Semi-Annual Fire Suppression System Inspection October 2026.pdf

PDF 215 KB Posted

Attached to
J012--Fire Suppression System Maintenance and
Solicitation number
36C25027Q0078
Issued by

About this file

This is a Life Safety Inspection Certificate documenting a semi-annual fire and life safety systems inspection conducted by CertaSite at VA Health Center, 1481 West 10th Street, Indianapolis, IN 46202, on October 20, 2026. The inspection covered kitchen suppression systems and industrial/paint booth suppression systems.

The inspection results indicate that 9 total systems were evaluated, with 4 systems passed and 4 systems serviced. All systems were tagged as compliant with no deficiencies found. The kitchen systems included four Ansul wet chemical suppression systems (R102 models ranging from 3-6 gallons) protecting basement kitchen, first floor center hood, first floor sushi, and first floor grill equipment. Each kitchen system featured fusible link detection devices, manual release mechanisms that operate properly, alarm system connectivity, UL 300 compliance, and hood exhaust fans functioning properly. However, all four kitchen systems were noted as not having completed the required semi-annual pipe integrity test per NFPA 17A Section 8.3.31(3), and owners' manuals were not on-site for any system. Additionally, five industrial/paint booth suppression systems manufactured by Kidde (UCH model, total flooding type) with mechanical control box/panel release and fusible link detection were inspected. These dry chemical systems used stored pressure containers with nitrogen expellant and were all connected to the building fire alarm system. All paint booth systems were noted as due for six-year maintenance. The inspection was performed by inspector Dalton Johnson of CertaSite, located at 706 Navco Drive, Lafayette, IN 47905, and was verified on October 20, 2026.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Life Safety Inspection Certificate VA Health Center 1481 West 10th Street Indianapolis, IN 46202

Inspection Date: 2026-10-20 System/Device Type: Kitchen Systems,Industrial / Paint Booths Inspection Cycle: Semi Annual Job #: 51208886

Location VA Health Center Company CertaSite Contact Contact Dalton Johnson Title Title

License

The inspection of your fire and life safety systems has been performed and completed in accordance with applicable Standards. Here is a comprehensive report of our findings.

Whenever deficiencies exist between acceptable standards and the actual tests results, notes and recommended solutions have been proposed for immediate review and approval.

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Overview Inspection Date: 2026-10-20 System/Device Type: Kitchen Systems,Industrial / Paint Booths

Inspection Cycle: Semi Annual

Location Information Company Name VA Health Center Contact Address 1481 West 10th Street Contact

Phone City, State Zip Code Indianapolis, IN 46202 Contact

Email Phone Email

Inspection Performed By Company CertaSite Inspector(s) Dalton Johnson Address 706 Navco Drive Office Phone City, State Zip Code Lafayette, IN 47905

Inspection Summary Total Items Serviced Passed Failed

Total Systems 9 100% 4 % 4 % 0 %

System Details Additional Tanks Air Test Test Links

Quantities 0 0 0 Fusible Links

Qty Temperature Type 4 360 K 4 360 K 1 360 K

3 500 A-PC

General Job Notes

Verification Company CertaSite Building VA Health Center

Contact Contact

Signed Signed

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

INSPECTION & TESTING

Inspection Date: 2026-10-20 Service Type: Inspection System/Device Type: Kitchen Systems,Industrial / Paint Booths

Inspection Cycle: Semi Annual

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE:

SIZE: 6 gallon LOCATION: Basment kitchen

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2023-06-26 Last Regulator Test Date: 2023-06-26

SIZE MFG Date Serial Number Master Cylinder 3 gallon

Slave 1 Cylinder:

Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) Griddle, char, 6 burner

NOZZLES TOTAL QTY INSTALLED: 8 DUCT: 4

SURFACE: 4 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:K

360 Degree Links:

450 Degree Links: 500 Degree Links: 165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

WERE

LINKS/DETECTION

no Visual only

TYPE OF AGENT TYPE Wet Chemical BRAND Ansulex

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

DEVICES CHANGED?

If not, why?

EXPELLANT

Expellant /Cartridge

Type(s):

CO2

Size(s)/Style(s):

101-30

Cartridge Condition:

Good

CARTRIDGE DATE:

2023-02-26

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

Electric

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? N/A

APPLICANCES SHUTDOWN?

MAKE UP AIR SHUTDOWN? N/A

PILOT LIGHTS RE-LIT? N/A

SHUNT TRIP RE-SET? N/A

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

OWNERS MANUAL ON-SITE? No

SYSTEM NOTES

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE: 2006-06-26

SIZE: 3 gallon LOCATION: 1st floor center hood

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2019-06-26 Last Regulator Test Date:

SIZE MFG Date Serial Number Master Cylinder 3 gallon

Slave 1 Cylinder:

Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) 6 burner, griddle, broaster x2

NOZZLES TOTAL QTY INSTALLED: 7 DUCT: 0

SURFACE: 7 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:K

360 Degree Links:

450 Degree Links: 500 Degree Links: 165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

WERE

LINKS/DETECTION

DEVICES CHANGED?

If not, why?

no Visual only

EXPELLANT

Expellant /Cartridge

Type(s):

Nitrogen

Size(s)/Style(s):

LT-30-R

Cartridge Condition:

Good

CARTRIDGE DATE:

2019-06-26

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

None

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? N/A

APPLICANCES SHUTDOWN?

MAKE UP AIR SHUTDOWN? N/A

PILOT LIGHTS RE-LIT? N/A

SHUNT TRIP RE-SET? N/A

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

SYSTEM NOTES Water wash covers ductwork and plenum

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE: 2006-06-26

SIZE: 3 gallon LOCATION: 1st floor sushi

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2019-06-26 Last Regulator Test Date:

SIZE MFG Date Serial Number Master Cylinder 3 gallon

Slave 1 Cylinder:

Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) Pizza oven

NOZZLES TOTAL QTY INSTALLED: 2 DUCT: 0

SURFACE: 2 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:K

360 Degree Links:

450 Degree Links: 500 Degree Links: 165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

WERE

LINKS/DETECTION

DEVICES CHANGED?

If not, why?

no Visual only

EXPELLANT

Expellant /Cartridge

Type(s):

CO2

Size(s)/Style(s):

101-30

Cartridge Condition:

Good

CARTRIDGE DATE:

2019-06-26

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

None

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? N/A

APPLICANCES SHUTDOWN?

MAKE UP AIR SHUTDOWN? N/A

PILOT LIGHTS RE-LIT? N/A

SHUNT TRIP RE-SET? N/A

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE: 2012-06-26

SIZE: 3 gallon LOCATION: 1st floor grill

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2026-02-26 Last Regulator Test Date: 2026-02-26

SIZE MFG Date Serial Number Master Cylinder 3 gallon

Slave 1 Cylinder:

Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) Griddle, fryer x2

NOZZLES TOTAL QTY INSTALLED: 3 DUCT: 0

SURFACE: 3 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:A-PC

360 Degree Links: 450 Degree Links: 500 Degree Links:

165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

WERE

LINKS/DETECTION

DEVICES CHANGED?

If not, why?

no Visual inspection only

EXPELLANT

Expellant /Cartridge

Type(s):

Nitrogen

Size(s)/Style(s):

LT-30-R

Cartridge Condition:

Good

CARTRIDGE DATE:

2026-06-25

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

None

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? N/A

APPLICANCES SHUTDOWN?

MAKE UP AIR SHUTDOWN? N/A

PILOT LIGHTS RE-LIT? N/A

SHUNT TRIP RE-SET? N/A

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED No

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Industrial / Paint Booth Suppression

SYSTEM

MANUFACTURER: Kidde TYPE: Total Flooding

MODEL: UCH MFG DATE: 2020-10-20

SERIAL NUMBER: DETECTION

TYPE: Fusible Link

TYPE OF RELEASE

SYSTEM:

Mechanical Control Box/Panel PANEL TYPE:

TESTING RESULTS

DATE: 2026-10-20

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

CYLINDER(S)

LOCATION: Outside HAZARD TYPE: Other

Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:

Cylinder 3:

AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure

DESCRIPTION Chemical container

BREAKER PANEL

LOCATION Left automan

NUMBERS

BATTERY

TYPE:

SIZE:

DETECTION

DEVICES

360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:

212 Degree Links:

280 Degree Links: Other Links: MAKE AND MODEL:

ML

EXPELLANT Expellant /Cartridge Type(s): Nitrogen

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes

LINKS CHANGED? IF NOT, WHY?

CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good

PIPE INTEGRITY TEST PERFORMED? N/A

HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes

ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes

OTHER ARE PRINTS AVAILABLE? no

SYSTEM NOTES Due 6year

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Industrial / Paint Booth Suppression

SYSTEM

MANUFACTURER: Kidde TYPE: Total Flooding

MODEL: UCH MFG DATE: 2020-10-20

SERIAL NUMBER: DETECTION

TYPE: Fusible Link

TYPE OF RELEASE

SYSTEM:

Mechanical Control Box/Panel PANEL TYPE:

TESTING RESULTS

DATE: 2026-10-20

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

CYLINDER(S)

LOCATION: Outside HAZARD TYPE: Other

Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:

Cylinder 3:

AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure

DESCRIPTION Chemical container

BREAKER PANEL

LOCATION Outside container

NUMBERS

BATTERY

TYPE:

SIZE:

DETECTION

DEVICES

360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:

212 Degree Links:

280 Degree Links: Other Links: MAKE AND MODEL:

ML

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes

LINKS CHANGED? IF NOT, WHY?

CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good

PIPE INTEGRITY TEST PERFORMED? N/A

HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes

ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes

SYSTEM NOTES Due 6 yr

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Industrial / Paint Booth Suppression

SYSTEM

MANUFACTURER: KIdde TYPE: Total Flooding

MODEL: UCH MFG DATE: 2020-10-20

SERIAL NUMBER: DETECTION

TYPE: Fusible Link

TYPE OF RELEASE

SYSTEM:

Mechanical Control Box/Panel PANEL TYPE:

TESTING RESULTS

DATE: 2026-10-20

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

CYLINDER(S)

LOCATION: Outside HAZARD TYPE: Other

Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:

Cylinder 3:

AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure

DESCRIPTION Chemical container

BREAKER PANEL

LOCATION

NUMBERS

BATTERY

TYPE:

SIZE:

DETECTION

DEVICES

360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:

212 Degree Links:

280 Degree Links: Other Links: MAKE AND MODEL:

ML

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes

LINKS CHANGED? IF NOT, WHY?

CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good

PIPE INTEGRITY TEST PERFORMED? N/A

HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes

ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes

SYSTEM NOTES Due 6yr maintenance

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Industrial / Paint Booth Suppression

SYSTEM

MANUFACTURER: KIdde TYPE: Total Flooding

MODEL: UCH MFG DATE: 2020-10-20

SERIAL NUMBER: DETECTION

TYPE: Fusible Link

TYPE OF RELEASE

SYSTEM:

Mechanical Control Box/Panel PANEL TYPE:

TESTING RESULTS

DATE: 2026-10-20

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

CYLINDER(S)

LOCATION: Outside HAZARD TYPE: Other

Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:

Cylinder 3:

AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure

DESCRIPTION Chemical container

BREAKER PANEL

LOCATION

NUMBERS

BATTERY

TYPE:

SIZE:

DETECTION

DEVICES

360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:

212 Degree Links:

280 Degree Links: Other Links: MAKE AND MODEL:

ML

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes

LINKS CHANGED? IF NOT, WHY?

CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good

PIPE INTEGRITY TEST PERFORMED? N/A

HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes

ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes

SYSTEM NOTES Due 6yr maintenance

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Industrial / Paint Booth Suppression

SYSTEM

MANUFACTURER: Kidde TYPE: Total Flooding

MODEL: UCH MFG DATE: 2020-10-20

SERIAL NUMBER: DETECTION

TYPE: Fusible Link

TYPE OF RELEASE

SYSTEM:

Mechanical Control Box/Panel PANEL TYPE:

TESTING RESULTS

DATE: 2026-10-20

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

CYLINDER(S)

LOCATION: Outside /chiller plant. HAZARD TYPE: Other

Size MFG Date Type Last Hydro Date Cylinder 1: IND-21 Cylinder 2:

Cylinder 3:

AGENT TYPE: Dry Chemical CONTAINER TYPE: Stored Pressure

DESCRIPTION Chemical storage container

BREAKER PANEL

LOCATION

NUMBERS

BATTERY

TYPE:

SIZE:

DETECTION

DEVICES

360 Degree Links: 450 Degree Links: 500 Degree Links: 165 Degree Links:

212 Degree Links:

280 Degree Links: Other Links: MAKE AND MODEL:

ML

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

DOES SYSTEM SHUTDOWN ANY EQUIPMENT? yes

LINKS CHANGED? IF NOT, WHY?

CONDITION OF CONDUIT CABLES? Good CONDITION OF VENT PLUG? Good CONDITION OF NOZZLES? Good

PIPE INTEGRITY TEST PERFORMED? N/A

HAS PYROCHEM ORING BEEN CHANGED? (if applicable) N/A SYSTEM INSTALLED PER MANUFACTUER? Yes

ALARM IS SYSTEM CONNECTED TO BUILDING FIRE ALARM? yes

SYSTEM NOTES Due 6year maintenance

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

GENERAL JOB

NOTES

Completed semi inspection on the 5- Dry systems and did a visual inspection on the 4- Ansul kitchen systems

Verification Company CertaSite Building VA Health Center

Contact Dalton Johnson Contact

Signed Signed

Date 2026-10-20 Date

File details come from the government source that posted it. Updated .