36C25518R0298-008.pdf
PDF 17 MB Posted
- Solicitation number
- 36C25518R0298
About this file
36C25518R0298 589A5-15-115 Topeka VAMC ED Project FINAL CDs - Part 2 of 9 (18 pages).pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25518C0172-000.docx | DOCX document | |
| 36C25518R0298-00003002.docx | DOCX document | |
| 36C25518R0298-00003001.docx | DOCX document | |
| 36C25518R0298-00003000.docx | DOCX document | |
| 36C25518R0298-00002000.docx | DOCX document | |
| 36C25518R0298-00002001.pdf | ||
| 36C25518R0298-00001000.docx | DOCX document | |
| 36C25518R0298-011.pdf | ||
| 36C25518R0298-013.pdf | ||
| 36C25518R0298-003.docx | DOCX document | |
| 36C25518R0298-009.pdf | ||
| 36C25518R0298-014.pdf | ||
| 36C25518R0298-015.pdf | ||
| 36C25518R0298-006.pdf | ||
| 36C25518R0298-007.pdf | ||
| 36C25518R0298-004.pdf | ||
| 36C25518R0298-005.pdf | ||
| 36C25518R0298-010.pdf | ||
| 36C25518R0298-012.pdf | ||
| 36C25518R0298-000.docx | DOCX document |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1D
NOTES:
6" CONCRETE SLAB-ON-GRADE w/ 6X6-W2.4xW2.4 WWF CENTERED IN SLAB
ON 15 MIL VAPOR BARRIER ON 4" CLEAN GRAVEL FILL ON PROPERLY
COMPACTED SUBGRADE. T/CONC SLOPES, RE: CIVIL
TEAR OUT EXISTING CONCRETE AND REPLACE WITH 6" CONCRETE SLAB-
ON-GRADE w/ 6X6-W2.4xW2.4 WWF CENTERED IN SLAB ON 15 MIL VAPOR
BARRIER ON 4" CLEAN GRAVEL FILL ON PROPERLY COMPACTED
SUBGRADE. T/CONC TO MATCH EXISTING BLDG SLAB. DOWEL TO
PERIMETER w/#3's @ 18" OC w/ EPOXY.
MC12X14.3 MIN STAIR STRINGER/PLATFORM HEADERS, HSS6X3 MIN POSTS
IN WALL, AND BASE CONNECTIONS PER STAIR SUPPLIER. COORD
GEOMETRY w/ ARCH
4" CONCRETE SLAB-ON-GRADE w/ 6x6-W1.4xW1.4 WWF CENTERED IN SLAB
ON 15 MIL VAPOR BARRIER ON 4" CLEAN GRAVEL FILL ON PROPERLY
COMPACTED SUBGRADE. T/CONC = MATCH EXISTING. SLAB SLOPED TO
DRAIN, RE: ARCH.
600S162-54 @ 12" OC (MIN) w/ 5/8" APA RATED 24/16, EXTERIOR GRADE OSB SHEATHING, EXPOSURE 1 GRADE w/ #12 SCREWS @ 6" OC @ EDGES AND
12" OC IN THE FIELD. 5/8" INTERIOR GYPSUM SHEATING, RE: ARCH. ADD
ADD'L STUDS AS REQUIRED TO PROVIDE STUD ALIGNED WITH EACH
ROOF JOIST BEARING POINT ABOVE.
CANOPY FRAMING BID ITEM #2 DEDUCT
2 1/2" CONC ON 1.5 VL COMP 22 GA DECK WITH 6X6-W1.4XW1.4 WWF TOTAL
DEPTH = 4". T/CONC TO MATCH EXISTING.
2" CONC ON 0.6C24 DECK WITH 6X6-W1.4XW1.4 WWF. TOTAL DEPTH = 2
1/2". T/CONC TO MATCH EXISTING.
REF F1/S-002 FOR JAMB REINFORCEMENT AND LINTEL DESIGN.
REF F1/S-002 FOR JAM REINFORCEMENT. REF PLAN FOR LINTEL DESIGN
AT THIS LOCATION ONLY.
18" DIA CONC COL w/ 14" DIA INSETS PER ARCH. REINFORCE w/ 8#5 VERT w/ #3 TIES @ 6" OC, TYP. NEW CONC COLUMNS SHALL MATCH MATERIAL, TEXTURE, COLOR, AND REVEALS OF EXISTING COLUMN. T/CONC COL TO
MATCH EXISTING CONC COL.
16" DIA CONC COL w/ 8#5 VERT w/ #3 TIES @ 6" OC. NEW CONC COLUMNS
SHALL MATCH MATERIAL, TEXTURE, COLOR, AND REVEALS OF EXISTING
COLUMN.
RE: 4/S-502 FOR CANTILEVER KNEE WALL BRACING DETAIL WHERE
BRACING OF THE TOP OF THE WALL IS NOT PROVIDED. RE: ARCH FOR
LOCATIONS.
1E
W16
W16
W
W
W
W
W
20G 8N 12K 20G 8N 12K 20G 8N 12K
18K18K
8K
18 LH
18K
2 .
EXISTING COLUMNS,
VERIFY IN FIELD
2 .
S-500
S-500
. .4
. 5
S-500
S-500
S-500
.6
W16X45 (LOW)
W16X45 (LOW)
S-500
W14 W14
. 7
W4X13 TO ALIGN WITH JOISTS
S-500
EXIST
16" DIA
COL
7R
7R
6R
6R 11R
11R9R
10R
10R8R
1F
3'-8 3/4" PER 1995 SET
4' - 4 1/4"
19' - 9" 19' - 11 3/4" 20' - 10 1/4" 20' - 0"
QR
XXYY
TYP 6 PLACES
S-500
D
E
1.8
MR
PR
1.5 7'
2"
6'
2"
EL.-2' - 10"
F1
EL.-2' - 10"
F1
L
E X
IS
T
W
X
E X
IS
T
W
X
EL.-2' - 10"
EXISTING FOOTING ASSUMED
TYP 6 PLACES
/2
3 PLACES
TYP 3
SIDES
S-500
S-500
5 7
20' - 7" 12' - 4 1/2"
W14X22
1' - 0" 1' - 0"0' - 8" 0' - 8"
S-500
C8X11.5
C 8X
.5
C8X11.5
C 8X
.5
S-500
17°
' - 1
/8
15' - 0 1/4"
5' - 3 1/4"
D.4
9' - 6"
15' - 1"
S-500
18K
EVERY EXIST JOIST
HSS4X4X1/4 BTWN
9 .
10.
S-502
SIM
S-502
SIM
HSS4X4X1/4, TYP
S-500
EXISTING STRUCTURE
TYP
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
1/8" = 1'-0"
1/19/2017 2:43:06 PM
S-100
LEVEL ONE FRAMING
AND FOUNDATION PLAN
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
1/8" = 1'-0"S-100
1 LEVEL ONE FRAMING AND FOUNDATION PLAN 4' 8' 16'
1/8" = 1'-0"
0'
NORTH
ALL DIMENSIONS AND ELEVATIONS ARE +/- AND SHALL BE FIELD
VERIFIED AND COORDINATED WITH THE EXISTING STRUCTURE. ANY
EXISTING STRUCTURAL MEMBERS AND GEOMETRYARE NOTES BASED
ON INFORMATION PROVIDED IN THE EXISTING STRUCTURAL DRAWINGS.
No. Description Date
NEW 6" 16 GA (MIN) COLD-FORMED STUDS @ 16"
OC w/ 5/8" EXTERIOR GYPBOARD SHEATHING &
INTERIOR GYPBOARD SHEATHING
W14X22
NOTES:
600S162-54 COLD-FORMED STUDS @ 16" OC MAX w/ 5/8" GYP SHEATHING BOTH SIDES. CONN SHEATHING PERPENDICULAR TO SUPPORTS w/ #8
SCREWS (MIN), 4" OC AT PANEL EDGES AND 12" OC AT INTERMEDIATE
FRAMING. TYP ALL ER ENTRY PARAPET WALLS AND STAIR ENCLOSURE.
1200S152-54 COLD-FORMED STUDS @ 16" OC MAX w/ 5/8" GYP SHEATHING BOTH SIDES. CONN SHEATHING PERPENDICULAR TO SUPPORTS w/ #8
SCREWS (MIN), 4" OC AT PANEL EDGES AND 12" OC AT INTERMEDIATE
FRAMING.
DEMO TOP OF EXISTING COL 1" BELOW TOP OF SLAB.
800S162-54 MIN LIGHT-GAGE METAL JOISTS @ 12" OC. PROVIDE BOTTOM
FLANGE LATERAL BRACING @ 3'-0" OC MAX. ANCHOR BRACE EACH END.
15/32" APA RATED 24/16 SHEATHING, PLYWOOD, EXTERIOR GRADE OVER
LIGHT-GAGE METAL JOISTS. CONN SHEATHING PERPENDICULAR TO
SUPPORTS w/ #8 SCREWS (MIN), 6" OC AT PANEL EDGES & 12" OC AT
INTERMEDIATE FRAMING. T/PLYWOOD RE: ARCH
LIGHT-GAGE BOX HEADER PER LIGHT-GAGE SHOP DRAWINGS.
EXTEND HSS4X4 CENTERED UNDER WALL TO BACK OF C12, FIELD WELD AT
CONN.
2 1/2" CONC ON 1.5 VL COMP 22 GA DECK WITH 6X6-W1.4XW1.4 WWF TOTAL
DEPTH = 4". T/CONC TO MATCH EXISTING.
MC12X14.3 MIN STAIR STRINGER/PLATFORM HEADERS, HSS6X3 MIN POSTS IN
WALL, AND BASE CONNECTIONS PER STAIR SUPPLIER. COORD GEOMETRY w/
ARCH
HSS4X4X1/4, TYP
RE: 4/S-502 FOR CANTILEVER KNEE WALL BRACING DETAIL WHERE BRACING
OF THE TOP OF THE WALL IS NOT PROVIDED. RE: ARCH FOR LOCATIONS.
W16
W
W
W
20G 8N 12K 20G 8N 12K 20G 8N 12K
EXIST 18K
EXIST 18K
8K
18 LH
S-300
45.
W16X45 (LOW)
W16X45 (LOW)GALV HSS6X2X1/4
EXIST
16" DIA
COL
7R
6R
6R
11R9R 10R8R
1F
QR
XXYY
D
E
1.8
EXIST
16" DIA
COL
EXIST
16" DIA
COL
EXIST
16" DIA
COL
EXIST
16" DIA
COL
EXIST
W8X35
EXIST
W8X58
MR
/2
EXIST
W8X24
PR
EXIST
W14X90
EXIST
W14X90
EXIST
W14X90
EXIST
W14X90
EXIST
W14X74
EXIST
W14X90
EXIST
W14X90
EXIST
W14X90
EXIST
W18X55
EXIST
W18X55
E X
IS
T
W 12X
EXIST
W
18X40
EXIST
W12X65
CANT
1.5
K
K
8K
8K
GALV
HSS6X2X1/4
GALV
HSS6X2X1/4
19' - 9" 19' - 11 3/4" 20' - 10 1/4" 20' - 0"
L
E X
IS
T
W
X
E X
IS
T
W
X
EXIST
W16X40
2' - 9 1/2" 2' - 9 1/2"
5 @ 2'-6" OC 1' - 10 3/4"
4 @ 2'-4 1/4" 4 @ 2'-4 3/8" 1' - 11 1/2"
E X
IS
T
W
X
E X
IS
T
W
X
S-502
HSS4X4X1/4 BETWEEN EVERY EXISTING JOIST
C8X11.5
C 8X
.5 C8X11.5
C 8X
.5
S-500
S-201
S-502
2' - 3" 15' - 0" 2' - 6"
S-503
S-501
C
X
C
X
C12X30
C12X30
S-201
RE: 1/S-201 FOR BID
ITEM #2 (DEDUCT)
7'
2"
6'
2"
D.4
9' - 6"
15' - 1"
S-503 1.
EXIST
W18X55
S-502
S-300
9 9
TYP
S-500
SIM
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
1/8" = 1'-0"
1/19/2017 2:43:06 PM
S-101
LEVEL TWO FRAMING
PLAN
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
1/8" = 1'-0"S-101
1 LEVEL TWO FRAMING PLAN 4' 8' 16'
1/8" = 1'-0"
0'
NORTH
ALL DIMENSIONS AND ELEVATIONS ARE +/- AND SHALL BE FIELD
VERIFIED AND COORDINATED WITH THE EXISTING STRUCTURE. ANY
EXISTING STRUCTURAL MEMBERS AND GEOMETRYARE NOTES BASED
1000S162-68 AT 2'-0" OC (MAX): ON TOP SIDE USE 1
1/2", 22 GAUGE WIDE RIB GALVANIZED ROOF DECK
ATTACHED IN A 36/5 PATTERN w/ #12 TEK SCREWS
AND (8) #10 TEK SCREWS FOR SIDE LAP FASTENERS.
ON BOTTOM SIDE USE 5/8" INTERIOR RATED
GYPBOARD SHEATHING.
(2) 1000S162-97 BOXED HEADER
SEE NOTES BELOW
FOR WALL INFO
S-300
GALV Pipe
3 1/2 Std.
7R
7R
6R
6R
11R9R 10R8R
1F
19' - 9" 19' - 11 3/4" 20' - 10 1/4" 20' - 0"
QR
4' - 4 1/4"
D
E
1.8
MR
PR
1.5
5 7
S-503
HSS6X
4X
1/
HSS6X4X1/4
HSS6X
4X 1/
S-501
O U T T
O O
U T
12' - 2"
W
ALL C
L TO
C
L
10' - 10"
NOTES:
PROVIDE WEEP HOLE AT EACH END AND CENTER IN BOTTOM OF MEMBER1
D.4
S-503
RE: 1/S101 FOR WALL INFO
S-300
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
1/8" = 1'-0"
1/19/2017 2:43:06 PM
S-102
ROOF FRAMING PLAN
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
1/8" = 1'-0"S-102
1 ROOF FRAMING PLAN 4' 8' 16'
1/8" = 1'-0"
0'
NORTH
ALL DIMENSIONS AND ELEVATIONS ARE +/- AND SHALL BE FIELD
VERIFIED AND COORDINATED WITH THE EXISTING STRUCTURE. ANY
EXISTING STRUCTURAL MEMBERS AND GEOMETRYARE NOTES BASED
Q
PR
6.163.8
QR
F
Q1R
1B
6R
QR
XX
YY
PR
S-501
E O
D ' - 2
' - 3
E Q
E Q
' - 1
/8
E O
D ' - 4
W8X10
W8X15W 8X
W8X15
W 8X
+/- 6"
MAX
1' - 6
3A
S-501 3B
S-501
1.5B 22 R
O O
F D
E C
K
W8X10
W8X10
RADIUSED HSS8X4X3/8
HEADER OVER DOOR
S-501
15' - 0 1/4"
E X
IS
T
W 12X
W 8X
S-501
S-501
SIM,
TYP
NOTES:
1 1/2", 22 GAUGE WIDE RIB GALVANIZED ROOF DECK ATTACHED IN A 36/5
PATTERN w/ #12 TEK SCREWS AND (4) #10 TEK SCREWS FOR SIDE LAP
FASTENERS.
S-501
TYP
H S
S 3-1/2X
1-1/2X 1/4
S-501
STAIRS
C150
D
E
1.8
S-504
S-504
1.5
S-503
S-501
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X24
W 8X24
W 8X
W 8X
W 8X
W 8X
HSS8X4X3/8
CONT H
IG
H
LO
W
W 8X24
W 8X
PROFILE OF
EOD BELOW
D.4
EQ
EQ
W 8X24
EXIS
T V
EN
EE
R
8" C
L
TO
HSS6X
2X
3/
HSS6X
2X
3/
HSS6X
2X
3/
S-504
SIM
EXIS
T
W
X40
EXIST
18" DIA
COL
EXIST
W
21X83
W 8X24
EQ
EQ
EQ
BELOW
HSS3-1/2X1-1/2X1/4
HSS3-1/2X1-1/2X1/4
HSS3-
1/
2X 1-
1/ 2X
1/
HSS3-
1/
2X 1-
1/ 2X
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
S-501
HSS4X4X1/4
HSS4X4X1/4
W
8X10
W 8X10
W 8X10
HSS3-
1/
2X 1-
1/ 2X
1/
LO
W
HSS3-
1/
2X 1-
1/ 2X
1/
HIG
H
S-501
S-501
S-501
S-501
HSS3-
1/
2X 1-
1/ 2X
1/
LOW
HIGH
S-503
S-501
S-501
S-501
S-501
S-501
LOW
TYP
TYP AT
CORNERS
HSS6X0.375
NOTES:
1 1/2", 22 GAUGE WIDE RIB GALVANIZED ROOF DECK ATTACHED IN A 36/5
PATTERN w/ #12 TEK SCREWS AND (4) #10 TEK SCREWS FOR SIDE LAP
FASTENERS.
18" DIA CONC COL w/ 14" DIA INSETS PER ARCH. REINFORCE w/ 8#5 VERT w/ #
3 TIES @ 6" OC, TYP. NEW CONC COLUMNS SHALL MATCH MATERIAL,
TEXTURE, COLOR, AND REVEALS OF EXISTING COLUMN. T/CONC COL TO
MATCH EXISTING CONC COL.
CONTRACTOR TO CONFIRM IF EXISTING BEAM IS W21 OR W12 AND REPORT
FINDINGS TO ARCH AND ENG OF RECORD AS SOON AS POSSIBLE FOLLOWING
PROJECT COMMENCEMENT.
1'
4"
TYP 3 PLACES
EXIST 18" DIA
COL
HSS4X4X1/4
D
E
1.8
S-503
S-501
D.4
HSS6X
2X
3/
EXIST
HSS2-1/2X2-1/2
EXIS
T
W
X40
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
HSS2-
1/
2X 2-
1/
HSS6X
2X
3/
HSS6X
2X
3/
EXIS
T
HSS2-
1/
2X 2-
1/
EXIS
T
W
X40
EXIST
18" DIA
COL
EXIST
18" DIA
COL
EXIST
W
27X84
EXIST
W
21X83
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
S-503
EXIST
W8X58
NOTES:
CONTRACTOR TO CONFIRM IF EXISTING BEAM IS W21 OR W12 AND REPORT
FINDINGS TO ARCH AND ENG OF RECORD AS SOON AS POSSIBLE FOLLOWING
PROJECT COMMENCEMENT.
BELOW
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
As indicated
1/19/2017 2:43:22 PM
S-201
LEVEL 2 PARTIAL PLANS
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
3/8" = 1'-0"S-201
3 PARTIAL PLAN AT AMBULANCE CANOPY
1/4" = 1'-0"S-201
1 PARTIAL PLAN AT ENTRY - BASE BID
1/4" = 1'-0"S-201
PARTIAL PLAN AT ENTRY - BID ITEM #2
(DEDUCT)
ALL DIMENSIONS AND ELEVATIONS ARE +/- AND SHALL BE FIELD
VERIFIED AND COORDINATED WITH THE EXISTING STRUCTURE. ANY
EXISTING STRUCTURAL MEMBERS AND GEOMETRYARE NOTES BASED
ON INFORMATION PROVIDED IN THE EXISTING STRUCTURAL DRAWINGS.
ALL DIMENSIONS AND ELEVATIONS ARE +/- AND SHALL BE FIELD
VERIFIED AND COORDINATED WITH THE EXISTING STRUCTURE. ANY
EXISTING STRUCTURAL MEMBERS AND GEOMETRYARE NOTES BASED
ON INFORMATION PROVIDED IN THE EXISTING STRUCTURAL DRAWINGS.
ALL DIMENSIONS AND ELEVATIONS ARE +/- AND SHALL BE FIELD
VERIFIED AND COORDINATED WITH THE EXISTING STRUCTURE. ANY
EXISTING STRUCTURAL MEMBERS AND GEOMETRYARE NOTES BASED
EXIST BM PER PLN
COLD-FORMED
JOISTS PER PLAN
COLD-FORMED
STUDS PER PLN
EXIST
MASONRY WALL
REMOVE TOP OF
EXIST COL THAT
EXTENDS ABOVE
ROOF SLAB TO 1"
BELOW T/CONC
QR
1" SHIM STACK UNDER HSS WITH
1/8" FILLET WELDS ALL AROUND
EXISTING WF AT GRIDS
HSS PER PLAN BETWEEN
BEAMS AND JOISTS
EXISTING JOISTS
PROVIDE 1/4" DIA HILTI KWIK-CON II+ CONCRETE
SCREW WITH MIN 1" EMBEDMENT LOCATED AT 6" MAX
FROM EACH END AND 1'-0" OC MAX BETWEEEN END
ANCHORS. PROVIDE 1" DIAMETER HOLE IN TOP FLANGE
OF HSS FOR CONSTRUCTION ACCESS, HOLE DOES NOT
NEED PLUGGED FOLLOWING SCREW INSTALLATION
GALV
HSS6X2X1/4
CONT
EXISTING
T/SLAB
ROOF DECK PER PLAN
PER PLAN
QR
END STUDS & WALL PER PLAN
SIMPSON HTT4 TENSION TIE OR APPROVED EQUIVALENT
5/8" DIA A307 THREADED ROD, TENSION FROM
BELOW AND THEN DAMAGE THREADS
HSS6x2 BETWEEN PANEL POINTS. CONNECT TO EXIST JOIST ON EACH SIDE w/ 1/4" FILLET WELD ALL
AROUND (SIM TO 2/S-503)
4"x4"x1/4" PLATE WASHER
PROVIDE 1/4" DIA HILTI KWIK-CON II+ CONCRETE
SCREW WITH MIN 1" EMBEDMENT LOCATED AT 6" MAX
FROM EACH END AND 1'-0" OC MAX BETWEEEN END
ANCHORS. PROVIDE 1" DIAMETER HOLE IN TOP FLANGE
OF HSS FOR CONSTRUCTION ACCESS, HOLE DOES NOT
NEED PLUGGED FOLLOWING SCREW INSTALLATION
SUBMIT EQUIVALENT CONCRETE SCREWS FOR APPROVAL.
HSS6x2x3/8
COLD-FORMED
JOISTS PER PLAN
EXISTING
T/SLAB
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
3/4" = 1'-0"
1/19/2017 2:43:23 PM
S-300
BUILDING SECTIONS
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
3/4" = 1'-0"S-300
1 SECTION
3/4" = 1'-0"S-300
2 SHEAR WALL ELEVATION
HI
LT
I3
C
LR
RIGID INSULATION PER
ARCH
SLAB AND REINF PER PLAN
T/SLAB
PER PLAN
#4 STIRRUPS @ 2'-0" OC
P E
R P
LA
N
#4 x 6'-0" @ 24" OC
4'-0"
#4 CONT
(2) #6 CONT, T&B
(2) #4 CONT, EA SIDE
1' - 6"
VENEER RE: ARCH
EXTERIOR SHEATHING
RE: ARCH
600S162-54 MIN MTL
STUDS @ 12" OC
INTERIOR SHEATHING
RE: ARCH
GROUT SOLID BELOW
GRADE RE: ARCH
PER PLAN
T/SLAB
EXISTING WALL
CHANNEL PER PLAN
METAL DECK PER PLAN
SLAB PER PLAN
EXISTING CONCRETE BEAM
PER PLAN
1/2" DIA HILTI HAS RODS @ 2'-0"
OC w/ 4" GAGE w/ HILTI HIT-HY
200 ADHESIVE, EMBED = 6". SUBMIT EQUIVALENT
ROD/ADHESIVE FOR APPROVAL.
PER PLAN
T/SLAB
EXISTING WALL
METAL DECK PER PLAN
SLAB PER PLAN
PER PLAN
CHANNEL PER PLAN
1/2" DIA HILTI HAS RODS @ 2'-0"
OC w/4" GAGE w/ HILTI HIT-HY
200 ADHESIVE, EMBED = 6"
SUBMIT EQUIVALENT ROD/ADHESIVE
FOR APPROVAL
6"
SLAB AND REINF PER PLAN
T/SLAB
PER PLAN
PER PLAN
EXISTING BUILDING
1' - 0"
(2) #4 CONT
1/2" ISOLATION JOINT3/4" DIA x 1'-6" SMOOTH DOWEL @
18" OC @ DOOR/CORRIDOR. DRILL,
DO NOT EPOXY. EMBED = 9"
SLAB AND REINF PER PLAN
T/SLAB
PER PLAN
EXISTING BUILDING
1/2" ISOLATION JOINT
RE: /5 S-500
#6 x 3'-6" TO MATCH FOUNDATION
REINF. DRILL AND EPOXY INTO
EXISTING, EMBED = 6"
STUD WALL NOT SHOWN FOR CLARITY
3" C
LR
P
LA
N
P E
R
CL
T/PAVEMENT
RE: CIVIL
SLAB AND REINF
RE: CIVIL
FTG & REINF PER
SCHEDPER PLAN
COLUMN &
REINF PER PLN
C
LR
1/2" ISOLATION JT
ACCENT BANDS TO MATCH EXIST
ADJACENT COLUMNS, RE: ARCH
(NO ACENT BANDS AT SIM)
QR
EXIST FOUNDATION WALL
EXISTING
STRUCTURE
GROUT FOR UNIFORM BEARING
NEW SLAB AND BEAMS PER PLAN
L2-1/2x2-1/2x1/4 CONT w/ 3/16"
FILLET WELD AT EACH BEAM,
TRIM AS REQ'D TO ALLOW FOR EJ
PER PLAN
T/SLAB
#3 VERT @ 2'-0" OC DRILL &
EPOXY. EMBED=3"
(2) #3 CONT
GROUT VOID SOLID3/8"x12"x12" END PL w/ 1/2" DIA HILTI HAS RODS w/ HILTI HIT-HY
200 ADHESIVE, EMBED = 6"
3/8"x12"x12" END PL w/ 1/2" DIA HILTI HAS RODS w/ HILTI HIT-
HY 200 ADHESIVE, EMBED = 6"
CHANNEL PER PLAN
BEAM PER PLAN
SUBMIT EQUIVALENT RODS/ADHESIVE
FOR APPROVAL
2" TYP
T Y
P
EXISTING CONC BEAM
SLAB & REINF PER PLAN
METAL DECK PER PLAN
3/8" SHEAR PL w/ (2) 3/4" DIA BOLTS
ANCHORS AND SPACING
PER /8 S-500
T/SLAB
PER PLAN
1/4 2
1/4 2
BEAM PER PLAN
SLAB & DECK PER PLAN
EXIST W14
T/SLAB
EXISTING
EXISTING SLAB
L2X2X1/4 CONT
3/16 2
1" BAR x 2" x 6"
TRIM EXIST EDGE OF
SLAB ANGLE DOWN 1"
BELOW EXIST SLAB
EXIST JOIST w/ 5" SEAT
QR
EXIST JOIST BEYOND
EXIST CONC WALL EXIST CONC WALL
SLAB & DECK PER PLAN
HSS PER PLAN, @ MIDSPAN
BTWN EXIST JOISTS
HSS PER PLAN, IN LINE WITH SECOND
PANEL POINT OF EXIST JOIST. WELD
TO EXIST JOIST w/ 3/16" FILLET WELD, ALL AROUND
EXIST SLAB
3/16
HSS TO HSS
EXISTING
T/SLAB
0' - 1 1/2" EJ
CL
EXT WALL RE: ARCH
SLAB AND REINF PER PLANPAVEMENT RE: CIVIL
T/SLAB
PER PLAN
PER PLAN
#4 @ 24" OC 2'-0"
#4 CONT
1/2" EXPANSION JOINT
INSULATION RE: ARCH
EXISTING STRUCTURE
BRICK VENEER RE: ARCH
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
As indicated
1/19/2017 2:43:23 PM
S-500
SECTIONS AND DETAILS
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
3/4" = 1'-0"S-500
5 SECTION
3/4" = 1'-0"S-500
8 SECTION
3/4" = 1'-0"S-500
7 SECTION
3/4" = 1'-0"S-500
4 SECTION
3/4" = 1'-0"S-500
6 SECTION
3/4" = 1'-0"S-500
1 SECTION
3/4" = 1'-0"S-500
3 SECTION AT LEVEL 1 SLAB EXTENSION
3/4" = 1'-0"S-500
2 SECTION
1 1/2" = 1'-0"S-500
9 SECTION
3/4" = 1'-0"S-500
10 SECTION
3/4" = 1'-0"S-500
11 SLOPING SLAB INFILL
EXISTING
CANOPY ABOVE
EXIST
16" DIA
COL
SLIDE BEARING:
UPPER ELEMENT 9" X 5"
LOWER ELEMENT 6" X 2"
SEE NOTES 2-5
(2) 1/2" DIA SS HILTI KWIK BOLT TZ AT
CENTER OF COLUMN EMBED 4" MIN
BEAM PER PLAN
1/8 4
1/8 4
BM TO SS PL
3A
S-501
3B
S-501
L8X8X1 w/ STD HOLES
(2) 1'-6" LONG
(2) 1'-7" LONG
S-501
1' - 1 1/2" 1' - 1 1/2"
3A
S-501
3B
S-501
/2
/2
CL
/2
/2
1/4 3-12
1/4 3-126" CONT EA
END
EXIST CMU
RADIUSED HSS PER PLAN
CENTERED UNDER EXIST CMU
3/8" PLATE
FACE BRICK RE ARCH
3/8" CANT PL
1/4 3-12
1/4 3-12
EXIST SKEWED
JOIST
F O
R R
O D
IM
R E
A
R C
H
STUDS PER PLAN
DEMO EXIST CMU + FACE BRICK
PARAPET DOWN TO TOP OF SLAB
S-501
SIM
INSULATION RE:ARCH
SHEATHING PER PLAN
BRICK VENEER RE:ARCH
INSULATION RE:ARCH
MTL DECK PER PLAN
JOIST PER PLAN
EXIST SLAB AND MTL DECK
EXIST BEAM
PER PLAN
T/SLAB
1/4 0'-3"
1/4 0'-3"
1/4
1/4
BEAM PER PLAN
3/8"x6-1/2" PL w/ OVS HOLES
3/8"x6" PL w/ (2) 3/4" DIA BOLTS
IN SSL HOLES
3/4" DIA A325SCA w/ 4" GAGE
1/2" TYP
1 1/2" TYP
1 1/2" TYP
TYP
1 1/2"
3" MAX
T Y
P
1/
2"
3"
1/4
1/4
BEAM PER PLAN
3/8"x6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
TYP
1 1/2" 3" MAX
T Y
P
1/
2"
3"
3" MAX 1 1/2"
BEAM PER PLAN
3/8" FULL DEPTH SHEAR TAB w/
(2) 3/4" DIA BOLTS IN SSL HOLES
W8X24 STUB
RE: ARCH
METAL DECK PER PLAN
HSS PER PLAN
ANGLE AND CONN
PER
1/4
1/4
(1/8)
PJP
3/16 2
3/16 2
HSS TO W8
(1/8)
PJP
/5 S-501
HSS PER PLAN
L2-1/2X1-1/2X1/4 LLH
METAL DECK PER PLAN
(1/8) 3-12
(1/8) 3-12
3" EA END
HSS PER PLAN
HSS PER PLAN
(1/8) 3
(1/8) 3 3/8"X2"X4" END PL
3/16
DEMO EXIST CMU + FACE BRICK
PARAPET DOWN TO TOP OF SLAB
EXIST SLAB
EXIST
W18X40
PROVIDE 1/4" DIA HILTI KWIK-
CON II+ CONCRETE SCREW
WITH MIN 1" EMBEDMENT AT
1'-0" OC MAX ALONG TRACK
10 GA MIN BENT PL X 8" LONG AT 16"
OC w/ (2) MASONRY ANCHORS AT 6"
GAGE INTO CENTER OF TOP COURSE
OF EXISTING BRICK VENEER
1/8 2
1/8 2BENT PL TO
CONT HSS
(2)1200S152-54 x (2)600T125-68
BOX BEAM
EXIST BACK-UP NOT SHOWN
FOR CLARITY
STUDS PER PLAN
PER PLAN
T/SLAB
BRICK VENEER
RE:ARCH
INSULATION
RE:ARCH
SHEATHING PER PLAN
EXIST SKEWED JOISTS
EXIST BRICK VENEER
1 1/2" CLR
1/4 4
L8 TO L8, TYP
1/4"x5"x5" PL WASHER w/ STD HOLE
1/2"x6" PL w/ 3 1/2"
DIA HOLE
1/4 4
1/4 4
PL TO W8
1/2" DIA A307 THREADED ROD, FINGER
TIGHTEN AND DAMAGE THREADS
LEVEL 2
112' - 7 1/4"
1.8
(2)600S162-54 x (2)600T125-68 BOX
BEAM BETWEEN JAMBS AT OPENING
CANOPY STRUCTURE PART
OF BID ITEM #2 (DEDUCT)
EXIST
W21X83
STUD WALL PER PLAN
EXISTING ROOF
STRUCTURE AND DECK
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
As indicated
1/19/2017 2:43:26 PM
S-501
SECTIONS AND DETAILS
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
3/4" = 1'-0"S-501
SLIDE BEARING DETAIL AT AMBULANCE
CANOPY
NOTES:
1. CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR ALONG THE FACE OF THE COLUMN TO LOCATE
EXISTING REINFORCEMENT PRIOR TO FABRICATION.
2. SLIDE BEARING SHALL BE EQUIVALENT TO MASTICORD OR CON-SLIDE (TYP CSB) SLIDE BEARINGS. MINIMUM DESIGN CAPACITY SHALL BE 2000 PSI AT 70 DEG F. THE COEFFICIENT OF FRICTION SHALL AVERAGE 0.05 UNDER A COMPRESSIVE LOCAD OF 2000 PSI. THE ELEMENTS SHALL BE FLAT, CLEAN, AND PREPARED FOR INSTALLATION IN
THE STRUCTURE.
3. THE LOWER ELEMENT SHALL CONSIST OF A NOMINAL 3/32" THICK TEFLON SLIDE SURFACE FACTORY BONDED TO FIBER REINFORCED BEARING PAD (1/2" MIN). THE TOTAL THICKNESS OF THE LOWER ELEMENT SHALL BE 3/4".
4. THE UPPER ELEMENT SHALL BE 1/4" STAINLESS STEEL PLATE.
5. STITCH WELD ELEMENTS TO THE STRUCTURE WITH A 1/8" FILLET WELD 1" LONG AT EACH END ON EACH SIDE.
3/4" = 1'-0"S-501
9 SECTION AT NEW DOOR OPENING
1 1/2" = 1'-0"S-501
2 TYPICAL W8 TO W8 MOMENT CONN
1 1/2" = 1'-0"S-501
1 TYPICAL W8 TO W8 SHEAR CONN
1 1/2" = 1'-0"S-501
6 SECTION AT W8 CANOPY EOD
3" = 1'-0"S-501
5 TYPICAL HSS DECK EDGE DETAIL
3" = 1'-0"S-501
4 TYPICAL HSS CORNER CONN
3/4" = 1'-0"S-501
8 SECTION AT PARAPET EXTENSION
3/4" = 1'-0" 3A
SLIDE BRG DETAIL AT COL
3/4" = 1'-0" 3B
SLIDE BRG DETAIL AT HOLD DOWN
3/4" = 1'-0"S-501
7 SECTION AT ENTRY CANOPY DOOR
LEVEL 2
112' - 7 1/4"
QRMR PR
S-502 w/ ARCH
7' - 8" OPNG COORD
w/ ARCH
3' - 5" COORD
DEMO SLAB AND JOIST
FOR NEW STAIR
REINF EACH SIDE OF CUT JOIST w/ L4X4X1/4
3/16
3/16 C12 TO 2L,
TYP
C12X30 FRAME AT SLAB
OPENING PERIMETER
JOIST DEMO SEQUENCING NOTES:
1. INSTALL NEW HANGER AND HEADER BEAMS.
2. PROVIDE TEMPORARY BRIDGING OF EXISTING JOISTS IN AREA TO BE DEMOED.
3. REMOVE THE SLAB AND METAL DECK IN THE AREA TO BE DEMOED.
4. INSTALL ALL ANGLE SUPPORTS. STRIP JOIST ANGLE LEGS AS REQUIRED ON ONE SIDE ONLY AT A TIME UNTIL REINFORCING IS
COMPLETE ON THAT SIDE BEFORE PROCEEDING TO THE OPPOSITE SIDE OF THE JOIST.
5. DEMO JOISTS IN THE AREA TO BE DEMOED.
6. INSTALL PERIMETER CHANNELS AND ESTABLISH CONT BEARING OF THE SLAB ALONG THE LENGTHS OF THE CHANNELS.
1"
1/8
1/8 2L TO JOIST,
TYP
3/16
2L TO BM,
TYP
SIM AT
LEVEL 1
EXIST W18 EXIST W18
BEAM PER PLAN
BEAM PER PLANHSS6X3 MIN POSTS IN WALL PER STAIR
SUPPLIER, COORD GEOMETRY w/ ARCH
LEVEL 2
112' - 7 1/4"
6R 8R1
S-502
DEMO SLAB AND JOIST
FOR NEW STAIR
PROVIDE ANGLES AT CONT JOISTS
TO SUPPORT NEW CHANNEL
FRAME, AS REQUIRED
CONNECT CHANNEL FRAME TO
EXISTING DECK WITH HILTI
MECHANICAL FASTENERS @ 12" OC
1/4
HSS TO BM,
EA END
BEAM PER PLAN (LOW)
w/ ARCH
10' - 1" OPNG COORD
w/ ARCH
4' - 2" COORD
EXIST
W12X19
EXIST
W14X43
HSS3X3X1/4 1"
C12X30
3/8"X9"X4 1/2" SHEAR PL w/ (3) A325N BOLTS IN SSL HORIZ w/ 1 1/2" EDGE
DISTANCE, WELD w/ 2-SIDED 1/4" FILLET
SIM AT
LEVEL 1
3" EOS
MC12X14.3 MIN STAIR
STRINGER/PLATFORM HEADERS AND
HSS6X3 MIN POSTS IN WALL PER STAIR
SUPPLIER, COORD GEOMETRY w/ ARCH
QR
EXIST
W18X55
EXIST 1-1/2" EJFILL VOID w/ NON-
SHRINK GROUT
3/8" BENT PL w/ 3/4"
HSA @ 12" OC
EXIST CONC BEAM & SLAB HSS PER PLAN, CENTERED
BETWEEN EXIST JOISTS
SHIM STACK PER /1 S-300
#3 CONT1/2" DIA ANCHOR RODS
DRILL & EPOXY @ 12" OC
EXIST SLAB & DECK
EXISTING
T/SLAB
SHEATHING RE: ARCH
COLD FORMED METAL STUDS RE:
ARCH, ATTACH (1) STUD @ EA
CHANNEL
MC3X7.1 @ 4'-0" OC MAX
M A
X
3/16
1/4"x3"x3" PL WASHER AT
THRU-BOLT CONDITIONS
3/8" PL w/ 3/4" DIA
A307 TRHU-BOLTS
(2) #12 SCREWS @
2'-0" OC MAX, 3" MAX
FROM EA END
EXIST SLAB ON METAL DECK
EAST OF GRID QR; EXIST CIP
SLAB WEST OF GRID QR
T Y
P
/4
6"
WHERE CIP SLAB >4" THICK WEST OF
GRID QR, THRU-BOLT IS NOT
REQUIRED; PROVIDE 3/8" PL w/ (4) 3/8" DIA HILTI KWIK BOLT TZ w/ 2" EMBED
T Y
P
/4
4"
NOTES:
1.) BRACING POST IS NOT REQUIRED WITHIN 2'-0" OF END OF WALL IF THERE IS A
WALL RETURN WITH THE RETURN HAVING A LENGTH OF AT LEAST 2'-0". IF NO
WALL RETURN EXISTS, BEGIN FIRST BRACING POST WITHIN 6" OF END OF WALL.
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
As indicated
1/19/2017 2:43:27 PM
S-502
SECTIONS AND DETAILS
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
3/8" = 1'-0"S-502
1 TRANSVERSE SECTION AT STAIR OPENING
3/8" = 1'-0"S-502
2 LONGITUDINAL SECTION AT STAIR OPENING
3/4" = 1'-0"S-502
3 SECTION @ LEDGE INFILL @ DOOR
No. Description Date
1" = 1'-0"S-502
4 KNEEWALL BRACING DETAIL
1.8 2
EXIST
HSS2-1/2X2-1/2
HSS6X2X3/8
HSS6X2X3/8
EXIST
W21X83
HSS6X4X1/4
GALV Pipe 3 1/2 Std.
HSS6X4X1/4
T/STL 123' - 10 1/2"
EXIST
W27X84
3/16 3
3/16 3END PL TO
HSS
1/4
PIPE TO END
PL
3/8"X4"X6" END PL, USE SINGLE
4" X 7" SHIM PLATE (3/16" MIN
THICK) AS REQUIRED WITH (2)
- 3" LONG 3/16" FILLET WELDS
S-503
WALL PER PLAN
(2) HSS6x2 BETWEEN PANEL POINTS ON
EACH SIDE OF HOLD DOWN LOCATION
HSS6X2 BETWEEN CROSS MEMBERS
SIMPSON HTT4 TENSION TIE
5/8" DIA A307 THREADED ROD, TENSION
FROM BELOW AND THEN DAMAGE THREADS
1/4 3
1/4 3
EXISTING JOISTS SKEWED
45 DEGREES FROM WALL
4"X4"X1/4" PLATE WASHER
1/4
1/4
PROVIDE 6"X6" SHIM STACK w/
ADDITIONAL SHIM PLATES (3/16" MIN)
AS REQUIRED UNDER END OF HSS6X2.
PROVIDE 3/16" FILLET WELD ALL
AROUND TO CONNECT ALL PARTS
EXIST CONT
HSS2 1/2x2 1/2
HSS4X4X1/4
PROVIDE HSS6x3x1/4 x 0'-8" LONG OR EQUIVALENT SHIM STACK w/
ADDITIONAL SHIM PLATES (3/16" MIN)
AS REQUIRED UNDER END OF HSS6X2.
PROVIDE 3/16" FILLET WELD ALL
AROUND TO CONNECT ALL PARTS
1/4
POST TO
HSS6X2
(3/16) 5
(3/16) 5
HSS6X2 TO
SHIM
ELEMENT,
EACH END
PROVIDE 1/4" DIA HILTI KWIK-CON II+ CONCRETE
SCREW WITH MIN 1" EMBEDMENT LOCATED AT 6" MAX
FROM EACH END AND 1'-0" OC MAX BETWEEEN END
ANCHORS. PROVIDE 1" DIAMETER HOLE IN TOP FLANGE
OF HSS FOR CONSTRUCTION ACCESS, HOLE DOES NOT
NEED PLUGGED FOLLOWING SCREW INSTALLATION
3/8"x4 1/2"x4 1/2" CAP PL, TYP
3/16
POST TO CAP
PL, TYP
(3/16) 4
(3/16) 4 HSS TO CAP
PL
HSS4X4X1/4
END STUD
3/16 4
3/16 4 W8 TO CAP
PL
EXISTING 0.6C ROOF DECK
FIELD
VERIFY
EXISTING JOIST SKEWED
45 DEGREES FROM WALL
COORD w/ ARCH
1 1/2"
1" 1 1/2"
1/2"
/2
/2
(2) 5/8" DIA A325SC-A BOLTS
1/4
POST TO CAP
PL
1/4 6
1/4 6END PL TO
SHEAR PL
3/8" CAP PL w/
OVS HOLES
3/8" X 6 1/2" X 4 1/2" END PL
3/8" SHEAR PL W/ STD HOLES
3/16
HSS TO END
PL
POST BELOW CAP PL
LEVEL 2
112' - 7 1/4"
1.8 2
EXIST
W21X83
EXIST
W27X84
PROVIDE HSS3x2x1/4 x 0'-8" LONG OR EQUIVALENT SHIM STACK w/
ADDITIONAL SHIM PLATES (3/16" MIN)
AS REQUIRED UNDER END OF
HSS6X2. PROVIDE 3/16" FILLET WELD
ALL AROUND TO CONNECT ALL PARTS
EXIST CONT
HSS2 1/2x2 1/2
PROVIDE HSS6x3x1/4 x 0'-8" LONG OR EQUIVALENT SHIM STACK w/
ADDITIONAL SHIM PLATES (3/16" MIN)
AS REQUIRED UNDER END OF HSS6X2.
PROVIDE 3/16" FILLET WELD ALL
AROUND TO CONNECT ALL PARTS
(3/16) 5
(3/16) 5
HSS6X2 TO
SHIM
ELEMENT,
EACH END
EXISTING 0.6C ROOF DECK
FIELD
VERIFY
EXISTING JOIST SKEWED
45 DEGREES FROM WALL
HSS6X2X3/8
H S
S X
X
/4
HSS6X4X1/4
HSS6X4X1/4
1/4
POST TO
HSS6X2, TYP
H S
S X
X
/4
1/4
POST TO
W27
S-503
SIM
(2)1200S152-54 x (2)600T125-68
BOX BEAM
12 GA CLIP w/ (4) 1/4" TEK
SCREWS EACH LEG, TOP & BOTT
FOR CLARITY
INTERSECTING STUD
WALL NOT SHOWN
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
As indicated
1/19/2017 2:43:28 PM
S-503
SECTIONS AND DETAILS
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
3/4" = 1'-0"S-503
2 SECTION AT EMERGENCY VESTIBULE - NE WALL
3" = 1'-0"S-503
3 VESTIBULE CORNER CONN
3/4" = 1'-0"S-503
SECTION AT EMERGENCY VESTIBULE - SW
WALL
1.8 21.5
EXIST
W21X83
EXIST
W27X84
HSS8X4X3/8
W8X24
W8X24
HSS6X0.375
W8X24
W8X24
1'-0" DIA EMBED PL (GALV)
w/ (4) 3/4" DIA x 10" HSA's
3/16
3/16
HSS TO
CONT W8
T&B FLG
1/4
1/4
3/8" x 6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
3/8" x 6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
1/4
1/4
1/4
1/4
3/8" x 6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
1/4
1/4
3/8" x 6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
W8X24
3" MAX1 1/2"
114'-8"
T/BEAM
WP OF SLOPING
BEAM =114'-7 1/2"
3" MAX
3" MAX
3/16
1 1/2" TYP
PROFILE TO MATCH
ARCH, TYP
(2) 3/4" DIA BOLTS
w/ 4" GAGE
W8X10
3/8" x 6 1/2" CAP PL w/ OVS HOLES
FIELD
VERIFY
3" MAX
1 1/2"
RE: ARCH
6"
(3/16) 4
(3/16) 4 HSS TO W8
FLG, TYP
(1/8) 3-12
(1/8) 3-12 PL TO HSS,
TYP
HSS3-1/2X1-1/2X1/4, TYP
1/4" PL, T/PL TO ALLIGN w/
T/W8. NOTCH AT W8 FOR
CONN TO BEAM IN FIELD, TYP
M
IN
T/STL 114' - 8"
COORD w/ ARCH
LEVEL 2
112' - 7 1/4"
1.8 21.5
W8X24
W8X24
HSS8X4X3/8
W8X24 W8X24
E X
IS
T
W X
EXIST
W27X84
E X
IS
T
D
IA
C O
L
EXIST
W21X83
H S
S X
.3
T/CONC 111' - 6"
1/4
1/4
3/8" x 6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
3" MAX
3" MAX
1 1/2"
3/16
TYP
FIELD
VERIFY
(3/16) 4
(3/16) 4
1'-0" DIA EMBED PL (GALV)
w/ (4) 3/4" DIA x 10" HSA's
3/16
3/8" x 6 1/2" DIA CAP PL
3/16
3/16
EXIST COL EXTENDS 1"
ABOVE ROOF DECK,
FIELD VERIFY
3/8" CAP PL w/ 1/2"
OVERHANG ALL AROUND
HSS6X0.375
3/8" x 6 1/2" DIA CAP PL w/ 3/16" FILLET
WELD ALL AROUND
3/8" x 6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
1/4
1/4
1/4
1/4
1/4
1/4
3/8" x 6" PL w/ (2) 3/4" DIA
BOLTS IN SSL HOLES
3/16
HSS TO W21
REF TYP W8 TO W8
MOMENT CONN
REF TYP W8 TO W8
MOMENT CONN
PROFILE TO
MATCH ARCH
1/16
COMBINED CAP PL AND
MOMENT CONN BOT FLG PL
1 1/2" TYP
1 1/ 2"
WP = 115' - 4 1/8"
WP = 114' - 7 1/2"
T/STL 114' - 8"
COORD w/ ARCH
COORD w/ ARCH
G
F
D
CBA
E
N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
F
E
D
C
B
A
97 8654321
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
D e p a rt m e n t o f V e te ra n s A ff a ir s
Dwg. Of
BLDG. 1
ARCHITECTS/ENGINEERS:
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
Building Key Plan: A/E Seal
TOPEKA, KS
C:\Users\Joseph\Documents\Project Work_Revit\2015 082 VA Topeka Revit v2016_Joseph.rvt
3/4" = 1'-0"
1/19/2017 2:43:28 PM
S-504
SECTIONS AND DETAILS
#589A5-15-115
UPGRADE
EMERGENCY
DEPARTMENT
01/20/2017
3/4" = 1'-0"S-504
SECTION AT HIGH AND LOW CANOPY - BID ITEM
#2 (DEDUCT)
3/4" = 1'-0"S-504
SECTION AT HIGH CANOPY - BID ITEM #2
(DEDUCT)
File details come from the government source that posted it.