S03- COPY OF ALL REPORTS ATTACHMENT.pdf

PDF 3 MB Posted

Attached to
H141--TEST & BALANCE CRITICAL CARE AREAS BASE + 4 OYS
Solicitation number
36C25226Q0020
Issued by

About this file

This document is a Test & Balance (TAB) Report from AccuStar Air Balance, Inc., comprehensively documenting HVAC air distribution and performance measurements for multiple critical care areas at the Milwaukee VA Medical Center. The report covers detailed air change and room pressure tests for various specialized medical spaces including the Electrophysiology Lab, Angio Suite, Animal Research Facility, Cath Lab, Chemical Lab, CT Suite, Dialysis Unit, Emergency Rooms, Endoscopy Ward, Intensive Care Unit, Isolation Rooms, Morgue, OR Recovery, Surgery OR Suites, and a new SPS Building expansion.

The TAB report provides precise measurements for each area, including supply and exhaust cubic feet per minute (CFM), room air changes per hour, room volumes, and room pressure differentials. Each section includes terminal unit tests, air distribution test sheets, and equipment data for air handling units and exhaust fans. The documentation appears to be part of a comprehensive HVAC commissioning effort for the VA Medical Center, with testing dates ranging from April to May 2025, indicating a systematic approach to verifying the performance of critical medical facility ventilation systems across multiple specialized areas.

View the file

Other files

File Type Posted
36C25226Q0020 0003.docx DOCX document
36C25226Q0020 0002.docx DOCX document
36C25226Q0020 0001.docx DOCX document
36C25226Q0020_1.docx DOCX document
S02-ATTACHMENT A - Room Data.xlsx XLSX spreadsheet
S02-ATTACHMENT B - SAMPLE REPORT.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(262) 502-STAR (7827) • FAX 502-7828 • W148 N6923 Terriwood Drive • Menomonee Falls, WI 53051

T E S T & B A L A N C E R E P O R T

Project Name: VA Hospital – 5th Floor – Electrophysiology Lab Location: Milwaukee, WI Architect: N.A.

Engineer: PSJ Engineering Mechanical Contractor: N.A.

Project Number: 124-314

This is to certify that AccuStar Air Balance, Inc. has balanced the systems described herein to their optimum performance capabilities. The testing and balancing have been performed in accordance with TABB recommended procedures and principles and the results of these tests are herein recorded.

04/22/25 Dated

Date 04/22/25

Project Name: VA Hospital – 5th Floor – Electrophysiology Lab System Name: V-18 Floor Number 5th

A I R C H A N G E A N D R O O M P R E S S U R E T E S T S H E E T

Room Use Supply CFM Exhaust CFM Room Air Changes Per Hr Room Number Design Actual Design Actual Volume FT Required Actual Pressure

5535 EP Lab 1,750 1,886 1,500 1,156 4,850 15 23.3 +.007”

Remarks

Project Name: VA Hospital – 5th Floor – Electrophysiology Lab System Name: V-18 Floor Number 5th

A I R D I S T R I B U T I O N T E S T S H E E T

Terminal Room Terminal Factor Design Test - FPM or CFM Final Number Number Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM

Supply 1,750 2,204

1 EP Lab SW 48” x 4” 1.0 - - 96 96

2 EP Lab SW 48” x 4” 1.0 - - 117 117

3 EP Lab SW 48” x 4” 1.0 - - 164 164

4 EP Lab SW 48” x 4” 1.0 - - 159 159

5 EP Lab SW 48” x 4” 1.0 - - 171 171

6 EP Lab SW 48” x 4” 1.0 - - 177 177

7 EP Lab CD 36” x 24” 1.0 - - 202 202

8 EP Lab CD 36” x 24” 1.0 - - 204 204

9 EP Lab CD 36” x 24” 1.0 - - 199 199

10 EP Lab CD 36” x 24” 1.0 - - 141 141

11 EP Lab CD 24” x 24” 1.0 - - 158 158

12 EP Lab CD 24” x 24” 1.0 - - 98 98

13 Control Rm CD 24” x 24” 1.0 - - 318 318

Exhaust

1 EP Lab LLE 24” x 12” 1.1 - - 499 549

2 EP Lab LLE 24” x 12” 1.1 - - 552 607

3 Control Rm EG 24” x 24” 1.1 - - 303 333

Project Name: VA Hospital – Angio Suite

Architect: N.A.

Engineer: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

05/31/25

Date 05/31/25

Project Name: VA Hospital – Angio Suite System Name: AC-3 Floor Number 2nd

2459 Angio Room 1 1,650 2,089 1,020 1,220 4,066 20 30.8 +.006”

2459 Angio Control 1 215 204 250 312 1,296 - - NR

2438 Angio Room 2 1,650 1,636 1,020 1,090 4,662 2.0 21.1 +.013”

2438 Angio Control 2 215 252 250 157 1,296 - - NR

2440 Soiled Utility 0 0 75 103 626 6.0 9.9 -.012”

2451 Soiled Utility 0 0 75 249 690 6.0 21.7 -.01”

2465 Clean Supply 200 205 100 106 1,401 4.0 8.8 +.008”

Project Name: VA Hospital – Angio Suite System Name: AHU-1-98 Floor Number 2nd

Supply 1,650 2,089

1 Angio 1-2459 CD 24” x 24” 1.0 165 165 185 185

2 Angio 1-2459 CD 24” x 24” 1.0 165 165 252 252

3 Angio 1-2459 CD 24” x 24” 1.0 165 165 159 159

4 Angio 1-2459 CD 24” x 24” 1.0 165 165 173 173

5 Angio 1-2459 CD 24” x 24” 1.0 165 165 168 168

6 Angio 1-2459 CD 24” x 24” 1.0 165 165 177 177

7 Angio 1-2459 CD 24” x 24” 1.0 165 165 137 137

8 Angio 1-2459 CD 24” x 24” 1.0 165 165 145 145

9 Angio 1-2459 CD 24” x 24” 1.0 165 165 344 344

10 Angio 1-2459 CD 24” x 24” 1.0 165 165 349 349

11 Control Rm CD 24” x 24” 1.0 215 215 204 204

Project Name: VA Hospital – Angio Suite System Name: EF-1-98 Floor Number 2nd

Exhaust 1,155 1,725

1 Angio 1 EG 12” x 12” 1.1 232 255 385 341 375

2 Angio 1 LLE 24” x 16” 1.1 232 255 374 332 365

3 Soiled Utility EG 10” x 8” 1.1 127 140 200 175 193

4 Control Rm. EG 14” x 14” 1.1 227 250 321 284 312

5 Angio 1 LLE 24” x 16” 1.1 232 255 470 436 480

Project Name: VA Hospital – Angio Suite System Name: Supply Floor Number 2nd

Supply 1,650 1,636

1 Angio 2 CD 24” x 24” 1.0 140 140 139 139

2 Angio 2 CD 24” x 24” 1.0 140 140 152 152

3 Angio 2 CD 24” x 24” 1.0 140 140 150 150

4 Angio 2 CD 24” x 24” 1.0 140 140 137 137

5 Angio 2 CD 24” x 24” 1.0 140 140 138 138

6 Angio 2 CD 24” x 24” 1.0 140 140 170 170

7 Angio 2 CD 24” x 24” 1.0 135 135 128 128

8 Angio 2 CD 24” x 24” 1.0 135 135 132 132

9 Angio 2 CD 24” x 24” 1.0 135 135 208 208

10 Angio 2 CD 24” x 24” 1.0 135 135 114 114

11 Angio 2 CD 24” x 24” 1.0 135 135 122 122

12 Angio 2 CD 24” x 24” 1.0 135 135 46 46

13 Control Rm CD 24” x 24” 1.0 215 215 252 252

Project Name: VA Hospital – Angio Suite System Name: Exhaust Floor Number 2nd

Exhaust 1,250 1,247

1 Angio 2 LLE 14” x 14” 1.1 286 315 254 279

2 Angio 2 EG 14” x 14” 1.1 286 315 247 272

3 Angio 2 LLE 14” x 14” 1.1 282 310 230 253

4 Angio 2 EG 14” x 14” 1.1 282 310 256 286

5 Control Rm EG 24” x 24” 1.1 227 250 143 157

Project Name: VA Hospital – Building 70 Animal Research Facility

Architect: Plunkett Keymar Reginato Engineer: Plunkett Keymar Reginato optimum performance capabilities. The testing and balancing have been performed in accordance with

04/16/25

Date 04/16/25

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: Floor Number 1st

Number Design Actual Design Actual Volume FT³ Design Actual Pressure

6 Storage 230 275 280 442 3,175 8.4 8.4 NR

7 Necropsy 580 608 760 829 1,849 24.7 26.9 -.025”

9 Storage 225 222 330 352 679 29.2 31.1 -.033”

11 Surgery Scrub 215 254 255 404 1,306 11.7 18.6 -.031”

13 Sheep OR 320 420 390 510 1,431 16.4 21.4 -.011”

14 Animal 205 305 280 422 934 18.0 27.1 -.019”

15 Animal 205 224 270 334 1,005 16.1 19.9 -.020”

16 Quarantine 195 191 250 387 879 17.1 26.4 -.030”

17 Quarantine 600 651 700 877 1,803 19.3 29.2 -.037”

19 Histo Lab 450 334 500 532 1,967 15.3 16.2 -.044”

21 Food Storage 210 189 270 406 1,893 8.6 12.9 NR

22 Animal Prep. 330 415 380 437 1,648 13.8 15.9 -.006”

23 Locker Rm. 55 118 100 151 466 12.9 19.4 NR

102 Lunch Rm. 480 485 430 417 2,160 13.3 13.5 NR

103 Animal 480 511 530 577 2,160 14.7 16.0 -.008”

104 Animal 475 535 530 682 2,160 14.7 18.9 -.019”

105 Animal 540 546 580 579 2,400 14.5 14.5 -.006”

106 Clean Cages 520 502 570 633 2,400 14.3 15.8 -.026”

*** Cage Wash 2,980 3,394 3,015 4,640 7,900 22.9 35.2 -.024”

111 Animal 380 472 440 670 1,688 15.6 23.8 -.014”

115 Animal 275 330 345 355 1,294 16.0 16.5 -.005”

116 Animal 320 341 370 377 1,320 16.8 17.1 -.006”

119 Animal 460 739 540 892 2,250 14.4 23.8 -.011”

Remarks *** Room 107, 108, 109, 112.

Supply VFD 57 Hz, Exhaust 60 Hz

Project Name: VA Hospital – Building 70 – Animal Research Facility

Number Design Actual Design Actual Volume FT² Design Actual Pressure

120 Lab 620 741 800 1,144 1,481 32.4 46.3 -.048”

121 Animal 340 354 390 569 1,575 14.9 21.7 -.023”

122 Procedure 270 276 450 463 2,022 13.4 13.7 -.030”

124 Procedure 215 213 380 355 1,366 16.7 15.6 -.022”

125 Animal 280 325 340 380 1,294 14.6 17.6 -.017”

130 OR 540 982 (1) 606 521 3,060 14.7 19.3 +.008”/

+.014”

131 Prep Room 170 190 250 235 1,035 14.5 13.6 -.004”/

+.005”

132 Surgery Scrub 120 120 190 212 815 14.0 15.6 +.004”/

+.005”

133 Surgery Stor 105 168 - - 690 9.1 14.6 +.012”/

+0.10”

136 OR 560 544 620 293 (2) 2,400 14.0 13.6 +.014”

137 Sterilization 375 362 643 1,094 2,113 18.2 31.1 -.053”

139 OR 1,010 1,004 1,115 566 4,547 14.7 13.2 +0.21”

140 Control Rm. 360 266 430 54 1,620 13.3 9.9 +.016”

141 Animal 460 502 515 624 2,160 14.3 17.3 -.017”

142 Animal 460 526 540 608 2,160 15.0 16.9 -.016”

143 Animal 460 519 540 708 2,160 15.0 19.7 -.027”

Remarks (1) = Room 130 – original design cfm is negative, this room needs to be positive. (2) = Rooms 136, 139, 140 – original design cfm is negative, these rooms need to be positive.

Project Name: VA Hospital – Building 70 – Animal Research Facility

161 ICU 560 350 640 686 2,437 15.7 16.9 -.024”

162 Procedure 550 372 600 426 2,193 16.4 11.7 -.019”

163 Animal 3,150 1,630 2,640 2300 11,760 16.1 11.7 -.052”

164 Animal 560 433 610 517 2,160 16.9 14.4 -.035”

165 Animal 560 376 600 442 2,160 16.7 12.3 -.045”

166 Animal 540 351 590 535 2,160 16.4 14.9 -.051”

167 Animal 550 387 610 433 2,160 16.9 12.0 -.022”

168 Animal 800 553 920 682 2,910 19.0 13.7 -.0258”

169 Biohazard Airlock 170 25 - - NR NR NR +.007 /

+.015”

170 Biohazard Shower 180 187 215 234 NR NR NR -.022 / -

.017”

171 Biohazard Animal Rm. 390 295 440 452 1,416 18.6 19.2 -.045”

172 Biohazard Animal Rm. 420 318 465 596 1,507 18.5 23.7 -.056”

173 Biohazard Animal Rm. 600 405 650 636 1,988 20.0 19.2 -.095”

70-A-213 Animal - 664 - 830 3,038 - 16.4 -.027”

70-A-213B Lab - 638 - 0 2,093 - 18.3 +.041”

Remarks (1) = Room 163 original design CFM is positive, this room needs to be negative.

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: 70-AHU-1 Supply Floor Number Ground

70-RH02 230 275

1 006 LD 70” x 3” (2) 2.92 79 230 286 94 275

70-RH03 580 608

2 007 LD 42” 1.0 290 290 263 308 308

3 007 LD 30” 1.0 290 290 274 300 300

70-RH04 225 222

4 009 LD 36” 1.0 225 225 208 222 222

70-RH05 215 254

5 011 LD 29” x 3” (2) 1.21 177 215 224 210 254

70-RH08 205 224

6 015 LD 30” 1.0 205 205 225 224 224

70-RH07 205 305

7 014 LD 30” 1.0 205 205 317 305 305

70-RH06 320 420

8 013 LD 42” 1.0 320 320 348 420 420

70-RH01 660 473

9 004 CD 24” x 24” 1.0 660 660 447 473 473

70-RH09 195 191

10 016 LD 30” 1.0 195 195 135 191 191

70-RH10 600 651

11 017 LD 41” x 3” (2) 1.71 175 300 308 192 328

12 017 LD 41” x 3” (2) 1.71 175 300 286 189 323

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: 70-AHU-1 Supply Floor Number Ground / 1st

70-RH14 155 232

13 023 CD 12” x 12” 1.0 55 55 81 118 118

14 003 CD 12” x 12” 1.0 100 100 92 114 114

70-RH13 330 415

15 022 LD 48” 1.0 330 330 421 415 415

70-RH11 550 334

16 019 LD 54” 1.0 550 550 401 334 334

70-RH12 210 189

17 021 LD 17” x 6” .71 296 210 336 266 189

70-RH107 1,410 1832

18 107 LD 30” 1.0 430 430 445 573 573

19 107 LD 30” 1.0 430 430 443 674 674

20 108 LD 48” 1.0 550 550 547 585 585

70-RH108 1,570 1562

21 112 LD 48” 1.0 600 600 649 577 577

22 109 LD 29” x 6-1/2” (4) 5.24 185 970 1,121 188 985

70-RH111 275 330

23 115 LD 42” 1.0 275 275 286 330 330

70-RH109 380 472

24 111 LD 47” x 3” (2) 1.96 194 380 321 241 472

70-RH110 350 469

25 114 CD 24” x 24” 1.0 350 350 376 469 469

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: 70-AHU-1 Supply Floor Number 1st

70-RH106 520 502

26 106 LD 48” 1.0 520 520 493 502 502

70-RH112 320 341

27 116 LD 42” 1.0 320 320 342 341 341

70-RH105 540 546

28 105 LD 48” 1.0 540 540 533 546 546

70-RH101 460 571

29 101 CD 24” x 24” 1.0 460 460 451 571 571

70-RH113 460 739

30 119 LD 42” 1.0 230 230 266 368 368

31 119 LD 42” 1.0 230 230 290 371 371

70-RH104 475 535

32 104 LD 48” 1.0 475 475 538 535 535

70-RH103 480 511

33 103 LD 48” 1.0 480 480 506 511 511

70-RH114 620 741

34 120 LD 4’ 1.0 80 80 172 197 197

35 120 LD 35” x 6-1/2” (4) 6.32 85 540 506 86 544

70-RH117 200 213

36 123 LD 30” 1.0 200 200 200 213 213

70-RH116 270 276

37 122 LD 48” 1.0 270 270 278 276 276

Project Name: VA Hospital – Building 70 – Animal Research Facility

70-RH102 480 485

38 102 LD 48” 1.0 480 480 508 485 485

70-RH128 1,010 1,004

39 139 CD 24” x 24” 1.0 260 260 206 255 255

39a 139 CD 24” x 24” 1.0 250 250 191 235 235

39b 139 CD 24” x 24” 1.0 250 250 209 276 276

40 139 CD 24” x 24” 1.0 250 250 199 238 238

70-RH122 170 190

41 131 LD 3’ 1.0 170 170 150 190 190

70-RH123 120 120

42 132 LD 2’ 1.0 120 120 126 120 120

70-RH124 460 516

43 138 LD 2’6” 1.0 250 250 147 141 141

44 133 CD 12” x 12” 1.0 105 105 170 168 168

45 135 CD 12” x 12” 1.0 105 105 161 207 207

70-RH127 375 362

46 137 LD 3’ 1.0 375 375 359 362 362

70-RH126 560 544

47 136 LD 4’ 1.0 560 560 546 544 544

70-RH125 120 162

48 134 LD 16” 1.0 60 60 57 72 72

49 134 LD 16” 1.0 60 60 72 90 90

Project Name: VA Hospital – Building 70 – Animal Research Facility

70-RH121 460 713

50 130 CD 24” x 24” 1.0 140 140 221 265 265

51 130 CD 24” x 24” 1.0 140 140 157 200 200

52 130 CD 24” x 24” 1.0 180 180 197 248 248

70-RH120 80 269

53 130 CD 24” x 24” 1.0 80 80 210 269 269

70-RH129 360 266

54 140 CD 24” x 24” 1.0 180 180 285 266 266

55 140 - - - 180 180 (1) -

70-RH115 340 354

56 121 LD 48” 1.0 340 340 341 354 354

70-RH130 460 502

57 141 LD 48” 1.0 460 460 490 502 502

70-RH119 280 325

58 125 LD 42” 1.0 280 280 307 325 325

70-RH133 350 487

59 126 CD 24” x 24” 1.0 350 350 394 487 487

70-RH131 460 526

60 142 LD 48” 1.0 460 460 495 526 526

70-RH118 215 213

61 124 LD 42” 1.0 215 215 202 213 213

70-RH132 460 519

62 143 LD 48” 1.0 460 460 447 519 519

Remarks (1) = Self- contained carrier unit was added.

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: 70-AHU-2 Exhaust Floor Number Ground / 1st

1 003 EG 10” x 10” 1.0 130 130 120 154 154

2 025 EG 6” x 6” 1.0 90 90 86 96 96

3 023 EG 12” x 12” 1.0 97 97 133 151 151

4 022 EG 16” x 16” 1.0 380 380 443 437 437

5 021 LLE 16” x 16” 1.0 270 270 345 406 406

6 017 LLE 18” x 8” 1.0 700 700 872 877 877

7 013 LLE 14” x 8” .78 501 390 641 654 510

8 014 LLE 14” x 8” 1.0 280 280 581 422 422

9 016 LLE 14” x 8” 1.0 250 250 379 387 387

10 015 LLE 14” x 8” 1.0 270 270 323 334 334

11 006 EG 18” x 18” 1.0 280 280 415 442 442

12 007 EG 16” x 4” 1.0 210 210 198 245 245

13 007 EG 16” x 4” 1.0 340 340 313 336 336

14 007 EG 16” x 4” 1.0 210 210 207 248 248

15 011 EG 18” x 12” 1.0 255 255 370 404 404

16 106 LLE 20” x 16” 2.22 257 570 668 285 633

17 105 LLE 20” x 16” 2.22 261 580 653 261 579

18 104 LLE 20” x 16” 2.22 239 530 682 307 682

19 103 LLE 20” x 16” 2.22 239 530 677 260 577

20 102 LLE 20” x 16” 2.22 239 530 484 188 417

21 107 Hood 14ӯ 1.07 579 620 679 641 686

22 108 Hood 12ӯ .785 764 600 659 973 764

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: 70-AHU-2 Exhaust Floor Number Ground / 1st

23 109 Hood 12ӯ .785 764 600 692 788 619

24 112 Hood 14ӯ 1.07 556 595 688 1,116 1,194

25 109 Hood 12ӯ .785 764 600 643 1,754 1,377

26 111 LLE 20” x 16” 2.22 198 440 691 302 (1) 670

27 115 LLE 20” x 12” 1.0 345 345 341 355 355

28 116 LLE 20” x 12” 1.0 370 370 372 377 377

29 119 LLE 24” x 16” 2.67 203 540 598 334 892

30 131 EG 12” x 12” 1.0 250 250 214 235 235

31 132 EG 12” x 12” 1.0 190 190 202 212 212

32 134 EG 12” x 12” 1.0 190 190 121 144 144

33 130 LLE 14” x 12” 1.0 216 216 215 233 233

34 121 LLE 20” x 12” 1.67 234 390 516 341 569

35 125 LLE 20” x 12” 1.0 340 340 376 380 380

36 124 LLE 20” x 16” 2.22 171 380 351 160 355

37 122 Hood 12” x 12” 1.0 450 450 414 463 463

38 130 LLE 14” x 12” 1.0 390 390 764 288 288

39 139 LLE 20” x 16” 1.0 580 580 233 212 212

40 137 Hood 16” x 10” 1.11 579 643 488 671 745

40a 137 Opening 6ӯ .196 - - 217 1,779 349

41 136 LLE 18” x 8” 1.0 535 535 300 293 293

42 139 LLE 20” x 16” 1.0 430 430 351 354 354

43 140 LLE 12” x 12” 1.0 0 0 51 54 54

44 141 LLE 20” x 16” 2.22 243 540 593 281 624

45 142 LLE 20” x 16” 2.22 243 540 577 274 608

46 143 LLE 20” x 16” 2.22 243 540 526 319 708

Remarks (1) = No volume damper.

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: AHU-3 Supply Floor Number 1st

RH-7 550 387

1 167 LD 48” 1.0 550 550 429 387 387

RH-6 800 553

2 168 LD 36” 1.0 400 400 276 274 274

3 168 LD 36” 1.0 400 400 289 279 279

RH-8 540 351

4 166 LD 48” 1.0 540 540 397 351 351

RH-9 560 376

5 165 LD 48” 1.0 560 560 428 376 376

RH-10 560 520

6 Corridor CD 24” x 24” 1.0 280 280 294 233 233

7 Corridor CD 24” x 24” 1.0 280 280 349 287 287

RH-11 560 350

8 161 LD 48” 1.0 560 560 357 350 350

RH-12 550 372

9 162 LD 48” 1.0 550 550 382 372 372

RH-13 560 433

10 164 LD 48” 1.0 560 560 450 433 433

RH-14 3,025 1,630

11 163 LD 35” x 3” (4) 2.92 360 1,050 648 206 602

12 163 LD 35” x 3” (4) 2.92 351 1,025 526 173 505

13 163 LD 35” x 3” (4) 2.92 325 950 587 179 523

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: HRC-4 Exhaust Floor Number 1st

1 165 LLE 20” x 16” 2.22 270 600 575 199 442

2 166 LLE 20” x 16” 2.22 266 590 593 241 535

3 167 LLE 20” x 16” 2.22 275 610 599 195 433

4 168 LLE 36” x 22” 5.50 167 920 737 124 682

5 164 LLE 20” x 16” 2.22 275 610 553 233 517

6 163 LLE 36” x 22” 5.50 185 1,020 710 130 715

7 163 LLE 12” x 10” .83 361 300 424 474 393

8 163 LLE 36” x 22” 5.50 185 1,020 985 172 946

9 163 LLE 18” x 12” 1.5 200 300 246 164 246

10 162 LLE 20” x 16” 2.22 270 600 557 192 426

11 161 LLE 20” x 16” 2.22 288 640 608 309 686

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: AHU-3 Supply Biohazard Floor Number 1st

RH-5 600 405

1 173 LD 4’ 1.0 600 600 495 405 405

RH-4 350 212

2 169 CD 16” x 16” 1.0 170 170 29 25 25

3 170 CD 16” x 16” 1.0 180 180 180 186 187

RH-3 480 397

4 Corridor LD 29” x 3” (2) 1.21 397 480 520 397 397

RH-2 420 318

5 172 LD 3” 1.0 420 420 324 318 318

RH-1 390 295

6 171 LD 3’ 1.0 390 390 322 295 295

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: AHU-3 Exhaust Biohazard Floor Number 1st

1 173 LLE 18” x 8” 1.0 650 650 681 636 636

2 172 LLE 18” x 8” 1.0 465 465 466 596 596

3 171 LLE 18” x 8” 1.0 440 440 487 452 452

4 *** Hood 12ӯ .785 701 550 602 749 588

5 170 EG 10” x 10” 1.0 215 215 222 234 234

Remarks *** = Bio-contained hall.

Project Name: VA Hospital – Building 70 – Animal Research Facility

System Name: Floor Number 2nd

A I R D I S T R I B U T I O N T E S T S H E E T

Terminal Room Terminal Factor Design Test - FPM or CFM Final Number Number Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM

70-A-213

Supply

1 70-A-213 SG 10” x 6” .42 - - 0 0

2 70-A-213 SG 10” x 6” .42 - - 0 0

3 70-A-213 SG 10” x 6” .42 - - 512 215

4 70-A-213 SG 10” x 6” .42 - - 304 128

5 70-A-213 Pt. Traverse 12” .785 - - 409 321

Exhaust

1 70-A-213 EG 22” x 22” 3.36 - - 63 212

2 70-A-213 EG 24” x 12” 2.0 - - 309 618

70-A-213B

1 70-A-213B SG 10” x 6” .42 - - 603 253

2 70-A-213B SG 10” x 6” .42 - - 617 259

3 70-A-213B SG 10” x 6” .42 - - 299 126

No Exhaust

Project Name: VA Hospital – Cath Lab

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

04/22/25

Project Name: VA Hospital – Cath Lab

System Name: V-25 Floor Number 5th

5503 Cath Lab 1,600 1,655 1,200 735 4,673 20 21.3 +.005

*5503 Cath Lab 1,655 1,655 1,200 1,698 4,673 20 21.8 -.006”

Remarks * = Isolation Mode

Project Name: VA Hospital – Cath Lab

System Name: V-25 Floor Number 5th

Supply

1 5503 SG 12” x 6” 1.0 400 400 348 399 399

2 5503 SG 12” x 6” 1.0 400 400 346 412 412

3 5503 SG 12” x 6” .71 563 400 334 614 436

4 5503 SG 12” x 6” 1.0 400 400 345 408 408

5 5546 CD 24” x 24” 1.0 - - 111 111

6 5546 CD 24” x 24” 1.0 - - 96 96

Return/Exh

7 5503 RG 24” x 24” 1.1 - - 668 735

8 5503 EG 24” x 24” 1.1 - - - -

9 5546 RG 24” x 24” 1.1 - - 87 96

Isolation Mode

Return/Exh

7 5503 RG 24” x 24” 1.1 - - 668 735

8 5503 EG 24” x 24” 1.1 - - 875 963

9 5546 RG 24” x 24” 1.1 - - 87 96

Project Name: VA Hospital – Cath Lab System Name: Floor Number 5th

Cath. Lab

Control Room

5546A

V-25

Project Name: VA Hospital – Chemical Lab 2C North, Building 111

Architect: Hammel Green and Abrahamson, Inc.

Engineer: Jaspel Engineering, Inc.

optimum performance capabilities. The testing and balancing have been performed in accordance with

04/23/25

Date 04/23/25

Project Name: VA Hospital – Chemical Lab 2C North, Building 111 System Name: AC-4 Floor Number 2nd

2600 Chem Lab 5,720 6,452 N.A. 5,213 27,828 6.0 13.9 No Door

Project Name: VA Hospital – Chemical Lab 2C North, Building 111

T E R M I N A L U N I T T E S T S H E E T

Box Room Box Design CFM K-Factor Damper Final CFM Number Served Size Min Max Position Min Max

VAV-1 2600 16” 500 2,610 1.66 100% 501 3,120

VAV-2 2600 16” 500 2,610 1.58 100% 511 2,843

VAV-3 2600D 6” 30 200 .77 50% 31 202

VAV-5 2600C 6” 60 200 1.43 70% 62 211

VAV-6 2600 6” 100 500 .48 70% 97 489

Project Name: VA Hospital – Chemical Lab 2C North, Building 111

VAV-1 2,610 3,120

1 2600 CD 24” x 24” 1.0 435 435 605 605

2 2600 CD 24” x 24” 1.0 435 435 803 803

3 2600 CD 24” x 24” 1.0 435 435 604 604

4 2600 CD 24” x 24” 1.0 435 435 513 513

5 2600 CD 24” x 24” 1.0 435 435 533 533

6 2600 CD 24” x 24” 1.0 435 435 62 62

VAV-2 2,610 2,843

7 2600 CD 24” x 24” 1.0 435 435 0 0

8 2600 CD 24” x 24” 1.0 435 435 282 282

9 2600 CD 24” x 24” 1.0 435 435 651 651

10 2600 CD 24” x 24” 1.0 435 435 597 597

11 2600 CD 24” x 24” 1.0 435 435 656 656

12 2600 CD 24” x 24” 1.0 435 435 682 682

VAV-3 200 202

13 2600D CD 24” x 24” 1.0 200 200 202 202

VAV-5 200 211

14 2600C CD 24” x 24” 1.0 200 200 211 211

Project Name: VA Hospital – Chemical Lab 2C North, Building 111

VAV-6 500 489

15 2600 CD 24” x 24” 1.0 250 250 264 254 254

16 2600 CD 24” x 24” 1.0 250 250 227 235 235

Project Name: VA Hospital – Chemical Lab 2C North, Building 111 System Name: ERU-2000 Exhaust Floor Number 2nd

ERV-2000

Exhaust 5,213

1 2600 EG 24” x 24” 1.10 N.A. N.A. 1,342 1,476

2 2600 EG 24” x 24” 2.62 N.A. N.A. 526 1,378

3 2600 EG 24” x 24” 2.62 N.A. N.A. 606 1,588

4 2600 EG 24” x 24” 1.10 N.A. N.A. 701 771

Project Name: VA Hospital – CT Suite Expansion -2nd Floor

Architect: Existing Facility Engineer: KJWW Engineering Consultants optimum performance capabilities. The testing and balancing have been performed in accordance with

05/29/25

Date 05/29/25

Project Name: VA Hospital – CT Suite Expansion – 2nd Floor System Name: AC-3 / V-26 Floor Number 2nd

Room Use Supply CFM Exhaust CFM Room Air Changes Per Hr Actual Rm.

Required Actual

2472 CT Scan 2,700 2,557 2,400 2,113 4,320 10 35.5 +0.0167”

2472 CT Scan * 2,700 2,557 3,000 3,003 4,320 12 41.7 -0.0203”

Remarks * = Iso Mode

Project Name: VA Hospital – CT Suite Expansion – 2nd Floor System Name: RTU-2488 Floor Number 2nd

Box Room Box Design CFM Final CFM Number Served Size Min Htg Max Min Htg Max

VAV-2476 2476 6” 125 125 470 121 121 458

VAV-2479B 2479B 4” 100 100 250 103 103 257

VAV-2480 2480 4” 225 225 225 218 218 218

VAV-2482 2482 7” 430 430 600 451 451 451

VAV-2483 2483 4” 100 100 300 105 105 314

VAV-2486 2486 6” 100 100 280 99 99 275

VAV-2487 2487 5” 215 215 375 211 211 370

VAV-2488 2488 10” 1,310 1,310 1,310 1,305 1,305 1,305

VAV-2479 ** 4” 175 175 310 173 173 305

Remarks ** = 2477, 2479, 2479A

Project Name: VA Hospital – CT Suite Expansion – 2nd Floor System Name: RTU-2488 Floor Number 2nd

VAV-2476 470 458

1 2476 CD 24” x 24” 1.0 235 235 233 233

2 2476 CD 24” x 24” 1.0 235 235 225 225

VAV-2479B 250 257

3 2479B CD 24” x 24” 1.0 250 250 257 257

VAV-2480 225 218

4 2480 CD 24” x 24” 1.0 225 225 218 218

VAV-2482 600 451

5 2482 CD 24” x 24” 1.0 300 300 451 451

6 2482 CD 24” x 24” 1.0 300 300 (1) 0 0

VAV-2483 300 314

7 2483 CD 24” x 24” 1.0 300 300 314 314

VAV-2486 280 275

8 2486 CD 24” x 24” 1.0 280 280 275 275

VAV-2487 375 370

9 2487 CD 24” x 24” 1.0 375 375 370 370

VAV-2488 1,310 1,305

10 2488 Pt. Traverse 10” .545 2,403 1,310 2,394 1,305

VAV-2479 310 305

11 2477 CD 24” x 24” 1.0 50 50 51 51

12 2479 CD 24” x 24” 1.0 210 210 206 206

13 2479A CD 24” x 24” 1.0 50 50 48 48

Remarks (1) Vent cover in place.

Project Name: VA Hospital – CT Suite Expansion – 2nd Floor System Name: AHU-2488 Returns Floor Number 2nd

1 2483 RG 24” x 24” 1.1 273 300 277 305

2 2480 RG 24” x 24” 1.1 227 250 236 260

3 2482 RG 24” x 24” 1.1 545 600 583 641

4 2487 RG 24” x 24” 1.1 341 375 341 375

5 2486 RG 24” x 24” 1.1 255 280 264 290

6 2476 RG 24” x 24” 1.1 427 470 452 497

Project Name: VA Hospital – CT Suite Expansion – 2nd Floor System Name: RTU-1 / EF-1 Floor Number 2nd

RTU-1

Supply 3,450 3,288

1 2472 CD 24” x 24” 1.0 540 540 545 545

2 2472 CD 24” x 24” 1.0 540 540 549 549

3 2472 CD 24” x 24” 1.0 540 540 413 418

4 2472 CD 24” x 24” 1.0 540 540 588 571

5 2472 CD 24” x 24” 1.0 540 540 479 474

6 2474 CD 24” x 24” 1.0 375 375 367 360

7 2474 CD 24” x 24” 1.0 375 375 370 371

EF-1 Isolation Mode 3,000 3,003

1 2472 EG 24” x 24” 1.1 1,364 1,500 1,272 1,399

2 2472 Velgrid 24” x 24” 2.24 670 1,500 716 1,604

Project Name: VA Hospital – CT Suite Expansion – 2nd Floor System Name: Misc. Exhaust Floor Number 2nd

1 2475 EG 12” x 12” 1.1 68 75 78 86

2 2485 EG 12” x 12” 1.1 68 75 85 94

Project Name: VA Hospital – Dialysis – 7th Floor

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

04/21/25

Date 04/21/25

Project Name: VA Hospital – Dialysis 7th Floor System Name: Floor Number 7th

Number Design Actual Design Actual Volume FT Design Actual Pressure

Bays 1-3 Dialysis Treat 260 259 - - 2,040 6 7.6 NR

Bays 4-8 Dialysis Treat 870 902 - - 4,080 6 13.3 NR

Bays 9-10 Dialysis Treat 220 240 - - 1,530 6 9.4 NR

Separation 11 Dialysis Treat 120 135 120 124 1,152 6 7.0 NR

Separation 12 Dialysis Treat 120 136 120 128 1,152 6 7.1 NR

Isolation 13 Dialysis Treat 240 238 120 125 1,296 6 11.0 NR

Isolation 13 Isolation Mode 240 238 340 360 1,296 12 16.7 -.016”

Project Name: VA Hospital – Dialysis 7th Floor System Name: Floor Number 7th

VAV-7110 260 259

1 Bays 1-3 CD 24” x 24” 1.0 130 130 119 119

2 Bays 1-3 CD 24” x 24” 1.0 130 130 140 140

VAV-7106 870 902

3 Bays 4-8 CD 24” x 24” 1.0 290 290 306 306

4 Bays 4-8 CD 24” x 24” 1.0 290 290 293 293

5 Bays 4-8 CD 24” x 24” 1.0 290 290 303 303

VAV-7114 220 240

6 Bays 9,10 CD 24” x 24” 1.0 110 110 119 119

7 Bays 9,10 CD 24” x 24” 1.0 110 110 121 121

VAV-7134 120 135

8 11 CD 24” x 24” 1.0 120 120 135 135

VAV-7135 120 136

9 12 CD 24” x 24” 1.0 120 120 136 136

VAV-7136 240 238

10 13 CD 24” x 24” 1.0 240 240 238 238

Project Name: VA Hospital – Emergency Rooms

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

04/16/25

Project Name: VA Hospital – Emergency Rooms

System Name: AHU-UC Floor Number 1st

Number Design Actual Design Actual Volume FT² Required Actual Pressure

1132 Exam 1 130 107 130 171 828 6.0 12.4 NR

1134 Exam 2 125 133 125 112 828 6.0 9.6 NR

1136 Exam 3 125 135 125 303 1,085 6.0 16.8 NR

1155 Exam 4 205 172 205 267 1,015 6.0 15.8 NR

1157 Exam 5 275 188 275 160 960 6.0 11.8 NR

1159 Exam 6 275 180 275 294 960 6.0 18.4 NR

1161 Exam 7 225 157 225 200 940 6.0 12.8 NR

1169 Exam 8 275 287 275 404 2,100 6.0 11.5 NR

1367 Exam 9 110 120 130 116 1,080 6.0 6.7 NR

1368 Exam 10 110 128 130 132 1,080 6.0 7.3 NR

1130 Treatment 170 28 170 139 990 6.0 8.4 NR

1144 De-Con 75 70 405 377 690 12 32.8 -.022”

1369 Exam 11 110 102 130 126 900 6.0 8.4 NR

1373 Exam 12 110 107 130 124 900 6.0 8.3 NR

1375 Exam 13 145 152 170 146 1,080 6.0 8.4 NR

1376 Exam 14 145 144 170 153 1,080 6.0 8.5 NR

1377 Exam 15 145 147 170 139 1,080 6.0 8.2 NR

1378 Exam 16 145 144 170 142 1,080 6.0 8.0 NR

1385 Exam 17 110 140 130 106 1,080 6.0 7.8 NR

1386 Exam 18 (ISO) 250 255 305 469 1,080 12 26.1 -.0168”

1388 Exam 19 (ISO) 265 277 320 541 1,080 12 30.1 -.0244”

1139 Clean Supply 250 262 75 75 1,562 4.0 10.1 +.0110”

1156 Soiled Utility 0 0 75 120 561 6.0 12.8 -.0121”

1379 Soiled Utility 0 0 75 136 649 6.0 12.6 -.0102”

Project Name: VA Hospital – Endoscopy GI Ward 7AN

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

05/27/25

Date 05/27/25

Project Name: VA Hospital – Endoscopy GI Ward 7AN System Name: Floor Number 7AN

Room Use Supply CFM Return/Exhaust CFM Room Air Changes Per Hr Room

7206 Scope Storage 400 405 - - 1,536 4.0 15.8 +0.014”

7207 GI/Endo 1,200 1,095 1,200 1,397 3,344 6.0 25.1 NR

7210 Scope Storage 75 78 - - 448 4.0 10.4 +0.009”

7211 Clean Utility 250 244 - - 1,805 4.0 8.1 +0.0122”

7212 Soiled Utility - - 150 161 739 6.0 13.1 -0.0131”

7230 Flouroscopy 1,600 1,613 1,600 1,525 4,453 6.0 21.7 NR

7236 GI/Endo 1,200 1,131 1,200 1,393 3,282 6.0 25.5 NR

7244 GI/Endo 1,200 1,234 1,200 1,323 2,991 6.0 26.5 NR

Project Name: VA Hospital – Endoscopy GI Ward 7AN

System Name: Supply Floor Number 7AN

VAV-7206 400 405

1 7206 CD 24” x 24” 1.0 400 400 405 405

VAV-7207 1,200 1,095

2 7207 CD 24” x 24” 1.0 400 400 369 369

3 7207 CD 24” x 24” 1.0 400 400 365 365

4 7207 CD 24” x 24” 1.0 400 400 361 361

VAV-7230 1,600 1,613

5 7230 SW 16” x 8” 1.0 535 535 533 533

6 7230 SW 16” x 8” 1.0 535 535 529 529

7 7230 SW 16” x 8” 1.0 530 530 551 551

VAV-C7A2B 75 78

8 7210 CD 24” x 24” 1.0 75 75 78 78

VAV-C7A02A 250 244

9 7211 CD 24” x 24” 1.0 250 250 244 244

VAV-7236 1,200 1,131

10 7236 CD 24” x 24” 1.0 400 400 386 386

11 7236 CD 24” x 24” 1.0 400 400 371 371

12 7236 CD 24” x 24” 1.0 400 400 374 374

VAV-7244 1,200 1,234

13 7244 CD 24” x 24” 1.0 400 400 430 430

14 7244 CD 24” x 24” 1.0 400 400 411 411

15 7244 CD 24” x 24” 1.0 400 400 393 393

Project Name: VA Hospital – Endoscopy GI Ward 7AN

System Name: Exhaust Floor Number 7AN

1 7207 EG 24” x 24” 1.1 545 600 641 705

2 7207 EG 24” x 24” 1.1 545 600 629 692

3 7230 EG 12” x 12” 1.1 364 400 349 384

4 7230 EG 12” x 12” 1.1 364 400 356 392

5 7230 EG 20” x 10” 1.1 364 400 321 353

6 7230 EG 20” x 10” 1.39 288 400 285 396

7 7212 EG 24” x 24” 1.1 136 150 146 161

8 7236 EG 24” x 24” 1.1 545 600 636 700

9 7236 EG 24” x 24” 1.1 545 600 630 693

10 7244 EG 24” x 24” 1.1 545 600 602 662

11 7244 EG 24” x 24” 1.1 545 600 601 661

Project Name: VA Hospital – Intensive Care Unit

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

04/21/25

Project Name: VA Hospital – Intensive Care Unit System Name: E-26/E-27, AC-24 Floor Number 5th

Number Design Actual Design Actual Volume FT² Required

Design Actual Pressure

2322 ICU-1 275 260 225 199 1,989 6 7.8 +.013”

2326 ICU-2 250 233 225 175 1,708 6 8.2 +.012”

2324 ICU-3 275 256 225 154 1,989 6 7.7 +.017”

2328 ICU-4 250 251 225 162 1,764 6 8.5 +.015”

2329 ICU-5 275 258 225 149 1,872 6 8.3 +.018”

2331 ICU-6 (ISO.) 275 251 680 588 2,223 12 15.9 -.015”

2514 ICU-7 (ISO.) 275 247 225 585 1,843 12 19.0 -.015”

2510 ICU-8 250 237 225 202 2,016 6 7.1 +.006”

2516 ICU-9 275 256 225 184 1,764 6 8.7 +.011”

2512 ICU-10 250 241 225 179 1,836 6 7.9 +.009”

2520 ICU-11 275 253 225 170 1,638 6 9.3 +.008”

2517 ICU-12 250 232 225 197 1,944 6 7.2 +.005”

2522 ICU-13 275 243 225 156 1,521 6 9.6 +.013”

2519 ICU-14 250 232 225 163 1,728 6 8.0 +.010”

2525 ICU-15 275 249 225 178 1,638 6 9.1 +.009”

2527 ICU-16 330 305 280 222 2,268 6 8.1 +.016”

2528 ICU-17 275 242 225 174 1,512 6 9.6 +.014”

2530 ICU-18 275 246 225 179 1,485 6 9.9 +.006”

2502 ISO VEST. 75 80 - - 392 11.5 12.2 +.008”

2333 SOILED UTIL. 75 78 160 144 640 6 13.5 -.005”

2524 SOILED. UTIL. 100 91 140 146 544 6 16.1 -.014”

2539 BED/BULK STOR. - 400 - 51 1,474 6 16.3 +.005”

Project Name: VA Hospital – Isolation Rooms 4C, 5C, 6C, 7C, 1514 Yellow Clinic

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

Project Name: VA Hospital – Isolation Rooms 4C, 5C, 6C, 7C, 1514 Yellow Clinic System Name: V-15 Floor Number 4th, 5th, 6th, 7th

4530 Isolation 460 412 510 460 1,536 12 18.0 -.009”

4532 Isolation 400 407 450 514 1,683 12 18.3 -.017”

4533 Isolation 430 338 480 386 1,394 12 16.6 -.011”

4535 Isolation 400 374 450 411 1,377 12 17.9 -.008”

5638 Isolation 150 213 250 338 1,296 12 15.6 -.022”

5642 Isolation 150 214 250 326 1,296 12 15.1 -.020”

6638 Isolation 300 307 400 420 1,620 12 15.6 -.027”

6640 Isolation 300 305 400 407 1,620 12 15.1 -.024”

7532 Isolation 460 444 540 528 1,937 12 16.4 -.018”

7533 Isolation 380 388 460 477 1,665 12 17.2 -.022”

7535 Isolation 410 415 490 518 1,785 12 17.4 -.026”

7537 Isolation 410 408 490 586 1,785 12 19.7 -.033”

1514 Isolation 100 112 150 0 (1) 640 12 10.5 +.021”

Remarks (1) Exhaust fan did not turn on with switch.

Project Name: VA Hospital – Isolation Rooms 4C, 5C, 6C, 7C, 1514 Yellow Clinic

System Name: V-15 Floor Number 4th

Supply

1 4530 CD 24” x 24” 1.0 230 230 218 227 227

2 4530 CD 24” x 24” 1.0 230 230 223 233 233

3 4532 CD 24” x 24” 1.0 200 200 183 199 199

4 4532 CD 24” x 24” 1.0 200 200 191 208 208

5 4533 CD 24” x 24” 1.0 215 215 133 162 162

6 4533 CD 24” x 24” 1.0 215 215 222 224 224

7 4535 CD 24” x 24” 1.0 200 200 188 198 198

8 4535 CD 24” x 24” 1.0 200 200 182 176 176

9 4530 EG 14” x 4” 1.0 255 255 253 245 245

10 4530 EG 14” x 4” 1.0 255 255 238 208 208

11 4532 EG 14” x 4” 1.0 225 225 237 262 262

12 4532 EG 14” x 4” 1.0 225 225 215 252 252

13 4533 EG 14” x 4” 1.0 240 240 284 203 203

14 4533 EG 14” x 4” 1.0 240 240 271 186 186

15 4535 EG 14” x 4” 1.0 225 225 236 216 216

16 4535 EG 14” x 4” 1.0 225 225 206 195 195

Project Name: VA Hospital – Isolation Rooms 4C, 5C, 6C, 7C, 1514 Yellow Clinic

System Name: V-15 Floor Number 5th

Supply

1 5638 CD 24” x 24” 1.0 150 150 213 213

2 5642 CD 24” x 24” 1.0 150 150 214 214

1 5638 EG 14” x 6” .58 216 125 241 140

2 5638 EG 18” x 8” 1.0 125 125 198 198

3 5642 EG 14” x 6” .58 216 125 240 139

4 5642 EG 18” x 8” 1.0 125 125 187 187

Project Name: VA Hospital – Isolation Rooms 4C, 5C, 6C, 7C, 1514 Yellow Clinic

System Name: V-15 Floor Number 6th

Supply

1 6638 CD 24” x 24” 1.0 300 300 310 307

2 6640 CD 24” x 24” 1.0 300 300 306 306

1 6638 EG 14” x 6” .58 345 200 355 206

2 6638 EG 18” x 8” 1.0 200 200 214 214

3 6640 EG 14” x 6” .58 345 200 346 201

4 6640 EG 18” x 8” 1.0 200 200 206 206

Project Name: VA Hospital – Isolation Rooms 4C, 5C, 6C, 7C, 1514 Yellow Clinic

System Name: V-15 Floor Number 7th

Supply

1 7532 CD 24” x 24” 1.0 230 230 219 219

2 7532 CD 24” x 24” 1.0 230 230 225 225

3 7533 CD 24” x 24” 1.0 190 190 196 196

4 7533 CD 24” x 24” 1.0 190 190 192 192

5 7535 CD 24” x 24” 1.0 205 205 210 210

6 7535 CD 24” x 24” 1.0 205 205 205 205

7 7537 CD 24” x 24” 1.0 205 205 207 207

8 7537 CD 24” x 24” 1.0 205 205 201 201

1 7532 EG 14” x 6” 1.0 225 225 220 220

2 7532 EG 14” x 6” 1.0 225 225 213 213

3 7532A EG 24” x 24” 1.0 90 90 95 95

4 7533 EG 14” x 6” 1.0 185 185 198 198

5 7533 EG 14” x 6” 1.0 185 185 183 183

6 7533A EG 24” x 24” 1.0 90 90 96 96

7 7535 EG 14” x 6” 1.0 185 185 202 202

8 7535 EG 14” x 6” 1.0 185 185 191 191

9 7535A EG 24” x 24” 1.0 120 120 125 125

10 7537 EG 14” x 6” 1.0 195 195 240 240

11 7537 EG 14” x 6” 1.0 195 195 231 231

12 7537A EG 24” x 24” 1.0 100 100 115 115

Project Name: VA Hospital – Morgue

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

04/23/25

Project Name: VA Hospital – Morgue System Name: AC-2 Floor Number 2nd

Box Use Supply CFM Exhaust CFM Room Air Changes Per Hr Room Number Design Actual Design Actual Volume FT³ Required Actual Pressure

2641 Morgue 1,340 1,134 1,520 1,373 6,270 12 13.1 -.009”

Project Name: VA Hospital – Morgue System Name: V-25 / E-2 Floor Number 2nd

Supply 1,340 1,134

1 Morgue CD 24” x 24” 1.0 335 335 262 262

2 Morgue CD 24” x 24” 1.0 335 335 314 314

3 Morgue CD 24” x 24” 1.0 335 335 287 287

4 Morgue CD 24” x 24” 1.0 335 335 271 271

Exhaust 1,520 1,373

1 Morgue EG 18” x 12” 1.1 409 450 215 237

2 Morgue EG 12” x 12” 1.1 282 310 241 265

3 Morgue Hood 38” x 28” 7.38 100 740 118 871

Project Name: VA Hospital – OR Recovery

Architect: N.A.

optimum performance capabilities. The testing and balancing have been performed in accordance with

05/28/25

Date 05/28/25

Project Name: VA Hospital – OR Recovery System Name: Floor Number 2nd

B240 Recovery 4,340 2,361 2,960 2,564 15,908 6.0 9.7 NR

Project Name: VA Hospital – OR Recovery

System Name: AC-3 Floor Number 2nd

1-MB-10 2,208 1,969

1 B240 CD 24” x 24” 1.0 690 690 655 502 502

2 B240 CD 24” x 24” 1.0 690 690 289 366 366

3 B240 CD 24” x 24” 1.0 690 690 557 843 843

4 Office 2217 CD 24” x 24” 1.0 138 138 86 151 151

5 Office 2217 CD 24” x 24” 1.0 - - 108 107

2-MB-10 2,310 882

1 B240 CD 24” x 24” 1.0 690 690 109 133 133

2 B240 CD 24” x 24” 1.0 690 690 113 111 111

3 B240 CD 24” x 24” 1.0 690 690 92 166 166

4 Office 2219 CD 24” x 24” 1.0 140 140 0 195 195

5 B240 CD 24” x 24” 1.0 100 100 30 132 132

6 Office 2219A CD 24” x 24” 1.0 - - 29 145 145

MB-1 100 121

1 Storage CD 24” x 24” 1.0 100 100 131 121 121

No Box 100 108

1 B240 CD 24” x 24” 1.0 100 100 103 108 108

Project Name: VA Hospital – OR Recovery

System Name: EF-23/ISO EF Floor Number Ground

EF-23 2,760 2,564

1 B240 EG 24” x 24” 1.1 627 690 247 391 430

2 B240 EG 24” x 24” 1.1 627 690 314 496 546

3 B240 EG 24” x 24” 1.1 627 690 344 556 612

4 B240 EG 24” x 24” 1.1 627 690 606 887 976

Project Name: VA Hospital – Surgery OR Suites 1-8

Architect: N.A.

Engineer: Beling Consultants optimum performance capabilities. The testing and balancing have been performed in accordance with

Project Name: VA Hospital – Surgery OR Suites 1-8

Room Use Supply CFM Exhaust CFM Room

Volume FT

Air Changes Per Hr Room

Pressure Number Design Actual Design Actual Required Actual

2246 OR-1 2,500 2,496 2,124 1,551 6,240 20 24.0 +.037”

2248 OR-2 1,910 2,193 1,623 1,656 4,800 20 27.4 +.063”

2252 OR-3 2,258 2,213 2,125 1,405 5,520 20 24.1 +.033”

2254 OR-4 2,798 2,797 2,380 1,573 6,597 20 25.4 +.082”

2256 OR-5 2,798 2,437 2,380 1,802 6,800 20 21.5 +.067”

2142B OR-6 1,935 1,980 1,740 1,351 4,108 20 28.9 +.024”

2142A OR-7 1,805 1,730 1,630 964 3,960 20 26.2 +.032”

2155 OR-8 960 1,036 810 518 2,967 20 21.0 +.039”

2260 Clean Supply 550 618 225 93 4,896 4 7.6 +.027”

2142D Clean Supply - 455 - 68 1,061 4.0 25.7 +.005”

Project Name: VA Hospital – Surgery OR Suites 1-8

OR-1

VAV-2246 SUPPLY 2,500 2,496

1 2246 LD 5’ 1.0 133 133 188 188

2 2246 LD 5’ 1.0 133 133 180 180

3 2246 LD 5’ 1.0 133 133 187 187

4 2246 LD 7’ 1.0 200 200 175 175

5 2246 LD 7’ 1.0 200 200 166 166

6 2246 LD 5’ 1.0 133 133 180 180

7 2246 LD 5’ 1.0 133 133 191 191

8 2246 LD 5’ 1.0 133 133 176 176

9 2246 LD 7’ 1.0 200 200 161 161

10 2246 LD 7’ 1.0 200 200 174 174

11 2246 CD 48” x 24” 1.0 225 225 176 176

12 2246 CD 48” x 24” 1.0 225 225 160 160

13 2246 CD 48” x 24” 1.0 225 225 194 194

14 2246 CD 48” x 24” 1.0 225 225 188 188

VEV-2246 EXHAUST 2,124 1,551

1 2246 LLE 20” x 20” 1.1 965 1,062 711 782

2 2246 LLE 20” x 26” 1.1 965 1,062 699 769

ROOM PRESSURE +.037” W.C.

Project Name: VA Hospital – Surgery OR Suites 1-8

System Name: Floor Number 2nd

A I R D I S T R I B U T I O N T E S T S H E E T

Terminal Room Terminal Factor Design Test - FPM or CFM Final Number Number Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM

OR-2

VAV-2248 SUPPLY 1,910 2,193

1 2248 LD 7’ 1.0 160 160 223 223

2 2248 LD 7’ 1.0 160 160 204 204

3 2248 LD 7’ 1.0 160 160 209 209

4 2248 LD 7’ 1.0 160 160 167 167

5 2248 LD 7’ 1.0 160 160 214 214

6 2248 LD 7’ 1.0 160 160 252 252

7 2248 LD 7’ 1.0 160 160 164 164

8 2248 LD 7’ 1.0 160 160 177 177

9 2248 CD 48” x 24” 1.0 210 210 222 222

10 2248 CD 48” x 24” 1.0 210 210 147 147

11 2248 CD 48” x 24” 1.0 210 210 214 214

VEV-2248 1,623 1,656

1 2248 LLE 10” x 32” 1.1 738 812 737 811

2 2248 LLE 20” x 20” 1.1 737 811 768 845

ROOM PRESSURE +0.063” W.C.

Project Name: VA Hospital – Surgery OR Suites 1-8

OR-3

VAV-2252 SUPPLY 2,258 2,213

1 2252 LD 5’ 1.0 123 123 175 175

2 2252 LD 5’ 1.0 123 123 176 176

3 2252 LD 5’ 1.0 123 123 179 179

4 2252 LD 7’ 1.0 185 185 127 127

5 2252 LD 7’ 1.0 185 185 131 131

6 2252 LD 5’ 1.0 123 123 197 197

7 2252 LD 5’ 1.0 123 123 200 200

8 2252 LD 5’ 1.0 123 123 191 191

9 2252 LD 7’ 1.0 185 185 230 230

10 2252 LD 7’ 1.0 185 185 232 232

11 2252 CD 48” x 24” 1.0 260 260 187 187

12 2252 CD 48” x 24” 1.0 260 260 92 92

13 2252 CD 48” x 24” 1.0 260 260 96 96

VEV-2252 EXHAUST 2,125 1,405

1 2252 LLE 12” x 36” 1.1 1,355 1,490 822 904

2 2252 LLE 24” x 6” 1.1 577 635 455 501

ROOM PRESSURE -+0.033” W.C.

Project Name: VA Hospital – Surgery OR Suites 1-8

OR-4

VAV-2254 SUPPLY 2,798 2,797

1 2254 LD 5’ 1.0 153 153 220 220

2 2254 LD 5’ 1.0 153 153 225 225

3 2254 LD 5’ 1.0 153 153 230 230

4 2254 LD 7’ 1.0 230 230 268 268

5 2254 LD 7’ 1.0 230 230 245 245

6 2254 LD 5’ 1.0 153 153 188 188

7 2254 LD 5’ 1.0 153 153 159 159

8 2254 LD 5’ 1.0 153 153 171 171

9 2254 LD 7’ 1.0 230 230 140 140

10 2254 LD 7’ 1.0 230 230 163 163

11 2254 CD 48” x 24” 1.0 240 240 257 257

12 2254 CD 48” x 24” 1.0 240 240 134 134

13 2254 CD 48” x 24” 1.0 240 240 176 176

14 2254 CD 48” x 24” 1.0 240 240 221 221

VEV-2254 EXHAUST 2,380 1,573

1 2254 LLE 14” x 30” 1.1 1,082 1,190 827 910

2 2254 LLE 16” x 26” 1.1 1,082 1,190 603 663

ROOM PRESSURE +.082” W.C.

Project Name: VA Hospital – Surgery OR Suites 1-8

OR-5

VAV-2256 SUPPLY 2,798 2,437

1 2256 LD 7’ 1.0 230 230 216 216

2 2256 LD 7’ 1.0 230 230 182 182

3 2256 LD 5’ 1.0 153 153 185 185

4 2256 LD 5’ 1.0 153 153 182 182

5 2256 LD 5’ 1.0 153 153 133 133

6 2256 LD 7’ 1.0 230 230 154 154

7 2256 LD 7’ 1.0 230 230 150 150

8 2256 LD 5’ 1.0 153 153 138 138

9 2256 LD 5’ 1.0 153 153 190 190

10 2256 LD 5’ 1.0 153 153 162 162

11 2256 CD 48” x 24” 1.0 240 240 239 239

12 2256 CD 48” x 24” 1.0 240 240 92 92

13 2256 CD 48” x 24” 1.0 240 240 202 202

14 2256 CD 48” x 24” 1.0 240 240 212 212

VEV-2256 EXHAUST 2,380 1,802

1 2256 LLE 12” x 36” 1.1 1,082 1,190 776 854

2 2256 LLE 12” x 36” 1.1 1,082 1,190 862 948

ROOM PRESSURE +0.067” W.C.

Project Name: VA Hospital – Surgery OR Suites 1-8

OR-6

SUPPLY 1,935 1,980

1 2142B LD 7’ 1.0 150 150 202 202

2 2142B LD 7’ 1.0 150 150 176 176

3 2142B LD 7’ 1.0 150 150 149 149

4 2142B LD 7’ 1.0 150 150 140 140

5 2142B LD 7’ 1.0 150 150 144 144

6 2142B LD 7’ 1.0 150 150 158 158

7 2142B LD 7’ 1.0 150 150 198 198

8 2142B LD 7’ 1.0 150 150 193 193

9 2142B CD 48” x 24” 1.0 245 245 220 220

10 2142B CD 48” x 24” 1.0 245 245 219 219

11 2142B CD 48” x 24” 1.0 245 245 181 181

EXHAUST 1,740 1,351

1 2142B LLE 32” x 12” 1.1 791 870 633 696

2 2142B LLE 32” x 12” 1.1 791 870 595 655

ROOM PRESSURE +.024” W.C.

Project Name: VA Hospital – Surgery OR Suites 1-8

OR-7

SUPPLY 1,805 1,730

1 2142A LD 6’ 1.0 120 120 202 202

2 2142A LD 6’ 1.0 120 120 163 163

3 2142A LD 7’ 1.0 140 140 161 161

4 2142A LD 7’ 1.0 140 140 172 170

5 2142A LD 6’ 1.0 120 120 142 142

6 2142A LD 6’ 1.0 120 120 154 154

7 2142A LD 7’ 1.0 140 140 176 176

8 2142A LD 7’ 1.0 140 140 167 167

9 2142A CD 48” x 24” 1.0 255 255 115 115

10 2142A CD 48” x 24” 1.0 255 255 133 133

11 2142A CD 48” x 24” 1.0 255 255 145 145

EXHAUST 1,630 964

1 2142A LLE 32” x 10” 1.1 741 815 447 492

2 2142A LLE 32” x 10” 1.1 741 815 429 472

ROOM PRESSURE +.032”

Project Name: VA Hospital – Surgery OR Suites 1-8

OR-8 960 1,036

1 2155 CD 48” x 24” 1.0 120 120 122 122

2 2155 CD 48” x 24” 1.0 120 120 141 141

3 2155 CD 48” x 24” 1.0 120 120 124 124

4 2155 CD 48” x 24” 1.0 120 120 122 122

5 2155 CD 48” x 24” 1.0 120 120 127 127

6 2155 CD 48” x 24” 1.0 120 120 137 137

7 2155 CD 48” x 24” 1.0 120 120 139 139

8 2155 CD 48” x 24” 1.0 120 120 126 126

Exhaust 518

1 2155 EG 20” x 10” 1.1 368 405 272 299

2 2155 EG 20” x 10” 1.1 368 405 199 219

Room Pressure +.039”

Project Name: VA Hospital – Surgery OR Suites 1-8

VAV-C2A01 855 694

1 C2A01 CD 24” x 24” 1.0 250 250 233 233

2 2228 CD 24” x 24” 1.0 355 355 241 241

3 C2A01 CD 24” x 24” 1.0 250 250 220 220

VAV-2244 395 407

1 2244 CD 24” x 24” 1.0 275 275 282 282

2 2244 CD 24” x 24” 1.0 120 120 125 125

VAV-C2A08 550 555

1 C2A08 CD 24” x 24” 1.0 275 275 257 257

2 C2A08 CD 24” x 24” 1.0 275 275 298 298

VAV-C2A09 480 387

1 C2A09 CD 24” x 24” 1.0 240 240 190 190

2 C2A09 CD 24” x 24” 1.0 240 240 197 197

VAV-2253 150 151

1 2253 CD 24” x 24” 1.0 150 150 151 151

VAV-2255 170 170

1 2255 CD 24” x 24” 1.0 170 170 170 170

VAV-C2A05 510 514

1 2251 CD 24” x 24” 1.0 150 150 125 125

2 C2A05 CD 24” x 24” 1.0 180 180 176 176

3 C2A05 CD 24” x 24” 1.0 180 180 213 213

VAV-C2A04 590 562

1 C2A04 CD 24” x 24” 1.0 590 590 562 562

Project Name: VA Hospital – Surgery OR Suites 1-8

System Name: SUPPLIES Floor Number 2nd

VAV-2263 260 159

1 2263 CD 24” x 24” 1.0 260 260 159 159

VAV-2262 380 383

1 2262 CD 24” x 24” 1.0 380 380 383 383

VAV-2258 155 147

1 2258 CD 24” x 24” 1.0 155 155 147 147

VAV-2257 175 162

1 2257 CD 24” x 24” 1.0 175 175 162 162

VAV-C2A04A 85 121

1 C2A04A CD 24” x 24” 1.0 85 85 121 121

RHC-4 370 376

1 2142D CD 24” x 24” 1.0 370 370 376 376

RHC-3 370 374

2 2142C CD 24” x 24” 1.0 370 370 374 374

RHC-6 250 237

3 2142H CD 24” x 24” 1.0 125 125 106 106

4 2142H CD 24” x 24” 1.0 125 125 131 131

RHC-5 150 158

5 2142J CD 24” x 24” 1.0 75 75 87 87

6 2142J CD 24” x 24” 1.0 75 75 71 71

CLEAN SUPPLY ROOM 652

1 2260 CD 24” x 24” 1.0 275 275 248 248

2 2260 CD 24” x 24” 1.0 275 275 370 370

3 CORRIDOR CD 24” x 24” 1.0 200 200 34 34

Project Name: VA Hospital – Surgery OR Suites 1-8 System Name: Exhaust Floor Number 2nd

VEV-C2A08 1,280 1,377

1 C2A08 EG 24” x 48” 1.0 1,280 1,280 1,377 1,377

VEV-2244 785 1,195

1 2244 LLE 12” x 20” 1.0 785 785 1,195 1,195

VEV-C2A09 1,070 1,412

1 C2A09 LLE 14” x 14” 1.0 1,070 1,070 1,412 1,412

VEV-C2A04 500 750

1 C2A04 EG 24” x 24” 1.0 500 500 750 750

VEV-2263 360 326

1 2263 EG 24” x 24” 1.0 360 360 326 326

VEV-2262 380 405

1 2262 EG 24” x 24” 1.0 380 380 405 405

VEV-C2A07 895 741

1 2251 EG 24” x 24” 1.0 895 895 741 741

NO BOX 75 188

1 2251 EG 24” x 24” 1.0 75 75 188 188

CLEAN SUPPLY ROOM 497

1 2260 EG 24” x 24” 1.0 100 100 91 91

2 2260 EG 24” x 24” 1.0 125 125 0 0

3 CORRIDOR EG 24” x 24” 1.0 300 300 404 404

VEV-2253 201

1 2253 EG 12” x 12” 1.0 150 150 201 201

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025 Location: Milwaukee, WI Architect: N.A.

Engineer: Chequamegon Mechanical Contractor: C3T, Inc.

Project Number: 124-314

This is to certify that AccuStar Air Balance, Inc. has balanced the systems described herein to their optimum performance capabilities. The testing and balancing have been performed in accordance with TABB recommended procedures and principles and the results of these tests are herein recorded.

05/30/25

Date 05/30/25

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025 System Name: Floor Number 1st

A I R C H A N G E A N D R O O M P R E S S U R E T E S T S H E E T

Room Use Supply CFM Exhaust CFM Room Air Changes P/Hr Room Design Actual Design Actual Vol Ft³ Design Actual Pressure

101 Decon 2,400 2,465 3,700 3,744 20,700 6.5 10.9 NEG

M102 Sterilizers 800 782 800 919 1,646 29.2 33.5 POS

M102A Aerator 200 231 520 704 1,159 26.9 36.4 NEG

112 Water Detergent 80 120 180 291 1,440 7.5 12.1 NEG

114 High Level Disinfection 95 129 245 330 1,067 13.8 18.6 NEG

116 Endoscope Processing 150 124 250 414 1,352 11.1 18.4 NEG

116A Scope Storage 50 100 50 71 697 4.3 8.6 NEG

120 Sterilization 6,565 6,630 4,800 3,241 20,520 19.2 19.4 POS

130 ETO 175 234 175 37 958 11.0 14.7 NEG/POS

131 Eq. Storage 4,400 4,075 4,800 4,893 4,815 59.8 61.0 NEG

135 ** 1,705 2,078 1,170 1,322 21,726 4.3 5.7 NEG/POS

140 Clean Receiving 270 350 270 364 2,700 6.0 8.1 NEG/POS

164 Ante PPE 200 201 - - 1,035 11.6 11.7 NEG/POS

174 Ante PPE 230 223 - - 1,350 10.2 9.9 POS/NEG

177 Airlock 230 241 200 244 1,200 11.5 12.2 POS/NEG

178 Clean Cart Holding 285 273 185 193 4,401 2.6 3.7 POS/NEG

Remarks ** Sterile / non-sterile storage

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025 A I R M O V I N G E Q U I P M E N T T E S T S H E E T

SYSTEM AHU-135-1A AHU-135-1B

Equipment Location Roof Roof

Area Served SPS Building 102 SPS Building 102

Equipment Manufacturer Twin City Twin City

Model 270 270

Serial Number 14-503434-1-1 14-503434-2-1

Specified Actual Specified Actual

Total CFM - Fan 20,055 (1) 21,524 20,055 (1) 21,524

Total CFM - Outlet 20,320 (1) 21,524 20,320 (1) 21,524

R/A CFM N.A. - N.A. -

O/A CFM 20,055 (1) 21,524 20,055 (1) 21,524

Total Static Pressure (Total/External) N.A. See N.A. See

Inlet Pressure N.A. Profile N.A. Profile

Discharge Pressure N.A. Sheet N.A. Sheet

Fan RPM N.A. 1,764 N.A. 1,764

Motor Manufacturer N.A. Westinghouse N.A. Westinghouse

Motor HP/BHP 30.0 30.0 30.0 30.0

Phase 3 / 60 3 / 60 3 / 60 3 / 60

Voltage 230 / 460 230 (2) 230 / 460 230 (2)

Amperage 68.6 / 34.3 44.0 (2) 68.6 / 34.3 44.0 (2)

Motor RPM 1,770 1,649 (2) 1,770 1,649 (2)

Motor Service Factor / Frame # N.A. 1.15 / 286T N.A. 1.15 / 286T

Starter Heater Elements VFD 56 HZ VFD 56 HZ

Motor Sheave (Bush) 2B5V62 x (B x 1-7/8”) 2B5V62 x (B x 1-7/8”)

Fan Sheave (Bush) 2B5V58 x (B x 1-15/16”) 2B5V58 x (B x 1-15/16”)

(No. of) + Belt Size (2) BX77 (2) BX77

Remarks: Static Pressure set point = 2.35” (1) Total of both fans. (2) At VFD. Fans tested to 58 HZ

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025 S T A T I C P R O F I L E S H E E T

System AHU-135-1A & 1B

Remarks:

A B C D

O.A.

Supply FanFilters

E F

Coils Filters Auto

Dampers

Condition A B C D E Supply Fan Total

F

100% O.A. -.59” -1.30” -1.64” -2.91” +3.48” 6.39” +3.33”

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025 System Name: AHU-135-1A and AHU-135-1B Floor Number 1st

Box Room Design CFM Multiplier Final CFM Number Served Min Max Min Max

SVAV-M102 M102 800 800 720 782 782

SVAV-M101-1 M101 400 400 425 413 413

SVAV-100 100 1,000 1,000 683 992 992

SVAV-166 166 260 260 405 252 252

SVAV-101 101 2,400 2,400 2,009 2,465 2,465

SVAV-112 112 375 375 441 473 473

SVAV-177 177 230 230 400 241 241

SVAV-174 174 230 230 393 223 223

SVAV-175 175 250 250 741 243 243

SVAV-178 178 385 385 385 374 374

SVAV-140 140 730 730 1,105 951 951

SVAV-135 135 1,705 1,705 1,455 2,078 2,078

SVAV-131-1 131 2,200 2,200 3,000 2,081 2,081

SVAV-131-2 131 2,200 2,200 2,732 1,994 1,994

SVAV-120 120 6,565 6,565 5,140 6,630 6,630

SVAV-164 164 200 200 414 201 201

SVAV-130 130 375 375 410 465 465

SVAV-150 144, 178 825 825 829 666 666

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025

SVAV-M102 800 782

1 M102 CD-5 24” x 24” 1.0 800 800 782 782

SVAV-M101-1 400 413

2 M101 CD-2 24” x 24” 1.0 160 160 170 170

3 M100 S-2 24” x 24” 1.0 240 240 243 243

SVAV-100 1,000 992

4 100 CD-4 24” x 24” 1.0 500 500 525 525

5 100 CD-4 24” x 24” 1.0 500 500 467 467

SVAV-166 260 252

6 165 CD-2 24” x 24” 1.0 130 130 137 137

7 166 CD-2 24” x 24” 1.0 130 130 115 115

SVAV-101 2,400 2,465

8 101 CD-3 24” x 24” 1.0 300 300 321 321

9 101 CD-3 24” x 24” 1.0 300 300 308 308

10 101 CD-3 24” x 24” 1.0 300 300 314 314

11 101 CD-3 24” x 24” 1.0 300 300 317 317

12 101 CD-3 24” x 24” 1.0 300 300 292 292

13 101 CD-3 24” x 24” 1.0 300 300 310 310

14 101 CD-3 24” x 24” 1.0 300 300 313 313

15 101 CD-3 24” x 24” 1.0 300 300 290 290

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025 System Name: AHU-135-1A and AHU-135-1B Floor Number 1st

A I R D I S T R I B U T I O N T E S T S H E E T

Terminal Room Terminal Factor Design Test - FPM or CFM Final Number Number Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM

SVAV-112 375 473

16 116A CD-1 24” x 24” 1.0 50 50 100 100

17 116 CD-1 24” x 24” 1.0 150 150 124 124

18 114 CD-1 24” x 24” 1.0 95 95 129 129

19 112 CD-1 24” x 24” 1.0 80 80 120 120

SVAV-177 230 241

20 177 CD-3 24” x 24” 1.0 230 230 241 241

SVAV-174 230 223

21 174 CD-3 24” x 24” 1.0 230 230 223 223

SVAV-175 250 243

22 175 CD-2 24” x 24” 1.0 125 125 120 120

23 176 CD-2 24” x 24” 1.0 125 125 123 123

SVAV-178 385 374

24 178 CD-2 24” x 24” 1.0 145 145 135 135

25 178 CD-2 24” x 24” 1.0 140 140 138 138

26 151 S-1 22” x 10” 1.0 100 100 101 101

SVAV-140 730 951

27 143 CD-1 24” x 24” 1.0 75 75 124 124

28 147 CD-2 24” x 24” 1.0 200 200 215 215

29 142 CD-3 24” x 24” 1.0 185 185 262 262

30 140 CD-3 24” x 24” 1.0 270 270 350 350

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025

SVAV-135 1,705 2,078

31 135 CD-3 24” x 24” 1.0 260 260 311 311

32 135 CD-3 24” x 24” 1.0 265 265 331 331

33 135 CD-3 24” x 24” 1.0 260 260 313 313

34 135 CD-3 24” x 24” 1.0 260 260 292 292

35 135 CD-3 24” x 24” 1.0 265 265 329 329

36 135 CD-3 24” x 24” 1.0 260 260 343 343

37 135 CD-2 24” x 24” 1.0 135 135 159 159

SVAV-131-1 2,200 2,081

38 131 CD-8 24” x 24” 1.0 550 550 481 481

39 131 CD-8 24” x 24” 1.0 550 550 546 546

40 131 CD-8 24” x 24” 1.0 550 550 488 488

41 131 CD-8 24” x 24” 1.0 550 550 566 566

SVAV-131-2 2,200 1,994

42 131 CD-8 24” x 24” 1.0 550 550 467 467

43 131 CD-8 24” x 24” 1.0 550 550 551 551

44 131 CD-8 24” x 24” 1.0 550 550 492 492

45 131 CD-8 24” x 24” 1.0 550 550 484 484

Project Name: Zablocki VAMC Expand SPS Building 102, June 2025 System Name: AHU-135-1A and AHU-135-1B Floor Number 1st

A I R D I S T R I B U T I O N T E S T S H E E T

Terminal Room Terminal Factor Design Test - FPM or CFM Final Number Number Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM

SVAV-120 6,565 6,630

46 120 CD-5 24” x 24” 1.0 805 805 702 702

47 120 CD-5 24” x 24” 1.0 705 705 642 642