ATTACHMENT A - Equipment List Updated.docx
DOCX document 49 KB Posted
- Attached to
- J061--Generator Maintenance Federal contract opportunity
- Solicitation number
- 36C25226Q0035
About this file
This document is an Equipment List detailing generator specifications for multiple buildings within a Department of Veterans Affairs facility. The comprehensive list includes 13 generators across Buildings 20, 43, 70, 102, 107/108, 111, 112, 123, 144, 146/147, 148, and 150, with detailed technical specifications for each. Generators vary in capacity from 80kW to 1500kW, using manufacturers including Cummins, Generac, Kohler, and Arthur Dietrich Corp, with power configurations primarily three-phase and utilizing diesel, natural gas, or dual fuel sources.
The document also outlines annual and triennial load bank testing requirements for these generators, with specific testing quantities for each building. Additionally, it provides a comprehensive list of 39 Automatic Transfer Switches (ATSs) across various buildings, detailing their manufacturer, amperage, voltage, and phase specifications. This equipment list appears to support Solicitation Number 36C25226Q0035 for Generator Maintenance, issued by the Veterans Health Administration Veterans Integrated Service Network 12, suggesting preparation for a maintenance or replacement contract for these critical power generation assets.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| P09 - Revised Final SOW V2.docx | DOCX document | |
| 36C25226Q0035 0002.docx | DOCX document | |
| P09 - Revised SOW.docx | DOCX document | |
| 36C25226Q0035 0001.docx | DOCX document | |
| S02 - ATTACHMENT B - PM Checklist.pdf | ||
| S02 - WD2015-4899 28 7.8.25.pdf | ||
| S02 - ATTACHMENT A - Equipment List.pdf | ||
| 36C25226Q0035.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Equipment Listing
Generators
Building 111
Generator #1
Generator #2
Generator #3
| Generator |
| Cummins |
| Generator |
| Cummins |
| Generator |
| Cummins |
| Model: |
| DQGAB- 10529835 |
| Model: |
| DQGAB- 10529837 |
| Model: |
| DQGAB- 10529837 |
| Ser. # |
| C120317222 |
| Ser. # |
| C120317796 |
| Ser. # |
| C120317221 |
| PHASE |
| 3 |
| PHASE |
| 3 |
| PHASE |
| 3 |
| KW: |
| 1500 |
| KW: |
| 1500 |
| KW: |
| 1500 |
| Power Factor |
| 0.8 |
| Power Factor |
| 0.8 |
| Power Factor |
| 0.8 |
| KVA |
| 1875 |
| KVA |
| 1875 |
| KVA |
| 1875 |
| 12 Capability |
| 8 pct |
Capability 8 pct
Capability 8 pct
| Connection |
| WYE |
| Connection |
| WYE |
| Connection |
| WYE |
| Battery |
| 24 volt |
| Battery |
| 24 volt |
| Battery |
| 24 volt |
| Voltage |
| 277/480 |
| Voltage |
| 277/480 |
| Voltage |
| 277/480 |
| Amps |
| 2255.3 |
| Amps |
| 2255.3 |
| Amps |
| 2255.3 |
| Fuel |
| Diesel, 200 gal/hr |
| Fuel |
| Diesel, 200 Gal/hr |
| Fuel |
| Diesel, 200 gal/hr |
| Radiator |
| Bearward |
| Radiator |
| Bearward |
| Radiator |
| Bearward |
| Part Num. |
| 5697000001 |
| Part Num. |
| 5697000001 |
| Part Num. |
| 5697000001 |
| Ref. Num. |
| A030D331 |
| Ref. Num. |
| A030D331 |
| Ref. Num. |
| A030D331 |
| Ser. Num. |
| W41906 |
| Ser. Num. |
| W41905 |
| Ser. Num. |
| W424655 |
| D.O. MF |
| 05-12 Rev 01 |
| D.O. MF |
| 05-12 Rev 01 |
| D.O. MF |
| 05-12 Rev 01 |
Building 70
Generators OLY Bldg 70
Generator #1 (A, B, and E Wings)
Generator #2 (C and D Wings)
Generator #3 (Chiller)
| Generator |
| Generac |
| Generator |
| Generac |
| Generator |
| Generac |
| Model: |
| 1290608200 |
| Model: |
| 1290608200 |
| Model: |
| 1290608100 |
| Ser. # |
| 2110471 |
| Ser. # |
| 2110470 |
| Ser. # |
| 2110468 |
| D.O. Manf. |
| 5.26.2011 |
| D.O. Manf. |
| 5.26.2011 |
| D.O. Manf. |
| 5.26.2011 |
| PHASE |
| 3 |
| PHASE |
| 3 |
| PHASE |
| 3 |
| KW: |
| 600 |
| KW: |
| 600 |
| KW: |
| 600 |
| Power Factor |
| 0.8 |
| Power Factor |
| 0.8 |
| Power Factor |
| 0.8 |
| KVA |
| 750 |
| KVA |
| 750 |
| KVA |
| 750 |
12 Capability
12 Capability
12 Capability
Connection
Connection
Connection
| Battery |
| 24v (12 ea 1.5h) |
| Battery |
| 24v (12 ea 1.5h) |
| Battery |
| 24v (12 ea 1.5h) |
| Voltage |
| 120/208v |
| Voltage |
| 120/208v |
| Voltage |
| 480V |
Amps
Amps
Amps
| Fuel |
| Natural Gas/Diesel |
| Fuel |
| Natural Gas/Diesel |
| Fuel |
| Natural Gas/Diesel |
Eng
Eng
Eng
| Model # |
| OJ4789 |
| Model # |
| OJ4789 |
| Model # |
| OJ4789 |
Ser #
Ser #
Ser #
Building 20
Building 43
Building 102
Generator
Generator
Generator
| Generator |
| Cummins |
| Generator |
| Arthur Dietrich |
Corp
| Generator |
| Generac |
| Model: |
| GGHG-7539842 |
| Model: |
| 230MD |
| Model: |
| 8HPNN3 |
| Ser. # |
| L080226645 |
| Ser. # |
| 361 |
| Ser. # |
| 8815113 |
| PHASE |
| 3 |
| PHASE |
| 3 |
PHASE
| KW: |
| 85 |
| KW: |
| 190 |
| PHASE |
| 3 Phase |
| Power Factor |
| 0.8 |
| Power Factor |
| 0.8 |
| KW: |
| 300KW w/Updated 400KW Alternator |
| KVA |
| 106 |
| KVA |
| 237.5 |
Power Factor
Capability
12 Capability
KVA
| Connection |
| WYE |
| Connection |
| WYE |
Capability I2T function for all generator protection
| Battery |
| 12 |
Battery
| Connection |
| 108/120Y 3 Phase 4 Wire |
| Voltage |
| 120/208V |
| Voltage |
| 277/480 |
Battery
| Amps |
| 294 |
| Amps |
| 285.7 |
| Voltage |
| 24 |
| Fuel |
| Natural Gas |
| Fuel |
| Diesel |
| Amps |
| 1155 CCA, 225AH |
| Fuel |
| Nat Gas/Diesel |
Transfer Switches (3)
Radiator
| Manufacturer |
| Cummins |
Radiator
| Part Num. |
| A029B191 |
| Model |
| OTECB-7482650 |
Part Num.
Ref. Num.
| Amp/Voltage |
| 225A-208V 3PH |
Ref. Num.
Ser Num.
Ser. Num.
D.O. MF
| Manufacturer |
| Cummins |
D.O. MF
| Eng. |
| QSB5-G3 NR3 |
| Model |
| OTECA-1334163 |
| Ser # |
| 73597562 |
| Amp/Voltage |
| 125A-208V 3PH |
Eng.
| Model # |
| NT85564 |
| Manufacturer |
| Cummins |
| Ser # |
| 58879 |
| Model |
| OTECA-7482646 |
| Amp/Voltage |
| 125A-208V 3PH |
Transfer Switches
| Manufacturer |
| ASGO |
| Model # |
| 634513 |
| Amp/Voltage: |
| 480/277 |
300A 3PH
| Manufacturer |
| ASGO |
| Model # |
| 635941 |
| Amp/Voltage: |
| 480/277 |
100A 3PH
Building 107/108
Building 112
Building 123
Generator
Generator
Generator
| Generator |
| Generac |
| Generator |
| Generac |
| Generator |
| Generac |
| Model: |
| SD100 |
| Model: |
| SD600 |
| Model: |
| SD600 |
| Ser. # |
| 3013340784 |
| Ser. # |
| 3014690871 |
| Ser. # |
| 3014729215 |
| PHASE |
| 3 |
| PHASE |
| 3 |
| PHASE |
| 3 |
| KW: |
| 100 |
| KW: |
| 600 |
| KW: |
| 600 |
| Power Factor |
| .8 |
| Power Factor |
| .8 |
| Power Factor |
| .8 |
| KVA |
| 125 |
| KVA |
| 750 |
| KVA |
| 750 |
12 Capability
| Connection |
| WYE |
| Connection |
| WYE |
| Connection |
| WYE |
Battery
Battery
Battery
| Voltage |
| 12v X 2 |
| Voltage |
| 12v X 2 |
| Voltage |
| 12v X 2 |
| Amps |
| 950cca |
| Amps |
| 1200cca |
| Amps |
| 1200cca |
| Fuel |
| Diesel |
| Fuel |
| Diesel |
| Fuel |
| Diesel |
Radiator
Radiator
Radiator
Part Num.
Part Num.
Part Num.
Ref. Num.
Ref. Num.
Ref. Num.
| Ser. Num. |
| 4563 |
| Ser. Num. |
| 00020 |
Ser. Num.
| D.O. MF |
| 6/2022 |
D.O. MF
D.O. MF
| Eng. |
| FPT |
| Eng. |
| Perkins |
| Eng. |
| Perkins |
| Model # |
| 2806C-E18TA63 |
| Ser # |
| 1993076 |
| Ser # |
| JG0F5335N10049H |
| Ser # |
| JG0F5335N111851K |
Building 144
Building 146/147
Building 148
Generator
Generator
Generator
| Generator |
| Cummins |
| Generator |
| Cummins |
| Generator |
| Cummins |
| Model: |
| 450GFGA |
| Model: |
| DSFAE-1339465 |
| Model: |
| DSFAE-1528326 |
| Ser. # |
| KM10J422873 |
| Ser. # |
| J130584343 |
| Ser. # |
| K150890671 |
D.O. MANUF
| PHASE |
| 3 |
PHASE
| PHASE |
| 3 |
| KW: |
| 80 |
| KW: |
| 80 |
| KW: |
| 450 |
| Power Factor |
| 0.8 |
| Power Factor |
| 0.8 |
| Power Factor |
| 0.8 |
| KVA |
| 100 |
| KVA |
| 100 |
| KVA |
| 562.5 |
Connection
Connection
Connection
| Battery |
| 4D 12V |
| Battery |
| 4D 12V |
| Battery |
| 24V |
| Voltage |
| 120/208 |
| Voltage |
| 120/208 |
| Voltage |
| 480 |
| Amps |
| 277 |
| Amps |
| 277 |
| Amps |
| 677 |
| Fuel |
| Diesel |
| Fuel |
| Diesel |
| Fuel |
| NATURAL GAS |
Radiator
Radiator
Eng.
| Part Num. |
| A029B191 |
Part Num.
| Model |
| GTA28 |
Ref. Num.
Ref. Num.
Ser Num.
Ser Num.
D.O. MF
D.O. MF
| Eng. |
| QSB5-G3 NR3 |
Eng.
| Ser # |
| 73597562 |
Ser #
BUILDING 150
Generator
| Generator |
| Kohler |
| Model: |
| Kohler 80REZGD |
| Ser. # |
| 33MYGMGK0006 |
| PHASE |
| 3 |
| KW: |
| 80 |
| Power Factor |
| .8 |
| KVA |
| 63-100 |
| Connection |
| 12 |
| Battery |
| 12V |
| Voltage |
| 12 |
| Amps |
| 130 |
| Fuel |
| Natural Gas |
Radiator
Part Num.
Ref. Num.
| Ser Num. |
| 02-002 |
| D.O. MF |
| 8/13/19 |
| Eng. |
| KG6208TASD 6.2L |
| Ser # |
| OE20191269 |
Annual Load Bank Testing
| Annual Load Bank Testing |
| Quantity |
| Building 111 – Generator #1,2&3 |
| 3 |
| Building 70 – Generators ABE, CD & Chiller |
| 3 |
| Building 102 Generator |
| 1 |
| Building 112 Generator |
| 1 |
| Building 123 Generator |
| 1 |
| Building 144 Generator |
| 1 |
| Building 146/147 Generator |
| 1 |
| Building 148 Generator |
| 1 |
| Building 20 Generator |
| 1 |
| Building 43 Generator |
| 1 |
| Building 107/108 Generator |
| 1 |
| Building 150 Generator |
| 1 |
Triennial Load Bank Testing (Option Year 1 and 4)
| 4 Hour Load Bank Testing |
| Quantity |
| Building 111 – Generator #1,2&3 |
| 3 |
| Building 70 – Generators ABE, CD & Chiller |
| 3 |
| Building 102 Generator |
| 1 |
| Building 112 Generator |
| 1 |
| Building 123 Generator |
| 1 |
| Building 144 Generator |
| 1 |
| Building 146/147 Generator |
| 1 |
| Building 148 Generator |
| 1 |
List of Automatic Transfer Switches (ATSs) in Buildings.
Automatic Transfer Switches (ATSs)
Building No.
| Quantity |
| Make |
| Amps/Voltage/Phase |
| 20 |
| 1 |
| OTECA-1334163 |
| 120/208V 3PH |
| 20 |
| 1 |
| OTECA-7482650 |
| 225A 120/208V 3PH |
| 20 |
| 1 |
| OTECA-7482649 |
| 125 A 120/208V 3PH |
| 43 |
| 1 |
| ASCO cat#D08ATSB30070NG0C |
| 70 A 480V 3PH |
| 43 |
| 1 |
| ASCO cat#J03ATSB30400NG0C |
| 400 A 480V 3PH |
| 70 |
| 4 |
| EATON cat#CBVIMGG31600BRU |
| 1600A 208V 3PH |
| 70 |
| 1 |
| EATON cat#CBVIMGG41200XRU |
| 1200A 480V 3PH |
| 70 |
| 1 |
| EATON cat#CBC9C3X40600BSU |
| 600A 480V 3PH |
| 102 |
| 2 |
| EATON cat#CTC8C3X30600BSU |
| 600A 120/208V 3PD |
| 102 |
| 2 |
| EATON cat# CBC3E30600BSU |
| 600A 120/208V 3PH |
| 107/108 |
| 1 |
| ASCO cat#J07ATBB30600C5XM 700 SERIES |
| 600A 120/208V |
| 111 |
| 4 |
| EATON cat#CTVIMGF32000XTU |
| 2000A 120-600V 3PH |
| 112 |
| 1 |
| EATON model#22C13511AD70XDSXXXX |
| 400A 277/480 3PH |
| 112 |
| 1 |
| EATON cat#CBC9C5X41200XSU |
| 1200A 120-480V 3PH |
| 123 |
| 1 |
| EATON cat#CBC9C5X41200XSU |
| 1200A 120/480V 3PH |
| 123 |
| 1 |
| EATON cat#9C5X40200XSU |
| 200A 120/480 3PH |
| 144 |
| 1 |
| CUMMINS model# 0306-5135-05 |
| 150A 480V 3 PH |
| 144 |
| 1 |
| CUMMINS model# 0306-5150-06 |
| 600A 480V 3 PH |
| 144 |
| 1 |
| CUMMINS model# 0306-5149-06 |
| 400A 480V 3 PH |
| 146/147 |
| 3 |
| CUMMINS model# 0306-5138-03 |
| 208V |
| 148 |
| 2 |
| CUMMINS model# 0306-5138-03 |
| 208V |
| 150 |
| 1 |
| KOHLER model# KEP-DCTC-0400S-NK |
| 400A 208V 3PH |
| 150 |
| 1 |
| Model# GMG9717 |
| 400A 600V 3 PH |
| Total Qty. |
| 34 |
List of exterior Automatic Transfer Switches (ATSs) in Building 70.
Automatic Transfer Switches (ATSs)
Building No.
| Quantity |
| Make |
| Amps/Voltage/Phase |
| 70 |
| 4 |
| EATON cat#CBVIMGG31600BRU |
| 1600A 208V 3PH |
| 70 |
| 1 |
| EATON cat#CBVIMGG41200XRU |
| 1200A 480V 3PH |
| Total Qty. |
| 5 |
File details come from the government source that posted it. Updated .