2010-3-3 ABB Y1284-OUT_SCHEM.pdf

PDF 10 MB Posted

Attached to
J061--Emergency Switchgear Repairs PWS 539
Solicitation number
36C25027Q0125
Issued by

About this file

This file is a comprehensive electrical schematic and design drawing package for a low-voltage switchgear system serving a hospital facility (UI284 VA Hospital, Cincinnati, OH). The document set includes outline drawings, one-line diagrams, control schematics, PLC programming diagrams, annunciator panel configurations, and detailed electrical specifications certified for construction.

The system comprises two generators with associated control modules, master and secondary Programmable Logic Controllers (PLCs), multiple annunciator boxes (GAB, MAB, ATS panels), remote annunciator stations, and sophisticated monitoring and alarm capabilities. Key system components include engine control circuits with status monitoring, generator synchronization logic, load bank testing provisions, and comprehensive alarm outputs for conditions such as generator overspeed, low oil pressure, high coolant temperature, battery charger failures, and fuel tank level monitoring. The electrical architecture incorporates 480/277V three-phase power distribution with UPS support, manual synchronizing circuits, feeder breaker schematics for hospital loads, and control power systems operating at 120VAC and 24VDC. The system is designed for A-B-C phase rotation only, includes provisions for portable generator integration, and provides multiple layers of protective relaying and status annunciation across distributed remote panels connected via Ethernet-based Modbus RTU communications. All drawings are marked "CERTIFIED FOR CONSTRUCTION" with revision control documentation dated 06/20/2008.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2

File details come from the government source that posted it. Updated .