This document is a BACnet Protocol Implementation Conformance Statement (PICS) for the Distech Controls EC-Net 4 product. The PICS describes the BACnet device profile, interoperability building blocks, object types, and data link layer options supported by the EC-Net 4 product. It indicates that the product supports BACnet IP, Ethernet, MS/TP, and various other networking options. The EC-Net 4 product is described as providing the ability to view, monitor, and control BACnet devices. This PICS is relevant to the federal contract opportunity for replacing a Building Automation System (Metasys) at a Department of Veterans Affairs facility.
View the file
Other files for this federal contract opportunity
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EC-Net 4 - BACnet PICS
1 of 11 Distech Controls EC-Net 4 BACnet PICS
BACnet Protocol Implementation Conformance Statement
Date: May 31, 2021 Vendor Name: Distech Controls Inc.
Product Name: EC-BOS-8 Product Model Number: EC-BOS-8 Application Software Version: 4.10.1.18 Firmware Revision: 4.10.1.18 BACnet Protocol Revision: 14
Product Description:
EC-Net 4 provides the ability to view, monitor, and control BACnet devices over IP, raw Ethernet, or MS/TP media. Devices, points, schedules, alarms, and logs can be learned and managed from EC-Net 4.
EC-Net points, schedules, histories, and alarming can be exposed to BACnet for monitor and control by foreign BACnet clients. In addition, BACnet objects like trendlog, schedule, calendar and event enrollment can be dynamically created, deleted and modified in EC-Net by foreign BACnet clients.
BACnet Standardized Device Profile (Annex L):
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Workstation (B-OWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
Additional BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing Device & Network Management
DS-RP-A, B DM-DDB-A, B
DS-RPM-A, B DM-DOB-A, B
DS-WP-A, B DM-ADM-A
DS-WPM-A, B DM-ANM-A
DS-COV-A, B DM-TS-A, B
DS-COVP-B DM-UTC-A, B
DS-V-A DM-ATS-A
DS-M-A DM-MTS-A
DM-DCC-B
DM-RD-B
DM-BR-B
DM-OCD-B
DM-LM-A, B
2 of 11 Distech Controls EC-Net 4 BACnet PICS
Alarm & Event Management Trending
AE-N-A T-V-A
AE-N-I-B T-VMT-I-B
AE-N-E-B T-VMT-E-B
AE-ACK-A, B T-ATR-A, B
AE-ASUM-B
AE-ESUM-B
AE-INFO-B
AE-VN-A
AE-VM-A
Scheduling Network Management
SCHED-VM-A NM-RC-B
SCHED-I-B
SCHED-E-B
Gateway
GW-EO-B
Segmentation Capability:
Feature Supported Window size
Transmit Segmented Messages yes 10
Receive Segmented Messages yes any
Standard Object Types Supported:
• Calendar, Event-Enrollment, Notification-Class, Schedule, and Trend-Log Object types can be dynamically created and deleted
• No general range restrictions exist; however, certain specific applications may have specific range restrictions.
• All potentially available properties are listed for each object type.
• Optional properties are listed in italics. Not all instances support all optional properties.
• Writable properties are listed in bold. Any range limitations are expressed in parentheses following the property name.
3 of 11 Distech Controls EC-Net 4 BACnet PICS
Object Type Properties
Analog Input
Object_Identifier
Object_Name
Object_Type
Present_Value Description Device_Type
Status_Flags
Event_State
Reliability Out_Of_Service Update_Interval
Units
Min_Pres_Value
Max_Pres_Value
Resolution COV_Increment Time_Delay (O)
Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)
Limit_Enable (O) Event_Enable (O)
Acked_Transitions (O) Notify_Type (O)
Event_Time_Stamps (O) Event-message-texts(O)
Event-Detection-Enable (O)
Property List
Analog Output
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Units
Min_Pres_Value
Max_Pres_Value
Resolution
Priority_Array
Relinquish_Default
COV_Increment
Time_Delay (O)
Notification_Class (O)
High_Limit (O)
Low_Limit (O)
Deadband (O)
Limit_Enable (O)
Event_Enable (O)
Acked_Transitions (O)
Notify_Type (O)
Event_Time_Stamps (O)
Event-message-texts(O)
4 of 11 Distech Controls EC-Net 4 BACnet PICS
Analog Value
Object_Identifier
Object_Name Object_Type
Present_Value Description Status_Flags Event_State
Reliability Out_Of_Service
Units Priority_Array
Relinquish_Default
Min_Pres_Value Max_Pres_Value
Resolution
COV_Increment (O) Time_Delay (O)
Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)
Limit_Enable (O) Event_Enable (O)
Acked_Transitions (O) Notify_Type (O)
Event_Time_Stamps (O) Event-message-texts(O)
Binary Input
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Polarity
Inactive_Text
Active_Text
Change_Of_State_Time (O)
Change_Of_State_Count (0)
Time_Of_State_Count_Reset (O)
Elapsed_Active_Time (0)
Time_Of_Active_Time_Reset (O)
Time_Delay (O)
Notification_Class (O)
Alarm_Value (O)
Event_Enable (O)
Acked_Transitions (O)
Notify_Type (O)
Event_Time_Stamps (O)
Event-message-texts(O)
5 of 11 Distech Controls EC-Net 4 BACnet PICS
Binary Output
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Polarity
Inactive_Text
Active_Text
Change_Of_State_Time (O)
Change_Of_State_Count
(0)
Time_Of_State_Count_Reset (O)
Elapsed_Active_Time (0)
Time_Of_Active_Time_Reset (O)
Minimum_Off_Time
Minimum_On_Time
Priority_Array
Relinquish_Default
Time_Delay (O)
Notification_Class (O)
Feedback_Value (O)
Event_Enable (O)
Acked_Transitions (O)
Notify_Type (O)
Event_Time_Stamps (O)
Event-message-texts(O)
Binary Value
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Status_Flags
Event_State
Reliability
Out_Of_Service
Inactive_Text
Active_Text
Change_Of_State_Time (O)
Change_Of_State_Count (0)
Time_Of_State_Count_Reset (O)
Elapsed_Active_Time (0)
Time_Of_Active_Time_Reset (O)
Minimum_Off_Time
Minimum_On_Time
Priority_Array
Relinquish_Default
Time_Delay (O)
Notification_Class (O)
Alarm_Value (O)
Event_Enable (O)
Acked_Transitions (O)
Notify_Type (O)
Event_Time_Stamps (O)
Event-message-texts(O)
Event-Detection-Enable (O)
Property List
Calendar Object_Identifier Object_Name Object_Type
Description Present_Value
Date_List
6 of 11 Distech Controls EC-Net 4 BACnet PICS
Device
Object_Identifier
Object_Name
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_Revision
Location
Description
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported
Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
Max_Segments_Accepted
Local_Time
Local_Date
UTC_Offset
Daylight_Savings_Status
APDU_Segment_Timeout
APDU_Timeout
Number_Of_APDU_Retries
Time Synchronization Recipients
Max_Master
Max_Info_Frames
Device_Address_Binding
Database_Revision
Configuration_Files
Last_Restore_Time
Backup_Failure_Timeout
Backup Preparation Time
Restore Preparation Time
Restore Completion Time
Backup and Restore State
Active_COV_Subsriptions
Last Restart Reason
Time of Device Restart
Restart Notification Recipients
UTC Time Synchronization
Recipients
Time Synchronization Interval
Align Interval
Interval Offset
Serial Number
Property List
File (Stream Access Only)
Object_Identifier Object_Name Object_Type Description
File_Type
File_Size Modification_Date
Archive Read_Only
File_Access_Method
7 of 11 Distech Controls EC-Net 4 BACnet PICS
Event Enrollment
Object_Identifier Object_Name Object_Type Description Event-Type Notify-Type
Event-Parameters
Status_Flags
Reliability
Object-Property-reference
Event-State
Event-Enable Acked_Transitions (O)
Notification-Class Event_Time_Stamps (O) Event-message-texts(O)
Event-Detection-Enable(O)
Property List
Loop
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Status_Flags
Event_State
Reliability
Out_Of_Service
Update_interval
Output_Units
Manipulated_Variable_Reference
Controlled_Variable_Reference
Controlled_Variable_Value
Controlled_Variable_Units
Setpoint_Reference
Setpoint
Action
Proportional_Constant
Proportional_Constant_Units
Integral_Constant
Integral_Constant_Units
Derivative_Constant
Derivative_Constant_Units
Bias
Maximum_Output
Minimum_Output
Priority_For_Writing
COV_Increment
Time_Delay
Notification_Class
Error_Limit
Deadband
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Event Message Texts
Event Detection Enable
Property List
Multi-state Input
Object_Identifier
Object_Name Object_Type
Present_Value
Description
Device_Type
Status_Flags Event_State
Reliability
Out_Of_Service
Number_Of_States State_Text
Time_Delay (O Notification_Class (O)
Alarm_Values (O) Fault_Values (O) Event_Enable (O)
Acked_Transitions (O) Notify_Type (O)
Event_Time_Stamps (O) Event Message Texts
Event Detection Enable
8 of 11 Distech Controls EC-Net 4 BACnet PICS
Multi-state Output
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Number_Of_States
State_Text
Priority_Array
Relinquish_Default
Time_Delay (O)
Notification_Class (O)
Feedback_Value (O)
Event_Enable (O)
Acked_Transitions (O)
Notify_Type (O)
Event_Time_Stamps (O)
Event Message Texts
Event Detection Enable
Property List
Multi-state Value
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Status_Flags
Event_State
Reliability
Out_Of_Service
Number_Of_States
State_Text
Priority_Array
Relinquish_Default
Time_Delay (O)
Notification_Class (O)
Alarm_Values (O)
Fault_Values (O)
Event_Enable (O)
Acked_Transitions (O)
Notify_Type (O)
Event_Time_Stamps (O)
Event Message Texts
Event Detection Enable
Property List
Notification Class
Object_Identifier Object_Name Object_Type Description
Notification_Class
Priority
Ack_Required
Recipient_List
Property List
Schedule
Object_Identifier
Object_Name
Object_Type
Description
Present Value
Effective_Period
Weekly_Schedule
Exception_Schedule
Schedule_Default List_Of_Object_Property_References
Priority_For_Writing Status_Flags
Reliability Out_Of_Service
9 of 11 Distech Controls EC-Net 4 BACnet PICS
Trend Log
Object_Identifier
Object_Name Object_Type Description
Enable Start_Time
Stop_Time Log_DeviceObjectProperty
Log_Interval COV_Resubscription_Interval
Client_COV_Increment
Stop_When_Full
Buffer_Size
Log_Buffer Record_Count
Total_Record_Count Logging Type
Trigger Status Flags Notification_Threshold
Records_Since_Notification Last_Notify_Record Event_State
Notification_Class Event_Enable Acked_Transitions Notify_Type
Event_Time_Stamps
Event Message Texts
Event Detection Enable
Property List
Large Analog Value
Object_Identifier
Object_Name Object_Type
Present_Value
Description
Status_Flags Event_State
Reliability Out_Of_Service
Units
Priority_Array Relinquish_Default
Min_Pres_Value Max_Pres_Value
Resolution
COV_Increment (O) Time_Delay (O)
Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)
Limit_Enable (O) Event_Enable (O)
Acked_Transitions (O) Notify_Type (O)
Event_Time_Stamps (O) Event-message-texts(O)
Integer Value
Object_Identifier Object_Name Object_Type
Present_Value Description Status_Flags Event_State
Reliability Out_Of_Service
Units Priority_Array
Relinquish_Default Min_Pres_Value Max_Pres_Value
Resolution
COV_Increment (O) Time_Delay (O)
Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)
Limit_Enable (O) Event_Enable (O)
Acked_Transitions (O) Notify_Type (O)
Event_Time_Stamps (O) Event-message-texts (O)
10 of 11 Distech Controls EC-Net 4 BACnet PICS
Positive Integer Value
Object_Identifier Object_Name Object_Type
Present_Value Description Status_Flags Event_State
Reliability Out_Of_Service
Units Priority_Array
Relinquish_Defa ult
Min_Pres_Value
Max_Pres_Value
Resolution
COV_Increment (O) Time_Delay (O)
Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)
Limit_Enable (O) Event_Enable (O)
Acked_Transitions (O) Notify_Type (O)
Event_Time_Stamps (O) Event-message-texts(O)
Event-Detection-Enable (O)
Property List
Character string Value
Object_Identifier Object_Name Object_Type
Present_Value Description Status_Flags Event_State
Reliability Out_Of_Service
Units Priority_Array
Relinquish_Default
Structured-View
Object_Identifier Object_Name Object_Type Description Node-type
Node-Subtype Subordinate-List
Subordinate-annotations
Property-List
Information and/or specifications published here are current as of the date of publication of this document. Distech Controls, Inc.
reserves the right to change or modify specifications without prior notice. The latest product specifications can be found by contacting our corporate headquarters, Brossard, Quebec. Products or features contained herein are covered by one or more U.S. or foreign patents. This document may be copied by parties who are authorized to distribute Distech Controls products in connection with distribution of those products, subject to the contracts that authorize such distribution. It may not otherwise, in whole or in part, be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form without prior written consent from Distech Controls, Inc. Distech Controls and the Distech Controls logo are trademarks of Distech Controls, Inc. ©, Distech Controls Inc., 2022. All rights reserved.
11 of 11 Distech Controls EC-Net 4 BACnet PICS
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800, 115200
MS/TP slave (Clause 9), baud rate(s):
Point-To-Point, EIA 232 (Clause 10), baud rate(s):
Point-To-Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause 11), medium:
Other:
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No
Networking Options:
Router, Clause 6 – Routing configurations: Ethernet-IP, Ethernet-MS/TP, IP-MS/TP
Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Yes No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ISO 10646 (UTF-8) IBM™/Microsoft™ DBCS ISO 8859-1
ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:
This product supports communications between BACnet and any third-party system to which EC-Net can connect. Contact Distech Controls for a list of supported protocols.
File details come from the government source that posted it. Updated .