36C25026Q0505 0001.docx
DOCX document 62 KB Posted
- Attached to
- Z2DZ--Improve Security and Safety 539-25-507
- Solicitation number
- 36C25026Q0505
About this file
This file is an Amendment/Modification to a Request for Quote (RFQ) issued by the Department of Veterans Affairs Network Contracting Office (NCO) in Cincinnati, Ohio for Project No. 539-25-507, Improve Site and Security for the Veterans Affairs Medical Center (VAMC) in Cincinnati, Ohio. The amendment (36C25026Q0505 0001) was issued on 06-17-2026 to provide the Government's responses to Requests for Information (RFIs) submitted by offerors. The contracting officer is Ronald Heidemann, and the bid date remains 06-25-2026.
The RFI responses address technical specifications and clarifications for door installation and access control systems. Key requirements include: solid core wood interior doors with natural birch veneer (1 3/4" thick, Grade A prefinished) with stainless steel armor plating at half height; door hardware to comply with NFPA 80 standards with manufacturer markings, specifically Corbin Russwin ED5000 Series Panic Hardware and Assa Abloy EPT/EPTL Electric Power Transfer components; access control systems utilizing JCI motion sensors on both sides with video call intercom relocation and card reader functionality; automatic door opening during business hours (6AM-6PM) via motion sensor and off-hours access via card reader or video intercom; interlock functionality with fire alarm systems to unlock doors; and a wander guard system with free egress at all times. The project timeline is 185 calendar days including material lead time. Existing door frames may remain and be repainted with Soft Off White ICI paint. All wiring for door controls and re-use of existing access control junction boxes and conduit connections are required.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment Drawing REF1 -V2.pdf | ||
| Atch 1 -WD.pdf | ||
| Atch 6 - REF1 Drawing.pdf | ||
| Atch 9 - Request for Information.docx | DOCX document | |
| Atch 12 - Single Source JCI PACS Redacted.pdf | ||
| Atch 13 - Single Source RF Technologies Redacted.pdf | ||
| 36C25026Q0505_1.docx | DOCX document | |
| Atch 3 - A Drawing.jpg | JPG image | |
| Atch 4 - B Drawing.jpg | JPG image | |
| Atch 5 - C Drawing.jpg | JPG image | |
| Atch 2 - CombinedSpecs 539-25-507.pdf | ||
| Atch 11 - VHA PCRA 2024_Final539-25-507.pdf | ||
| Atch 7 - VHA Directive 1192.01, Seasonal Influen..pdf | ||
| Atch 8 - Contractor EMR Certification Form.docx | DOCX document | |
| Atch 10 - Instructions for VAAR 852.219-75.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO:
Specify authority)
THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 06-17-2026 539-26-2-6074-0021 539-25-507 36C250 Department of Veterans Affairs Network Contracting Office (NCO) 10 260 E. University Avenue Cincinnati OH 45219 36C250 Department of Veterans Affairs Network Contracting Office (NCO) 10 260 E. University Avenue Cincinnati OH 45219 To all Offerors/Bidders
36C25026Q0505 05-27-2026
X X X 539-3660162-6074-854200- 3223 23
NRNR001
X This amendment is issued to provide the following information:
-Post the Government's response to the RFI's (see page 2)
Ronald Heidemann Contracting Officer
NCO1015L3-0502
CONTINUATION PAGE
IMPROVE SITE AND SECRUITY
FOR THE
VETERANS AFFAIRS MEDICAL CENTER (VAMC)—CINCINNATI, OH
PROJECT NUMBER: 539-25-507
QUESTIONS AND ANSWERS (RFIs)
TO REQUEST FOR QUOTE (RFQ) NUMBER
36C25026Q0505
QUESTIONS AND ANSWERS
1. RFI #1 Question: Please resubmit the Atch+6+-+REF1++Drawing.pdf because we cannot read the drawings. They are too blurry.
Answer: Please review re-submission. Notes added from reference drawing. Reference #7 for control needs from JCI (see attached drawing).
2. RFI #2 Question: Is the bid date of 6/25/2026 still accurate?
Answer: Yes
3. RFI #3 Question: Are there any door schedules?
Answer:
| Door |
| Door Description |
| Fire Rating |
| Type |
| Material |
| Size |
| # |
| W |
| H |
| T |
| HG |
| WD |
| 2 |
| 3'-5" |
| 7'-0" |
| 1 3/4" |
| 1 1/2 hour fire |
Typical Interior door to be solid core wood doors: Natural Birch Veneer; Rotary cut “RA100”; 1 3/4” thick; ½” Maximum under cut. Grade A Prefinished.
Stainless Steel door protection to be installed using the following: Half height (door) stainless steel armor plates shall be installed
4. RFI #4 Question: When it comes to the door hardware are there any manufacturer preferences/standards?
Answer:
Current: Corbin Russwin Inc., ED5000 Series Panic Hardware 265M, Assa Abloy EPT/EPTL Electric Power Transfer All hardware components, including hinges, closers, and latches, must bear manufacturer markings indicating fire suitability. NFPA 80, Section 4.3 specifies that hinges must be steel or stainless steel with ball bearings
5. RFI #5 Question: What is the timeline for this project?
Answer: Including material lead time; specifically, doors, 185 calendar days.
6. Can existing door frame remain?
Answer: Yes…Soft Off White ICI Paints, paint frame.
7. Access Controls for Door.
Answer: JCI- motion sensor both sides. Video call intercom system relocation.
Control system from breezeway to CLC building 2 side: If off hours then card reader or video intercom system will auto open doors when access is valid. If timing during business hours 6AM-6PM then motion sensor will automatically open the door.
CLC building 2 to breezeway will have motion sensors on. Installation of wander guard system. Free egress at all times.
Including: presence sensors.
Upon activation of fire alarm: panic device latches remain latched and automatic operator disabled.
Existing access control junction box with conduit connections, wall mounted reader, intercom and wiring to be maintained and re-used for new wiring of new door/pacs equipment. Providing all wiring for door controls. Provide interlock with fire alarm to unlock doors.
ATTACHMENT:
Attachment Drawing REF1 -V2.
image1.png
File details come from the government source that posted it. Updated .