S06 - Att 4 EC-Net B-BC_PICS.pdf

PDF 170 KB Posted

Attached to
Z1DA--Replace Building Automation System (Metasys) 676-21-007 Federal contract opportunity
Solicitation number
36C25224B0006
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12

About this file

This document is a BACnet Protocol Implementation Conformance Statement (PICS) for the Distech Controls EC-Net 4 product. The PICS describes the BACnet device profile, interoperability building blocks, object types, and data link layer options supported by the EC-Net 4 product. It indicates that the product supports BACnet IP, Ethernet, MS/TP, and various other networking options. The EC-Net 4 product is described as providing the ability to view, monitor, and control BACnet devices. This PICS is relevant to the federal contract opportunity for replacing a Building Automation System (Metasys) at a Department of Veterans Affairs facility.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Replace Building Automation System (Metasys) 676-21-007, newest first.
File Type Posted
36C25224B0006 0005.docx DOCX document
S06 - Att 1 Wage Determination Update WI20240011 20240705.pdf PDF
36C25224B0006 0004.docx DOCX document
S06 - Att 1 Pre-Bid RFIs 20240703.pdf PDF
S06 - Att 3 Wage Determination Update WI20240011 20240628.pdf PDF
36C25224B0006 0003.docx DOCX document
S06 - Att 2 Pre-Bid RFIs 20240628.pdf PDF
S06 - Att 1 Pre-Bid Visit Sign In 20240612.pdf PDF
S06 - Att 2 Pre-Bid RFIs 20240530.pdf PDF
S06 - Att 1 Wage Determination Update WI20240011 20240524.pdf PDF
S06 - Att 6 140sp3106.pdf PDF
S06 - Att 5 ECB BACnet Series B-ASC_PICS_15.pdf PDF
S06 - Att 8 Replace BAS BID Specifications_REVISED 20240202.pdf PDF
S06 - Att 3 ECB BACnet Series B-AAC_PICS_15.pdf PDF
36C25224B0006 0002.docx DOCX document
S06 - Att 7 ACM Spreadsheet Inventory.pdf PDF
S06 - Preproposal Visit Sign-in.pdf PDF
36C25224B0006 0001-1.docx DOCX document
36C25224B0006 0001.docx DOCX document
S02 - Att 1 BAS BID Project Manual 676-21-007.pdf PDF
S02 - Att 4 Wage Det WI20240011 MOD4 15Mar24.pdf PDF
S02 - Att 3 BAS Drawings 2 of 2 676-21-007.pdf PDF
S02 - Att 2 BAS Drawings 1 of 2 676-21-007.pdf PDF
36C25224B0006_1.docx DOCX document
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EC-Net 4 - BACnet PICS

1 of 11 Distech Controls EC-Net 4 BACnet PICS

BACnet Protocol Implementation Conformance Statement

Date: May 31, 2021 Vendor Name: Distech Controls Inc.

Product Name: EC-BOS-8 Product Model Number: EC-BOS-8 Application Software Version: 4.10.1.18 Firmware Revision: 4.10.1.18 BACnet Protocol Revision: 14

Product Description:

EC-Net 4 provides the ability to view, monitor, and control BACnet devices over IP, raw Ethernet, or MS/TP media. Devices, points, schedules, alarms, and logs can be learned and managed from EC-Net 4.

EC-Net points, schedules, histories, and alarming can be exposed to BACnet for monitor and control by foreign BACnet clients. In addition, BACnet objects like trendlog, schedule, calendar and event enrollment can be dynamically created, deleted and modified in EC-Net by foreign BACnet clients.

BACnet Standardized Device Profile (Annex L):

BACnet Advanced Operator Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Additional BACnet Interoperability Building Blocks Supported (Annex K):

Data Sharing Device & Network Management

DS-RP-A, B DM-DDB-A, B

DS-RPM-A, B DM-DOB-A, B

DS-WP-A, B DM-ADM-A

DS-WPM-A, B DM-ANM-A

DS-COV-A, B DM-TS-A, B

DS-COVP-B DM-UTC-A, B

DS-V-A DM-ATS-A

DS-M-A DM-MTS-A

DM-DCC-B

DM-RD-B

DM-BR-B

DM-OCD-B

DM-LM-A, B

2 of 11 Distech Controls EC-Net 4 BACnet PICS

Alarm & Event Management Trending

AE-N-A T-V-A

AE-N-I-B T-VMT-I-B

AE-N-E-B T-VMT-E-B

AE-ACK-A, B T-ATR-A, B

AE-ASUM-B

AE-ESUM-B

AE-INFO-B

AE-VN-A

AE-VM-A

Scheduling Network Management

SCHED-VM-A NM-RC-B

SCHED-I-B

SCHED-E-B

Gateway

GW-EO-B

Segmentation Capability:

Feature Supported Window size

Transmit Segmented Messages yes 10

Receive Segmented Messages yes any

Standard Object Types Supported:

• Calendar, Event-Enrollment, Notification-Class, Schedule, and Trend-Log Object types can be dynamically created and deleted

• No general range restrictions exist; however, certain specific applications may have specific range restrictions.

• All potentially available properties are listed for each object type.

• Optional properties are listed in italics. Not all instances support all optional properties.

• Writable properties are listed in bold. Any range limitations are expressed in parentheses following the property name.

3 of 11 Distech Controls EC-Net 4 BACnet PICS

Object Type Properties

Analog Input

Object_Identifier

Object_Name

Object_Type

Present_Value Description Device_Type

Status_Flags

Event_State

Reliability Out_Of_Service Update_Interval

Units

Min_Pres_Value

Max_Pres_Value

Resolution COV_Increment Time_Delay (O)

Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)

Limit_Enable (O) Event_Enable (O)

Acked_Transitions (O) Notify_Type (O)

Event_Time_Stamps (O) Event-message-texts(O)

Event-Detection-Enable (O)

Property List

Analog Output

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Device_Type

Status_Flags

Event_State

Reliability

Out_Of_Service

Units

Min_Pres_Value

Max_Pres_Value

Resolution

Priority_Array

Relinquish_Default

COV_Increment

Time_Delay (O)

Notification_Class (O)

High_Limit (O)

Low_Limit (O)

Deadband (O)

Limit_Enable (O)

Event_Enable (O)

Acked_Transitions (O)

Notify_Type (O)

Event_Time_Stamps (O)

Event-message-texts(O)

4 of 11 Distech Controls EC-Net 4 BACnet PICS

Analog Value

Object_Identifier

Object_Name Object_Type

Present_Value Description Status_Flags Event_State

Reliability Out_Of_Service

Units Priority_Array

Relinquish_Default

Min_Pres_Value Max_Pres_Value

Resolution

COV_Increment (O) Time_Delay (O)

Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)

Limit_Enable (O) Event_Enable (O)

Acked_Transitions (O) Notify_Type (O)

Event_Time_Stamps (O) Event-message-texts(O)

Binary Input

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Device_Type

Status_Flags

Event_State

Reliability

Out_Of_Service

Polarity

Inactive_Text

Active_Text

Change_Of_State_Time (O)

Change_Of_State_Count (0)

Time_Of_State_Count_Reset (O)

Elapsed_Active_Time (0)

Time_Of_Active_Time_Reset (O)

Time_Delay (O)

Notification_Class (O)

Alarm_Value (O)

Event_Enable (O)

Acked_Transitions (O)

Notify_Type (O)

Event_Time_Stamps (O)

Event-message-texts(O)

5 of 11 Distech Controls EC-Net 4 BACnet PICS

Binary Output

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Device_Type

Status_Flags

Event_State

Reliability

Out_Of_Service

Polarity

Inactive_Text

Active_Text

Change_Of_State_Time (O)

Change_Of_State_Count

(0)

Time_Of_State_Count_Reset (O)

Elapsed_Active_Time (0)

Time_Of_Active_Time_Reset (O)

Minimum_Off_Time

Minimum_On_Time

Priority_Array

Relinquish_Default

Time_Delay (O)

Notification_Class (O)

Feedback_Value (O)

Event_Enable (O)

Acked_Transitions (O)

Notify_Type (O)

Event_Time_Stamps (O)

Event-message-texts(O)

Binary Value

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Status_Flags

Event_State

Reliability

Out_Of_Service

Inactive_Text

Active_Text

Change_Of_State_Time (O)

Change_Of_State_Count (0)

Time_Of_State_Count_Reset (O)

Elapsed_Active_Time (0)

Time_Of_Active_Time_Reset (O)

Minimum_Off_Time

Minimum_On_Time

Priority_Array

Relinquish_Default

Time_Delay (O)

Notification_Class (O)

Alarm_Value (O)

Event_Enable (O)

Acked_Transitions (O)

Notify_Type (O)

Event_Time_Stamps (O)

Event-message-texts(O)

Event-Detection-Enable (O)

Property List

Calendar Object_Identifier Object_Name Object_Type

Description Present_Value

Date_List

6 of 11 Distech Controls EC-Net 4 BACnet PICS

Device

Object_Identifier

Object_Name

Object_Type

System_Status

Vendor_Name

Vendor_Identifier

Model_Name

Firmware_Revision

Application_Software_Revision

Location

Description

Protocol_Version

Protocol_Revision

Protocol_Services_Supported

Protocol_Object_Types_Supported

Object_List

Max_APDU_Length_Accepted

Segmentation_Supported

Max_Segments_Accepted

Local_Time

Local_Date

UTC_Offset

Daylight_Savings_Status

APDU_Segment_Timeout

APDU_Timeout

Number_Of_APDU_Retries

Time Synchronization Recipients

Max_Master

Max_Info_Frames

Device_Address_Binding

Database_Revision

Configuration_Files

Last_Restore_Time

Backup_Failure_Timeout

Backup Preparation Time

Restore Preparation Time

Restore Completion Time

Backup and Restore State

Active_COV_Subsriptions

Last Restart Reason

Time of Device Restart

Restart Notification Recipients

UTC Time Synchronization

Recipients

Time Synchronization Interval

Align Interval

Interval Offset

Serial Number

Property List

File (Stream Access Only)

Object_Identifier Object_Name Object_Type Description

File_Type

File_Size Modification_Date

Archive Read_Only

File_Access_Method

7 of 11 Distech Controls EC-Net 4 BACnet PICS

Event Enrollment

Object_Identifier Object_Name Object_Type Description Event-Type Notify-Type

Event-Parameters

Status_Flags

Reliability

Object-Property-reference

Event-State

Event-Enable Acked_Transitions (O)

Notification-Class Event_Time_Stamps (O) Event-message-texts(O)

Event-Detection-Enable(O)

Property List

Loop

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Status_Flags

Event_State

Reliability

Out_Of_Service

Update_interval

Output_Units

Manipulated_Variable_Reference

Controlled_Variable_Reference

Controlled_Variable_Value

Controlled_Variable_Units

Setpoint_Reference

Setpoint

Action

Proportional_Constant

Proportional_Constant_Units

Integral_Constant

Integral_Constant_Units

Derivative_Constant

Derivative_Constant_Units

Bias

Maximum_Output

Minimum_Output

Priority_For_Writing

COV_Increment

Time_Delay

Notification_Class

Error_Limit

Deadband

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Event Message Texts

Event Detection Enable

Property List

Multi-state Input

Object_Identifier

Object_Name Object_Type

Present_Value

Description

Device_Type

Status_Flags Event_State

Reliability

Out_Of_Service

Number_Of_States State_Text

Time_Delay (O Notification_Class (O)

Alarm_Values (O) Fault_Values (O) Event_Enable (O)

Acked_Transitions (O) Notify_Type (O)

Event_Time_Stamps (O) Event Message Texts

Event Detection Enable

8 of 11 Distech Controls EC-Net 4 BACnet PICS

Multi-state Output

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Device_Type

Status_Flags

Event_State

Reliability

Out_Of_Service

Number_Of_States

State_Text

Priority_Array

Relinquish_Default

Time_Delay (O)

Notification_Class (O)

Feedback_Value (O)

Event_Enable (O)

Acked_Transitions (O)

Notify_Type (O)

Event_Time_Stamps (O)

Event Message Texts

Event Detection Enable

Property List

Multi-state Value

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Status_Flags

Event_State

Reliability

Out_Of_Service

Number_Of_States

State_Text

Priority_Array

Relinquish_Default

Time_Delay (O)

Notification_Class (O)

Alarm_Values (O)

Fault_Values (O)

Event_Enable (O)

Acked_Transitions (O)

Notify_Type (O)

Event_Time_Stamps (O)

Event Message Texts

Event Detection Enable

Property List

Notification Class

Object_Identifier Object_Name Object_Type Description

Notification_Class

Priority

Ack_Required

Recipient_List

Property List

Schedule

Object_Identifier

Object_Name

Object_Type

Description

Present Value

Effective_Period

Weekly_Schedule

Exception_Schedule

Schedule_Default List_Of_Object_Property_References

Priority_For_Writing Status_Flags

Reliability Out_Of_Service

9 of 11 Distech Controls EC-Net 4 BACnet PICS

Trend Log

Object_Identifier

Object_Name Object_Type Description

Enable Start_Time

Stop_Time Log_DeviceObjectProperty

Log_Interval COV_Resubscription_Interval

Client_COV_Increment

Stop_When_Full

Buffer_Size

Log_Buffer Record_Count

Total_Record_Count Logging Type

Trigger Status Flags Notification_Threshold

Records_Since_Notification Last_Notify_Record Event_State

Notification_Class Event_Enable Acked_Transitions Notify_Type

Event_Time_Stamps

Event Message Texts

Event Detection Enable

Property List

Large Analog Value

Object_Identifier

Object_Name Object_Type

Present_Value

Description

Status_Flags Event_State

Reliability Out_Of_Service

Units

Priority_Array Relinquish_Default

Min_Pres_Value Max_Pres_Value

Resolution

COV_Increment (O) Time_Delay (O)

Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)

Limit_Enable (O) Event_Enable (O)

Acked_Transitions (O) Notify_Type (O)

Event_Time_Stamps (O) Event-message-texts(O)

Integer Value

Object_Identifier Object_Name Object_Type

Present_Value Description Status_Flags Event_State

Reliability Out_Of_Service

Units Priority_Array

Relinquish_Default Min_Pres_Value Max_Pres_Value

Resolution

COV_Increment (O) Time_Delay (O)

Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)

Limit_Enable (O) Event_Enable (O)

Acked_Transitions (O) Notify_Type (O)

Event_Time_Stamps (O) Event-message-texts (O)

10 of 11 Distech Controls EC-Net 4 BACnet PICS

Positive Integer Value

Object_Identifier Object_Name Object_Type

Present_Value Description Status_Flags Event_State

Reliability Out_Of_Service

Units Priority_Array

Relinquish_Defa ult

Min_Pres_Value

Max_Pres_Value

Resolution

COV_Increment (O) Time_Delay (O)

Notification_Class (O) High_Limit (O) Low_Limit (O) Deadband (O)

Limit_Enable (O) Event_Enable (O)

Acked_Transitions (O) Notify_Type (O)

Event_Time_Stamps (O) Event-message-texts(O)

Event-Detection-Enable (O)

Property List

Character string Value

Object_Identifier Object_Name Object_Type

Present_Value Description Status_Flags Event_State

Reliability Out_Of_Service

Units Priority_Array

Relinquish_Default

Structured-View

Object_Identifier Object_Name Object_Type Description Node-type

Node-Subtype Subordinate-List

Subordinate-annotations

Property-List

Information and/or specifications published here are current as of the date of publication of this document. Distech Controls, Inc.

reserves the right to change or modify specifications without prior notice. The latest product specifications can be found by contacting our corporate headquarters, Brossard, Quebec. Products or features contained herein are covered by one or more U.S. or foreign patents. This document may be copied by parties who are authorized to distribute Distech Controls products in connection with distribution of those products, subject to the contracts that authorize such distribution. It may not otherwise, in whole or in part, be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form without prior written consent from Distech Controls, Inc. Distech Controls and the Distech Controls logo are trademarks of Distech Controls, Inc. ©, Distech Controls Inc., 2022. All rights reserved.

11 of 11 Distech Controls EC-Net 4 BACnet PICS

Data Link Layer Options:

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800, 115200

MS/TP slave (Clause 9), baud rate(s):

Point-To-Point, EIA 232 (Clause 10), baud rate(s):

Point-To-Point, modem, (Clause 10), baud rate(s):

LonTalk, (Clause 11), medium:

Other:

Device Address Binding:

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No

Networking Options:

Router, Clause 6 – Routing configurations: Ethernet-IP, Ethernet-MS/TP, IP-MS/TP

Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Yes No

Character Sets Supported:

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

ISO 10646 (UTF-8) IBM™/Microsoft™ DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:

This product supports communications between BACnet and any third-party system to which EC-Net can connect. Contact Distech Controls for a list of supported protocols.

File details come from the government source that posted it. Updated .