Semi-Annual Fire Suppression System Inspection December 2025.pdf

PDF 171 KB Posted

Attached to
J012--Fire Suppression System Maintenance and
Solicitation number
36C25027Q0078
Issued by

About this file

This is a Life Safety Inspection Certificate documenting the semi-annual inspection of kitchen hood suppression systems at VA Health Center in Indianapolis, Indiana, completed on December 18, 2025, by CertaSite, a fire and life safety company.

The inspection covers four Ansul wet chemical kitchen hood suppression systems (Model R102) protecting various cooking equipment across different kitchen locations. The basement kitchen system uses a 6-gallon capacity with eight nozzles and requires cartridge replacement as it was not serviced by the manufacturer. The first floor center hood system (3-gallon capacity, seven nozzles) has a last hydrotest date of June 26, 2019. The first floor sushi station system (3-gallon capacity, two nozzles) is in good condition with CO2 expellant. The first floor grill system (3-gallon capacity, three nozzles) is flagged as past due for hydro testing, with the last hydrotest completed on December 18, 2012. All four systems are UL 300 compliant with properly functioning manual releases, alarm systems connected, and hood exhaust fans operating correctly. Critical deficiency noted across all systems: none have completed the semi-annual pipe integrity test required by NFPA 17A Section 8.3.31(3). Additional issues include outdated cartridge dates on multiple systems and the grill system's significantly overdue hydrostatic testing requirement. The inspection was signed by CertaSite contact Dalton Johnson on December 18, 2025.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Life Safety Inspection Certificate VA Health Center 1481 West 10th Street Indianapolis, IN 46202

Inspection Date: 2025-12-18 System/Device Type: Kitchen Systems Inspection Cycle: Semi Annual Job #: 44779915

Location VA Health Center Company CertaSite Contact Contact Dalton Johnson Title Title

License

The inspection of your fire and life safety systems has been performed and completed in accordance with applicable Standards. Here is a comprehensive report of our findings.

Whenever deficiencies exist between acceptable standards and the actual tests results, notes and recommended solutions have been proposed for immediate review and approval.

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

INSPECTION & TESTING

Inspection Date: 2025-12-18 Service Type: Inspection System/Device Type: Kitchen Systems Inspection Cycle: Semi Annual

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE:

SIZE: 6 gallon LOCATION: Basment kitchen

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2023-06-26 Last Regulator Test Date: 2023-06-26

SIZE MFG Date Serial Number Master Cylinder 3 gallon 2010

Slave 1 Cylinder: 3 gallon 2012 Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) Griddle, char, 6 burner

NOZZLES TOTAL QTY INSTALLED: 8 DUCT: 4

SURFACE: 4 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:K

360 Degree Links:

450 Degree Links: 500 Degree Links: 165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

TYPE OF AGENT TYPE Wet Chemical BRAND Ansulex

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

WERE

LINKS/DETECTION

DEVICES CHANGED?

If not, why?

yes

EXPELLANT

Expellant /Cartridge

Type(s):

Nitrogen

Size(s)/Style(s):

Double Tank

Cartridge Condition: CARTRIDGE DATE:

2021-06-26

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

Electric

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? Yes APPLICANCES SHUTDOWN? All electrical

MAKE UP AIR SHUTDOWN? N/A

PILOT LIGHTS RE-LIT? Yes SHUNT TRIP RE-SET? Yes

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED Yes

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

OWNERS MANUAL ON-SITE? Yes

SYSTEM NOTES Needs cartridge replaced. It was not serviced by the manufacturer

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE: 2006-06-26

SIZE: 3 gallon LOCATION: 1st floor center hood

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2019-06-26 Last Regulator Test Date:

SIZE MFG Date Serial Number Master Cylinder 3 gallon 2007

Slave 1 Cylinder:

Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) 6 burner, griddle, broaster x2

NOZZLES TOTAL QTY INSTALLED: 7 DUCT: 0

SURFACE: 7 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:K

360 Degree Links:

450 Degree Links: 500 Degree Links: 165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

WERE

LINKS/DETECTION

DEVICES CHANGED?

If not, why?

yes

EXPELLANT Expellant /Cartridge Type(s):

Size(s)/Style(s):

LT-30-R

Cartridge Condition:

CARTRIDGE DATE:

2019-06-26

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Nitrogen

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

None

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? N/A

APPLICANCES SHUTDOWN? All electrical

MAKE UP AIR SHUTDOWN? N/A

PILOT LIGHTS RE-LIT? N/A

SHUNT TRIP RE-SET? Yes

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED Yes

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

SYSTEM NOTES Water wash covers ductwork and plenum

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE: 2006-06-26

SIZE: 3 gallon LOCATION: 1st floor sushi

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2019-06-26 Last Regulator Test Date:

SIZE MFG Date Serial Number Master Cylinder 3 gallon 2007

Slave 1 Cylinder:

Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) Pizza oven

NOZZLES TOTAL QTY INSTALLED: 2 DUCT: 0

SURFACE: 2 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:K

360 Degree Links:

450 Degree Links: 500 Degree Links: 165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

WERE

LINKS/DETECTION

DEVICES CHANGED?

If not, why?

yes

EXPELLANT Expellant /Cartridge Type(s):

Size(s)/Style(s):

101-30

Cartridge Condition:

CARTRIDGE DATE:

2019-06-26

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

CO2 Good

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

None

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? N/A

APPLICANCES SHUTDOWN? All electrical

MAKE UP AIR SHUTDOWN? N/A

PILOT LIGHTS RE-LIT? N/A

SHUNT TRIP RE-SET? Yes

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED Yes

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

SYSTEM NOTES

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Kitchen Hood Suppression

TYPE OF SYSTEM

MANUFACTURER: Ansul TYPE: Wet Chemical

MODEL: R102 MFG DATE: 2012-06-26

SIZE: 3 gallon LOCATION: 1st floor grill

TESTING RESULTS

SYSTEM TAGGED

FOR NON

COMPLIANCE?

No

DEFICIENCIES:

if blank, none found

CYLINDERS

Last Hydrotest Date 2012-12-18 Last Regulator Test Date:

SIZE MFG Date Serial Number Master Cylinder 3 gallon 2012

Slave 1 Cylinder:

Slave 2 Cylinder

Slave 3 Cylinder

EQUIPMENT

PROTECTED

(Left to Right) Griddle, fryer x2

NOZZLES TOTAL QTY INSTALLED: 3 DUCT: 0

SURFACE: 3 PLENUM: 0

DETECTION

DEVICES

MAKE / MODEL:A-PC

360 Degree Links: 450 Degree Links: 500 Degree Links:

165 Degree Links:

275 Degree Links: 280 Degree Links: 115 Degree Links: Other Links:

WERE

LINKS/DETECTION

DEVICES CHANGED?

If not, why?

yes

EXPELLANT Expellant /Cartridge Type(s):

Size(s)/Style(s):

LT-30-R

Cartridge Condition:

CARTRIDGE DATE:

2011-06-26

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

Nitrogen

FUEL, GAS,

SHUTDOWNS

SHUTOFF TYPE:

Electric

TYPE OF GAS: GAS VALVE LOCATION:

GAS VALVE FUNCTIONS? Yes APPLICANCES SHUTDOWN? All electrical MAKE UP AIR SHUTDOWN? Yes PILOT LIGHTS RE-LIT? Yes SHUNT TRIP RE-SET? Yes

MANUAL RELEASE

OPERATES PROPERLY? Yes PROPER LOCATION? Yes NOZZLE SEALS / CAPS REPLACED Yes

ALARM

ALARM SYSTEM CONNECTED? Yes

DOES ALARM OPERATE PROPERLY? N/A

OTHER

HOOD EXHAUST FAN PROPERLY FUNCTIONS? Yes SYSTEM IS UL 300 COMPLIANT? Yes

SYSTEM INSTALLED PER MANFACTURER SPECIFICATION? IF NO, HAS

CUSTOMER BEEN ADVISED Yes, SEMI-ANNUAL PIPE INTEGRITY TEST COMPLETED?

**PIPE INTEGRITY TEST REQUIRED SEMI-ANNUALLY PER NFPA 17A, 8.3.31 (3)

No

SYSTEM NOTES Past Due for Hydro test

CertaSite | 706 Navco Drive, Lafayette, IN 47905 | CertaSitePro.comQuestions? Call | Email Customer@CertaSitePro.com

GENERAL JOB

NOTES

Verification Company CertaSite Building VA Health Center

Contact Dalton Johnson Contact

Signed Signed

Date 2025-12-18 Date

File details come from the government source that posted it. Updated .