' - 5"9' - 5"9' - 5"9' - 5"9' - 5"2"
L3A
"WAITING
F263
NURSE
F264
WAITING
F268
PRE-
CATARACT
E214
WAITING
E206
CLEAN
E254
ADMIN
OFFICE
F255
ACA
ACA
ACA
ACA
10.6
ACA
ACA
11.5
ACA
ACA
H
ACA
G
ACA
E
ACA
D
ACA
C
ACA
B
ACA
A
ACA
E.1
ACA
F
ACA
B.2
ACA
D.8
ACA
D.7
L1N
L3A L3AL3A
L3A
L3A
L1N
L3A
2' - 6"12' - 6"
L3N
L3A
L3A
L3A
1' - 6"13' - 5"15' - 11"22' - 4"1' - 0"15' - 3"
/2
ACA
10.1
11.8
F.2 F.9 G.5
12.1
52' - 8"16' - 9"
69' - 5"
L3A 3
/2
/2
CLEAR
5' - 1"
L3N L3N L3N
L3N
L3N
L3AR
L3T
L3T
L3T
E.5
HALL
C2E4 4
L3N
L3N
L3N
L3AR
L2T
L3NL3AL1N
L3A
L3A L3A
L3N
L3N
L3N
L3N
11' - 1 1/2"
L3N
F.1
L3A
L3AR
L3AR
L3N
L3AR
EXAM
F247
EXAM
F244
EXAM
F243
EXAM
F241
EXAM
F240
11' - 3" 5' - 0" 6' - 0" 10' - 0" 6' - 0" 5' - 0" 9' - 5"
L3N
1' - 2"
L3A
L3N
L3N
L3N
L3A
8' - 8" L3N L3N
L3N
L3N
BID DEDUCT #
1L1N
INFILL FLOOR SLAB
- REF. STRUCTURAL
SHEET S-102.3
L3A
ADDITION
REMODEL
AREA
WALL MATERIALS
LEGEND FOR WALL TAGS
MATERIAL
WIDTH
S - STRUCTURAL METAL STUDS, 20 ga. OR
HEAVIER, (REF. STRUCT.)
L - LIGHT GAUGE METAL STUDS, 20 ga. INTERIOR, 16 ga.
EXTERIOR (REF. SPECS.)
B - CONCRETE MASONRY UNIT, STANDARD
WEIGHTS FOR EXTERIOR & INTERIOR, UNLESS
NOTED OTHERWISE (REF. STRUCT.)
WALL WIDTHS
0 - 7/8" HAT CHANNEL
1 - 1 5/8" HAT CHANNEL/ STUDS
4 - 4" METAL STUD FRAMING
6 - 6" METAL STUD FRAMING OR CONCRETE MASONRY UNIT
8 - 8" METAL STUD FRAMING OR CONCRETE MASONRY
UNIT
NOTES:
PROVIDE ACCOUSTICAL SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS OF WALLS WITH SOUND BATT.
ALL STUD FRAMING TO BE 16" O.C., TYP.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL PENETRATIONS OF
SMOKE PARTITION WALLS AS REQUIRED BY CODE.
PROVIDE ALL NEW WALLS THAT GO TO STRUCTURE w/ 1 1/2"
MTL. DEFLECTION TRACK - REF STRUCT.
N - NONE
A - ACC0USTICAL
XXXX
INSULATION
WALL INSULATION
WALL HEIGHT
SHADED WALLS INDICATES WALLS
THAT EXTEND TO DECK
INSTALL 5/8" TYPE X GYP BD ON ONE SIDE OF FURRING,
TYP. INSTALL 5/8" TYPE X GYP BD ON BOTH SIDES OF
STUD FRAMING, TYP., UNLESS NOTED OTHERWISE.
EXTEND GYP BD TO 6" ABOVE CEILING UNLESS REQUIRED
OTHERWISE. PROVIDE ACCOUSTICAL SEALANT AT TOP
AND BOTTOM OF ALL PENETRATIONS OF WALL WITH
SOUND BATT.
WALLS TO RECEIVE GYPSUM BOARD PRODUCT ON BOTH
FACES OF METAL STUD AND WALLS THAT REQUIRE
ACOUSTICAL SOUND BATT INSULATION SHALL BE
CONSTRUCTED TO MEET A MINIMUM 45 STC UNLESS
OTHERWISE NOTED.
FIRE TAPE AND/OR FILL VOIDS AT TOP OF WALL - FIRE
RATED WALL AS REQUIRED BY CODE - REF. SPEC.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS ON ONE SIDE OF SMOKE PARTITION
WALLS AS REQUIRED BY CODE - REF. SPECS
INSTALL FIRE RATED SEAL/CLOSURE @ ALL OPENINGS,
GAPS AND TOP & BOTTOM OF FRAMING AS SPECIFIED.
BRACE ALL STUD WALLS TO STRUCTURE ABOVE @ 4'-0" O.C.
OR EXTEND ALL STUDS TO DECK ABOVE, TYP.
T - THERMAL
RATING
R - RATED INDICATES WALL IS RATED FOR FIRE,
OCCUPANCY, AND/ OR SMOKE - REF. LIFE SAFETY
SHEETS
RATED
INDICATES WALL THAT EXTEND 6"
ABOVE CEILING
M - WIRE MESH REINFORCEMENT (REF. SPECS.)
3 - 3 5/8" METAL STUD FRAMING
PROVIDE COATED GLASS MAT TILE BACKER BOARD AT ALL
SHOWER & WET AREAS AND AS BACKER FOR CERAMIC WALL TILE.
TOILET & SINK AREAS TO RECEIVE MOISTURE-RESISTANT GYP
BOARD. PROVIDE 20GA. STUDS AS REQUIRED IN TCNA AND GA-216.
L0N L1N
L3N L3A L3AM L6A B4NR B8N
WIRE MESH
REINFORCEMEN
T
ACOUST. BATT
INSUL.ACOUST. BATT INSUL. ACOUST. BATT INSUL.
7/8" HAT CHANNEL
5/8" TYPE X GYP BD. 1 5/8" MTL. STUD
5/8" TYPE X GYP BD.
5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD.
7/8" HAT CHANNEL
6" CMU
8" CMU
3 5/8" MTL. STUD 3 5/8" MTL. STUD 3 5/8" MTL.
STUD
6" MTL. STUD
L3AR
ACOUST. BATT INSUL.
2X 5/8" TYPE X
GYP BD.
3 5/8" MTL. STUD
SUBSTRATE
T Y
P
T Y
P
T Y
P
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
B.O. DECK
FIRE RESISTIVE
JOINT SYSTEM
T Y
P
SUBSTRATE
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
CLG. - REF.
CLG. PLANS
B.O. DECK B.O. DECK
B.O. DECKB.O. DECK
B.O. DECKB.O. DECKB.O. DECK
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
DEFLECTIO
N TRACK
DEFLECTION TRACK
DEFLECTION TRACKDEFLECTION TRACK
DEFLECTION TRACK
ACOUST. SEALANT
L1NR
1 5/8" MTL.
STUD
3X 5/8" TYPE
X GYP BD.
CLG. - REF. CLG.
PLANS
B.O. DECK
FINISHED FLOOR
FIRE RESISTIVE
JOINT SYSTEM
DEFLECTION TRACK
ACOUSTICAL
SEALANT
2 HOUR
UL U411
METAL SECURITY
MESH
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS104
SECOND FLOOR - DIMENSIONS PLAN
589-334
04/03/2018
1/8" = 1'-0" A
SECOND FLOOR PLAN - DIMENSIONS
1" = 80'-0"
KEY PLAN SECOND FLOOR
N
4' 8' 16'
1/8" = 1'-0"
0'
1 1/2" = 1'-0"
ACA
ACA
ACA
ACA
10.6
ACA
ACA
11.5
ACA
ACA
H
ACA
G
ACA
E
ACA
D
ACA
C
ACA
B
ACA
E.1
ACA
F
ACA
B.2
ACA
D.8
ACA
D.7
ACA
10.1
11.8
F.2 F.9 G.5
12.1
E.5 F.1
L1N
NOT IN SCOPE OF WORK
BID DEDUCT #1
AS504
A4A5
INFILL FLOOR SLAB
- REF. STRUCTURAL
SHEET S-102.3
L3N
L3AR
L3A
L3AR
L3A
L3AR
L3A
L3A
L3N
L3A
L3A
L3A
L3A
L3A
L3A L3N
L3A
L3A
L3A
L3N
L3A
L3A
L3N
L3A
L3N
L3N
L3N
L3N
L3A
L3A
L3A
L3N
L3A
L3A L3NR
L3A
L3A
L3A
L3A
L3A L3A L3A L3A
L
AL3AR
L
N
L0N
L1N
L3N
L3A
L1N
L3A
L3N
L3A
L3A
L3A
L3A
L3N
L3AR
L3T
L3T
L3T
L3N
L3N
L3AR
L3NR
L1N
L3N
L3N
L3N
L3N
L3N
L3A
L3AR
L3AR
L3N
L3AR
L3A L3A L3A L3A
WAITING /
DILATION
E209
DIRTY
E253
ELEC
F252
SWAMP
E215
LASER
E255
TLT
F253
EXAM 1
E226
EXAM 2
E225
EXAM 3
E223
EXAM 4
E222
EXAM 5
E221
EXAM 6
E219
EXAM 7
E218 EXAM 8
E217
FUNDUS
E216
VISUAL
FIELDS
E211
VISUAL
FIELDS
E212
REFRAC
E212A
PROCEDURE
E213
EXAM 9
E220
JAN
E205
EQUIP
E205A
N.S.
E211A
WORK RM.
E224A
REFRAC
E210
IMAGING
F256
EXAM 10
F273
EXAM 22
F258
EXAM 21
F259
EXAM 11
F272
EXAM 12
F271
EXAM 13
F270
EXAM 14
F269
EXAM 18
F262
EXAM 19
F261
EXAM 20
F260
STORAGE
BD265
CORR
C2E3
CORR
C2E2
CORR
C2E1
CORR
C2F21
WAITING
DILATION
F257
CORR
C2F24
CORR
C2F22
CORR
C2F23
STAIR #11
F248
WAITING
F263
NURSE
F264
WAITING
F268
PRE-
CATARACT
E214
WAITING
E206
CLEAN
E254
ADMIN
OFFICE
F255
HALL
C2E4
EXAM
F247
EXAM
F244
EXAM
F243
EXAM
F241
EXAM
F240
3' - 1" ±2' - 5"5' - 6"1' - 11"6' - 3"6' - 3"5' - 0"6' - 4" ±
11' - 4"9' - 9"6' - 5" ±10' - 4"6"6' - 6"1' - 11"11' - 2"
CLEAR, TYP
4' - 0"
4' - 10" ±
1' - 9"
8' - 0"
3"8' - 4" ±5' - 10" ±7' - 3"9' - 5"9' - 5"9' - 5"9' - 5"9' - 5"2"
2' - 6"12' - 6"
1' - 5 1/2"13' - 5"15' - 11"22' - 4"1' - 0"15' - 3"
/2
52' - 8"16' - 9"
69' - 4 1/2"
/2
/2
CLEAR
5' - 1"
11' - 2 1/2" 5' - 0" 6' - 0" 10' - 0" 5' - 11 1/2" 5' - 0 1/2" 9' - 5"
L3N
L1NR
L1NR
1' - 2"
L3A
L3N L3N
L3N
AI501
L1N
L3A
L3A
ADDITION
REMODEL
AREA
WALL MATERIALS
LEGEND FOR WALL TAGS
MATERIAL
WIDTH
S - STRUCTURAL METAL STUDS, 20 ga. OR
HEAVIER, (REF. STRUCT.)
L - LIGHT GAUGE METAL STUDS, 20 ga. INTERIOR, 16 ga.
EXTERIOR (REF. SPECS.)
B - CONCRETE MASONRY UNIT, STANDARD
WEIGHTS FOR EXTERIOR & INTERIOR, UNLESS
NOTED OTHERWISE (REF. STRUCT.)
WALL WIDTHS
0 - 7/8" HAT CHANNEL
1 - 1 5/8" HAT CHANNEL/ STUDS
4 - 4" METAL STUD FRAMING
6 - 6" METAL STUD FRAMING OR CONCRETE MASONRY UNIT
8 - 8" METAL STUD FRAMING OR CONCRETE MASONRY
UNIT
NOTES:
PROVIDE ACCOUSTICAL SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS OF WALLS WITH SOUND BATT.
ALL STUD FRAMING TO BE 16" O.C., TYP.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL PENETRATIONS OF
SMOKE PARTITION WALLS AS REQUIRED BY CODE.
PROVIDE ALL NEW WALLS THAT GO TO STRUCTURE w/ 1 1/2"
MTL. DEFLECTION TRACK - REF STRUCT.
N - NONE
A - ACC0USTICAL
XXXX
INSULATION
WALL INSULATION
WALL HEIGHT
SHADED WALLS INDICATES WALLS
THAT EXTEND TO DECK
INSTALL 5/8" TYPE X GYP BD ON ONE SIDE OF FURRING,
TYP. INSTALL 5/8" TYPE X GYP BD ON BOTH SIDES OF
STUD FRAMING, TYP., UNLESS NOTED OTHERWISE.
EXTEND GYP BD TO 6" ABOVE CEILING UNLESS REQUIRED
OTHERWISE. PROVIDE ACCOUSTICAL SEALANT AT TOP
AND BOTTOM OF ALL PENETRATIONS OF WALL WITH
SOUND BATT.
WALLS TO RECEIVE GYPSUM BOARD PRODUCT ON BOTH
FACES OF METAL STUD AND WALLS THAT REQUIRE
ACOUSTICAL SOUND BATT INSULATION SHALL BE
CONSTRUCTED TO MEET A MINIMUM 45 STC UNLESS
OTHERWISE NOTED.
FIRE TAPE AND/OR FILL VOIDS AT TOP OF WALL - FIRE
RATED WALL AS REQUIRED BY CODE - REF. SPEC.
PROVIDE SEALANT AT TOP & BOTTOM AND ALL
PENETRATIONS ON ONE SIDE OF SMOKE PARTITION
WALLS AS REQUIRED BY CODE - REF. SPECS
INSTALL FIRE RATED SEAL/CLOSURE @ ALL OPENINGS,
GAPS AND TOP & BOTTOM OF FRAMING AS SPECIFIED.
BRACE ALL STUD WALLS TO STRUCTURE ABOVE @ 4'-0" O.C.
OR EXTEND ALL STUDS TO DECK ABOVE, TYP.
T - THERMAL
RATING
R - RATED INDICATES WALL IS RATED FOR FIRE,
OCCUPANCY, AND/ OR SMOKE - REF. LIFE SAFETY
SHEETS
RATED
INDICATES WALL THAT EXTEND 6"
ABOVE CEILING
M - WIRE MESH REINFORCEMENT (REF. SPECS.)
3 - 3 5/8" METAL STUD FRAMING
PROVIDE COATED GLASS MAT TILE BACKER BOARD AT ALL
SHOWER & WET AREAS AND AS BACKER FOR CERAMIC WALL TILE.
TOILET & SINK AREAS TO RECEIVE MOISTURE-RESISTANT GYP
BOARD. PROVIDE 20GA. STUDS AS REQUIRED IN TCNA AND GA-216.
L0N L1N
L3N L3A L3AM L6A B4NR B8N
WIRE MESH
REINFORCEMEN
T
ACOUST. BATT
INSUL.ACOUST. BATT INSUL. ACOUST. BATT INSUL.
7/8" HAT CHANNEL
5/8" TYPE X GYP BD. 1 5/8" MTL. STUD
5/8" TYPE X GYP BD.
5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD. 5/8" TYPE X GYP BD.
7/8" HAT CHANNEL
6" CMU
8" CMU
3 5/8" MTL. STUD 3 5/8" MTL. STUD 3 5/8" MTL.
STUD
6" MTL. STUD
L3AR
ACOUST. BATT INSUL.
2X 5/8" TYPE X
GYP BD.
3 5/8" MTL. STUD
SUBSTRATE
T Y
P
T Y
P
T Y
P
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF. CLG.
PLANS
CLG. - REF.
CLG. PLANS
CLG. - REF.
CLG. PLANS
B.O. DECK
FIRE RESISTIVE
JOINT SYSTEM
T Y
P
SUBSTRATE
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
ACOUST. SEALANT
CLG. - REF.
CLG. PLANS
B.O. DECK B.O. DECK
B.O. DECKB.O. DECK
B.O. DECKB.O. DECKB.O. DECK
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR FINISHED FLOOR
DEFLECTIO
N TRACK
DEFLECTION TRACK
DEFLECTION TRACKDEFLECTION TRACK
DEFLECTION TRACK
ACOUST. SEALANT
L1NR
1 5/8" MTL.
STUD
3X 5/8" TYPE
X GYP BD.
CLG. - REF. CLG.
PLANS
B.O. DECK
FINISHED FLOOR
FIRE RESISTIVE
JOINT SYSTEM
DEFLECTION TRACK
ACOUSTICAL
SEALANT
2 HOUR
UL U411
METAL SECURITY
MESH
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
JUAR
Columbia, Missouri
EXPAND PHARMACY AND LOBBY
AS104.1
SECOND FLOOR - DIMENSIONS PLAN - BID
DEDUCT #1
589-334
04/03/2018
1/8" = 1'-0" A
SECOND FLOOR PLAN - DIMENSIONS -
BID DEDUCT #1
N
4' 8' 16'
1/8" = 1'-0"
0'
1" = 80'-0"
KEY PLAN SECOND FLOOR
1 1/2" = 1'-0"
11.8
F.2
5/8" TYPE X GYP. BD. ON 7/8"
MTL. HAT CHANNEL
LIQUID APPLIED AIR/WATER
BARRIER - REF. SPECS.
5/8" EXT.GYP. BD.
SHEATHING
6" FOIL FACED BATT. INSUL.
5/8" GYP. BD. ON 6"
MTL. STUD @ 16" O.C.
CAST STONE - MATCH
EXIST. - REF. SPECS..
CAULK - TYP.
2HR COLUMN WRAP - UL DESIGN X528 - REF. SPECS.
COLUMN - REF. STRUCTURAL
ACA
H
11.8
LIQUID APPLIED AIR/WATER
BARRIER - REF. SPECS.
5/8" GYP. BD. SHEATHING
6" FOIL FACED BATT. INSUL.
5/8" TYPE X GYP. BD.
ON 6" MTL. STUD @ 16"
O.C.
CAST STONE - MATCH
EXIST. - REF. SPECS.
CAULK - TYP.
5/8" GYP BD. ON
BENT 1 5/8" MTL.
STUD
2HR COLUMN WRAP - UL
DESIGN X528 - REF. SPECS.
11.8
F.9
CAULK - TYP.
5/8" EXT. GYP BD. ON 6"
MTL. STUD @ 16" O.C.
LIQUID APPLIED
AIR/WATER BARRIER -
REF. SPECS.
CAST STONE - MATCH
EXIST. - REF. SPECS.
FOIL FACED 6"
BATT. INSUL.
2HR COLUMN WRAP - UL
DESIGN X528 - REF.
SPECS.
COLUMN - REF.
STRUCTURAL
5/8" GYP BD ON 1 5/8" MTL
STUD
ACA
H
10.1
5/8" TYPE X GYP BD. ON
3 5/8" MTL. STUDS @
16" O.C.
CAULK - TYP.
2HR COLUMN WRAP - UL
DESIGN X528 - REF.
SPECS. ANODIZED ALUM.
STOREFRONT SYSTEM W/ 1"
INSUL GLAZING - REF SPEC
LIQUID APPLIED AIR/WATER
BARRIER - REF. SPECS.
5/8" GYP. BD. SHEATHING
6" FOIL FACED BATT. INSUL.
CAST STONE - MATCH EXIST.
ADJ. - REF. SPECS.
COLUMN, REF. STRUCTURAL
WIRE MESH
REINFORCIN
G
5/8" TYPE X GYP BD. ON
3 5/8" MTL. STUDS @
16" O.C.
11.8
G.5
CAULK - TYP.
2HR COLUMN WRAP - UL
DESIGN X528 - REF.
SPECS.
LIQUID APPLIED AIR/WATER
BARRIER - REF. SPECS.
CAST STONE - MATCH EXIST.
ADJ. - REF. SPECS.
6" FOIL FACED BATT. INSUL.
5/8" TYPE X GYP.
BD. ON 3 5/8" MTL.
STUD @ 16" O.