S02 Drawings - 515-21-101.pdf

PDF 33 MB Posted

Attached to
Z1DA--HVAC Upgrades Phase II 515-21-101 Federal contract opportunity
Solicitation number
36C25023B0045
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document is a presolicitation notice for an invitation for bids on an HVAC upgrades project at a VA medical center. The Department of Veterans Affairs intends to solicit bids for project 515-21-101 to provide all labor, materials, equipment, and supervision to complete HVAC upgrades at the VA medical center in Battle Creek, Michigan. The project magnitude is estimated between $2-5 million. The contract type will be firm fixed price with an award date targeted within 120 days of bid opening in May 2023. This is a 100% set-aside for qualified Service-Disabled Veteran Owned Small Businesses. The NAICS code is 238220 for plumbing, heating, and air conditioning contractors with a $19 million small business size standard. All work must comply with manufacturer recommendations, codes and standards and be performed during normal business hours excluding federal holidays.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXECUTIVE MEDICAL CENTER DIRECTOR

PROJECT # 515-22-101 SIGNATURE DATE

ASSISTANT DIRECTOR

ASSOCIATE DIRECTOR

CHIEF OF STAFF

ASSOCIATE DIRECTOR FOR PATIENT SERVICES

ASSOCIATE C.O.S. FOR MENTAL HEALTH

CHIEF. FMS

CHIEF, ENGINEERING SECTION

CHIEF, ENVIRONMENTAL MANAGEMENT SECTION

INFECTIOUS CONTROL OFFICER

PATIENT SAFETY MANAGER

GEMS COORDINATOR

SAFETY SPECIALIST

CHIEF, POLICE SERVICE

CHIEF, FIRE SECTION

UNION SAFETY REPRESENTATIVE

CONTRACTING OFFICER

CONTRACTING OFFICER REPRESENTATIVE

PROJECT LOCATION

PROJECT LOCATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C U s e rs

\c h a w k \D o c u m e n ts \1

.1

.1

A v c h a w k D

D

W

.r v t

/7

/2

:2

:4

P M

GI000

COVER SHEET

GUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 CDH DMC

515-21-101

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK VA MEDICAL CENTER

BATTLE CREEK, MI

100% BID DOCUMENTS

100% BID DOCUMENTS

FULLY SPRINKLERED

SHEET INDEX

SHEET NUMBER SHEET NAME

GENERAL

GI000 COVER SHEET

05-GI101 BUILDING 05 - LIFE SAFETY PLAN

05-GC101 BUILDING 05 - INFECTION CONTROL/PHASING PLAN

14-GI102 BUILDING 14 - LIFE SAFETY PLAN

14-GC102 BUILDING 14 - INFECTION CONTROL/PHASING PLAN

83-GI103 BUILDING 83 - LIFE SAFETY PLAN

83-GC103 BUILDING 83 - INFECTION CONTROL/PHASING PLAN

HA101 BUILDING 05 & 83 - HAZARDOUS MATERIAL REMOVAL PLAN

CIVIL

05-C100 BUILDING 05 - SITE PLAN

14-C100 BUILDING 14 - SITE PLAN

83-C100 BUILDING 83 - SITE PLAN

ARCHITECTURAL

AE001 ARCHITECTURAL SYMBOLS AND ABBREVIATIONS

05-AD101 BUILDING 05 - FIRST FLOOR REFLECTED CEILING DEMO PLAN

05-AD102 BUILDING 05 - DEMOLITION ATTIC PLAN

05-AE111 BUILDING 05 - FIRST FLOOR REFLECTED CEILING PLAN

14-AD100 BUILDING 14 - DEMOLITION FLOOR PLANS

14-AE100 BUILDING 14 - FLOOR PLANS

83-AD102 BUILDING 83 - BASEMENT FLOOR REFLECTED CEILING DEMO PLAN

83-AE112 BUILDING 83 - BASEMENT FLOOR REFLECTED CEILING PLAN

FIRE SUPPRESSION

F001 FIRE SUPPRESSION COVER SHEET

05-FS100 BUILDING 05 - FIRE SUPPRESSION PLAN

14-FS100 BUILDING 14 - FIRE SUPPRESSION PLAN

83-FS100 BUILDING 83 - FIRE SUPPRESSION PLAN

MECHANICAL

M001 ABBREVIATIONS, LEGENDS & DRAWING INDEX

05-MD103 BUILDING 05 - ATTIC PLAN - REMOVALS

05-MH101 BUILDING 05 - FIRST FLOOR PLAN - DUCTWORK

05-MH103 BUILDING 05 - ATTIC PLAN - DUCTWORK

05-MP103 BUILDING 05 - ATTIC PLAN - PIPING

14-M100 BUILDING 14 - BASEMENT PLAN

14-M101 BUILDING 14 - FIRST FLOOR PLAN

14-M102 BUILDING 14 - SECOND FLOOR PLAN

14-MD103 BUILDING 14 - ATTIC PLAN - REMOVALS

14-MH103 BUILDING 14 - ATTIC PLAN - DUCTWORK

14-MP100 BUILDING 14 - STEAM RISER

14-MP103 BUILDING 14 - ATTIC PLAN - PIPING

83-MD100 BUILDING 83 - BASEMENT PLAN - REMOVALS

83-MH100 BUILDING 83 - BASEMENT PLAN - DUCTWORK

83-MP100 BUILDING 83 - BASEMENT PLAN - PIPING

M401 BUILDING 05 ENLARGED MECHANICAL PLANS

M402 BUILDING 14 HX ENLARGED MECHANICAL PLANS

M403 BUILDING 14 AHU'S 1 & 2 ENLARGED MECHANICAL PLANS

M404 BUILDING 14 AHU'S 3 & 4 ENLARGED MECHANICAL PLANS

M405 BUILDING 83 ENLARGED MECHANICAL PLANS

M501 MECHANICAL DETAILS

M502 MECHANICAL DETAILS

M503 MECHANICAL DETAILS

M504 MECHANICAL DETAILS

M505 MECHANICAL DETAILS

M506 MECHANICAL HOT WATER SYSTEM SCHEMATIC

M601 MECHANICAL SCHEDULES

M602 MECHANICAL SCHEDULES

M701 MECHANICAL CONTROLS

M702 MECHANICAL CONTROLS

M703 MECHANICAL CONTROLS

M704 MECHANICAL CONTROLS

ELECTRICAL

E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS

05-EDP100 BUILDING 05 - BASEMENT FLOOR DEMOLITION POWER PLAN

05-EDP103 BUILDING 05 - ATTIC FLOOR DEMOLITION POWER PLAN

05-EP100 BUILDING 05 - BASEMENT FLOOR POWER PLAN

05-EP103 BUILDING 05 - ATTIC FLOOR POWER PLAN

14-EDP103 BUILDING 14 - ATTIC FLOOR DEMOLITION POWER PLAN

14-EP103 BUILDING 14 - ATTIC FLOOR POWER PLAN

83-EDP100 BUILDING 83 - BASEMENT FLOOR DEMOLITION POWER PLAN

83-EP100 BUILDING 83 - BASEMENT FLOOR POWER PLAN

EP500 ELECTRICAL DETAILS

EP600 ELECTRICAL SCHEDULES

Contact:Contact:Contact: Contact:

GUIDON DESIGN INC.

Christopher Hawk

PE, Project Manager

MECHANICAL,

ELECTRICAL &

PLUMBING

Mark Vanderwoude

PE

STRUCTURAL

ENGINEER

GUIDON DESIGN INC.BATTLE CREEK VA MEDICAL CENTER

Brian Maher

COR

5500 Armstrong Road Battle Creek, MI 49037 p: 269.966.5600 x 35487 e: brian.maher@va.gov

OWNER

GUIDON DESIGN INC.

James Gooden

Architect

1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 145 e: jgooden@guidondesign.com

ARCHITECT

1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 119 e: mvanderwoude@guidondesign.com

1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 167 e: chawk@guidondesign.com

AREA MAP

VICINITY MAP

CAMPUS MAP

PROJECT LOCATION

Contact:

HEAPY, INC.

William Samson

PE

MECHANICAL,

ELECTRICAL &

PLUMBING

1440 W Dorothy Lane Dayton, OH 45409 p: 937.224.0861 x 1024 e: wjsamson@heapy.com

N

N

N

Revisions: Date:

DN

DN

DN

MAIN REFRIGERATION

STORAGE

TRANSFORMER RM

004A

STAIR

S3

ELEV

STAIR

S4

005E

C01

CRAWL SPACE

CRAWL SPACE CRAWL SPACE

CRAWL SPACE

EXIT

E X

IT

STAIR

S2

TOILET

100D

HSK

100G

STOR

100F

PATIENT DINING

SERVING

100L

DISHWASHING AREA

101E

FOOD BANK

REFRIGERATOR

101D

FOOD TRAY

ASSEMBLY

REFRIG

101C

REFRIG

119C

SOILED LINEN

REFRIG

119B

STOR

118 REFRIG

FREEZER

116A

STORAGE

116B

RECEIVING

TOILET

PAPER STORAGE

112B

PAPER STORAGE

112A

CART WASH

STAIR

S3

ELEV

TEMPORARY DRY

STORAGE

103H

CLOSET

103F

CHIEF

103D

SECRETARY

103C

CLINICAL SECTION

CHIEF

103B

TEMPORARY TRAY

LINE

103K

TEMPORARY KITCHEN

103G

REFRIG.

EQUIPMENT CLEANING

INGREDIENT CONTROL

108A

INGREDIENT CONTROL

CLERKS

TOILET

106A

HSK

REFRIG.

NOURISHMENT

101B

SUPERVISORS

TOILET

LOCKER RM

102A

FIRE CLOSET

103A SUPERVISOR

101A

STORAGE

100B

STAIR

S1

RETAIL STORE

100A

PATIENT DINING

CHIEFS OFFICE

100I

CANTEEN OFFICE

100H

CLOSET

100HA

FOOD COURT

100C

OFFICE

100J

SERVING

100K

ELEC

100E

COOKING/ FOOD PREP

FIRE CLOSET

101B

HALL

C15

HALL

C13

HALL

C12A

HALL

C14

HALL

C12

HALL

C11

E X

IT

EXIT

EXIT

E X

IT

E X

IT

STAIR

S2

STAIR

S1 IT

ATTIC

EXIT

EXIT

CODE CRITERIA

GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED

EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC

HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.

NOTES:

CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE

AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

CODE REVIEW

THE 2021 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS. FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE HAS BEEN USED.

PROJECT SCOPE

THE PROJECT SCOPE IS WITHIN A VARIETY OF BUILDING AND DOES NOT AFFECT CONSTRUCTION TYPE, CHANGE OCCUPANCY TYPES OR MEANS OF EGRESS ROUTES. THE REQUIRED CONSTRUCTION AFFECTING CONSTRUCTION RATINGS SHALL MATCH EXISTING ADJACENT CONSTRUCTION TYPE AT TO MEET THE FIRE RESISTIVE RATING OUTLINED BELOW. MEANS OF EGRESS WILL NOT CHANGE. THE EXISTING CONSTRUCTION AND CODE PARAMETERS WILL REMAIN UNCHANGED. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241 WHERE CONSTRUCTION WILL REQUIRE AREA UNDER CONSTRUCTION TO NOT BE PROTECTED BY A FIRE SPRINKLER SYSTEM. THERE IS NO ANTICIPATED AE SCOPE REQUIRED FOR COORDINATION WITH THE STATE HISTORIC PRESERVATION OFFICE.

CODE ANALYSIS

THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2021 IBC. CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE IB AND LSC 18 CONSTRUCTION AS FOLLOWS:

1. OCCUPANCY TYPE: I-2 INSTITUTIONAL, IBC CHAPTER 3/LSC CHAPTER 18 HEALTHCARE

2. CONSTRUCTION TYPE: IB (IBC CHAPTER 5)

3. FIRE RESISTIVE RATINGS TYPE IB CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:

STRUCTURAL FRAME: NONCOMBUSTIBLE, 2-HOUR FIRE RESISTIVE

BEARING WALLS

EXTERIOR: NONCOMBUSTIBLE, 2-HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 2-HOUR FIRE RESISTIVE

NON-BEARING WALLS AND PARTITIONS

EXTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE-RESISTIVE

FLOOR: NONCOMBUSTIBLE, 2-HOUR FIRE RESISTIVE

ROOF: NONCOMBUSTIBLE, 1-HOUR FIRE RESISTIVE

SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE >4 STORIES (IBC 713.4, LSC 12.3.6)

SHAFT ENCLOSURES 1-HOUR FIRE RESISTIVE <4 STORIES (IBC 713.4, LSC 12.3.6)

4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC.

5. ALLOWABLE HEIGHT: EXISTING, NO CHANGE (IBC, TABLE 504.3)

6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: EXISTING, NO CHANGE (IBC, TABLE 504.4)

7. ALLOWABLE AREA: EXISTING, NO CHANGE (IBC, TABLE 506.2)

8. BUILDING SEPARATION: EXISTING, NO CHANGE (IBC, TABLE 602)

9. OCCUPANCY SEPARATION: EXISTING, NO CHANGE

10. MEANS OF EGRESS: EXISTING, NO CHANGE

11. WHERE GENERAL ANESTHESIA OR LIFE SUPPORT EQUIPMENT IS USED AND ESSENTIAL ELECTRICAL SYSTEM PER NFPA 99 SHALL BE PROVIDED.

12. HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS DESCRIBED IN TABLE 18.3.2.1 SHALL BE PROTECTED

AS INDICATED. (LSC 18.3.2.2)

TABLE 18.3.2.1 HAZARDOUS AREA PROTECTION

HAZARDOUS AREA DESCRIPTION: PROTECTION / SEPARATION (MINIMUM FIRE RESISTANCE RATING)

• BOILER AND FUEL-FIRED HEATER ROOMS: 1 HOUR

• CENTRAL/BULK LAUNDRIES LARGER THAN 100 FT2 (9.3 M2): 1 HOUR

• LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE MATERIALS IN QUANTITIES LESS THAN THOSE THAT WOULD BE CONSIDERED A SEVERE HAZARD:

SEE 18.3.6.3.11.

• LABORATORIES THAT USE HAZARDOUS MATERIALS THAT WOULD BE CLASSIFIED AS A SEVERE HAZARD IN ACCORDANCE WITH NFPA 99, STANDARD FOR HEALTH CARE

FACILITIES: 1 HOUR

• PAINT SHOPS EMPLOYING HAZARDOUS SUBSTANCES AND MATERIALS IN QUANTITIES LESS THAN THOSE THAT WOULD BE CLASSIFIED AS A SEVERE HAZARD: 1

HOUR

• PHYSICAL PLANT MAINTENANCE SHOPS: 1 HOUR

• ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL (242 L): 1 HOUR

• STORAGE ROOMS LARGER THAN 50 FT2(4.6 M2) BUT NOT EXCEEDING 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL: SEE 18.3.6.3.11.

• STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL: 1 HOUR

• ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GAL (242 L): 1 HOUR

13. INTERIOR FINISH

• WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 10.2 OF THE NFPA 101 TO CLASS A MATERIALS. (LSC 18.4.3.6.2)

• · CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.

• FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I.

• FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS SERVING AS

FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD METHODS OF FIRE

TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.

• UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA 260, NFPA

261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590

14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.

15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.

• FIRE ALARM SYSTEM SHALL BE PROVIDED LSC, NFPA 70 (NEC) AND NFPA 72. (LSC 9.6.1)

• FIRE ALARM MAY BE BY MANUAL MEANS (LSC 18.3.4.2.1)(LSC 9.6.2)

• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS PER 9.6.3. (LSC 18.3.4.3)

• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.

• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM PER 9.6.4. (LSC 18.3.4.3.2)

16. FIRE SUPPRESSION:

SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.

THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF VETERANS

AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:

STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:

ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 250 GPM

ALL OTHER AREAS SHALL BE PROTECTED AS:

LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 100 GPM

ALL SPRINKLERS WITHIN THE SMOKE ZONE SHALL BE QUICK RESPONSE SPRINKLERS.

17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.

CODE ANALYSIS - NFPA 101, INSTITUTIONAL HEALTHCARE CHAPTER 18

REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS,

GUIDELINES AND REGULATIONS, BELOW LISTING IS NOT

COMPREHENSIVE.

NFPA 10 Standard for Portable Fire Extinguisher NFPA 13 Standard for The Installation of Sprinkler Systems NFPA 72 Fire Alarm Code NFPA 70, NEC National Electrical Code NFPA 80 Standard for Fire Doors and Fire Windows NFPA 99 Healthcare Facilities Code NPFA 101 Life Safety Code NFPA 220 Standard on Types of Building Construction NFPA 241 Standard for Safeguarding Construction Alteration, And Demolition Operations

ICC Codes, International Code Council full listing of current codes, Including but not limited to:

International Building Code International Plumbing Code International Mechanical Code International Fuel Gas Code International Fire Code International Energy and Conservation Code

ASHRAE Standards, as referenced within other codes including, but not limited To:

Standard 90.1-2013, Energy Standard for Buildings except Low-Rise Residential Buildings Standard 170-2017, Ventilation of Healthcare Facilities Standard 188-2018, Legionellosis: Risk Management For Building Water Systems

Accessibility Codes ADAAG, Ada Accessibility Guidelines VA Barrier Free Design Guide Pg-18-13, ABAAS

FGI, The Facility Guidelines Institute Guidelines for Design and Construction of Hospitals Guidelines for Design and Construction of Outpatient Facilities

Systems Relating to Maintenance of Facilities Osha, Occupational, Safety and Health Administration Standards

Codes and guidelines referenced within NFPA And ICC codes are to also be followed and applied to all design and construction. Refer to VA Manual Pg-18-3, specifications for additional codes, standards, guidelines and regulations.

Contractor Is responsible for constructing work compliant with OSHA, Occupational, Safety and Health Administration Standards.

VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD

STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

GOVERNING CODES

VA DESIGN MANUALS PG-18-10

ARCHITECTURAL

ASBESTOS ABATEMENT

AUTOMATED TRANSPORT SYSTEMS

COMMISSIONING AND RETRO COMISSIONING

ELECTRICAL

ESTIMATING

FIRE PROTECTION

HVAC

INTERIOR DESIGN

LIGHTING DESIGN

PHYSICAL SECURITY

PLUMBING

SITE PARKING, SITE DEVELOPMENT, SITE APPENDIX

STEAM, HEATING, HOT WATER, AND OUTSIDE DISTRIBUTION

SYSTEMS

STRUCTURAL

SUSTAINABILITY

TELECOMMUNICATIONS

AUG-14

JUL-11

NOV-20

NOV-13

DEC-19

MAR-11

DEC-15

NOV-20

NOV-20

DEC-15

OCT-20

NOV-14

APR-13, FEB-13

SEPT-16, NOV-20

FEB-14

MAY-14

TEB-16

2018 ED

2019 ED

2019 ED

2020 ED

2019 ED

2018 ED

2018 ED

2021 ED

2019 ED

2018 ED

2018 ED

2018 ED

2018 ED

2018 ED

2018 ED

2018 ED

2018 ED

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C

U s e rs \d c h ri s te n s e n \D o c u m e n ts \1

.1

.1

A v d c h ri s te n s e n M

N F

X

.r v t

/7

/2

:2

:4

P M

05-GI101

BUILDING 05 - LIFE SAFETY PLAN

GUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 JLG DMC

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/16" = 1'-0"05-GI101

2 B05 - BASEMENT

SCALE: 1/16" = 1'-0"05-GI101

3 B05 - FIRST FLOOR

SCALE: 1/16" = 1'-0"05-GI101

4 B05 - ATTIC

Revisions: Date:

KEY PLAN

Scale: NTS

NN N

DN

DN

TEMPORARY IC BARRIER WALL

CONSTRUCTION (DUST WALL)

5/8" TYPE X GYP BD

3 5/8" STEEL STUDS @ 16" O.C.

BEAD OF CONT. SEALANT

6-MIL FIRE RETARDENT POLY INTERIOR SIDE

CEILING

2" DEEP LEG 3 5/8" STEEL SLIP TRACK

3 5/8" STEEL STUD TRACK

6" M

IN

CONTINUOUSLY ADHERE 6-MIL. FIRE

RETARDANT POLY TO DECK WITH TAPE

CONTINUOUSLY ADHERE FIRE RETARDENT

POLY TO FLOOR WITH TAPE

EXISTING DECK

CONSTRUCTION

SIDE

OCCUPIED

SIDE

PUBLIC

SIDE

1 HOUR FIRE RATED METAL DOOR ASSEMBLY

AND FRAME WITH SEALS, CARD READER,

HARDWARE AND CLOSER

TRIATEK MONITOR

HAND SANITIZER

SEAL ALL EDGES WITH TAPE

SEAL ALL EDGES WITH TAPE

REFER TO TEMPORARY BARRIER TYPE FOR

REQUIRED CONDITION TO STRUCTURE ABOVE

VA / OSHA TEMPORARY SIGNAGE

INFECTION CONTROL PROJECT INFORMATION

CONSTRUCTION ACTIVITY - FIRE RISK: D

PATIENT RISK GROUP: LOW

CLASS OF PRECAUTION MATRIX: II

A. REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED

BY CLASS IN SPECIFICATION 010110 AND ADDITIONAL INFORMATION.

B. REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE

FOR ADDITIONAL INFORMATION.

C. COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND

FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE

CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE

PROJECT BOUNDARY.

D. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER

WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR

AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY

IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE

APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND

PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA

PROTOCOLS AND PLAN IS APPROVED.

E. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR

AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE

PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR

PROVIDED CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW

THE FLOOR PLATE OF THE PROJECT BOUNDARY.

F. ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 5:00 PM

AND 5:00 AM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE

CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED

IN A SAFE MANOR UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED

AND BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.

G. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED

DURING NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF

OPERATION.

H. WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE BETWEEN

THE HOURS OF 5:00 PM AND 5:00 AM. EVERY EFFORT SHALL BE MADE TO

KEEP NOISE AND VIBRATION TO A MINIMUM.

I. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36"

STICKY WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR

LOCATION. MAT SHALL BE REPLACED OR CLEANED AS NECESSARY

J. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH

TEMPORARY DOOR LOCATION.

K. CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,

MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE

LIQUIDS UP TO 30 GALLONS.

L. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED

WITH 4 MIL. POLY SHEET.

M. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT

BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED

ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED

WITH A LID.

N. ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY

STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE

MATERIALS SHALL NOT BE STORED IN THE FACILITY.

O. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE

PROJECT BOUNDARY.

A. PROJECT AREAS TO BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT

CONSTRUCTION.

B. PROJECT SHALL BE COMPLETED DURING NIGHT SHIFTS, 7:00 PM TO 5:00 AM

WHERE INDICATED. COORDINATE WITH COR. ALL WORK TO BE COMPLETED

AND OPEN FOR PUBLIC USE AT THE END OF EACH NIGHT'S WORK.

C. REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION

FOR EACH PHASE AND AREA OF WORK.

PHASING GENERAL NOTES

INFECTION CONTROL GENERAL NOTES

INFECTION CONTROL PLAN NOTES

TEMPORARY WALLS. SEE PLAN AND PLAN NOTES

TEMPORARY CONSTRUCTION ACCESS DOORS

REFERENCE AREA FOR ABOVE CEILING

WORK ON FLOOR BELOW.

RE: ENGINEERING DRAWINGS FOR FULL

SCOPE OF WORK

BEYOND PROJECT BOUNDARY

PROJECT BOUNDARY

IC / PHASING LEGEND

1. PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH

CARD READER ACCESS. REFER TO ELEVATION 2/GI101.

2. PROVIDE TEMPORARY INFECTION CONTROL BARRIER WALL CONSTRUCTION.

REFER TO DETAIL 1/GI101.

3. PROVIDE TEMPORARY INFECTION CONTROL PLASTIC BARRIER WALL

CONSTRUCTION. REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.

INFECTION CONTROL PLAN NOTES

1. SCOPE OF WORK IN THIS PROJECT AREA TO OCCUR BETWEEN 7:00 PM AND

5:00 AM ON WEEKDAY NIGHTS. SPACE AND SUPPORTING SYSTEMS SHALL BE

ONLINE PRIOR TO 5:00 AM.

PHASING PLAN NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C

U s e rs \d c h ri s te n s e n \D o c u m e n ts \1

.1

.1

A v d c h ri s te n s e n M

N F

X

.r v t

/7

/2

:2

:3

P M

05-GC101

BUILDING 05 - INFECTION

CONTROL/PHASING PLANGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 JLG DMC

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1 1/2" = 1'-0"05-GC101

1 TEMPORARY INFECTION CONTROL BARRIER WALL CONSTRUCTION

SCALE: 1/4" = 1'-0"05-GC101

2 TEMPORARY WALL CONSTRUCTION ELEVATION

SCALE: 1/16" = 1'-0"05-GC101

4 B05 - BASEMENT IC/PHASING PLAN

SCALE: 1/16" = 1'-0"05-GC101

6 B05 - ATTIC IC/PHASING PLAN

SCALE: 1/16" = 1'-0"05-GC101

5 B05 - FIRST FLOOR IC/PHASING PLAN

Revisions: Date:

KEY PLAN

Scale: NTS

N

N

E X

IT

E X

IT

E X

IT

E X

IT

E X

IT

E X

IT

E X

IT

E X

IT

EXIT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C

U s e rs \d c h ri s te n s e n \D o c u m e n ts \1

.1

.1

A v d c h ri s te n s e n M

N F

X

.r v t

/7

/2

:2

:4

P M

14-GI102

BUILDING 14 - LIFE SAFETY PLAN

GUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 JLG DMC

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/16" = 1'-0"14-GI102

1 B14 - BASEMENT LIFE SAFETY

SCALE: 1/16" = 1'-0"14-GI102

2 B14 - FIRST FLOOR LIFE SAFETY

SCALE: 1/16" = 1'-0"14-GI102

3 B14 - SECOND FLOOR LIFE SAFETY

SCALE: 1/16" = 1'-0"14-GI102

4 B14 - ATTIC LIFE SAFETY

NOTE:

REFER TO SHEET GI101 FOR CODE ANALYSIS.

Revisions: Date:

KEY PLAN

Scale: NTS

N

NN

INFECTION CONTROL PROJECT INFORMATION

CONSTRUCTION ACTIVITY - FIRE RISK: D

PATIENT RISK GROUP: LOW

CLASS OF PRECAUTION MATRIX: II

A. REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED

BY CLASS IN SPECIFICATION 010110 AND ADDITIONAL INFORMATION.

B. REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE

FOR ADDITIONAL INFORMATION.

C. COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND

FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE

CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE

PROJECT BOUNDARY.

D. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER

WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR

AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY

IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE

APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND

PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA

PROTOCOLS AND PLAN IS APPROVED.

E. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR

AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE

PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR

PROVIDED CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW

THE FLOOR PLATE OF THE PROJECT BOUNDARY.

F. ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 5:00 PM

AND 5:00 AM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE

CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED

IN A SAFE MANOR UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED

AND BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.

G. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED

DURING NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF

OPERATION.

H. WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE BETWEEN

THE HOURS OF 5:00 PM AND 5:00 AM. EVERY EFFORT SHALL BE MADE TO

KEEP NOISE AND VIBRATION TO A MINIMUM.

I. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36"

STICKY WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR

LOCATION. MAT SHALL BE REPLACED OR CLEANED AS NECESSARY

J. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH

TEMPORARY DOOR LOCATION.

K. CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,

MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE

LIQUIDS UP TO 30 GALLONS.

L. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED

WITH 4 MIL. POLY SHEET.

M. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT

BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED

ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED

WITH A LID.

N. ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY

STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE

MATERIALS SHALL NOT BE STORED IN THE FACILITY.

O. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE

PROJECT BOUNDARY.

A. PROJECT AREAS TO BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT

CONSTRUCTION.

B. PROJECT SHALL BE COMPLETED DURING NIGHT SHIFTS, 7:00 PM TO 5:00 AM

WHERE INDICATED. COORDINATE WITH COR. ALL WORK TO BE COMPLETED

AND OPEN FOR PUBLIC USE AT THE END OF EACH NIGHT'S WORK.

C. REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION

FOR EACH PHASE AND AREA OF WORK.

PHASING GENERAL NOTES

INFECTION CONTROL GENERAL NOTES

INFECTION CONTROL PLAN NOTES

TEMPORARY WALLS. SEE PLAN AND PLAN NOTES

TEMPORARY CONSTRUCTION ACCESS DOORS

REFERENCE AREA FOR ABOVE CEILING

WORK ON FLOOR BELOW.

RE: ENGINEERING DRAWINGS FOR FULL

SCOPE OF WORK

BEYOND PROJECT BOUNDARY

PROJECT BOUNDARY

IC / PHASING LEGEND

1. PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH

CARD READER ACCESS. REFER TO ELEVATION 2/GI101.

2. PROVIDE TEMPORARY INFECTION CONTROL BARRIER WALL CONSTRUCTION.

REFER TO DETAIL 1/GI101.

3. PROVIDE TEMPORARY INFECTION CONTROL PLASTIC BARRIER WALL

CONSTRUCTION. REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.

INFECTION CONTROL PLAN NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C

U s e rs \d c h ri s te n s e n \D o c u m e n ts \1

.1

.1

A v d c h ri s te n s e n M

N F

X

.r v t

/7

/2

:2

:4

P M

14-GC102

BUILDING 14 - INFECTION

CONTROL/PHASING PLANGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 JLG DMC

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/16" = 1'-0"14-GC102

1 B14 - BASEMENT IC/PHASING PLAN

SCALE: 1/16" = 1'-0"14-GC102

2 B14 - FIRST FLOOR IC/PHASING PLAN

SCALE: 1/16" = 1'-0"14-GC102

3 B14 - SECOND FLOOR IC/PHASING PLAN

SCALE: 1/16" = 1'-0"14-GC102

4 B14 - ATTIC IC/PHASING PLAN

Revisions: Date:

KEY PLAN

Scale: NTS

N

NN

EXIT

EXIT

E X

IT

E X

IT

EXIT

EXIT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C

U s e rs \d c h ri s te n s e n \D o c u m e n ts \1

.1

.1

A v d c h ri s te n s e n M

N F

X

.r v t

/7

/2

:2

:4

P M

83-GI103

BUILDING 83 - LIFE SAFETY PLAN

GUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 JLG DMC

100% BID DOCUMENTS

FULLY SPRINKLERED

NOTE:

REFER TO SHEET GI101 FOR CODE ANALYSIS.

SCALE: 1/16" = 1'-0"83-GI103

1 B83 - BASEMENT

Revisions: Date:

KEY PLAN

Scale: NTS

INFECTION CONTROL PROJECT INFORMATION

CONSTRUCTION ACTIVITY - FIRE RISK: D

PATIENT RISK GROUP: LOW

CLASS OF PRECAUTION MATRIX: II

A. REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED

BY CLASS IN SPECIFICATION 010110 AND ADDITIONAL INFORMATION.

B. REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE

FOR ADDITIONAL INFORMATION.

C. COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND

FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE

CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE

PROJECT BOUNDARY.

D. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER

WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR

AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY

IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE

APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND

PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA

PROTOCOLS AND PLAN IS APPROVED.

E. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR

AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE

PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR

PROVIDED CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW

THE FLOOR PLATE OF THE PROJECT BOUNDARY.

F. ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 5:00 PM

AND 5:00 AM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE

CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED

IN A SAFE MANOR UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED

AND BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.

G. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED

DURING NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF

OPERATION.

H. WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE BETWEEN

THE HOURS OF 5:00 PM AND 5:00 AM. EVERY EFFORT SHALL BE MADE TO

KEEP NOISE AND VIBRATION TO A MINIMUM.

I. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36"

STICKY WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR

LOCATION. MAT SHALL BE REPLACED OR CLEANED AS NECESSARY

J. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH

TEMPORARY DOOR LOCATION.

K. CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,

MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE

LIQUIDS UP TO 30 GALLONS.

L. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED

WITH 4 MIL. POLY SHEET.

M. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT

BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED

ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED

WITH A LID.

N. ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY

STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE

MATERIALS SHALL NOT BE STORED IN THE FACILITY.

O. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE

PROJECT BOUNDARY.

A. PROJECT AREAS TO BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT

CONSTRUCTION.

B. PROJECT SHALL BE COMPLETED DURING NIGHT SHIFTS, 7:00 PM TO 5:00 AM

WHERE INDICATED. COORDINATE WITH COR. ALL WORK TO BE COMPLETED

AND OPEN FOR PUBLIC USE AT THE END OF EACH NIGHT'S WORK.

C. REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION

FOR EACH PHASE AND AREA OF WORK.

PHASING GENERAL NOTES

INFECTION CONTROL GENERAL NOTES

INFECTION CONTROL PLAN NOTES

TEMPORARY WALLS. SEE PLAN AND PLAN NOTES

TEMPORARY CONSTRUCTION ACCESS DOORS

REFERENCE AREA FOR ABOVE CEILING

WORK ON FLOOR BELOW.

RE: ENGINEERING DRAWINGS FOR FULL

SCOPE OF WORK

BEYOND PROJECT BOUNDARY

PROJECT BOUNDARY

IC / PHASING LEGEND

DISH WASH

017A

KITCHEN

STAIR

S3

OFFICE

017F

HSK

017D

OFFICE

017C

OFFICE

017B

MECH

019E

M A

X

M A

X

1. PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH

CARD READER ACCESS. REFER TO ELEVATION 3/GI101.

2. PROVIDE TEMPORARY INFECTION CONTROL BARRIER WALL CONSTRUCTION.

REFER TO DETAIL 2/GI101.

3. PROVIDE TEMPORARY INFECTION CONTROL PLASTIC BARRIER WALL

CONSTRUCTION. REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.

INFECTION CONTROL PLAN NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C

U s e rs \d c h ri s te n s e n \D o c u m e n ts \1

.1

.1

A v d c h ri s te n s e n M

N F

X

.r v t

/7

/2

:2

:4

P M

83-GC103

BUILDING 83 - INFECTION

CONTROL/PHASING PLANGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 JLG DMC

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/16" = 1'-0"83-GC103

1 B83 - BASEMENT IC/PHASING PLAN

Revisions: Date:

KEY PLAN

Scale: NTS

DN

DN

PROJECT BOUNDARY

BEYOND PROJECT BOUNDARY

AREA FOR REMOVAL OF ASBESTOS-CONTAINING

FIBERGLASS DUCT COVERING

A. HAZMAT REMOVAL NOTES APPLY TO ENTIRE ROOMS. CONTRACTOR SHALL

IDENTIFY ALL MATERIALS DESCRIBED BY NOTE IN EACH ROOM AND

REMOVE ACCORDING TO SAFETY STANDARDS. REFERENCE SPECIFICATION

02 82 11.

B. ALL HAZARDOUS MATERIALS SHALL BE REMOVED IN COMPLIANCE WITH

APPLICABLE CODES AND LAWS.

C. THE CONTRACTOR IS RESPONSIBLE TO VERIFY THE HAZARD(S) AND LEVEL

OF PROTECTION REQUIRED FOR ALL EMPLOYEES OR SUBCONTRACTORS

TO COMPLETE THE CONSTRUCTION WORK.

D. REFER TO SPECIFICATION AND ATTACHMENTS FOR ADDITIONAL

INFORMATION.

1. REMOVE ASBESTOS-CONTAINING FIBERGLASS DUCT COVERING -

APPROXIMATE 4,800 SF.

2. REMOVE ASBESTOS-CONTAINING LAYERED PAPER PIPE INSULATION -

APPROXIMATE 25 LF.

3. REMOVE ASBESTOS-CONTAINING MUD JOINTS - APPROXIMATE 44 JOINTS.

HAZARDOUS MATERIAL REMOVAL GENERAL NOTES

HAZARDOUS MATERIAL REMOVAL PLAN NOTES

HAZARDOUS MATERIAL REMOVAL LEGEND

AREA FOR REMOVAL OF ASBESTOS-CONTAINING LAYERED

PAPER PIPE INSULATION AND MUD JOINTS

COOKING/ FOOD PREP

FOOD TRAY

ASSEMBLY

DISHWASHING AREA

101E

REFRIG

119C

REFRIG

101C

FOOD BANK

REFRIGERATOR

101D

REFRIG

INGREDIENT CONTROL

INGREDIENT CONTROL

108A

SUPERVISORS

CLERKS

HALL

C15

NOURISHMENT

101B

REFRIG.

HALL

C12A

SUPERVISOR

101A

STORAGE

100B

HALL

C12

PATIENT DINING

OFFICE

100J

SERVING

100K

SERVING

100L

DISH WASH

017A

KITCHEN

STAIR

S3

OFFICE

017F

HSK

017D

OFFICE

017C

OFFICE

017B

MECH

019E

2 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

937.224.0861

C

U s e rs \d c h ri s te n s e n \D o c u m e n ts \1

.1

.1

A v d c h ri s te n s e n M

N F

X

.r v t

/7

/2

:2

:5

P M

HA101

BUILDING 05 & 83 - HAZARDOUS

MATERIAL REMOVAL PLANGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

CHRISTOPHER HAWK

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

REPLACE HVAC SYSTEM PHASE II

BATTLE CREEK, MI

515-21-101

5, 14, 83

FREDERICK VOLLMERHAUSEN

04/07/2023 JLG DMC

100% BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

SCALE: 1/16" = 1'-0"HA101

1 B05 - FIRST FLOOR HAZMAT PLAN

SCALE: 1/16" = 1'-0"HA101

2 B83 - BASEMENT HAZMAT PLAN

KEY PLAN

Scale: NTS

KEY PLAN

Scale: NTS

N

N N

SECTION REFERENCE

DRAWING NUMBER

SHEET LOCATION

DRAWING NUMBER

SHEET

LOCATION

DETAIL REFERENCE

OBJECT

REFERENCED

OBJECT

REFERENCED

X

XXXX

X

XXXX

SCALE: ??

VIEW TITLE

N

NORTH ARROW

LED WALL MOUNTED LIGHT FIXTURE

LED SURFACE MOUNTED LIGHT FIXTURE

LED SURFACE MOUNTED LIGHT FIXTURE

LED RECESSED LIGHT FIXTURE

HVAC RETURN AIR GRILLE

HVAC SUPPLY DIFFUSER

PENDANT LIGHT

ACCESS PANEL

EXIT LIGHTING

S

D

SPEAKER

SMOKE DETECTOR

LED RECESSED LIGHT FIXTURE

A 9'-0"

CEILING TAG CEILING TYPE

FINISHED CEILING HEIGHT

REFER TO CEILING LEGEND FOR MORE

INFORMATION

EXTENT OF REVISION

REVISION SET

MECH/ELEC ITEMS: REFER TO MEP SHEETS AS APPLICABLE

PROJECT BOUNDARY

BEYOND PROJECT BOUNDARY, NIC

DETAIL/DRAWING SCALE

TITLE OF DETAIL/DRAWING

DETAIL/DRAWING NUMBER

SHEET NUMBER

A/C AIR CONDITION

A/E ARCHITECT/ENGINEER

AB ANCHOR BOLT

ABC AGGREGATE BASE COURSE

AC ASBESTOS CEMENT OR ASPHALTIC CONCRETE

ACS DR ACCESS DOOR

ACS FLR ACCESS FLOOR

ACS PNL ACCESS PANEL

ACST ACOUSTIC

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADC AUTOMATIC DOOR CLOSER

ADDL ADDITIONAL

ADDN ADDITION

ADH ADHESIVE

ADJ ADJACENT, ADJOINING, OR ADJUSTABLE

ADMIN ADMINISTRATION

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGGR AGGREGATE

AHJ AUTHORITY HAVING JURISDICTION

AHR ANCHOR

AHU AIR HANDLING UNIT

AIA AMERICAN INSTITUTE OF ARCHITECTS

AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINUM

AMP AMPERE

AMT AMOUNT

ANOD ANODIZE

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

ANT ANTENNA

APPD APPROVED

APPROX APPROXIMATE

AR AS REQUIRED

ARCH ARCHITECT

ASB ASBESTOS

ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION

ASKLR AUTOMATIC SPRINKLER

ASPH ASPHALT

ASSN ASSOCIATION

ATCH ATTACHMENT

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AVG AVERAGE

AW ACID WASTE

AWI ARCHITECTURAL WOODWORKING INSTITUTE

AWS AMERICAN WELDING SOCIETY

AWT ACOUSTICAL WALL TREATMENT

B PL BASE PLATE

BALC BALCONY

BAT BATTEN

BB BULLETIN BOARD

BD BOARD

BEV BEVEL

BI FLD DR BIFOLDING DOORS

BITUM BITUMINOUS

BKG BACKING

BLD BUILD

BLDG BUILDING

BLKG BLOCKING

BLKT BLANKET

BM BEAM OR BENCHMARK

BOT BOTTOM

BRCG BRACING

BRDG BRIDGING

BRG BEARING

BRKT BRACKET

BRZ BRONZE

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT-UP ROOFING

C CELSIUS CHANNEL OR CHANNEL CELSIUS

C CONC CAST CONCRETE

C TO C CENTER TO CENTER

CAB CABINET

CB CORNER BEAD

CBB CEMENTITIOUS (BACKER) BOARD

CC CUBIC CENTIMETER

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTERCLOCKWISE

CEM CEMENT

CEM PLAS CEMENT PLASTER

CER CERAMIC

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFLG COUNTERFLASHING

CFM CUBIC FEET PER MINUTE

CFMF COLD-FORMED METAL FRAMING

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CGSFU CERAMIC GLAZED STRUCTURAL FACING UNITS

CH BD CHALKBOARD

CHEM CHEMICAL

CHFR CHAMFER

CI CAST IRON

CIP CAST-IN-PLACE

CIR CIRCLE

CIRC CIRCULAR

CJ CONSTRUCTION JOINT OR CONTROL JOINT

CL CENTER LINE

CLDG CLADDING

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CNR CORNER

CNTR COUNTER

CO CARBON MONOXIDE, CLEANOUT

CO₂ CARBON DIOXIDE

COL COLUMN

COM COMMON

COMB COMBINATION, COMBINED

COMM COMMUNICATION

COMP COMPONENT

CONC CONCRETE

COND CONDENSER OR CONDITION

CONF CONFERENCE

CONN CONNECT

CONSTR CONSTRUCTION

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CORR CORRIDOR

CPM CRITICAL PATH METHOD

CPRS COMPRESSIBLE

CPT CARPET

CRS COLD ROLLED STEEL

CS CAST CONCRETE STONE

CSB CONCRETE SPLASH BLOCK

CSG CASING

CSK COUNTER SUNK

CSMT CASEMENT

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTF CERAMIC TILE FLOOR

CTG COATING

CTR CENTER

CTRL CONTROL

CTV CABLE TELEVISION

CU COPPER C

CU FT CUBIC FEET

CU IN CUBIC INCH

CU YD CUBIC YARD

CURT CURTAIN

CYL CYLINDER

CYL L CYLINDER LOCK

N NORTH

NA NOT APPLICABLE

NAT NATURAL

NATL NATIONAL

NC NOISE CRITERIA

NCOMBL NONCOMBUSTIBLE

NEG NEGATIVE

NEUT NEUTRAL

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NR NOISE REDUCTION

NRC NOISE REDUCTION COEFFICIENT

NRP NONREMOVABLE

NS NARROW STILE

NUM NUMERAL

O/O OUT TO OUT

O OXYGEN

OA OUTSIDE AIR OR OVERALL

OC ON CENTER

OCC OCCUPY

OCT OCTAGON

OD OUTSIDE DIAMETER OR OUTSIDE DIMENSION

OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED

OFD OVERFLOW DRAIN

OFF OFFICE

OF/OI OWNER FURNISHED/OWNER INSTALLED

OH OVERHANG

OH DR OVERHEAD (COILING) DOOR

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

OPT OPTIONAL

OR OPERATING ROOM OR OUTSIDE RADIUS

ORD ORDNANCE OR OVERFLOW ROOF DRAIN

ORG ORGANIC

ORIG ORIGINAL

ORN ORNAMENTAL

OUT OUTLET

OZ OUNCE

PAR PARALLEL OR PARAPET

PART PARTIAL

PAT PATTERN

PB PUSHBUTTON

PBD PARTICLEBOARD

PC PIECE, POLYCARBONATE OR PORTLAND CEMENT

PCC PRECAST CONCRETE

PCCP CONCRETE PAVEMENT

PCD PAPER CUP DISPENSER

PCF POUNDS PER CUBIC FOOT

PCP PORTLAND CEMENT PLASTER

PED PEDESTAL

PEN PENETRATE

PEND PENDANT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PGBD PEGBOARD

PHS PHILLIPS HEAD SCREW

PKG PACKAGE

PL PLATE, PROPERTY LINE

PLAM PLASTIC LAMINATE

PLAS PLASTER OR PLASTIC

PLBG PLUMBING

PLYWD PLYWOOD

PMTL PAINTED METAL

PNEU PNEUMATIC

PNL PANEL

POLY POLYETHYLENE (PLASTIC)

PR PAIR

PRCST PRECAST

PREFAB PREFABRICATE

PREFIN PREFINISH

PRELIM PRELIMINARY

PREP PREPARATION

PRESS PRESSURE

PREV PREVIOUS

PRKG PARKING

PRMLD PREMOLDED

PROJ PROJECT

PROP PROPERTY

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT, PNEUMATIC TUBE, OR PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PVC POLYVINYL CHLORIDE (PLASTIC)

PVG PAVING

PWR POWER

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QRY QUARRY

QT QUARRY TILE

QTB QUARRY TILE BASE

QTF QUARRY TILE FLOOR

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

R RADIUS OR RISER

RA RETURN AIR

RAD RADIATOR

RB RESILIENT BASE OR RUBBER BASE

RB HK ROBE HOOK

RBM REINFORCED BRICK MASONRY

RBR RUBBER

RCP REFLECTED CEILING PLAN

RCVR RECEIVER

RD ROAD OR ROOF DRAIN

REC RECESSED

RECD RECEIVED

RECPT RECEPTACLE

RECT RECTANGLE

REF REFERENCE OR REFRIGERATOR

REFR REFRACTORY REFRIGERATION OR REFRIGERATION

REFRACTORY

REG REGISTER

REINF REINFORCE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RESIL RESILIENT

RET RETURN

REV REVISION

RF RADIO FREQUENCY

RFG ROOFING

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RH RIGHT HAND

RHMS ROUND HEAD MACHINE SCREW

RHR RIGHT HAND REVERSE

RHWS ROUND HEAD WOOD SCREW

RL ROOF LEADER

RLG RAILING

RM ROOM

RND ROUND

RO ROUGH OPENING

ROW RIGHT OF WAY

RPM REVOLUTIONS PER MINUTE

RS ROUGH SAWN

RT RIGHT

RV ROOF VENT

RVS REVERSE

RWD REDWOOD

RWL RAIN WATER LEADER

W/ WITH

W/O WITHOUT

WARR WARRANTY

WBL WOOD BLOCKING

WC WALL COVERING OR WATER CLOSET

WC WL HNG WATER CLOSET, WALL HUNG

WCHR WATER CHILLER

WCL WL MTD WATER COOLER, WALL HUNG

WD WOOD

WDW WINDOW

WF WIDE FLANGE

WFAB WALL FABRIC

WFR WOOD FRAME

WFS WOOD FURRING STRIPS

WH WATER HEATER

WHSE WAREHOUSE

WLD WELDED

WM WIRE MESH

WP WATERPROOFING

WPD WATER PRESSURE DROP

WPM WATERPROOF MEMBRANE

WR WEATHER RESISTANT

WS WEATHERSTRIP

WSCT WAINSCOT

WT WEIGHT

WWF WELDED WIRE FABRIC

X BRACE CROSS BRACE

XPS EXTRUDED POLYSTYRENE BOARD (INSULATION)

YD YARD

YR YEAR

1. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING REVIT®

SOFTWARE IN A MICROSOFT WINDOWS ENVIRONMENT. A BUILDING INFORMATION

MODEL (BIM) HAS BEEN DEVELOPED FOR DESIGN COMMUNICATION. THE MODEL

DOES NOT CONTAIN COMPLETE INFORMATION FOR USE IN COST ESTIMATING,

SYSTEMS PERFORMANCE, COORDINATION, SCHEDULING, OR FACILITIES

MANAGEMENT.

2. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING THE

CONSTRUCTION SPECIFICATIONS INSTITUTE'S UNIFORM DRAWING SYSTEM AND THE

NATIONAL CAD STANDARD AS GUIDES.

3. DISCREPANCIES IN THE CONTRACT DOCUMENTS SHALL BE IMMEDIATELY BROUGHT

TO THE ATTENTION OF THE ARCHITECT AND OWNER’S REPRESENTATIVE/COR.

CONTRACTOR SHALL PROVIDE THE HIGHER GRADE OF QUALITY AND/OR GREATER

QUANTITY OF WORK WHEN BIDDING IF A CLARIFICATION CAN NOT BE OBTAINED BY

THE BID DUE DATE.

4. CONTRACTOR IS RESPONSIBLE FOR COORDINATING SCOPE OF WORK WITH

OWNER’S REPRESENTATIVE/COR AND VARIOUS FACILITY PERSONNEL INVOLVED

WITH UTILITY SHUT DOWN, INFECTION CONTROLS, OCCUPANT/EMPLOYEE SAFETY,

ACCESS CONTROL, ETC.

5. ANY INDICATION OF PROJECT LIMITS OR BOUNDARY OF DEMARCATION ARE SHOWN

FOR THE CONVENIENCE OF THE CONTRACTOR, THE FULL SCOPE OF THE PROJECT

LIMIT OF BOUNDARY REQUIRES COORDINATION WITH THE DESIGN SCOPE OF WORK

AND ACCESS TO EXISTING UTILITIES FOR TIE IN.

6. DRAWINGS ARE PREPARED FROM FIELD VERIFICATION, EXISTING FACILITY DRAWING

BASE FILES, AND USING DIMENSIONS, CONFIGURATIONS AND DETAILS OF SPECIFIC

MANUFACTURERS AS A BASIS OF DESIGN. CONTRACTOR IS RESPONSIBLE FOR

VERIFICATION OF ACTUAL DIMENSIONS, THE COORDINATION OF THE DETAILS WITH

THE PRODUCTS WHICH ARE PROVIDED PER THE SCOPE OF THE SPECIFICATIONS

AND THE SURROUNDING CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS,

ROUGH-IN DIMENSIONS, CONNECTIONS, AND OVERALL INSTALLATION

REQUIREMENTS.

7. CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE ENTIRE SCOPE OF

WORK OUTLINED IN THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE

FOR THE COORDINATION OF ALL SUB-CONTRACTORS AND THE SCOPE OF WORK

THEY PROVIDE. SUB-CONTRACTORS ARE RESPONSIBLE FOR THEIR FULL SCOPE OF

WORK WITHIN THE CONTRACT DOCUMENTS, TRADES ARE NOT SEGMENTED TO ONLY

CERTAIN SHEETS AND SPECIFICATIONS, CROSS COORDINATION IS REQUIRED.

8. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR

UNDERSTANDING INFORMATION OUTLINED IN THE SPECIFICATIONS, KEY NOTES,

GENERAL NOTES, LEGEND, CODES, ETC., PROVIDED IN THE CONTRACT DOCUMENTS.

9. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR PROVIDING

AND MAINTAINING SMOKE/FIRE RATINGS OF NEW CONSTRUCTION AND EXISTING

CONSTRUCTION AS INDICATED ON DRAWINGS. THIS INCLUDES PATCHING

PENETRATIONS IN SHAFTS, WALLS, SLABS AND ROOF. ONLY U.L. APPROVED

METHODS, MATERIALS AND INSTALLATION ARE ACCEPTABLE.

10. MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL DRAWINGS SHOW

INFORMATION IN A DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE GENERAL

CONTRACTOR IS TO COORDINATE THE LOCATIONS OF ALL MECHANICAL, PLUMBING

AND ELECTRICAL EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL AND

STRUCTURAL DETAILING OF SHAFTS, CHASES, CEILING CONSTRUCTION, ETC.

11. CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IDENTIFIED AND NOT

IDENTIFIED IN THE CONTRACT DOCUMENTS WITH THE EXISTING AND NEW

CONSTRUCTION ELEMENTS. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION

BETWEEN THE CONTRACT DOCUMENTS, INSTALLED AND UNINSTALLED

CONSTRUCTION BEFORE THE ORDERING OF MATERIALS AND EQUIPMENT. NOTIFY

ARCHITECT AND OWNER’S REPRESENTATIVE/COR OF ANY DISCREPANCIES OR

MISSING DIMENSIONS.

12. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR GENERAL

ORIENTATION AND CONTEXT ONLY.

13. THE TERM "ALIGN" MEANS TO INSTALL DIFFERENT/SIMILAR COMPONENTS OF

CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.

14. ALL DIMENSIONS INDICATED ARE TO FACE OF EXISTING MEMBERS, FACE OF NEW

STRUCTURAL MEMBERS, FACE OF NEW MASONRY, FACE OF NEW STUDS OR COLUMN

GRID LINES UNLESS NOTED OTHERWISE.

15. ROUGH OPENINGS SHALL ALLOW FOR SHIM SPACE.

16. CONTRACTOR TO PROVIDE WORK WHERE DETAILS AND NOTES ARE IDENTIFIED AS

“TYPICAL” OR “SIMILAR” EACH INSTANCE THAT IS THE SAME IN NATURE TO THE

DETAIL, AREA, OR ITEM REFERENCED.

17. PROVIDED WORK SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.

CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF DELIVERY, MOUNTING,

INSTALLATION, NECESSARY BLOCKING AND ROUGH-IN.

18. INSTALLED WORK IS THE CONTRACTOR INSTALLING OWNER FURNISHED MATERIALS

AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF MATERIAL

DELIVERY, MOUNTING, INSTALLATION AND ROUGH IN.

19. FURNISHED WORK IS THE CONTRACTOR FURNISHING THE MATERIALS AND

EQUIPMENT TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF

DELIVERY AND ROUGH-IN.

20. ALL PROVIDED WORK SHALL BE WITH NEW MATERIALS UNLESS SPECIFICALLY

CALLED OUT AS SALVAGED OR RELOCATED WITHIN THE CONTRACT DOCUMENTS.

21. ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH THE PROJECT SHALL BE

FAMILIAR WITH THE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND

HEALTH ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS PROJECT.

22. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROTECTING ALL

UTILITY LINES. LOCATIONS SHOWN ARE APPROXIMATE. REPAIR ALL DAMAGE TO

UTILITY LINES CAUSED BY CONSTRUCTION OPERATIONS AT NO COST TO THE

OWNER.

23. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING AND SHORING

REQUIRED DURING CONSTRUCTION.

24. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ADJACENT

CONSTRUCTION, FINISHES, EQUIPMENT, AND TRAVEL ROUTE TO AND FROM THE

CONSTRUCTION SITE. ANY DAMAGE OR UNACCEPTABLE WEAR BY THE

CONSTRUCTION TEAM SHALL BE REPAIRED/REPLACED BY THE CONTRACTOR AT NO

COST TO THE OWNER.

25. IN THE CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT

DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER

QUALITY OF WORK, AS DETERMINED BY THE COR SHALL BE PROVIDED.

D DEPTH OR PENNY (NAIL)

D LABEL CLASS D DOOR

DAT DATUM

DB DECIBEL

DBL DOUBLE

DBL GLZ DOUBLE GLAZE

DC DIRECT CURRENT

DEG DEGREE

DEL DELETE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL DIAGRAM OR DIAGRAM DIAGONAL

DIFF DIFFERENCE OR DIFFUSER

DIM DIMENSION

DIR DIRECTION

DISP DISPENSER

DIST DISTANCE

DIV DIVIDE OR DIVISION

DL DEAD LOAD

DOC DOCUMENT

DOZ DOZEN

DN DOWN

DR DOOR, DRAIN, DRESSING ROOM, OR DRIVE

DS DOWNSPOUT

DSGN DESIGN

DW DISHWASHER

DWG DRAWING

DWTR DUMBWAITER

E EAST

EA EACH

EFF EFFICIENCY

EFS EXTERIOR FINISH SYSTEM

EIFS EXTERIOR INSULATION AND FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELAST ELASTOMERIC

ELEC ELECTRIC

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

ENGR ENGINEER

ENVIR ENVIRONMENT

EPA ENVIRONMENTAL PROTECTION AGENCY

EPDM ETHYLENE PROPYLENE DIENE MONOMER

EPO EMERGENCY POWER OFF

EPS EXPANDED POLYSTYRENE BOARD (INSULATION)

EQ EQUAL

EQL SP EQUALLY SPACED

EQUIP EQUIPMENT

EQUIV EQUIVALENT

ERD EXISTING ROOF DRAIN

ESC ESCAPE OR ESCUTCHEON

ESCAL ESCALATOR

EST ESTIMATE

ETC AND SO FORTH OR ET CETERA

ETS EXPOSE TO STRUCTURE

EW EACH WAY

EWC ELECTRIC WATER COOLER

EWS EYE WASH STATION

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION OR EXPOSED

EXT EXTERIOR, EXTERNAL, OR EXTINGUISHER

F FAHRENHEIT OR FEMALE

FA FIRE ALARM

FAB FABRIC

FAC FACTOR

FACIL FACILITY

FAS FASCIA

FCO FLOOR CLEANOUT

FCTY FACTORY

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND EQUIPMENT

FH FLAT HEAD OR FLAT HEAD SCREWS

FHC FIRE HOSE CABINET

FHMS FLAT HEAD MACHINE SCREW

FHP FULL HEIGHT PARTITION

FHWS FLAT HEAD WOOD SCREW

FIG FIGURE

FIL FILLET

FIN FINISH

FIP FILLER PANEL

FIXT FIXTURE

FL FLOORLINE

FLASH FLASHING

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLR FLOOR

FLUOR FLUORESCENT

FM FACTORY MUTUAL

FM-G FACTORY MUTUAL GLOBAL

FO FINISHED OPENING

FOC FACE OF CONCRETE OR FACE OF CURB

FOF FACE OF FINISH

FOM FACE OF…