Semi-Annual Fire Suppression System Inspection October 2026.pdf
PDF 215 KB Posted
- Attached to
- J012--Fire Suppression System Maintenance and
- Solicitation number
- 36C25027Q0078
About this file
This is a Life Safety Inspection Certificate documenting a semi-annual fire and life safety systems inspection conducted by CertaSite at VA Health Center, 1481 West 10th Street, Indianapolis, IN 46202, on October 20, 2026. The inspection covered kitchen suppression systems and industrial/paint booth suppression systems.
The inspection results indicate that 9 total systems were evaluated, with 4 systems passed and 4 systems serviced. All systems were tagged as compliant with no deficiencies found. The kitchen systems included four Ansul wet chemical suppression systems (R102 models ranging from 3-6 gallons) protecting basement kitchen, first floor center hood, first floor sushi, and first floor grill equipment. Each kitchen system featured fusible link detection devices, manual release mechanisms that operate properly, alarm system connectivity, UL 300 compliance, and hood exhaust fans functioning properly. However, all four kitchen systems were noted as not having completed the required semi-annual pipe integrity test per NFPA 17A Section 8.3.31(3), and owners' manuals were not on-site for any system. Additionally, five industrial/paint booth suppression systems manufactured by Kidde (UCH model, total flooding type) with mechanical control box/panel release and fusible link detection were inspected. These dry chemical systems used stored pressure containers with nitrogen expellant and were all connected to the building fire alarm system. All paint booth systems were noted as due for six-year maintenance. The inspection was performed by inspector Dalton Johnson of CertaSite, located at 706 Navco Drive, Lafayette, IN 47905, and was verified on October 20, 2026.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Life Safety Inspection Certificate VA Health Center 1481 West 10th Street Indianapolis, IN 46202
Inspection Date: 2026-10-20 System/Device Type: Kitchen Systems,Industrial / Paint Booths Inspection Cycle: Semi Annual Job #: 51208886
Location VA Health Center Company CertaSite Contact Contact Dalton Johnson Title Title
License
The inspection of your fire and life safety systems has been performed and completed in accordance with applicable Standards. Here is a comprehensive report of our findings.
Whenever deficiencies exist between acceptable standards and the actual tests results, notes and recommended solutions have been proposed for immediate review and approval.
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Overview Inspection Date: 2026-10-20 System/Device Type: Kitchen Systems,Industrial / Paint Booths
Inspection Cycle: Semi Annual
Location Information Company Name VA Health Center Contact Address 1481 West 10th Street Contact
Phone City, State Zip Code Indianapolis, IN 46202 Contact
Email Phone Email
Inspection Performed By Company CertaSite Inspector(s) Dalton Johnson Address 706 Navco Drive Office Phone City, State Zip Code Lafayette, IN 47905
Inspection Summary Total Items Serviced Passed Failed
Total Systems 9 100% 4 % 4 % 0 %
System Details Additional Tanks Air Test Test Links
Quantities 0 0 0 Fusible Links
Qty Temperature Type 4 360 K 4 360 K 1 360 K
3 500 A-PC
General Job Notes
Verification Company CertaSite Building VA Health Center
Contact Contact
Signed Signed
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
INSPECTION & TESTING
Inspection Date: 2026-10-20 Service Type: Inspection System/Device Type: Kitchen Systems,Industrial / Paint Booths
Inspection Cycle: Semi Annual
Kitchen Hood Suppression
TYPE OF SYSTEM
MANUFACTURER: Ansul TYPE: Wet Chemical
MODEL: R102 MFG DATE:
SIZE: 6 gallon LOCATION: Basment kitchen
TESTING RESULTS
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
Last Hydrotest Date 2023-06-26 Last Regulator Test Date: 2023-06-26
SIZE MFG Date Serial Number Master Cylinder 3 gallon
Slave 1 Cylinder:
Slave 2 Cylinder
Slave 3 Cylinder
EQUIPMENT
PROTECTED
(Left to Right) Griddle, char, 6 burner
NOZZLES TOTAL QTY INSTALLED: 8 DUCT: 4
SURFACE: 4 PLENUM: 0
DETECTION
DEVICES
MAKE / MODEL:K
360 Degree Links:
450 Degree Links: 500 Degree Links: 165 Degree Links:
275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:
WERE
LINKS/DETECTION
no Visual only
TYPE OF AGENT TYPE Wet Chemical BRAND Ansulex
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
DEVICES CHANGED?
If not, why?
EXPELLANT
Expellant /Cartridge
Type(s):
CO2
Size(s)/Style(s):
101-30
Cartridge Condition:
Good
CARTRIDGE DATE:
2023-02-26
FUEL, GAS,
SHUTDOWNS
SHUTOFF TYPE:
Electric
TYPE OF GAS: GAS VALVE LOCATION:
GAS VALVE FUNCTIONS? N/A
APPLICANCES SHUTDOWN?
MAKE UP AIR SHUTDOWN? N/A
PILOT LIGHTS RE-LIT? N/A
SHUNT TRIP RE-SET? N/A
MANUAL RELEASE
OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No
ALARM
ALARM SYSTEM CONNECTED? Yes
DOES ALARM OPERATE PROPERLY? N/A
OTHER
HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes
SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS
CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?
**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)
No
OWNERS MANUAL ON-SITE? No
SYSTEM NOTES
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Kitchen Hood Suppression
TYPE OF SYSTEM
MANUFACTURER: Ansul TYPE: Wet Chemical
MODEL: R102 MFG DATE: 2006-06-26
SIZE: 3 gallon LOCATION: 1st floor center hood
TESTING RESULTS
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
Last Hydrotest Date 2019-06-26 Last Regulator Test Date:
SIZE MFG Date Serial Number Master Cylinder 3 gallon
Slave 1 Cylinder:
Slave 2 Cylinder
Slave 3 Cylinder
EQUIPMENT
PROTECTED
(Left to Right) 6 burner, griddle, broaster x2
NOZZLES TOTAL QTY INSTALLED: 7 DUCT: 0
SURFACE: 7 PLENUM: 0
DETECTION
DEVICES
MAKE / MODEL:K
360 Degree Links:
450 Degree Links: 500 Degree Links: 165 Degree Links:
275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:
WERE
LINKS/DETECTION
DEVICES CHANGED?
If not, why?
no Visual only
EXPELLANT
Expellant /Cartridge
Type(s):
Nitrogen
Size(s)/Style(s):
LT-30-R
Cartridge Condition:
Good
CARTRIDGE DATE:
2019-06-26
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
FUEL, GAS,
SHUTDOWNS
SHUTOFF TYPE:
None
TYPE OF GAS: GAS VALVE LOCATION:
GAS VALVE FUNCTIONS? N/A
APPLICANCES SHUTDOWN?
MAKE UP AIR SHUTDOWN? N/A
PILOT LIGHTS RE-LIT? N/A
SHUNT TRIP RE-SET? N/A
MANUAL RELEASE
OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No
ALARM
ALARM SYSTEM CONNECTED? Yes
DOES ALARM OPERATE PROPERLY? N/A
OTHER
HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes
SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS
CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?
**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)
No
SYSTEM NOTES Water wash covers ductwork and plenum
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Kitchen Hood Suppression
TYPE OF SYSTEM
MANUFACTURER: Ansul TYPE: Wet Chemical
MODEL: R102 MFG DATE: 2006-06-26
SIZE: 3 gallon LOCATION: 1st floor sushi
TESTING RESULTS
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
Last Hydrotest Date 2019-06-26 Last Regulator Test Date:
SIZE MFG Date Serial Number Master Cylinder 3 gallon
Slave 1 Cylinder:
Slave 2 Cylinder
Slave 3 Cylinder
EQUIPMENT
PROTECTED
(Left to Right) Pizza oven
NOZZLES TOTAL QTY INSTALLED: 2 DUCT: 0
SURFACE: 2 PLENUM: 0
DETECTION
DEVICES
MAKE / MODEL:K
360 Degree Links:
450 Degree Links: 500 Degree Links: 165 Degree Links:
275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:
WERE
LINKS/DETECTION
DEVICES CHANGED?
If not, why?
no Visual only
EXPELLANT
Expellant /Cartridge
Type(s):
CO2
Size(s)/Style(s):
101-30
Cartridge Condition:
Good
CARTRIDGE DATE:
2019-06-26
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
FUEL, GAS,
SHUTDOWNS
SHUTOFF TYPE:
None
TYPE OF GAS: GAS VALVE LOCATION:
GAS VALVE FUNCTIONS? N/A
APPLICANCES SHUTDOWN?
MAKE UP AIR SHUTDOWN? N/A
PILOT LIGHTS RE-LIT? N/A
SHUNT TRIP RE-SET? N/A
MANUAL RELEASE
OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No
ALARM
ALARM SYSTEM CONNECTED? Yes
DOES ALARM OPERATE PROPERLY? N/A
OTHER
HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes
SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS
CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?
**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)
No
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Kitchen Hood Suppression
TYPE OF SYSTEM
MANUFACTURER: Ansul TYPE: Wet Chemical
MODEL: R102 MFG DATE: 2012-06-26
SIZE: 3 gallon LOCATION: 1st floor grill
TESTING RESULTS
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
Last Hydrotest Date 2026-02-26 Last Regulator Test Date: 2026-02-26
SIZE MFG Date Serial Number Master Cylinder 3 gallon
Slave 1 Cylinder:
Slave 2 Cylinder
Slave 3 Cylinder
EQUIPMENT
PROTECTED
(Left to Right) Griddle, fryer x2
NOZZLES TOTAL QTY INSTALLED: 3 DUCT: 0
SURFACE: 3 PLENUM: 0
DETECTION
DEVICES
MAKE / MODEL:A-PC
360 Degree Links: 450 Degree Links: 500 Degree Links:
165 Degree Links:
275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:
WERE
LINKS/DETECTION
DEVICES CHANGED?
If not, why?
no Visual inspection only
EXPELLANT
Expellant /Cartridge
Type(s):
Nitrogen
Size(s)/Style(s):
LT-30-R
Cartridge Condition:
Good
CARTRIDGE DATE:
2026-06-25
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
FUEL, GAS,
SHUTDOWNS
SHUTOFF TYPE:
None
TYPE OF GAS: GAS VALVE LOCATION:
GAS VALVE FUNCTIONS? N/A
APPLICANCES SHUTDOWN?
MAKE UP AIR SHUTDOWN? N/A
PILOT LIGHTS RE-LIT? N/A
SHUNT TRIP RE-SET? N/A
MANUAL RELEASE
OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No
ALARM
ALARM SYSTEM CONNECTED? Yes
DOES ALARM OPERATE PROPERLY? N/A
OTHER
HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes
SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS
CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?
**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)
No
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Industrial / Paint Booth Suppression
SYSTEM
MANUFACTURER: Kidde TYPE: Total Flooding
MODEL: UCH MFG DATE: 2020-10-20
SERIAL NUMBER: DETECTION
TYPE: Fusible Link
TYPE OF RELEASE
SYSTEM:
Mechanical Control Box/Panel PANEL TYPE:
TESTING RESULTS
DATE: 2026-10-20
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
CYLINDER(S)
LOCATION: Outside HAZARD TYPE: Other
Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:
Cylinder 3:
AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure
DESCRIPTION Chemical container
BREAKER PANEL
LOCATION Left automan
NUMBERS
BATTERY
TYPE:
SIZE:
DETECTION
DEVICES
360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:
212 Degree Links:
280 Degree Links: Other Links: MAKE AND MODEL:
ML
EXPELLANT Expellant /Cartridge Type(s): Nitrogen
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes
LINKS CHANGED? IF NOT, WHY?
CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good
PIPE INTEGRITY TEST PERFORMED? N/A
HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes
ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes
OTHER ARE PRINTS AVAILABLE? no
SYSTEM NOTES Due 6year
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Industrial / Paint Booth Suppression
SYSTEM
MANUFACTURER: Kidde TYPE: Total Flooding
MODEL: UCH MFG DATE: 2020-10-20
SERIAL NUMBER: DETECTION
TYPE: Fusible Link
TYPE OF RELEASE
SYSTEM:
Mechanical Control Box/Panel PANEL TYPE:
TESTING RESULTS
DATE: 2026-10-20
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
CYLINDER(S)
LOCATION: Outside HAZARD TYPE: Other
Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:
Cylinder 3:
AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure
DESCRIPTION Chemical container
BREAKER PANEL
LOCATION Outside container
NUMBERS
BATTERY
TYPE:
SIZE:
DETECTION
DEVICES
360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:
212 Degree Links:
280 Degree Links: Other Links: MAKE AND MODEL:
ML
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes
LINKS CHANGED? IF NOT, WHY?
CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good
PIPE INTEGRITY TEST PERFORMED? N/A
HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes
ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes
SYSTEM NOTES Due 6 yr
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Industrial / Paint Booth Suppression
SYSTEM
MANUFACTURER: KIdde TYPE: Total Flooding
MODEL: UCH MFG DATE: 2020-10-20
SERIAL NUMBER: DETECTION
TYPE: Fusible Link
TYPE OF RELEASE
SYSTEM:
Mechanical Control Box/Panel PANEL TYPE:
TESTING RESULTS
DATE: 2026-10-20
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
CYLINDER(S)
LOCATION: Outside HAZARD TYPE: Other
Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:
Cylinder 3:
AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure
DESCRIPTION Chemical container
BREAKER PANEL
LOCATION
NUMBERS
BATTERY
TYPE:
SIZE:
DETECTION
DEVICES
360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:
212 Degree Links:
280 Degree Links: Other Links: MAKE AND MODEL:
ML
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes
LINKS CHANGED? IF NOT, WHY?
CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good
PIPE INTEGRITY TEST PERFORMED? N/A
HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes
ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes
SYSTEM NOTES Due 6yr maintenance
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Industrial / Paint Booth Suppression
SYSTEM
MANUFACTURER: KIdde TYPE: Total Flooding
MODEL: UCH MFG DATE: 2020-10-20
SERIAL NUMBER: DETECTION
TYPE: Fusible Link
TYPE OF RELEASE
SYSTEM:
Mechanical Control Box/Panel PANEL TYPE:
TESTING RESULTS
DATE: 2026-10-20
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
CYLINDER(S)
LOCATION: Outside HAZARD TYPE: Other
Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:
Cylinder 3:
AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure
DESCRIPTION Chemical container
BREAKER PANEL
LOCATION
NUMBERS
BATTERY
TYPE:
SIZE:
DETECTION
DEVICES
360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:
212 Degree Links:
280 Degree Links: Other Links: MAKE AND MODEL:
ML
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes
LINKS CHANGED? IF NOT, WHY?
CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good
PIPE INTEGRITY TEST PERFORMED? N/A
HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes
ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes
SYSTEM NOTES Due 6yr maintenance
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
Industrial / Paint Booth Suppression
SYSTEM
MANUFACTURER: Kidde TYPE: Total Flooding
MODEL: UCH MFG DATE: 2020-10-20
SERIAL NUMBER: DETECTION
TYPE: Fusible Link
TYPE OF RELEASE
SYSTEM:
Mechanical Control Box/Panel PANEL TYPE:
TESTING RESULTS
DATE: 2026-10-20
SYSTEM TAGGED
FOR NON
COMPLIANCE?
No
DEFICIENCIES:
if blank, none found
CYLINDERS
CYLINDER(S)
LOCATION: Outside /chiller plant. HAZARD TYPE: Other
Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:
Cylinder 3:
AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure
DESCRIPTION Chemical storage container
BREAKER PANEL
LOCATION
NUMBERS
BATTERY
TYPE:
SIZE:
DETECTION
DEVICES
360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:
212 Degree Links:
280 Degree Links: Other Links: MAKE AND MODEL:
ML
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes
LINKS CHANGED? IF NOT, WHY?
CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good
PIPE INTEGRITY TEST PERFORMED? N/A
HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes
ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes
SYSTEM NOTES Due 6year maintenance
CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com
GENERAL JOB
NOTES
Completed semi inspection on the 5- Dry systems and did a visual inspection on the 4- Ansul kitchen systems
Verification Company CertaSite Building VA Health Center
Contact Dalton Johnson Contact
Signed Signed
Date 2026-10-20 Date