S06 - Att 3 ECB BACnet Series B-AAC_PICS_15.pdf

PDF 400 KB Posted

Attached to
Z1DA--Replace Building Automation System (Metasys) 676-21-007 Federal contract opportunity
Solicitation number
36C25224B0006
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12

About this file

This document is a Protocol Implementation Conformance Statement (PICS) for the Distech Controls Advanced Application Controller (B-AAC) product line. The PICS details the BACnet device profiles, interoperability building blocks, supported object types, and other technical specifications for these controllers. The related federal contract opportunity is a solicitation from the Department of Veterans Affairs to replace an existing Building Automation System with new equipment. The solicitation number is 36C25224B0006 and the procurement is for the Z1DA--Replace Building Automation System (Metasys) 676-21-007 project. No additional details about the contract requirements, response dates, pricing, or other salient information are provided in the given materials.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Replace Building Automation System (Metasys) 676-21-007, newest first.
File Type Posted
S06 - Att 1 Wage Determination Update WI20240011 20240705.pdf PDF
36C25224B0006 0005.docx DOCX document
S06 - Att 1 Pre-Bid RFIs 20240703.pdf PDF
36C25224B0006 0004.docx DOCX document
S06 - Att 2 Pre-Bid RFIs 20240628.pdf PDF
S06 - Att 1 Pre-Bid Visit Sign In 20240612.pdf PDF
S06 - Att 3 Wage Determination Update WI20240011 20240628.pdf PDF
36C25224B0006 0003.docx DOCX document
S06 - Att 6 140sp3106.pdf PDF
S06 - Att 5 ECB BACnet Series B-ASC_PICS_15.pdf PDF
S06 - Att 2 Pre-Bid RFIs 20240530.pdf PDF
S06 - Att 1 Wage Determination Update WI20240011 20240524.pdf PDF
S06 - Att 7 ACM Spreadsheet Inventory.pdf PDF
S06 - Att 4 EC-Net B-BC_PICS.pdf PDF
S06 - Att 8 Replace BAS BID Specifications_REVISED 20240202.pdf PDF
36C25224B0006 0002.docx DOCX document
S06 - Preproposal Visit Sign-in.pdf PDF
36C25224B0006 0001-1.docx DOCX document
36C25224B0006 0001.docx DOCX document
S02 - Att 4 Wage Det WI20240011 MOD4 15Mar24.pdf PDF
S02 - Att 1 BAS BID Project Manual 676-21-007.pdf PDF
36C25224B0006_1.docx DOCX document
S02 - Att 3 BAS Drawings 2 of 2 676-21-007.pdf PDF
S02 - Att 2 BAS Drawings 1 of 2 676-21-007.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04

Distech Controls Advanced Application Controller PICS

BACnet Protocol Implementation Conformance Statement

Date February 4th, 2021 Vendor Name Distech Controls Inc.

Product Name ECB-300 Series, ECB-400 Series, ECB-600 Series Product Model Number ECB-300, ECB-350, ECB-400, ECB-403, ECB-410, ECB-413, ECB-450, ECB-253, ECB-600, ECB-610, ECB-650

Application Software Version B:2.1.10235.2 A:3.12.20322.1 Firmware Revision 2.3.19222.1 BACnet Protocol Revision Version 1, Revision 15

Product Description:

The ECB-300 Series, ECB-400 Series, and ECB-600 Series are microprocessor-based programmable controllers designed to control various building automation applications such as Air Handling Units, Multi-zone Applications, Chillers, Boilers, pumps, Cooling Towers, Roof Top Units, and lighting control applications.

BACnet Standardized Device Profile (Annex L):

BACnet Advanced Workstation (B-AWS) BACnet Operator Workstation (B-OWS) BACnet Operator Display (B-OD) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA)

Additional BACnet Interoperability Building Blocks Supported (Annex K):

Required for B-AAC Profile:

Application Service BIBBS

Data Sharing – Read Property - Execute DS-RP-B Data Sharing – ReadPropertyMultiple - Execute DS-RPM-B Data Sharing – Write Property - Execute DS-WP-B Data Sharing – WritePropertyMultiple - Execute DS-WPM-B Alarm and Event – Notification Internal - Execute AE-N-I-B Alarm and Event – ACK - Execute AE-ACK-B Alarm and Event – Information - Execute AE-INFO-B Alarm and Event – Alarm Summary - Execute AE-ASUM-B Alarm and Event – Enrollment Summary - Execute AE-ESUM-B Scheduling-Internal - Execute SCHED-I-B Device Management – Dynamic Device Binding - Execute DM-DDB-B Device Management – Dynamic Object Binding - Execute DM-DOB-B Device Management – DeviceCommunicationControl - Execute DM-DCC-B Device Management – TimeSynchronization - Execute or Device Management – UTCTimeSynchronization - Execute

DM-TS-B or

DM-UTC-B

Device Management – ReinitializeDevice - Execute DM-RD-B

Not Required for B-AAC Profile:

Application Service BIBBS

Data Sharing – Read Property - Initiate DS-RP-A Data Sharing – Read Property Multiple - Initiate DS-RPM-A Data Sharing – Write Property - Initiate DC-WP-A Data Sharing – Write Property Multiple - Initiate DS-WPM-A Data Sharing – COV - Initiate DS-COV-A Data Sharing – COV - Execute DS-COV-B Data Sharing – COV Unsolicited - Initiate DS-COVU-A Data Sharing – COV Unsolicited - Execute DS-COVU-B

2 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04

Device Management – Dynamic Device Binding - Initiate DM-DDB-A Device Management – Reinitialize Device - Execute DM-RD-B Device Management – Automatic Time Synchronization - Initiate DM-ATS-A Device Management – Manual Time Synchronization - Initiate DM-MTS-A File Access – Atomic Read File N/A File Access – Atomic Write File N/A Remote Device Management – Confirmed Private Transfer N/A Remote Device Management – Unconfirmed Private Transfer N/A

Standard Object Types Supported The following is a list of the standard object types as define by the standard. The objects checked are currently supported by this product. See the section in this document for the supported object type for details.

Accumulator Analog Input Analog Output Analog Value Averaging Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Life Safety Point Life Safety Zone Loop Multistate Input Multistate Output Multistate Value Notification Class Program Pulse Converter Schedule Trend Log

BACnet Analog Input (AI) Object Type Dynamically Creatable Dynamically Deletable

Property Name M a n d a to ry

O p ti o n a l

P ro p ri e ta

RW ID Range

Object_Identifier R 75

Object_Name RW 77

Object_Type R 79

Present_Value R 85

Status_Flags R 111

Event_State R 36

Reliability R 103

Out_Of_Service RW 81

Units R 117

3 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

COV_Increment RW 22

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

High_Limit RW 45

Low_Limit RW 59

Deadband RW 25

Limit_Enable RW 52

Event_Enable RW 35

Event_Detection_Enable RW 353

Acked_Transitions R 0

Notify_Type RW 72

Event_Time_Stamps R 130

Property_List R 371

BACnet Analog Output (AO) Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value RW 85

Status_Flags R 111

Event_State R 36

Out_Of_Service RW 81

Units R 117

Min_Present_Value R 69

Max_Present_Value R 65

Priority_Array R 87

Relinquish_Default RW 104

COV_Increment RW 22

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

4 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

High_Limit RW 45

Low_Limit RW 59

Deadband RW 25

Limit_Enable RW 52

Event_Enable RW 35

Event_Detection_Enable RW 353

Acked_Transitions R 0

Notify_Type RW 72

BACnet Analog Value (AV) Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value RW 85

Status_Flags R 111

Event_State R 36

Out_Of_Service RW 81

Units R 117

Priority_Array R 87

Relinquish_Default RW 104

COV_Increment RW 22

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

High_Limit RW 45

Low_Limit RW 59

Deadband RW 25

Limit_Enable RW 52

Event_Enable RW 35

Event_Detection_Enable RW 353

5 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

Acked_Transitions R 0

Notify_Type RW 72

BACnet Binary Input (BI) Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value R 85

Status_Flags R 111

Event_State R 36

Reliability R 103

Out_Of_Service RW 81

Polarity R 84

Inactive_Text 46

Active_Text 4

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

Alarm_Value RW 6

Event_Enable RW 35

Event_Detection_Enable RW 353

Acked_Transitions R 0

Notify_Type RW 72

6 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04

BACnet Binary Output (BO) Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value RW 85

Status_Flags R 111

Event_State R 36

Out_Of_Service RW 81

Polarity R 84

Inactive_Text 46

Active_Text 4

Priority_Array R 87

Relinquish_Default RW 104

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

Feedback_Value R 40

Event_Enable RW 35

Event_Detection_Enable RW 353

Acked_Transitions R 0

Notify_Type RW 72

BACnet Binary Value (BV) Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value RW 85

Status_Flags R 111

Event_State R 36

7 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

Out_Of_Service RW 81

Inactive_Text 46

Active_Text 4

Priority_Array R 87

Relinquish_Default RW 104

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

Alarm_Value RW 6

Event_Enable RW 35

Event_Detection_Enable RW 353

Acked_Transitions R 0

Notify_Type RW 72

BACnet Calendar Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value R 85

Date_List RW 23

Time_To_Next_State R 1001

Next_State R 1002

Device Object n d a ti o n a l

P ro p ri e

Object_Identifier RW 75

8 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

System_Status R 112

Vendor_Name R 121

Vendor_Identifier R 120

Model_Name R 70

Firmware_Revision R 44

Application_Software_Version R 12

Location RW 58

Protocol_Version R 98

Protocol_Revision R 139

Protocol_Services_Supported R 97

Protocol_Object_Types_Supported R 96

Object_List R 76

Max_APDU_Length_Accepted R 62

Segmentation_Supported R 107

Local_Date R 56

Local_Time R 57

UTC_Offset RW 119

Daylight_Savings_Status R 24

APDU_Timeout RW 10

Number_Of_APDU_Retries RW 73

Time_Synchronization_Recipients RW 116

Max_Master RW 64

Max_Info_Frames RW 63

Device_Address_Binding R 30

Database_Revision R 155

Active_COV_Subscriptions R 152

Utc_Time_Synchronization_Recipients RW 206

Time_Synchronization_Interval RW 204

Align_Intervals RW 193

Interval_Offset RW 195

Property_Lists R 371

9 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04

BACnet File Object Type n d a ti o n a l

P ro p ri e

Object_Name R 77

Object_Type R 79

File_Type R 43

File_Size R 42

Modification_Date R 71

Archive RW 13

Read_Only R 99

File_Access_Method R 41

BACnet Loop Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value R 85

Status_Flags R 111

Event_State R 36

Reliability R 103

Out_Of_Service RW 81

Output_Units R 82

Manipulated_Variable_Reference R 60

Controlled_Variable_Reference R 19

Controlled_Variable_Value R 21

Controlled_Variable_Units R 20

Setpoint_Reference R 109

Setpoint R 108

Action RW 2

Proportional_Constant RW 93

Proportional_Constant_Units R 94

Integral_Constant RW 49

10 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

Integral_Constant_Units R 50

Derivative_Constant RW 26

Derivative_Constant_Units R 27

Bias RW 14

Priority_For_Writing R 88

LoopDeadband RW 1011

Saturation_Time RW 1003

COV_Increment RW 22

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Ramp_Time RW 1005

Saturation_Time_Low_Limit_Enable RW 1006

Saturation_Time_High_Limit_Enable RW 1007

BACnet Multi-state Input (MSI) Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value R 85

Status_Flags R 111

Event_State R 36

Reliability R 103

Out_Of_Service RW 81

Number_of_States R 74

State_Text R 110

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

Alarm_Values RW 7

Fault_Values RW 39

Event_Enable RW 35

Event_Detection_Enable RW 353

11 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

Acked_Transitions R 0

Notify_Type RW 72

BACnet Multi-state Value (MSV) Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Present_Value RW 85

Status_Flags R 111

Event_State R 36

Reliability R 103

Out_Of_Service RW 81

Number_of_States R 74

State_Text R 110

Priority_Array R 87

Relinquish_Default RW 104

COV_Period RW 1004

COV_Min_Send_Time RW 1000

Time_Delay RW 113

Notification_Class RW 17

Alarm_Values RW 7

Fault_Values RW 39

Event_Enable RW 35

Event_Detection_Enable RW 353

Acked_Transitions R 0

Notify_Type RW 72

12 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04

BACnet Program Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Program_State R 92

Program_Change RW 90

Description_Of_Halt R 29

Reason_For_Halt R 100

Status_Flags R 111

Reliability R 103

Out_Of_Service R 81

BACnet Notification Class Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

Notification_Class R 17

Priority RW 86

Ack_Required RW 1

Recipient_List RW 102

BACnet Schedule Object Type n d a ti o n a l

P ro p ri e

Object_Name RW 77

Object_Type R 79

13 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04 a n d a ti o n a l

P ro p ri e

Present_Value R 92

Effective_Period RW 32

Weekly_Schedule RW 123

Exception_Schedule RW 38

Schedule_Default RW 174

List_Of_Object_Property_References R 54

Priority_For_Writing W 88

Status_Flags R 111

Reliability R 103

Out_Of_Service RW 81

Time_To_Next_State R 1001

Next_State R 1002

Segmentation Capability:

Segmented Request supported Window size: N/A Segmented Response supported Window size: N/A

Data Link Layer Options:

BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________ MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800 MS/TP slave (Clause 9), baud rate(s):

Point-To-Point, EIA 232 (Clause 10), baud rate(s):

Point-To-Point, modem, (Clause 10), baud rate(s):

LonTalk, (Clause 11), medium: __________ Other:

Device Address Binding:

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)

Yes No

Networking Options:

Router, Clause 6 - Routing configurations: Ethernet-IP, Ethernet-MS/TP, IP-MS/TP Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices?

Yes No

Character Sets Supported:

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

ANSI X3.4 IBM/Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

14 of 14 Distech Controls Advanced Application Controller PICS 2021/02/04

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:

Not applicable