Wausau CBOC 11/15/2019 Appendix C.1: ASR
LEASE NO. 36C252-20-R0001 LESSOR: ______ GOVERNMENT: ________ Page 1 of 2
AGENCY SPECIFIC REQUIREMENTS (ASR) - Wausau CBOC DEPARTMENT SHELL/TI
Interior and Exterior Janitorial and cleaning is a Lessor responsibility.
GENERAL TI
Pull cords connected to Nurse Call system necessary in-patient bathrooms and public toilets GENERAL SHELL
Corridors for patient areas must have minimum of 6'-0" width GENERAL TI
Provide Acoustical separation of STC 45 around all conference and group rooms in non-staff areas GENERAL TI
No code blue in parking lots SITE --
Provide exterior monument sign at facility site entry. Follow VA signage standards. SITE SHELL
Provide building mounted exterior building identification sign with VA logo in prominent location.
Follow VA signage standards.
SITE SHELL
The Lessor shall provide 1 flagpoles at a location to be approved by the Contracting Officer. SITE SHELL
Vestibule floor mats to be recessed to avoid tripping/falling hazard LOBBY/ENTRY SHELL
Main team workrooms to have natural light from exterior window thru meeting rooms with borrowed light or another source if not on exterior wall
PACT SHELL
Medical Equipment Storage and Clean Utility rooms, storing sterile supplies and equipment, require temperature and humidity control at all times.
PACT SHELL
The doors separating the lobby area from the PACT cross corridor need to have PIV card readers for access control.
PACT SHELL
At Medication Alcoves provide TempTrak monitoring with dedicated power. PACT SHELL
Shared Medical Appointment Room should be divided with an accordion movable partition. STC 45 rated.
PACT TI
Exam rooms off of team workrooms shall have hinged door access. Corridor side access for patients shall be a surface mounted sliding door.
PACT TI
Emergency power required for CAP accreditation (Stand-By) LAB SHELL
Provide Temp Track monitoring on all refrigerators and freezers and provide stand-by power to this equip. (refrigerators and freezers should have emergency power backup).
LAB SHELL
The lab area will always need to be maintained with a relative humidity of between 20% and 60%. LAB SHELL
The lab area will always need to be maintained with a temperature between 18º C and 25 º C. LAB SHELL
The specimen collection toilets will have a pass-thru on the lab side. LAB TI
The Blood collection rooms need to be arranged to allow a door on the patient side of the room and one on the lab side.
LAB TI
Rough in sink plumbing in all Mental Health Rooms (OFDC1) and similar MENTAL HEALTH SHELL
Patient Consult rooms need acoustical treatment to provide quiet rooms that support therapy MENTAL HEALTH TI
Maximize daylight in Mental Health consult and group rooms. MENTAL HEALTH TI
Dimmable lighting needed in MH offices for TBI patients who are light sensitive MENTAL HEALTH TI
Wi-Fi needed for both public via hotspots and private (VA) wired. For public Wi-Fi, system needs to be filtered. For VA Wi-Fi, cat 6 cables need to be pulled from the Telecom closet to wireless access point locations. Locations to be provided by VA. Wireless access points for VA wireless will be GFE, Contractor installed.
OI&T SHELL
GENERAL SHELL
Provide 25%- 50% natural light to all the space.
VHATOMHeimE Line
VHATOMHeimE Line
VHATOMHeimE Line
VHATOMHeimE Line
VHATOMHeimE Line
Wausau CBOC 11/15/2019 Appendix C.1: ASR
LEASE NO. 36C252-20-R0001 LESSOR: ______ GOVERNMENT: ________ Page 2 of 2
The demarcation room where the main data cables enter the building should be near to the Main OIT Communications room but does not need to be directly adjacent.
OI & T SHELL
The lessor shall provide the data cable install from the rack room to the data ports. OI & T SHELL
IT will provide data circuits. Requirement is for physical access into the Telecommunications Room from an outside demarc via conduit.
OI & T SHELL
Provide recessed sprinkler heads in Audiology booth AUDIOLOGY TI
Visual fire alarms (strobes) needed in booth AUDIOLOGY SHELL
The perimeter partitions around Audiology and the internal corridor partitions in the department shall be STC 45 rated.
AUDIOLOGY TI