S06 - Att 5 ECB BACnet Series B-ASC_PICS_15.pdf
PDF 315 KB Posted
- Attached to
- Z1DA--Replace Building Automation System (Metasys) 676-21-007 Federal contract opportunity
- Solicitation number
- 36C25224B0006
About this file
This document is a BACnet Protocol Implementation Conformance Statement (PICS) for Distech Controls' ECB-VAV Series, ECB-103, ECB-203 Series, and ECB-PTU Series of BACnet terminal application programmable controllers. The PICS outlines the BACnet device profiles, interoperability building blocks, object types, and data link layer options supported by these products. The controllers are designed for equipment such as VAV boxes, fan coil units, and heat pumps, and communicate using an MS/TP network. The document provides detailed technical specifications on the capabilities and features of these BACnet controllers.
This PICS is related to federal contract opportunity 36C25224B0006 to replace a Building Automation System (Metasys) for the Department of Veterans Affairs. The solicitation seeks products and services to upgrade the building control system, but the PICS document itself does not contain specifics on the requirements, response dates, pricing, or other procurement details for this particular contract opportunity.
View the file
Other files for this federal contract opportunity
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
Distech Controls Application Specific Controllers PICS
BACnet Protocol Implementation Conformance Statement
Date February 4th, 2021 Vendor Name Distech Controls Inc.
Product Name ECB-VAV Series, ECB-103, ECB-203
Series ECB-PTU Series
Product Model Number
ECB-VAVS-O, ECB-VAVS, ECB-VAV,
ECB-VVTS, ECB-VAV-N, ECB-103,
ECB-203, ECB-253
ECB-PTU-107, ECB-PTU-207,
ECB-PTU-208, ECB-PTU-307, &
ECB-PTU-308
Application Software Version
B:2.2.12041.1 A:2.17.20287.2
B:2.2.12041.1 A:2.7.20287.2
Firmware Revision 1.3.19222.1 1.3.19222.1 BACnet Protocol Revision
Version 1, Revision 15 Version 1, Revision 15
Product Description:
The ECB-VAVS Series, ECB-103, ECB-203 Series, and ECB-PTU Series are BACnet terminal application programmable controllers that communicate using MS/TP network and are designed to control equipment such as variable air volume box, fan coil units, roof top units, heat pump unit, chilled ceiling, unit ventilator, etc.
BACnet Standardized Device Profile (Annex L):
BACnet Advanced Workstation (B-AWS) BACnet Operator Workstation (B-OWS) BACnet Operator Display (B-OD) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA)
Additional BACnet Interoperability Building Blocks Supported (Annex K):
Required for B-ASC Profile:
Application Service BIBBS
Data Sharing - Read Property - Execute DS-RP-B Data Sharing - Write Property - Execute DC-WP-B Device Management - Dynamic Device Binding - Execute DM-DDB-B Device Management - Dynamic Object Binding - Execute DM-DOB-B Device Management - Device Communication Control - Execute DM-DCC-B
Not Required for B-ASC Profile:
Application Service BIBBS
Data Sharing - Read Property - Initiate DS-RP-A Data Sharing - Read Property Multiple - Initiate DS-RPM-A Data Sharing - Read Property Multiple - Execute DS-RPM-B Data Sharing - Write Property - Initiate DC-WP-A Data Sharing - Write Property Multiple - Initiate DS-WPM-A Data Sharing - Write Property Multiple - Execute DS-WPM-B Data Sharing - COV - Initiate DS-COV-A Data Sharing - COV - Execute DS-COV-B Data Sharing - COV Unsolicited - Initiate DS-COVU-A Data Sharing - COV Unsolicited - Execute DS-COVU-B Device Management - Dynamic Device Binding - Initiate DM-DDB-A Device Management - Reinitialize Device - Execute DM-RD-B Device Management - Time Synchronization - Execute DM-TS-B Device Management - UTC Time Synchronization - Execute DM-UTC-B Scheduling - Internal- Execute SCHED-I-B
2 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
File Access – Atomic Read File N/A File Access – Atomic Write File N/A Remote Device Management – Confirmed Private Transfer N/A Remote Device Management – Unconfirmed Private Transfer N/A
Standard Object Types Supported The following is a list of the standard object types as define by the standard. The objects checked are currently supported by this product. See the section in this document for the supported object type for details.
Accumulator Analog Input Analog Output Analog Value Averaging Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Life Safety Point Life Safety Zone Loop Multistate Input Multistate Output Multistate Value Notification Class Program Pulse Converter Schedule Trend Log
BACnet Analog Input (AI) Object Type Dynamically Creatable Dynamically Deletable
Property Name
M a n d a to ry
O p ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value R 85
Status_Flags R 111
Event_State R 36
Reliability R 103
Out_Of_Service RW 81
Units R 117
COV_Increment RW 22
COV_Period RW 1004
COV_Min_Send_Time RW 1000
3 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
M a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Property_List R 371
BACnet Analog Output (AO) Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value RW 85
Status_Flags R 111
Event_State R 36
Out_Of_Service RW 81
Units R 117
Min_Present_Value R 69
Max_Present_Value R 65
Priority_Array R 87
Relinquish_Default RW 104
COV_Increment RW 22
COV_Period RW 1004
BACnet Analog Value (AV) Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value RW 85
Status_Flags R 111
Event_State R 36
Out_Of_Service RW 81
4 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
M a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Units R 117
Priority_Array R 87
Relinquish_Default RW 104
COV_Increment RW 22
COV_Period RW 1004
BACnet Binary Input (BI) Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value R 85
Status_Flags R 111
Event_State R 36
Reliability R 103
Out_Of_Service RW 81
Polarity R 84
Inactive_Text 46
Active_Text 4
COV_Period RW 1004
BACnet Binary Output (BO) Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
5 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
M a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Present_Value RW 85
Status_Flags R 111
Event_State R 36
Out_Of_Service RW 81
Polarity R 84
Inactive_Text 46
Active_Text 4
Priority_Array R 87
Relinquish_Default RW 104
COV_Period RW 1004
BACnet Binary Value (BV) Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value RW 85
Status_Flags R 111
Event_State R 36
Out_Of_Service RW 81
Inactive_Text 46
Active_Text 4
Priority_Array R 87
Relinquish_Default RW 104
COV_Period RW 1004
6 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
BACnet Calendar Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value R 85
Date_List RW 23
Time_To_Next_State R 1001
Next_State R 1002
Device Object a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier RW 75
Object_Name RW 77
Object_Type R 79
System_Status R 112
Vendor_Name R 121
Vendor_Identifier R 120
Model_Name R 70
Firmware_Revision R 44
Application_Software_Version R 12
Location RW 58
Protocol_Version R 98
Protocol_Revision R 139
Protocol_Services_Supported R 97
Protocol_Object_Types_Supported R 96
Object_List R 76
Max_APDU_Length_Accepted R 62
Segmentation_Supported R 107
Local_Date R 56
Local_Time R 57
7 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
M a n d a ti o n a l
P ro p ri e ta ry RW ID Range
UTC_Offset RW 119
Daylight_Savings_Status R 24
APDU_Timeout RW 10
Number_Of_APDU_Retries RW 73
Max_Master RW 64
Max_Info_Frames RW 63
Device_Address_Binding R 30
Database_Revision R 155
Active_COV_Subscriptions R 152
BACnet File Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
File_Type R 43
File_Size R 42
Modification_Date R 71
Archive RW 13
Read_Only R 99
File_Access_Method R 41
BACnet Loop Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Type R 79
8 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
M a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Present_Value R 85
Status_Flags R 111
Event_State R 36
Reliability R 103
Out_Of_Service RW 81
Output_Units R 82
Manipulated_Variable_Reference R 60
Controlled_Variable_Reference R 19
Controlled_Variable_Value R 21
Controlled_Variable_Units R 20
Setpoint_Reference R 109
Setpoint R 108
Action RW 2
Proportional_Constant RW 93
Proportional_Constant_Units R 94
Integral_Constant RW 49
Integral_Constant_Units R 50
Derivative_Constant RW 26
Derivative_Constant_Units R 27
Bias RW 14
Priority_For_Writing R 88
LoopDeadband RW 1011
Saturation_Time RW 1003
COV_Increment RW 22
COV_Period RW 1004
COV_Min_Send_Time RW 1000
Ramp_Time RW 1005
Saturation_Time_Low_Limit_Enable RW 1006
Saturation_Time_High_Limit_Enable RW 1007
BACnet Multi-state Input (MSI) Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
9 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
M a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Type R 79
Present_Value R 85
Status_Flags R 111
Event_State R 36
Reliability R 103
Out_Of_Service RW 81
Number_of_States R 74
State_Text R 110
COV_Period RW 1004
BACnet Multi-state Value (MSV) Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value RW 85
Status_Flags R 111
Event_State R 36
Reliability R 103
Out_Of_Service RW 81
Number_of_States R 74
State_Text R 110
Priority_Array R 87
Relinquish_Default RW 104
COV_Period RW 1004
10 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
BACnet Program Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Program_State R 92
Program_Change RW 90
Description_Of_Halt R 29
Reason_For_Halt R 100
Status_Flags R 111
Reliability R 103
Out_Of_Service R 81
BACnet Schedule Object Type a n d a ti o n a l
P ro p ri e ta ry RW ID Range
Object_Identifier R 75
Object_Name RW 77
Object_Type R 79
Present_Value R 92
Effective_Period RW 32
Weekly_Schedule RW 123
Exception_Schedule RW 38
Schedule_Default RW 174
List_Of_Object_Property_References R 54
Priority_For_Writing W 88
Status_Flags R 111
Reliability R 103
Out_Of_Service RW 81
Time_To_Next_State R 1001
Next_State R 1002
11 of 11 Distech Controls Application Specific Controllers PICS 2021/02/04
Segmentation Capability:
Segmented Request supported Window size: N/A Segmented Response supported Window size: N/A
Data Link Layer Options:
BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________ MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800 MS/TP slave (Clause 9), baud rate(s):
Point-To-Point, EIA 232 (Clause 10), baud rate(s):
Point-To-Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause 11), medium: __________ Other:
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)
Yes No
Networking Options:
Router, Clause 6 - Routing configurations: Ethernet-IP, Ethernet-MS/TP, IP-MS/TP Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices?
Yes No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI X3.4 IBM/Microsoft DBCS ISO 8859-1
ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:
Not applicable
File details come from the government source that posted it. Updated .