Saginaw VA Med Center Water Storage Tank Evaluation 2024.pdf

PDF 3 MB Posted

Attached to
655-26-201 Repaint Water Tower
Solicitation number
36C25026R0062
Issued by

About this file

This is a Single Pedestal Tank Inspection Report for the water storage tank located at Aleda E. Lutz VA Medical Center in Saginaw, Michigan. The inspection was conducted on July 23, 2024, by Derek Goff (NACE Level 3 Coatings Inspector and AMPP Senior Certified Coatings Inspector) from B&N Inspection and was approved on August 2, 2024. The tank is a 250,000-gallon single pedestal structure with a height to tank centerline of 151 feet.

The overall tank condition is rated as good with no significant coating failures, corrosion, or structural discontinuities. The exterior coating system is in sound condition with good adhesion properties but exhibits chalking indicative of UV protection breakdown; the tank is identified as a candidate for washing and overcoating at the next scheduled maintenance. The interior coating system is rated in fair condition with localized corrosion and coating failures visible below the typical water line, with areas above the water line in good condition. The report recommends removal and replacement of the interior coating system at the next scheduled maintenance using new NSF/ANSI 61 approved products. Exterior and interior structural components including the roof, safety railings, manways, ladders, anchor bolts, and pipes are all in satisfactory to good condition. A Type A adhesion test performed on the exterior coating system on the south side yielded a 4A result, confirming good adhesion. One minor non-conformance was noted regarding the roof safety railing toe bar, where some areas exceed the OSHA-required maximum height of 0.25 inches above the surface.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Aleda E. Lutz VA Medical Center Re: Water Tower ROV Evaluation Attn: Calvin Hugo From: B&N Inspection

Mr. Hugo, This letter is in reference to the recent inspection of the Single Pedestal Water Storage Tank at the Aleda E. Lutz VA Medical Center in Saginaw, MI. The attached tank inspection report was completed by Derek Goff (Director of Operations, NACE Level 3 Coatings Inspector, & AMPP Senior Certified Coatings Inspector) on July 23, 2024.

Executive Summary:

• The overall condition of the tank is good. No significant coating failures, corrosion, or discontinuities were found. The site is secured, maintained, and well kept.

• The exterior coating system is in sound condition and exhibits good adhesion properties. The exterior coating system is “chalking,” which indicates the UV protection is breaking down. The tank exterior is a candidate for washing and overcoating at the time of the next scheduled maintenance.

• The exterior roof is in overall good condition. The safety railing is functioning properly and in sound condition. The roof vent appears to be functioning properly and is in sound condition.

• The interior dry areas are in good condition. Typical wear and tear are visible, but no significant corrosion or coating failures were found. The ladder is sound, stable, and in good condition.

• The interior coating system is in fair condition. Localized corrosion and coating failures are visible below the typical water line. The areas above the water line appear in good condition with normal wear and tear visible. Due to the age of the existing coating system and availability of new NSF/ANSI 61 approved products, removal and replacement of the interior system is recommended at the time of the next scheduled maintenance.

Very Respectfully, Derek Goff Director of Operations NACE Level 3 Coatings Inspector #31446 AMPP Senior Certified Coatings Inspector

SINGLE PEDESTAL TANK INSPECTION REPORT

REPORT #VA HOSPITAL ROV - 20240723-1, APPROVED

VA SAGINAW, SAGINAW, MICHIGAN, UNITED STATES

Started: 07/23/2024, 7:52 AM EDT - Location: 43.45,-83.96 Submitted: 08/02/2024, 10:46 AM EDT - Location: 38.65,-90.32 Approved: 08/02/2024, 10:46 AM EDT

INSPECTION OF THE ALEDA E. LUTZ VA MEDICAL CENTER WATER TOWER

1500 WEISS ST. SAGINAW, MI 48602

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 1 of 29

GENERAL

NON-CONFORMANCE

SITE

Date of Evaluation: 07/23/2024, EDT Name of Inspectors: Derek Goff, Nick Lamm Name of Tank: VA Hospital ROV Height to TCL: 151 Tank Capacity: 250000 gal Exterior: White Interior Wet: White Interior Dry: White Location: 1500 Weiss St, Saginaw, MI Type of Inspection: Periodic

EXTERIOR COMPONENTS

Balcony Obstruction Lights Present: No

ACCESS ROAD TO SITE

Access Road Condition: Sat Comments: Access to the tank is a paved road at the VA Hospital Site

FENCE

Fence Condition: Sat Comments: Tank is secured by a 8 ft steel fence Type: Decorative Height: 8 ft Gate / Site Entrance: Sat Locked?: Yes Width: 45 in

SITE LAYOUT

General Description of Site: VA Hospital Site

Distance to Nearest Structures: 12 Units: Feet Direction from Tank: East Structure Type: Commercial

Nearest Power Lines: 100 Units: Feet Direction from Tank: North

VALVE VAULT

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 2 of 29

Photo Description: General Exterior Tank View Photo Description: Utility building in close proximity to tank. Paved access to site

Photo Description: Security Fence Photo Description: Security Fence

Photo Description: Tank exterior view Photo Description: Security fence

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 3 of 29

NAME PLATE INFORMATION

RISER

Photo Description: Tank exterior view

Nameplate Present: Sat Comments: Good condition Location on Tank: East Attachment Details: Welded Serial or Contract Number: NA

Photo Description: Tank Name Plate located on the entrance door

RISER FOUNDATION

Riser Foundation Condition: Sat Riser Type: Dry Projection Above Grade: 2 in Concrete Condition: Sat

Exterior Coating Condition: Sat

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 4 of 29

ANCHOR BOLTS

Anchor Bolts Condition: Sat Number of Bolts: 16 Diameter: 1.5 in Condition: Good

ANCHOR BOLT CHAIRS

Anchor Bolt Chairs Condition: Sat Width: 6 in Height: 12 in Condition: Good

BASE PLATES

Base Plates Condition: Sat Riser Floor Plate Thickness: Sat

DIAGONAL BRACING

Diagonal Bracing Condition: N/A Comments: No diagonal bracing

RISER LADDER

Riser Ladder Condition: Sat Comments: Overall Good Condition Side Rail Size: 2.5 in Ladder Type: Continuous Rungs: Sat Size: 0.75 in Spacing: 12 in Width: 16 in Ladder Condition: Good Ladder Safe-Climbing Device Present: Yes Type: Cable Condition: Good

BRACKET

Bracket Condition: N/A

Painted: Yes

INLET / OUTLET PIPE

Inlet / Outlet Pipe Condition: Sat Comments: Appears in sound condition Circumference / Diameter: 6 in Reinforcing Plate: N/A Protective Cover: Sat Lead Joint: No

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 5 of 29

Photo Description: Tank foundation and surrounding area

Photo Description: Anchor bolts in typical condition

Photo Description: Anchor bolts in typical condition Photo Description: Overflow pipe discharge area

Photo Description: Overflow pipe mesh screen in good condition

Photo Description: Overflow pipe discharge area

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 6 of 29

Photo Description: Anchor bolts in typical condition Photo Description: Anchor bolts in typical condition

Photo Description: Anchor bolts in typical condition Photo Description: Anchor bolt chairs

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 7 of 29

Photo Description: Anchor bolt chairs

Photo Description: Tank foundation and bottom plate

Concrete pad is chipping

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 8 of 29

Photo Description: Overflow pipe

Photo Description: Overflow pipe Photo Description: Anchor Bolts

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 9 of 29

Photo Description: Interior Dry - interior piping

Photo Description: Interior Dry - Mechanical and electrical controls

Photo Description: Interior Dry

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 10 of 29

MANWAY

Photo Description: Interior Dry - Looking up the riser

Photo Description: Interior Dry

RISER MANWAY

Riser Manway Condition: Sat Comments: Riser manway entrance into lower bowl in good condition

Manway Type: Round Neck: N/A

ROOF MANWAY

Roof Manway Condition: Sat Comments: Roof manway is in good condition Manway Type: Round Size: 30 in

Locked: No

Curb: 12 in Cover Overlap: 5 in Welded: Outside

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 11 of 29

Photo Description: Roof manway opening Photo Description: Manway neck

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 12 of 29

Photo Description: Interior of manway lid with overlap Photo Description: Tank manway lid in good condition

Photo Description: Rider manway

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 13 of 29

Photo Description: Riser manway lid with overlap

Photo Description: Riser neck

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 14 of 29

Photo Description: Pressure sealed manway entrance to lower bowl

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 15 of 29

TOWER LADDER

Photo Description: Manway to exterior - top of riser

TOWER LADDER

Rung Shape: Square Rung Shape and Size: 0.75 in Rung Spacing: 12 in Width: 16 in Condition: Good Conduit Attachment: Yes Conduit Attachment Condition: Sat Ladder Safe Climbing Device Present: Yes Condition: Good Operational: Yes Safety Belt and Sleeve Available: Yes Painted: No

LADDER SAFETY CAGE

Ladder Safety Cage Present: No

VANDAL DETERRENT

Vandal Deterrent Present: No

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 16 of 29

LADDER PLATFORMS

Ladder Platforms Present: Yes

Drainage: Sat Condition: Good Do Ladders Extend Above Platforms: Yes

SAFETY RAIL

Safety Rail Present: No

Photo Description: View from roof into riser Photo Description: Dry Riser and ladder

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 17 of 29

Photo Description: Ladder with 12” spacing between rungs

Photo Description: Ladder with appropriate stand off distance between ladder and wall

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 18 of 29

EXTERIOR COMPONENTS

Photo Description: Riser Manway 24” opening

BOWL

Bowl Condition: Sat Comments: Overall condition of the bowl is good. No significant dents, damage, or other concerns

% Failure to Primer: 5 % % Failure to Rust: 0 % Overflow Pipe: Sat Comments: Overflow pipe in good condition. Drains to a splash pad and appears drainage is good Circumference/Diameter: 6 in Air Break: N/A Screen Type: #24 Drain Type: Splash Pad Brackets: N/A

BALCONY

Balcony Condition: N/A

Toe Bar: Sat Comments: Toe bar is present but there are areas where the distance above surface exceeds 0.25 in

Height Off Balcony: 0.25 in Size: 2 in Connection to Toe Bar and to Shell Present: N/A Comments: Toe bar is welded to safety railing upright Condition: Good

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 19 of 29

SHELL

Drainage: Sat

Balcony Entrance: N/A Balcony Obstruction Lights Present: No

SIGN/LOGO

Sign / Logo Present: Yes Condition: Fair Application Type: Painted Color: Blue

Photo Description: Logos are beginning to fade

EXTERIOR SHELL

Exterior Shell Condition: Sat Comments: Exterior shell appears in good condition % Failure to Primer: 0 % % Failure to Rust: 0 % Shell Rings: Sat Comments: Shell rings appear in sound condition Additional Remarks about the Shell: The overall condition of the shell appears to be good. There are no visible discontinuities or coating failures. The exterior top coat is beginning to chalk, showing signs of degradation.

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 20 of 29

ROOF

SHELL

Shell Condition: Sat Target Gage Present: N/A Level Gage Present: N/A Shell Coating Condition: Sat Comments: Overall coatings condition is good Shell and Roof Ladder: N/A Comments: Shell and Roof Ladder are in good condition Shell Ladder: Fixed Shell and Roof Ladder Safety Cage Present: No Bolted or Welded: Welded

INTERIOR SHELL

Interior Shell Condition: Sat Comments: The overall condition of the interior shell is good. There are no visible discontinuities or leaks visible

Shell Stiffening Angle Present: No Condition: Good Shell Coating Condition: Sat Comments: Areas above the typical water line are in good condition. Areas below the water line show initial stages of corrosion

Shell Rings: Sat Comments: Shell rings appear in good condition

ROOF LADDER

Roof Ladder Type: Fixed Brackets: N/A Comments: No roof ladder Ladder Safe-Climbing Device Present: Yes Type: Cable Condition: Good Vertical Bars: N/A Horizontal Bars: N/A

ROOF SAFETY RAILING

Roof Safety Railing Present: Yes Railing Type: Continuous Handrail: Sat Height: 42 in Size: 2 in Mid-rail Size: 2 in Upright Size: 2 in Toe Bar: Sat Comments: Toe rail in place. There are areas where the toe bar distance from the roof is greater than 0.25 in and object may pass between.

Size: 2 in Height Above Roof: 0.25 in

ROOF VENT

Roof Vent Condition: Sat Comments: Roof vent is in good condition Type: Non-Downturned Condition: Good Neck Height: 12 in Screen: Sat Comments: Screen is in good condition and free of debris

ROOF OBSTRUCTING LIGHTS

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 21 of 29

Roof Obstructing Lights Present: No

ANTENNAS

Antennas Present: Yes Number: 1 Location: East Antenna Attachment: Bracket Brackets: Sat

Photo Description: Roof toe bar. Some areas exceed 0.25in above the roof

Photo Description: Roof Safety Railing

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 22 of 29

Photo Description: Roof Safety Railing Photo Description: Roof Vent

Photo Description: Roof Vent

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 23 of 29

Photo Description: Roof Antenna

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 24 of 29

INTERIOR

Photo Description: Roof vent mesh screen in good condition

Photo Description: Roof vent mesh screen in good condition

ROOF STRUCTURE

Main Rafters / Stiffeners: N/A Comments: Visual only - appear in sound condition

INTERIOR

Coating Condition: Sat Comments: Coating condition is good. Areas below the typical water line show signs of coating degradation and early corrosion.

Type of Coating Failures: Staining Mixing System and Type: None Interior Ladder Present: Yes Rungs: N/A Comments: Visual observation only. Ladder has minor corrosion but appears in good condition Width: N/A Toe Room: N/A Ladder Condition: N/A Head Clearance: N/A Bracket: N/A Ladder Safe Climbing Device Present: Yes Overflow Pipe: Sat Comments: Overflow collection box visible on riser

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 25 of 29

Location of Overflow Inlet Below or Above Unwelded Seams: Overflow is welded to the interior riser

Inlet Type: Weir Box

Overflow Pipe Size: 6 in Bowl Coating Condition: Good Bowl Plate Thickness: N/A Welding Estimate in Container: N/A Seam Sealing / Pit Filling Estimates in Container: N/A Number of Gallons (approx): 250000 Riser Safety Grate: N/A Comments: Dry riser Interior Container Piping: N/A

Photo Description: Interior bowl - coating failure and staining visible

Photo Description: Coating failure and corrosion visible on riser connection

Photo Description: Interior roof view from bowl. Ladder in good condition

Photo Description: Interior roof view from bowl.

Coating above the water line and roof in good condition

Photo Description: Coating failure and staining visible on shell

Photo Description: Interior view looking up the riser -staining visible at typical water line

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 26 of 29

Photo Description: Interior ladder in sound condition Photo Description: Staining on shell - interior welds appear sound

Photo Description: Staining and minor corrosion visible on riser and connections

Photo Description: Interior

Photo Description: Overflow collection box

Photo Description: Interior Ladder

Photo Description: View of interior roof Photo Description: Interior manway hatch with corrosion and staining visible.

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 27 of 29

TESTING

REMARKS AND SIGNATURES

Photo Description: Interior piping with corrosion and staining visible in lower bowl

Location: Adhesion on exterior coating system is good. Tank is candidate for clean and overcoat Adhesion Test: Yes Location: South Type: Type A Results: 4A

REMARKS

The tank was evaluated on 7/23/2024. At the time of evaluation, the overall condition of the tank is good. The exterior of the tank is in good condition with no significant coating failures or discontinuities visible. The exterior coating is lightly “chalking”, indicating that the Polyurethane top coat UV protection is beginning to wear down. The existing coating system shows good adhesion properties making this tank a candidate for washing and overcoating. Overcoating would extend the service life of the existing coating while providing adequate protection to the structure.

The interior coating system is in overall good condition. Coating failure and localized corrosion were visible but were limited to below the typical water line. Corrosion was visible along the riser, on the shell and in the lower bowl areas but it was minor.

The tank has been well kept and in turn the coating system has performed well. Due to the age of the current coating system and the early indication of corrosion, B&N would recommend that that interior coating system be removed and replaced at a time that is feasible for the tank owner. New NSF/ANSI 61 compliant coating systems are now available that ensures materials and products are safe for public use. A proactive approach to the tanks maintenance plan would ensure that the tank can continue to properly function and provide the VA hospital with the appropriate water supply needed to run daily operations.

The toe bar connected to the safety railing on the roof has areas where the distance above the surface exceeds 0.25 in. OSHA regulations state the maximum height above the surface is 0.25 inches to avoid objects falling below.

SIGNATURES

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 28 of 29

SINGLE PEDESTAL TANK INSPECTION REPORT APPROVAL SIGNATURES

Name: Derek Goff Type: Quality Systems Manager Date: 07/30/2024, 12:00 PM EDT

Name: Derek Goff Date: 07/30/2024, 12:01 PM EDT

Name: Derek Goff Date: 08/02/2024, 10:46 AM EDT

The information contained herein is confidential and cannot be reproduced or distributed without prior written consent. © 2024 Page 29 of 29

File details come from the government source that posted it. Updated .