These construction documents detail a project to replace Chiller No. 2 at the Captain James A. Lovell Federal Health Care Center in North Chicago, Illinois. The project involves removing the existing 1000-ton York centrifugal chiller and installing a new 1000-ton water-cooled centrifugal magnetic drive chiller, along with associated components including chilled water and condenser water pumps, variable frequency drives (VFDs), local piping, valves, chemical feed system, electrical power, and controls. The work aims to bring the chiller plant into compliance with current VA and industry standards, with a focus on reestablishing long-term reliability of the facility's cooling infrastructure.
The contract (Solicitation Number 36C25225B0020) specifies a detailed performance schedule, with key milestones including mobilization, demolition, pre-HVAC construction, and system installation. The project requires comprehensive documentation, including daily reports, progress meetings, safety plans, and closeout records. Critical requirements include maintaining strict infection control protocols, providing negative air pressure in work areas, using HEPA filtration, and ensuring minimal disruption to the ongoing healthcare facility operations. The project is being executed by the Department of Veterans Affairs Veterans Health Administration, with an emphasis on safety, quality control, and precise coordination of all construction activities.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06 - Att 1 Updated RFI Responses FINAL rev23JUL25v3.pdf | ||
| 36C25225B0020 0003.docx | DOCX document | |
| S06 - Att 2 Wage Determination Update -Building and Res 20250718.pdf | ||
| 36C25225B0020 0002.docx | DOCX document | |
| S06 - Att 1 Pre-Bid RFIs 556-24-106 Replace Chiller 2 FINAL 21JUUL25.pdf | ||
| S05 - Att 4 Pre-Bid RFI Response 3 Jul 2025.pdf | ||
| S06 - Att 3 Wage Determination Update -Building and Res 20250627.pdf | ||
| S06 - Att 1 Replace Chiller 2 preproposal Site Visit Sign-in Sheets.pdf | ||
| S06 - Att 2 VAAR 852.219-75 Limitations on Subcontracting Marked Special Trade.pdf | ||
| 36C25225B0020 0001.docx | DOCX document | |
| S02 - Att 03 Wage Determination -Building and Residential 20250425.pdf | ||
| 36C25225B0020_1.docx | DOCX document | |
| S02 - Att 01 Construction Specs.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
G000
COVER SHEET REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AEA SSK
23022.010
100%R CONSTRUCTION
DOCUMENTS
SHEET LIST - GENERAL
Sheet Number Sheet Name
G000 COVER SHEET
Grand total: 1
SHEET LIST - ELECTRICAL
Sheet Number Sheet Name
E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
ED101 BASEMENT LEVEL FLOOR PLAN - OVERALL - ELECTRICAL -
DEMO
ED102 FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMO
ED400 FLOOR PLANS - ENLARGED - ELECTRICAL - DEMOLITION
E101 BASEMENT LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
E102 FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
E400 FLOOR PLANS - ENLARGED - ELECTRICAL
E500 ONE-LINE DIAGRAM
E700 ELECTRICAL SCHEDULES
Grand total: 9
SHEET LIST - MECHANICAL
Sheet Number Sheet Name
M000 MECHANICAL SYMBOLS AND ABBREVIATIONS
MD101 BASEMENT LEVEL FLOOR PLAN - OVERALL - MECHANICAL -
DEMO
MD102 FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL -
DEMO
MD400 FLOOR PLANS - ENLARGED - MECHANICAL- DEMOLITION
M001 FIRST LEVEL FLOOR PLAN - EQUIPMENT ACCESS
M101 BASEMENT LEVEL FLOOR PLAN - OVERALL - MECHANICAL
M102 FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL
M400 FLOOR PLANS - ENLARGED - MECHANICAL
M500 DETAILS AND SECTIONS
M501 CONTROL SCHEMATICS
M600 MECHANICAL SCHEDULES
Grand total: 11
Captain James A. Lovell Federal Health Care Center (FHCC)
REPLACE CHILLER 2
3001 N GREEN BAY RD,
NORTH CHICAGO, IL 60064
VA CONTRACT #: 36C252-23-D-0061
TASK ORDER #: 36C25224N0254
N Base Bid: Period services at Captain James A. Lovell FHCC, North Chicago, IL, to enable complete and compliant demolition and replacement of an existing 1000-ton York centrifugal chiller and associated system, including a new 1000-ton water-cooled centrifugal magnetic drive chiller, chilled water pump, condenser water pump, VFD's, local piping, valves, chemical feed system, electrical power, and controls, integrating it with the existing chiller plant necessary to reestablish long-term reliability.
Revisions: Date:
ABBREVIATION
GENERAL ABBREVIATIONS
DESCRIPTION ABBREVIATION DESCRIPTION
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
AD ACCESS DOOR/PANEL
AFF ABOVE FINISHED FLOOR
AMB AMBIENT
DIA DIAMETER
DN DOWN
E EXISTING
EC ELECTRICAL CONTRACTOR
EFF EFFICIENCY
GC GENERAL CONTRACTOR
FPM FEET PER MINUTE
FPS FEET PER SECOND
L LENGTH
LF LINEAR FEET
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MFR MANUFACTURER
MIN MINIMUM
NIC NOT IN CONTRACT
NTS NOT TO SCALE
PC PLUMBING CONTRACTOR
PSIG POUNDS PER SQUARE INCH GAUGE
RPM REVOLUTIONS PER MINUTE
SHT SHEET
TOB TOP OF BEAM
GPM GALLONS PER MINUTE
TOS TOP OF STEEL
BOB BOTTOM OF BEAM
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
UNION
Y STRAINER WITH BLOWDOWN
ELBOW UP
ELBOW DOWN
TEE UP
PIPING
- SOLID LINE INDICATES SYSTEM SUPPLY
-- DASHED LINE INDICATES SYSTEM RETURN
NUMBER INDICATES NOMINAL DIAMETER IN INCHES,
LETTER(S) INDICATES SYSTEM.
REFER TO ABBREVIATIONS FOR SYSTEM TYPE.
GENERAL MECHANICAL SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
# SHEET NOTE
DENOTES SPECIFIC REQUIREMENT FOR THE SHEET ON WHICH THE NOTE APPEARS
AND IS USED TO DESCRIBE WORK THAT IS TOO LENGTHY TO PLACE ON PLAN.
DIAMETER
DENOTES CONNECTION OF NEW WORK TO EXISTING
SYSTEM/OR DISCONNECT POINT ON DEMO PLANS
PROTECT EXISTING SYSTEM FROM ENTRANCE OF FOREIGN DEBRIS DURING WORK.
ARROW INDICATES DOWNWARD PIPE SLOPE
#/# INDICATES SLOPE IN INCHES PER FOOT
WHERE PIPING IS NOT MARKED, REFER TO SPECIFICATIONS FOR REQUIREMENTS
ARROW INDICATES DIRECTION OF FLOW IN PIPING
ISOLATION VALVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
CHECK VALVE
ARROW INDICATES DIRECTION OF NORMAL FLOW
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
PIPE IN SLEEVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
CIRCUIT SETTER, AUTOFLOW, ETC.
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
PRESSURE GAUGE
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIESTHERMOMETER - HORIZONTAL PIPE
TEE DOWN
TEE HORIZONTAL
PIPE REDUCER
INDICATES POINT WHERE PIPING CHANGES FROM ONE SIZE TO ANOTHER.
SMALL POINT OF ARROW INDICATES SMALLER SIZE SIDE OF TRANSITION.
REQUIRED SERVICE CLEARANCE FOR EQUIPMENT
CONTINUATION
FIRST SYMBOL APPLIES TO ROUND DUCT AND PIPING.
SECOND SYMBOL APPLIES TO RECTANGULAR AND OVAL DUCT.
AIR VENT
AUTOMATIC FLOW CONTROL VALVE
# INDICATES FLOW TO BE BALANCED IN GPM
BACKFLOW PREVENTER
CALIBRATED BALANCING VALVE
VALVE - THROTTLING SERVICE
VALVE - SHUTOFF SERVICE
P/T PORT
PIPE CAP
PIPE CONTINUATION
PRESSURE GAUGE STEAM REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
PRESSURE REDUCING VALVE
PUMP
RELIEF VALVE
S SENSOR
SUCTION DIFFUSER
THERMOMETER - VERTICAL PIPE REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
VACUUM BREAKER
Y STRAINER
STEAM TRAP
CC CONTROLS CONTRACTOR
ABBREVIATION
PLUMBING ABBREVIATIONS
DESCRIPTION
CHEMICAL VENTCV
CHEMICAL WASTECW
BOTTLE/GLASS FILLERBF
ABBREVIATION DESCRIPTION
DOMESTIC HOT WATERDHW
DOMESTIC HOT WATER CIRCULATIONDHWC
LAVATORYL
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
BACK FLOW PREVENTERBFP
BATH TUBBT
COMPRESSED AIR (NON-MEDICAL)CA
PROPANELPG
LEAVING WATER TEMPERATURELWT
BTU (1000'S)MBH
CONDENSATE DRAINCD
CLEANOUTCO
CONDENSATE PUMPCP
MOP SINKMS
NORMALLY CLOSEDNC
NORMALLY OPENNO
CLINICAL SINKCS
DOMESTIC COLD WATERDCW
DRINKING FOUNTAINDF
NON-POTABLE WATERNPW
POST INDICATOR VALVEPIV
PRESSURE REDUCING VALVEPRVDOUBLE GRADE CLEANOUTDGCO
DEIONIZED WATERDI
DEIONIZED WATER CIRCULATINGDIC
ROOF DRAINRD
REVERSE OSMOSIS WATERRO
DEIONIZED HOT WATERDIH
RPZ
S
REDUCED PRESSURE ZONE (BACK FLOW PREVENTER)
SINK
DEIONIZED HOT WATER CIRCULATINGDIHC
DISTILLED WATERDIS
DISTILLED WATER CIRCULATINGDISC
SANITARY SEWERSAN
DOMESTIC SOFT COLD WATERSCW
DOMESTIC SOFT HOT WATERSHW
DIALYSIS WATER RETURNDR
DIALYSIS WATER SUPPLYDS
DRAIN TILEDT
DOMESTIC SOFT HOT WATER CIRCULATINGSHWC
SEWAGE EJECTORSE
SHOWERSH
EMERGENCY EYE WASHEEW
EMERGENCY SHOWERES
EMERGENCY SHOWER AND EYE WASH COMBOESEW
STORM OVERFLOWSO
SUMP PUMPSP
SERVICE SINKSS
EXPANSION TANKET
ELECTRIC WATER COOLEREWC
ENTERING WATER TEMPERATUREEWT
STORM SEWERST
TEMPERATURETEMP
URINALUR
FILTERF
FLOOR CLEANOUTFCO
FLOOR DRAINFD
VENTV
VENT THROUGH ROOFVTR
FLOOR SINKFS
WB
WC
WALL BOX
WATER CLOSET
NATURAL GASG
WALL CLEANOUTWCO
GRADE CLEANOUTGCO
HUB DRAINHD
WATER HEATERWH
WATER SOFTENERWS
HORSEPOWERHP
WPD
YCO
WATER PRESSURE DROP
YARD CLEANOUTGREASE VENTGV
HOSE BIBHB
GREASE WASTEGW
DOWN SPOUT NOZZLEDSN
RECTANGULAR DUCTWORK
W = DIMENSION IN VIEW (INCHES)
H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
ROUND DUCTWORK
D = DUCT DIAMETER
TURNING VANES
FLEXIBLE PIPING
WxH
D"Ø
HVAC SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
W/H
FLAT OVAL DUCTWORK
W = DIMENSION IN VIEW (INCHES)
H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
DUCT CROSS SECTION - SUPPLY
DUCT CROSS SECTION - RETURN
DUCT CROSS SECTION - EXHAUST
CROSS SECTION INDICATES DUCT EXTENDING PERPENDICULAR TO THE PAGE. IN
PLAN VIEW THIS INDICATES A DUCT RISE OR DROP TO ANOTHER LEVEL. SOLID
INTERIOR LINE INDICATES EXTENSION UP. DASHED INTERIOR LINE INDICATES
EXTENSION DOWN.
MANUAL BALANCE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE MANUAL BALANCE DAMPERS IN AN
ACCESSIBLE LOCATION AND AS CLOSE TO THE MAIN DUCT AS POSSIBLE.
CONTROL DAMPER
FIRE/SMOKE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
DIFFUSER
REFER TO SPECIFICATIONS FOR TYPE.
FLEXIBLE DUCT
REFER TO SPECIFICATIONS FOR TYPE. REFER TO DETAILS FOR INSTALLATION
REQUIREMENTS. MAXIMUM LENGTH SHALL BE 48 INCHES UNLESS NOTED OTHERWISE
ON THE PLANS OR IN THE SPECIFICATIONS.
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - NO COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - HOT WATER COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - ELECTRIC COIL
VB-#
### CFM
VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
### = AIRFLOW IN CFM
REFER TO VARIABLE VOLUME BOX SCHEDULE FOR TYPES AND SIZING. AIRFLOW
LISTED IS NOMINAL DESIGN CFM AND GPM. FINAL VALUES ARE TO BE DETERMINED BY
TESTING AND BALANCING CONTRACTOR AND PROGRAMMED BY CONTROLS
CONTRACTOR.
VB-#
#.# GPM
VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
#.# = WATER FLOW RATE IN GPM
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - DUAL DUCT
D#
DIFFUSER TAG
D = TYPE # = TYPE NUMBER
### = AIRFLOW IN CFM
REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE TO
AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, PROVIDE
D1 FOR SUPPLY OR G1 FOR RETURN/EXHAUST.
FLOW ARROW ARROW INDICATES DIRECTION OF AIRFLOW FROM DIFFUSERS WITH ADJUSTABLE
THROWS.
DIFFUSER BLANK OFF SHADED AREA INDICATES QUADRANT OF DIFFUSER TO BE PROVIDED WITH BLANK OFF
PANEL.
RETURN GRILLE
EXHAUST GRILLE
WALL REGISTER / GRILLE
DUCT MOUNTED REGISTER / GRILLE
LINEAR SLOT
REFER TO VARIABLE VOLUME BOX SCHEDULE FOR TYPES AND SIZING. AIRFLOW
LISTED IS NOMINAL DESIGN CFM AND GPM. FINAL VALUES ARE TO BE DETERMINED BY
TESTING AND BALANCING CONTRACTOR AND PROGRAMMED BY CONTROLS
CONTRACTOR.
SMOKE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
ABBREVIATION
HVAC ABBREVIATIONS
DESCRIPTION
AIR BLENDERAB
AIR CONDITIONING UNIT (SPLIT SYSTEM INDOOR UNIT)AC
AIR HANDLING UNITAHU
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
BOILER FEED UNITBFU
BOILERBLR
CONSTANT AIR VOLUME BOXCAV
COOLING COILCC
CONDENSATE DRAINCD
CUBIC FEET PER MINUTECFM
CHILLERCH
CONDENSATE PUMPCP
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
COOLING TOWERCT
CONDENSING UNITCU
CABINET UNIT HEATERCUH
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
DIFFUSERD
DUAL DUCTDD
DIRECT EXPANSIONDX
EXHAUST AIREA
ENTERING AIR TEMPERATUREEAT
EXHAUST FANEF
EFFICIENCYEFF
ENERGY RECOVERY COILERC
ENERGY RECOVERY WHEELERW
EXPANSION TANKET
ENTERING WATER TEMPERATUREEWT
FILTER BANK (CONSISTING OF ONE OR MORE FILTERS)FB
FAN COIL UNITFCU
FLOW MEASURING STATIONFMS
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
FUEL OIL VENTFOV
FIRE DAMPERFRD
FIRE SMOKE DAMPERFSD
FINNED TUBE RADIATORFTR
GRILLEG
GLYCOL CHILLED WATER RETURNGCWR
GLYCOL CHILLED WATER SUPPLYGCWS
GRAVITY EXHAUSTGE
GLYCOL HEATING HOT WATER RETURNGHWR
GLYCOL HEATING HOT WATER SUPPLYGHWS
GRAVITY INTAKEGI
HEATING COILHC
PRESSURE/TEMPERATURE TEST PORT
TEMPERATURE CONTROL SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
WALL MOUNTED CONTROL DEVICE
# INDICATES TYPE
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION.
T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON MONOXIDE, ETC.)
OCCUPANCY SENSOR
REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. WHEN SENSOR IS
NOT SHOWN ON ELECTRICAL DRAWINGS IT SHALL BE PROVIDED AND INSTALLED BY
THE TEMPERATURE CONTROLS CONTRACTOR.
DUCT, PIPE, OR CEILING MOUNTED CONTROL
SENSOR
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON DIOXIDE, ETC.)
CONTROL VALVE (3-WAY)
CONTROL VALVE (2-WAY)
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
F/S FLOW MEASURING STATION REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
FIRE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
CD
FD
SD
FS
DAMPER SHALL BE SAME SIZE AS DUCT UNLESS NOTED OTHERWISE. REFER TO
SEQUENCES, SCHEMATICS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
FLOW SWITCHF
ABBREVIATION DESCRIPTION
HORSEPOWERHP
HIGH PRESSURE STEAM CONDENSATEHPC
HIGH PRESSURE STEAM SUPPLY (86 PSIG AND ABOVE)HPS
HEAT RECOVERY CHILLERHRC
HUMIDIFIERHUM
HEATING HOT WATER RETURNHWR
HEATING HOT WATER SUPPLYHWS
LOW PRESSURE STEAM CONDENSATELPC
LOW PRESSURE STEAM SUPPLY (0-12 PSIG)LPS
LOUVERLV
LEAVING WATER TEMPERATURELWT
BTU (1000'S)MBH
MANUAL DAMPERMD
MOTOR OPERATED DAMPERMOD
MEDIUM PRESSURE STEAM CONDENSATEMPC
MEDIUM PRESSURE STEAM SUPPLY (13-85 PSIG)MPS
NORMALLY CLOSED, NOISE CRITERIANC
NORMALLY OPEN, NUMBERNO
OUTDOOR AIROA
PUMPP
PUMPED CONDENSATEPC
PRESSURE REDUCING VALVEPRV
PUMPED STEAM CONDENSATEPSC
REGISTERR
RETURN AIRRA
RELIEF AIRREA
REFRIGERANT DX LIQUIDREFL
REFRIGERANT DX SUCTION GASREFS
RETURN FANRF
RELATIVE HUMIDITYRH
ROOF TOP UNITRTU
SUPPLY AIRSA
SMOKE DAMPERSD
SUPPLY FANSF
STATIC PRESSURESP
STEAMSTM
TEMPERATURETEMP
TRANSFERTR
UNIT HEATERUH
VARIABLE AIR VOLUME BOXVAV
VENT THROUGH ROOFVTR
WET BULB TEMPERATUREWB
WATER COLUMNWC
WATER PRESSURE DROPWPD
WATER SOURCE HEAT PUMP RETURNWSHPR
WATER SOURCE HEAT PUMP SUPPLYWSHPS
MECHANICAL GENERAL NOTES:
A. THESE NOTES APPLY TO ALL SHEETS CONTAINING HVAC, PIPING, PLUMBING, TEMPERATURE CONTROLS WORK. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. WHERE A DISCREPANCY EXISTS BETWEEN THESE PLANS AND THE PROJECT SPECIFICATIONS, THE SPECIFICATION REQUIREMENTS SHALL TAKE PRECEDENCE OVER THE DRAWINGS.
B. VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL. BE ADVISED THAT LOCATIONS SHOWN ARE APPROXIMATE. AN ATTEMPT HAS BEEN MADE TO SHOW ALL PIPING, FIXTURES, DUCTWORK, AND OUTLETS. CONTRACTOR SHALL VISIT THE SITE TO VERIFY COMPONENTS, LOCATIONS AND SIZES SHOWN OR NOT SHOWN. ALL COMPONENTS NEED TO BE REMOVED IN THE DEMOLITION AREA UNLESS NOTED ON THE DRAWINGS. IF DEVIATION BETWEEN EXISTING CONDITIONS AND NEW WORK IS FOUND, CONTRACTOR SHALL NOTIFY ENGINEER.
C. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED OPERATION DURING THE CONSTRUCTION OF THE ADDITIONS AND REMODELING/ALTERATION OF THE EXISTING BUILDING. SERVICES TO THE EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS OPERATION EXCEPT DURING SCHEDULED SHUTDOWNS FOR EXTENSION OR MODIFICATION. PLAN TO COMPLETE SHUTDOWNS DURING OFF HOURS TO MINIMIZE IMPACT TO THE OWNER. COORDINATE SHUTDOWNS WITH THE OWNER A MINIMUM OF 14 WORKING DAYS PRIOR TO WORK. PROVIDE TEMPORARY SERVICES WHERE NECESSARY TO ACCOMPLISH ANY SHUTDOWN. THIS INCLUDES BUT IS NOT LIMITED TO STAFFING AND EQUIPMENT FOR FIRE WATCHES, PROVISIONS FOR BOTTLED WATER, AND TEMPORARY HEATING OR COOLING EQUIPMENT. TEMPORARY MEASURES SHALL NOT BE REMOVED UNTIL THE PERMANENT SYSTEMS ARE OPERATIONAL AND HAVE PASSED ALL
REQUIRED TESTING.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR OWN DEMOLITION, REMOVAL, CAPPING, STORING, ABANDONING, DISCONNECTING, RELOCATING AND RECONNECTION OF EXISTING EQUIPMENT AND MATERIAL. ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND REFINISHING SHALL MATCH THE EXISTING CONSTRUCTION AS NEARLY AS POSSIBLE.
E. EXCEPT WHERE OTHERWISE SHOWN OR NOTED ON THE DRAWINGS AS "TO BE RETAINED, RELOCATED", ALL EXISTING EQUIPMENT AND MATERIAL IN AREAS TO BE REMODELED/ALTERED SHALL BE REMOVED WHERE THEY INTERFERE WITH PROPOSED NEW CONSTRUCTION AND/OR WITH PROPOSED USAGE OF SPACE BY OWNER AS FOLLOWS:
a. REMOVE ANY PIPING PROTRUDING ABOVE FINISHED FLOOR OR THROUGH WALL AND CAP WITHIN 3 PIPE DIAMETERS OF NEAREST ACTIVE MAIN WITH MATERIAL TO MATCH EXISTING.
b. IN REMODELED/ALTERED AREAS, ANY PIPING OR DUCTWORK PASSING THROUGH THE REMODELED AREAS TO SERVE (OR BEING SERVED FROM EXISTING ADJACENT, REMOTE, OR
SURROUNDING AREAS THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR
USAGE TO BE ACCOMPLISHED IN THE REMODELED AREA.
c. REMOVE UNUSED OR ABANDONED HANGERS AND PATCH ABANDONED PENETRATIONS TO MATCH EXISTING.
d. PENETRATIONS THROUGH EXISTING WALLS AND FLOORS FORMERLY OCCUPIED BY REMOVED PIPING OR DUCTWORK SHALL BE PATCHED TO MATCH EXISTING CONSTRUCTION.
e. RE-SUPPORT ANY PIPING AND DUCTWORK THAT WAS SUPPORTED FROM BUILDING ELEMENTS REMOVED AS PART OF THE WORK.
f. MAINTAIN CONTROL WIRING OR PNEUMATIC TUBING REQUIRED FOR THE CONTINUED PROPER OPERATION OF THE BUILDING AUTOMATION SYSTEM.
F. ALL EXISTING EQUIPMENT BEING REMOVED WILL BE HANDED OVER TO OWNER FOR FIRST RIGHT OF SALVAGE. IF OWNER REFUSES SALVAGE ITEMS, REMOVING CONTRACTOR SHALL BE
RESPONSIBLE FOR DISPOSAL.
G. CONTRACTOR SHALL REFER TO THE DRAWINGS OF ALL TRADES TO FAMILIARIZE THEMSELVES WITH EXTENT OF WORK INCLUDING BUT NOT LIMITED TO WHERE NEW PARTITIONING IS BEING INSTALLED, WHERE EXISTING PARTITIONING IS BEING REMOVED, WHERE CEILINGS ARE BEING REMOVED AND/OR REPLACED, ETC.
H. THESE DRAWINGS ARE NECESSARILY DIAGRAMMATIC IN NATURE. NOT ALL FITTINGS, OFFSETS, VENTS OR DRAINS ARE SHOWN. THE CONTRACTOR SHALL INCLUDE ALL FITTINGS, OFFSETS, VENTS, DRAINS, AND DEVICES REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING SYSTEM.
I. PROVIDE ACCESS DOORS IN DUCTWORK AND/OR ARCHITECTURAL ELEMENTS WHERE REQUIRED TO ACCESS ALL EQUIPMENT REQUIRING MAINTENANCE AND ADJUSTMENT. THIS EQUIPMENT INCLUDES BUT IS NOT LIMITED TO SENSORS, DAMPERS, ACTUATORS, CONTROL DEVICES, VALVES, ETC. ACCESS DOORS SHALL BE SIZED TO PROVIDE APPROPRIATE ACCESS BASED ON HEIGHT OF ACCESS REQUIRED AND ACTIVITY. INSTALL SUCH THAT ACCESS DOOR IS FULLY OPERABLE WITHOUT THE REMOVAL OF ARCHITECTURAL ELEMENTS SUCH AS CEILING RUNNERS, SUPPORTS, ETC.
INSTALL IN A LOCATION SUCH THAT STEPPING OR LEANING OVER PERMANENT EQUIPMENT OR FURNITURE IS NOT REQUIRED. WHERE ACCESS DOORS ARE REQUIRED IN ARCHITECTURAL ELEMENTS THAT PROVIDE A FIRE AND/OR SMOKE RATING, ACCESS DOOR SHALL MAINTAIN THE REQUIRED RATING.
J. SEAL ALL WALL PENETRATIONS (DUCTWORK, PIPING, CONTROLS, CONDUITS, ETC.) WITH NON-COMBUSTIBLE MATERIAL. SEAL PENETRATIONS INTO ROOMS THAT REQUIRE PRESSURE CONTROL OR
SOUND ISOLATION. WITH NON-COMBUSTIBLE MATERIAL AND CAULK.
K. PIPING AND DUCTWORK SHALL NOT BE ROUTED OVER ELECTRICAL AND TELECOM ROOMS. WHERE ROUTING OVER SUCH ROOMS IS UNAVOIDABLE, CONTRACTOR SHALL COORDINATE WITH OWNER, DESIGN TEAM, AHJ, AND OTHER TRADES REGARDING LOCATION OF PANELS AND UTILITY ROUTING AND SHALL PROVIDE DRIP PANS UNDER ALL UTILITIES WITH MOISTURE SENSORS OR
DRAIN PIPING AS REQUIRED BY THE SPECIFICATIONS.
L. REMOVAL AND REINSTALLATION OF CEILINGS REQUIRED FOR THE COMPLETION OF WORK IS THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL REPAIR OR REPLACE ALL DAMAGED CEILING COMPONENTS TO MATCH EXISTING. WHERE AN IDENTICAL MATCH IS NO LONGER AVAILABLE, CONTRACTOR SHALL PROVIDE A SIMILAR REPLACEMENT UPON APPROVAL FROM THE OWNER.
M. LOCATE PIPING AND DUCTWORK IN EXTERIOR BUILDING WALLS ON THE WARM SIDE OF THE BUILDING AND VAPOR BARRIER. COORDINATE INSTALLATION OF BUILDING INSULATION TO RUN
CONTINUOUS BETWEEN PIPING AND BUILDING WALL.
N. SUPPORT ALL DUCTWORK, PIPING AND EQUIPMENT FROM BUILDING STRUCTURE MEMBERS. DO NOT USE WIRE OR PERFORATED METAL TO SUPPORT PIPING. DO NOT SUPPORT PIPING FROM OTHER PIPING, DUCTWORK, AND/OR ELECTRICAL CONDUITS. SUPPORT FROM BOTTOM CHORD OF BAR JOISTS ONLY AT PANEL POINTS. ALL COMPONENTS REQUIRING MAINTENANCE SHALL BE SUPPORTED IN SUCH A MANNER AS TO BE READILY ACCESSIBLE WITHOUT REMOVAL OF THE CEILING SYSTEM AND TO ALLOW FOR REMOVAL FROM THE SYSTEM WHEN SUCH REMOVAL IS
REQUIRED FOR MAINTENANCE.
O. PROVIDE CONSTRUCTION FILTERS ON AIR MOVING EQUIPMENT SERVING THE CONSTRUCTION AREA AS WELL AS ALL RETURN/EXHAUST DUCT PENETRATIONS COMING FROM THE CONSTRUCTION AREA. AT THE COMPLETION OF WORK, REMOVE ALL TEMPORARY AND CONSTRUCTION FILTERS AND PROVIDE NEW FILTERS FOR ALL AIR MOVING EQUIPMENT.
P. PROTECT ALL DUCTWORK AND PIPING DURING CONSTRUCTION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. AT A MINIMUM, DUCTWORK AND PIPING ENDS SHALL BE COVERED AND SEALED TO PREVENT THE COLLECTION OF DUST AND DEBRIS. CLEAN ALL INTERIOR SURFACES PRIOR TO INSTALLATION AND PROTECT ONCE INSTALLED. MEDICAL GAS PIPING SHALL BE
PROTECTED IN ACCORDANCE WITH NFPA 99 REQUIREMENTS.
Q. AT THE COMPLETION OF WORK, CLEAN ALL STRAINERS PROVIDED AS A PART OF THE WORK AS WELL AS PRIMARY SYSTEM STRAINERS LOCATED AT PUMPS WHERE SYSTEMS WERE EXTENDED. ON
EXISTING EQUIPMENT, COORDINATE WORK WITH OWNER.
R. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
S. REFER TO SCHEDULES FOR SIZES OF FINAL RUNOUTS TO EQUIPMENT, FIXTURES, DIFFUSERS, GRILLES, AND TERMINAL DEVICES. FINAL RUNOUT SIZES LISTED SHALL BE USED TO WITHIN 10
EQUIVALENT DIAMETERS OF FINAL CONNECTION POINT. FINAL PIPING CONNECTION TO EQUIPMENT SHALL MATCH EQUIPMENT CONNECTION SIZE, PROVIDE TRANSITIONS AS REQUIRED. REFER TO
DETAILS, DIAGRAMS AND SCHEMATICS FOR ADDITIONAL
T. FOR ALL PIPING, CONDUIT, AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
U. REFER TO SPECIFICATIONS FOR EQUIPMENT LABELING REQUIREMENTS.
V. PROVIDE PIPE LABELS AND FLOW DIRECTION ARROWS. LABELS SHALL BE PRECOILED, SEMIRIGID PLASTIC FORMED TO COVER FULL CIRCUMFERENCE OF PIPE AND TO ATTACH TO PIPE WITHOUT
FASTENERS OR ADHESIVE, APPLIED WITH ADHESIVE DIRECTIONAL TAPE. INCLUDE IDENTIFICATION OF PIPING SERVICE USING FULL NAME DESIGNATIONS PER DRAWINGS AND AN ARROW
INDICATING FLOW DIRECTION. LETTERING SIZE PER ASME/ANSI 13.1
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
M000
MECHANICAL SYMBOLS AND
ABBREVIATIONS
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
MD400
G
F
E
D
C
B
KEY PLAN
N
AREA OF WORK
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
MD101
BASEMENT LEVEL FLOOR PLAN -
OVERALL - MECHANICAL - DEMO
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
3/32" = 1'-0"
BASEMENT LEVEL FLOOR PLAN - OVERALL - MECHANICAL - DEMOLITION
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
N
MD400
J.
H.
J
H
G
F
E
D
C
B
A
(E)CH-2
KEY PLAN
N
AREA OF WORK
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
MD102
FIRST LEVEL FLOOR PLAN -
OVERALL - MECHANICAL - DEMO
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
3/32" = 1'-0"
FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL - DEMOLITION
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
(E)CH-2
CHILLERS
(E)24" CHWS
(E)10"
(E)24" CHWR
(E)14"
(E)CWP-2
(E)CH-1
(E)CH-3
H
G
F E
(D)CP-12
PIPE TRENCH
B100
(E)14" CS
(E)16" CS
(E )1
4" C
S
(E)12"
G
F
KEY PLAN
N
AREA OF WORK
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:3
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
MD400
FLOOR PLANS - ENLARGED -
MECHANICAL- DEMOLITION
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
FIRST LEVEL FLOOR PLAN - ENLARGED - MECHANICAL - DEMOLITION
1/4" = 1'-0"
BASEMENT LEVEL FLOOR PLAN - ENLARGED - MECHANICAL - DEMOLITION
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
N
N
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
SHEET NOTES:
1. REMOVE EXISTING WATER COOLED CHILLER.
2. REMOVE CHILLED WATER RETURN PIPING FROM MAIN BACK TO PUMP
3. REMOVE EXISTING CHILLED WATER PUMP AND RELATED CONTROLS.
4. REMOVE EXISTING CHILLED WATER RETURN PIPING AND BYPASS FROM PUMP TO CHILLER.
5. REMOVE CHILLED WATER SUPPLY FROM CHILLER TO EXISTING SHUTOFF VALVE.
6. REMOVE CONDENSER WATER SUPPLY FROM CHILLER TO POINT INDICATED. PREPARE PIPE FOR
CONNECTION TO NEW.
7. REMOVE EXISTING CONDENSER WATER RETURN FROM CHILLER DOWN TO BASEMENT.
8. REMOVE CONDENSER WATER SUPPLY PIPING FROM PUMP BACK TO POINT INDICATED.
9. REMOVE CONDENSER WATER SUPPLY FROM PUMP UP TO CHILLER.
10. REMOVE CONDENSER WATER SUPPLY FROM PUMP UP TO POINT SHOWN AT BYPASS HEADER. PREPARE
TAP AT BYPASS HEADER FOR CONNECTION TO NEW PIPE.
11. REMOVE REFRIGERANT SAFETY VENT FROM CHILLER TO VERTICAL RISER. PREPARE RISER FOR
CONNECTION TO NEW.
12. REMOVE CONDENSER WATER PUMP, PAD AND RELATED CONTROLS.
13. REMOVE AND SALVAGE EXISTING 4" SIDESTREAM FILTER FOR RE-INSTALLATION AT THE NEW CHILLED
WATER PUMP.
1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
GENERAL NOTES:
LOCKERS
OFFICE
ELECTRICAL
CORRIDOR
C100 Space
B105
CLEAN UP
JAN
CONTROL ROOM
Space
B109
CORRIDOR
C101
STORAGE
CHILLERS
VESTIBULE
C101A
CHILLER ENCLOSURE
CH-2
(E)CH-1
(E)CH-3
CH-4
CH-5 (E)
(E)CH-6
ECC (ENGINEERING
CONTROL CENTER)
LOCATED IN THIS ROOM
J.
H.
J
H
G
F
E
D
C
B
A
KEY PLAN
N
AREA OF WORK
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
M001
FIRST LEVEL FLOOR PLAN -
EQUIPMENT ACCESS
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
3/32" = 1'-0"
FIRST LEVEL FLOOR PLAN - EQUIPMENT ACCESS
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
N
1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
SHEET NOTES:
1. EXISTING OVERHEAD DOOR
2. OUTLINE OF NEW CHILLER FOOTPRINT. ACCESS PATH THROUGH THE MECHANICAL ROOM IS SHOWN.
MINIMUM HORIZONTAL CLEARANCE MEASURED IS 8'-0". CONTRACTOR SHALL VERIFY DIMENSIONS AVAILABLE
AND REQUIRED PRIOR TO BIDDING.
GENERAL NOTES:
S D
PIPE TRENCH
B100
M400
G
F
E
D
C
B
KEY PLAN
N
AREA OF WORK
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
M101
BASEMENT LEVEL FLOOR PLAN -
OVERALL - MECHANICAL
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
3/32" = 1'-0"
BASEMENT LEVEL FLOOR PLAN - OVERALL - MECHANICAL
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
LOCKERS
OFFICE
ELECTRICAL
CORRIDOR
C100 Space
B105
CLEAN UP
JAN
CONTROL ROOM
Space
B109
CORRIDOR
C101
STORAGE
CHILLERS
VESTIBULE
C101A
CHILLER ENCLOSURE
M400
CH-2
J.
H.
J
H
G
F
E
D
C
B
A
KEY PLAN
N
AREA OF WORK
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
M102
FIRST LEVEL FLOOR PLAN -
OVERALL - MECHANICAL
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
3/32" = 1'-0"
FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
KEY PLAN
AREA OF WORK
CHILLERS
CH-2
1 10" CHWS
12" CR
12" CS
VFD-CWP-212
(E)24" CHWS
(E)24" CHWR
(E)10" CHW BYPASS
(E)14" CR
BYPASS
M500
M500
CWP-2
H
G
F E
(E)CH-1
(E)CH-3
CWP-1
XFMR CH-2
M500
M500
M500
PIPE TRENCH
B100
CP-12
VFD-CWP-12
12" CS
12" CS
(E)12" CS
(E)12" CR
(E)16" CS
(E)14" CS
(E)14" CS
G
F
M500 M500
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
M400
FLOOR PLANS - ENLARGED -
MECHANICAL
REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
N
1/4" = 1'-0"
FIRST LEVEL FLOOR PLAN - ENLARGED - MECHANICAL
1/4" = 1'-0"
BASEMENT LEVEL FLOOR PLAN - ENLARGED - MECHANICAL
N
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
SHEET NOTES:
1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. PROVIDE SEISMIC RESTRAINTS IN ACCORDANCE WITH SPECIFICATION REQUIREMENTS
GENERAL NOTES:
1. CONNECT 10'' CHWS TO EXISTING VALVE AT THE MAIN.
2. PROVIDE NEW SHUTOFF VALVE IN EXISTING 10'' CHWR TO THE PUMP. EXTEND 10'' CHWR TO THE PUMP.
3. PROVIDE NEW SHUTOFF VALVUE IN 10'' CHWR BYPASS LINE. CONNECT 10'' CHWR TO EX. 10'' CHWR.
4. RE-INSTALL EXISTING 4'' SIDESTEAM FILTER.
5. PROVIDE SHUT OFF VALVE.
6. PROVIDE BASKET STRAINER.
7. PROVIDE FLEXIBLE CONNECTOR.
8. 12'' CWS DOWN TO PIT.
9. 12'' CWS UP.
10. REFRIGERANT RELIEF PIPING CONNECTED TO THE UNIT. PROVIDE FLEXIBLE CONNECTION. INSTALLATION
AND SIZE PER MANUFACTURER'S RECOMMENDATION.
11. CONNECT REFRIGERANT RELIEF PIPING TO EXISTING.
12. VFD SHALL BE INSTALLED ON EXISTING COLUMN. INSTALL AT MAXIMUM 5'-6" ABOVE FLOOR TO TOP OF VFD.
13. PROVIDE MANUFACTURER REQUIRED SERVICE CLEARANCE AS SHOWN BY DASHED LINE.
14. PROVIDE TUBE PULL CLEARANCE AS RECOMMENDED BY THE BOILER MANUFACTURER.
15. FURNISH AND INSTALL FLOW METER IN STRAIGHT RUN OF PIPE, PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS. PROVIDE A MINIMUM CLEARANCE OF 3 PIPE DIAMETER UPSTREAM AND 2 PIPE DIAMETER
DOWNSTREAM OF FLOW METER. FLOR METER SHALL BE ONICON SERIES F-3200 OR EQUAL.
FLANGE
CONNECTION,
TYP.
12'' CWS
CONDENSER
FLOW METER
EXISTING CONCRETE HOUSKEEPING PAD SHALL REMAIN
PROVIDE NEOPRENE PADS BENEATH
CHILLER. ANCHOR TO PAD WITH
THROUGH BOLTS PER CHILLER
MANUFACTUERS INSTALLATION
INSTRUCTIONS
12" CWR
TEMPERATURE CONTROL VALVE, TYP.
FLOW METER
FLEXIBLE
CONNECTOR,
TYP.
FLANGE
CONNECTION, TYP.
10'' CHWR
FLOW SWITCH
10'' CHWS
EVAPORATOR
EXISTING CONCRETE HOUSKEEPING PAD SHALL REMAIN
PROVIDE NEOPRENE PADS BENEATH
CHILLER.
ANCHOR TO PAD WITH THROUGH BOLTS PER
CHILLER MANUFACTURERS INSTALLATION
INSTRUCTIONS
FLOW METER
MARINE WATER BOX WITH
TOP AND SIDE
CONNECTIONS
THERMOMETER, TYP.
FLEXIBLE CONNECTOR, TYP.
P/T TAP, TYP
PRESSURE GAUGE, TYP.
TEMPERATURE CONTROL ISOLATION VALVE, TYP.
6'' HIGH CONCRETE
HOUSEKEEPING
PAD
INERTIA BASE. REFER TO INERTIA
BASE DETAIL 8/M500
TRIPLE DUTY
VALVE (ANGLE
OR STRAIGHT
PATTERN
DEPENDING
ON THE
APPLICATION)
SUCTION DIFFUSER AND SUPPORT STAND
ISOLATION VALVE
VERTICAL BASKET
STRAINER
TO CHILLER CH-2
(E) 16" CS
12" CS
(E)12" CS BYPASS
FLEXIBLE CONNECTOR (TYP.)
12" CS
12" CS
FLOOR
STRUT CLAMP HANGERS VERTICAL PIPE SUPPORTCLEVIS HANGER ROLLER SUPPORTTRAPEZE HANGER
OVERSIZE HANGER TO
ALLOW LONGITUDINAL
PIPE EXPANSION AND
PIPE INSULATION TO
PASS THROUGH
UNBROKEN (TYP)
STEEL PIPE
SADDLE, TACK
WELDED TO PIPE,
FILL SADDLE
WITH INSULATION
INSULATION AND
NEOPRENE MOUNTS
RISER CLAMP
INSULATION
LUG, COUPLING, OR HUB
THREADED ROD
CLEVIS HANGER
INSULATION
HIGH DENSITY
INSULATION
INSERT
INSULATION SHIELD
INSULATION
PIPE INSULATION (TYP)
THREADED ROD (TYP)
HIGH DENSITY INSULATION INSERT
UNI-STRUT OR
EQUIVALENT
INSULATION SHIELD (TYP)
INSTALL CLAMP ON ALL
PIPES LESS THAN 4"Ø
CWP-2 INERTIA BASE
RE-INSTALL IN-LINE FILTER
4" CHWS
M500
M500
C H
W R
C H
W R
24" CHWS
24" CHWR
10" CHWR
10" CHWR
CH-2
F
M500
10" CHWS
2" V
TRIPLE DUTY
VALVE
FLEXIBLE CONNECTOR, TYP.
TO CH-2
(E) 10" CHW BYPASS
HIGH PERFORMANCE BUTTERFLY VALVE
SUCTION DIFFUSER
(E) 24" CHWR
PROVIDE 6" HOUSEKEEPING PAD
INERTIA BASE. REFER TO INERTIA BASE DETAIL 8/M500
THERMOMETER, TYP.
ISOLATION VALVE
INSTALL EXISTING SIDESTREAM FILTER
4"
10" CHWR
10" CHWR
P/T TAP, TYP.
SUPPORT STAND FOR SUCTION DIFFUSER
6" CONCRETE HOUSEKEEPING PAD
ANCHOR INERTIA BASE TO CONCRETE PAD WITH THROUGH
BOLTS. INSTALL IN ACCORDANCE WITH MANUFACTURERS
INSTALLATION INSTRUCTIONS
8" DEEP INERTIA BASE MASS, INTEGRAL TO INERTIA BASE
ASSEMBLY, FILLED WITH CONCRETE. DEPTH OF BASE SHALL
COMPLY WITH ASHRAE APPLICATIONS HANDBOOK, CHAPTER 49,
TABLE 47. INTEGRAL SPRING WITH 0.75" MINIMUM DEFLECTION
ANCHOR PUMP TO EQUIPMENT PER MANUFACTURERS INSTRUCTIONS
12" CS
C S
12" CS
16" CS HEADER (E)
12" CS BYPASS (E)
12" CR (E)
SUCTION DIFFUSER WITH STAND
CP-12
INERTIA BASE
M500
M500
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
M500
DETAILS AND SECTIONS REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
NO SCALEM500
CHILLER CONDENSER WATER CONNECTION1
NO SCALEM500
CHILLER EVAPORATOR CHILLED WATER CONNECTION2
NO SCALEM500
CONDENSER WATER PUMP3
NO SCALEM500
HYD - PIPE SUPPORT - TYPICAL FOR ALL PIPING4
1/4" = 1'-0"M500
CWP-25
1/4" = 1'-0"M500
CH-26
NO SCALEM500
CHILLED WATER PUMP7
NO SCALEM500
INERTIA BASE DETAIL8
MARINE WATER BOX WITH
TOP AND SIDE
CONNECTIONS
1/4" = 1'-0"M500
CP-129
CHWR
SEQUENCE OF OPERATION
CHILLER, PUMP AND VALVE CONTROL SHALL BE AN EXTENSION OF THE EXISTING CAMPUS/BUILDING SYSTEM.
CHILLER CONTROL:
• THE BMS SHALL ENABLE THE CHILLER. EXISTING BMS ALGORITHM AND SEQUENCING FOR ENABLING CHILLER 2 SHALL REMAIN AS
CURRENTLY PROGRAMMED.
• WHEN A CHILLER IS ENABLED REMOTELY OR MANUALLY, ITS ASSOCIATED EVAPORATOR AND CONDENSER CONTROL VALVES SHALL
BE OPEN. WHEN A CHILLER IS DISABLED, ITS ASSOCIATED EVAPORATOR AND CONDENSER CONTROL VALVES SHALL BE CLOSED. EACH CONTROL VALVE SHALL BE A LINE SIZE TWO POSITION ACTUATOR WITH END SWITCHES. CONTROL VALVE END SWITCHES SHALL BE DIRECTLY INTERLOCKED WITH ITS CORRESPONDING CHILLER CONTROL PANEL AS DICTATED BY THE CHILLER MANUFACTURER.
1. UPON CHILLER SHUTDOWN, ISOLATION VALVES SHALL STAY OPEN FOR TWO MINUTES AFTER THE CHILLER SHUTS DOWN.
• CHILLER SHALL NOT BE ALLOWED TO START UNTIL FLOW IS PROVEN THROUGH THE EVAPORATOR AND CONDENSER AS SENSED BY THE FLOW SWITCH FURNISHED BY THE CHILLER MANUFACTURER. FLOW SWITCH SHALL BE WIRED DIRECTLY TO THE CHILLER
CONTROL PANEL INDEPENDENT OF THE BMS AS DICTATED BY THE CHILLER MANUFACTURER.
• THE CHILLED WATER TEMPERATURE SETPOINT SHALL BE AN INPUT SIGNAL FROM THE EXISTING BMS SYSTEM.
• BMS SHALL MONITOR THE FLOW RATE MEASURED BY THE FLOW METER THROUGH THE CHILLER AND EVAPORATOR.
CHILLED WATER PUMP CONTROL:
• THE DDC SYSTEM SHALL START THE PUMP VIA THE VFD AND SHALL RUN CONTINUOUSLY WHEN THE CHILLER IS ENABLED.
1. PROVIDE A USER ADJUSTABLE TIME DELAY FOR STARTING AND STOPPING THE PUMPS TO ALLOW FOR AN ORDERLY CHILLED
WATER SYSTEM START-UP, SHUT DOWN, AND SEQUENCING.
• IN CASE OF VFD FAULT DETECTION, THE DDC SYSTEM SHALL WAIT 30 SECONDS (ADJUSTABLE.) AND THEN CALL THE VFD TO START. IF THE VFD DOES NOT START, THE DDC SYSTEM SHALL CALL A SECOND TIME. IF THE VFD STILL HAS NOT STARTED, AN ALARM SHALL BE
SENT TO THE OPERATOR INTERFACE.
• INSTALL A CURRENT STATUS SWITCH TO PROVE PUMP OPERATION. LOCATE SWITCHES SO THEY SENSE PUMP STATUS WHEN OPERATED BY THE VFD OR IN BYPASS MODE. IF THE LEAD OR LAG PUMP CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE AND THE DDC SYSTEM SHALL START THE STANDBY PUMP VIA THE VFD. IF THE STANDBY PUMP CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, A SECOND ALARM SHALL BE SENT TO THE OPERATOR
INTERFACE. THE SEQUENCE SHALL BE REPEATED TWICE.
• THE DDC SYSTEM SHALL CONTROL THE OPERATING PUMP VFD(S) FROM THE DIFFERENTIAL PRESSURE ACROSS THE CHILLER. INITIAL SETPOINT SHALL BE 10 PSIG (ADJUSTABLE). FINAL SETPOINT SHALL BE OPTIMIZED BY THE BALANCING CONTRACTOR AND SHALL EQUAL THE DIFFERENTIAL PRESSURE REQUIRED TO MAINTAIN SCHEDULED CHILLER WATERFLOW.
1. BALANCING CONTRACTOR SHALL ALSO DETERMINE THE MINIMUM DIFFERENTIAL REQUIRED TO MAINTAIN THE CHILLERS MINIMUM
FLOW AND VERIFY THE PUMP SPEED DOES NOT DROP BELOW THIS SETTING.
• BMS SHALL MONITOR THE FLOW RATE MEASURED BY THE FLOW METER THROUGH THE CHILLER AND EVAPORATOR
BYPASS VALVE CONTROL:
• THE CHILLED WATER BYPASS VALVES SHALL BE MANUAL ON/OFF VIA A BMS COMMAND POINT
• THE CHILLED WATER BYPASS VALVES SHALL NOT BE ALLOWED TO OPEN IF THE CHILLER ISOLATION VALVE IS OPEN.
• THE CONDENSER WATER BYPASS VALVES SHALL BE INTEGRATED IN TO THE EXISTING BMS CONDENSER WATER RETURN
TEMPERATURE CONTROL ALGORITHIM.
CONDENSER WATER PUMP CONTROL:
• THE DDC SYSTEM SHALL START THE PUMP VIA THE VFD AND SHALL RUN CONTINUOUSLY WHEN THE CHILLER IS ENABLED.
1. PROVIDE A USER ADJUSTABLE TIME DELAY FOR STARTING AND STOPPING THE PUMPS TO ALLOW FOR AN ORDERLY CHILLED
WATER SYSTEM START-UP, SHUT DOWN, AND SEQUENCING.
• IN CASE OF VFD FAULT DETECTION, THE DDC SYSTEM SHALL WAIT 30 SECONDS (ADJUSTABLE.) AND THEN CALL THE VFD TO START. IF THE VFD DOES NOT START, THE DDC SYSTEM SHALL CALL A SECOND TIME. IF THE VFD STILL HAS NOT STARTED, AN ALARM SHALL BE
SENT TO THE OPERATOR INTERFACE.
• INSTALL A CURRENT STATUS SWITCH TO PROVE PUMP OPERATION. LOCATE SWITCHES SO THEY SENSE PUMP STATUS WHEN OPERATED BY THE VFD OR IN BYPASS MODE. IF THE LEAD OR LAG PUMP CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE AND THE DDC SYSTEM SHALL START THE STANDBY PUMP VIA THE VFD. IF THE STANDBY PUMP CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, A SECOND ALARM SHALL BE SENT TO THE OPERATOR
INTERFACE. THE SEQUENCE SHALL BE REPEATED TWICE.
• THE DDC SYSTEM SHALL CONTROL THE OPERATING PUMP VFD(S) FROM THE DIFFERENTIAL PRESSURE. INITIAL SETPOINT SHALL BE 10 PSIG (ADJUSTABLE). FINAL SETPOINT SHALL BE OPTIMIZED BY THE BALANCING CONTRACTOR AND SHALL EQUAL THE DIFFERENTIAL
PRESSURE REQUIRED TO MAINTAIN SCHEDULED CHILLER WATERFLOW.
1. BALANCING CONTRACTOR SHALL ALSO DETERMINE THE MINIMUM DIFFERENTIAL REQUIRED TO MAINTAIN THE CHILLERS MINIMUM
FLOW AND VERIFY THE PUMP SPEED DOES NOT DROP BELOW THIS SETTING.
• BMS SHALL MONITOR THE FLOW RATE MEASURED BY THE FLOW METER THROUGH THE CHILLER AND EVAPORATOR
MISCELLANEOUS:
• INSTALL FLOW METERS AS INDICATED ON PLANS.
• IN ADDITION TO BYPASS CONTROL VALVE CONTROL, FLOW METER SHALL BE USED TO MONITOR FLOW RATE, CALCULATE PEAK
OPERATING TONNAGE, AND TOTALIZE BUILDING TON-HOURS.
• MONITOR MAKEUP WATER CONSUMPTION TO COOLING TOWERS THROUGH WATER METER.
CHILLER
CHWS CHWS
CHWR
CWS
CWR CWR
CWS
T
FT
DP
T
T
VFD
VFD
CR
F
DP 9
GENERAL NOTES
1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER.
2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 36 INCHES.
3. WIRE ALL SENSORS AND CONTROL DEVICES BACK TO CONTROLLER.
4. ALL SENSORS SHALL BE INSTALLED IN TEES OR THREAD-O-LETS. P/T PLUGS ARE NOT ACCEPTABLE.
5. DIFFERENTIAL PRESSURE SENSOR SHALL BE LOCATED IN THE SUPPLY AND RETURN PIPING NEAR THE DEVICE WITH THE HIGHEST
PRESSURE DROP (VERIFY LOCATION WITH ENGINEER PRIOR TO INSTALLATION).
6. FLOW METER SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR. THIS FLOW METER IS SEPARATE FROM THE CHILLER
FLOW METER FURNISHED BY THE CHILLER MANUFACTURER AND WIRED TO THE CHILLER CONTROL PANEL.
7. CONTROLS CONTRACTOR SHALL INCLUDE BAS INTEGRATION OF CHILLER #2 INTO EXISTING BAS, UPDATING THE GRAPHICS AND TRAINING
OF MAINTENANCE STAFF.
CWP-2
CP-12
CH-2
REMARKS:
1. E = ELECTRIC P = PNEUMATIC BO = BY OTHERS S = REFERENCED POINT FROM HARDWIRE ELSEWHERE ON DDC NETWORK
2. A = ANALOG B = BINARY
3. I = INPUT O = OUTPUT
4. G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE
5. T = TRENDING EH = EVENT HISTORY AR = ARCHIVE TT = TOTALIZATION GP = GRAPHICAL POINT
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
Phase
STAMP
www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
11/11/2024
100% Construction Documents 11/11/2024
100%R Construction Documents 11/26/2024
/2
/2
:0
:2
P
M
A u to d e s k D o c s /2
.0
V
A L o v e ll R e p la c e C h ill e r
/ 5
-1
.B
.M E
.r v t
M501
CONTROL SCHEMATICS REPLACE CHILLER 2
NORTH CHICAGO, IL 60064 - 3048
556-24-106
B188
11/26/2024 AKE DAB
23022.010
100%R CONSTRUCTION
DOCUMENTS
DIRECT DIGITAL CONTROL POINTS LIST - CHILLED WATER LOOP CONTROL -
WATER-COOLED CHILLERS
POINT
ID POINT DESCRIPTION SOURCE (1) TYPE (2) I/O (3) UNITS
1 CHILLED WATER PUMP VFD STATUS E D I ENABLED / DISABLED
2 CHILLED WATER PUMP VFD START/STOP E D O -
3 CHILLED WATER PUMP VFD SPEED CONTROL E A O -
4 CHILLED WATER PUMP CURRENT STATUS SWITCH E D I ON / OFF
5 CHILLED WATER RETURN TEMPERATURE E A I DEGREES F
6 CHILLED WATER FLOW METER E A I GPM
7 CHILLED WATER SUPPLY TEMPERATURE E A I DEGREES F
8 DIFFERENTIAL PRESSURE SENSOR - CONDENSER BARREL E A I PSI
9 DIFFERENTIAL PRESSURE SENSOR - CHILLER BARREL E A I PSI
10 EVAPORATOR CONTROL VALVE E B O -
11 EVAPORATOR CONTROL VALVE E B O -
12 CHILLER START/STOP E D O -
13 CHILLER CONDENSER FLOW SWITCH O D I PASS / FAIL
14 CHILLER HEAD PRESSURE CONTROL O A I PSI
15 CHILLER EVAPORATOR FLOW SWITCH O D I PASS / FAIL
16 CHILLED WATER SUPPLY TEMPERATURE E A I DEGREES F
17 CHILLER STATUS E D I ON / OFF
18 CONDENSER CONTROL VALVE E A O -
19 CONDENSER RETURN TEMPERATURE E A I DEGREES F
20 CHILLED WATER CONDENSOR PUMP VFD STATUS E D I ENABLED / DISABLED
21 CHILLED WATER CONDENSOR PUMP VFD SPEED CONTROL E A O -
22 CONDENSER SUPPLY TEMPERATURE E B I DEGREES F
23 CONDENSER CONTROL VALVE E B O -
24 CONDENSER WATER SUPPLY BYPASS VALVE E B O -
25 CONDENSER WATER RETURN BYPASS VALVE E B O -
26 CHILLED WATER RETURN BYPASS VALVE E B O -
REMARKS:
1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE WITH THE FOLLOWING ACCESSORIES: DISCONNECT, SUCTION DIFFUSER, TRIPLE DUTY DISCHARGE VALVE
(CHECK, BALANCING, ISOLATION), FLEXIBLE CONNECTORS, FLANGES, AND TEMPERATURE AND PRESSURE GAUGES
ON EACH CONNECTION.
3. PROVIDE HOUSEKEEPING PAD AND INERTIA BASE.
4. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED
ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING
EQUIPMENT.
5. INTEGRATE VFD BACNET INTERFACE INTO BAS
ABBREVIATIONS: PT= PIPE AND TANK INSULATION, MF= MINERAL FIBER(FIBERGLASS),
CS= CALCIUM SILICATE, E= ELASTOMERIC.
NOTE:
(1) PLATE NUMBER REFERENCED ARE PROVIDED TO CLARIFY THE SCOPE OF
INSTALLATION. INSTALL INSULATION AND ACCESSORY COMPONENTS PER APPLICABLE
MICA AND MANUFACTURERS RECOMMENDATIONS.
ABBREVIATIONS: MF = MINERAL FIBER/FIBERGLASS, E = ELASTOMERIC, CG = CELLULAR GLASS
REMARKS:
1. PLATE NUMBER REFERENCED ARE PROVIDED TO CLARIFY THE SCOPE OF INSTALLATION. INSTALL
INSULATION AND ACCESSORY COMPONENTS PER APPLICABLE MICA AND MANUFACTURERS
RECOMMENDATIONS.
2. MICA REFERENCE PLATES FOR PIPING ARE 1-100 FOR FIBERGLASS AND CELLULAR GLASS PIPE
INSULATION, 1-200 FOR ELASTOMERIC AND 1-900 FIBERGLASS WITH HEAT TRACE.
3. INCLUDES AIR CONDITIONING CONDENSATE, P-TRAPS FOR FLOOR DRAINS/SINKS RECEIVING AIR
CONDITIONING CONDENSATE OR ICE MAKER DRAIN PIPING, AND SANITARY DRAINAGE PIPING
FROM ELECTRIC WATER COOLERS TO MAIN.
REMARKS:
1. IF NO CC IN CONTRACT, MC TO WIRE CONTROLS AND EC TO PIPE CONDUIT.
2. ALL LOW VOLTAGE WIRING OF PANELS TO BE COVERED IN MC BID, WIRING
CONTRACTOR TO BE SUBCONTRACTOR TO MC.
3. INSTALLING CONTRACTOR IS RESPONSIBLE FOR FIELD ALIGNMENT SERVICES WHEN
REQUIRED BY COMMON MOTOR REQUIREMENTS SPECIFICATION OR BY INDIVIDUAL
EQUIPMENT SPECIFICATIONS.
4. ALL HARDWARE, SOFTWARE, EQUIPMENT, ACCESSORIES, WIRING (POWER AND
SENSOR), PIPING, RELAYS, SENSORS, POWER SUPPLIES, TRANSFORMERS, AND
INSTRUMENTATION REQUIRED FOR A COMPLETE AND OPERATIONAL DDC SYSTEM,
BUT NOT SHOWN ON THE ELECTRICAL DRAWINGS, ARE THE RESPONSIBILITY OF THE
CC.
REMARKS:
1. CHILLER PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.
2. UTILIZE EXISTING STRUCTURAL CONCRETE PAD. ANCHOR CHILLER TO PAD.
3. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, INTEGRAL DISCONNECT, BACNET INTERFACE.
4. EQUIPMENT SHALL BE SEISMICALLY RATED. REFER TO SPECIFICATIONS
5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY
DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW
SCCR WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT.
6. EFFICIENCY SHALL COMPLY WITH FEMP EFFICIENCY REQUIREMENTS AT AHRI RATING CONDITIONS. UNIT EFFICIENCIES ARE
SCHEDULED AT AHRI CONDITIONS
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
A
B
C
D
E
F
A
B
C
D
E
F