This document includes a statement of work for a federal solicitation requiring high voltage electrical testing and maintenance services. The Department of Veterans Affairs seeks a contractor to clean, test, adjust, calibrate, and inspect electrical distribution equipment including power transformers, switchgear, motor control centers, and panel boards located at the Northern Indiana Healthcare System facilities in Fort Wayne and Marion, Indiana. Services must be performed in accordance with the statement of work every three years. The government will issue a request for quote on August 24th, 2022 with responses due September 6th, 2022. A site visit for each location is scheduled for August 30th. Questions are due by September 1st and should be directed to the contracting officer. The solicitation number is 36C25022Q0983.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HIGH VOLTAGE DISCONNECTS (15KV)

1. Spyrun Disconnect

2. Anthony Disconnect

3. 500KVA West Disconnect Cutler Hammer

4. 1500KVA East Disconnect Cutler Hammer

5. Metering Section

OIL FILLED TRANSFORMERS — PAD AMOUNT

1. 500 KVA West - Outside BLDG 16 North

2. 500 KVA East - Outside BLDG 16 North

3. 1500 KVA West - Outside BLDG 16 North

4. 1500 KVA East – Outside BLDG 16 North

5. 112.5 KVA - Outside Trailer North

DRY TRANSFORMERS

STEP UP 112.5 KVA - 101 - BLDG 1 RM 42A

STEP UP 30 KVA - PP9 - BLDG 1 SUB BASE

30 KVA - MRI - BLDG 17 RM 102

150 KVA - DP - BLDG 1 RM A155

150 KVA - 103 - BLDG 1 RM 399

150 KVA - 104 - BLDG 1 RM 399

STEP UP 150 KVA - 105 - BLDG 1 RM 399

45 KVA - 102 - BLDG 1 RM 42

75 KVA - CRDP1 - BLDG 1 RM 41

25 KVA - 269 - BLDG 1 rm 269

15 KVA - A - BLDG 7 BASEMENT -

15 KVA - B - BLDG 7 BASEMENT -

15 KVA - PP-TELE - BLDG 1 RM 57

112.5 KVA - 201 - BLDG 2 RM 104

30 KVA - 202 - BLDG 1 RM A155

30 KVA - B5B - BLDG 5 BASEMENT

EQUIPMENT TO BE TESTED AT Ft Wayne Campus

Attachment 5

25 KVA - B5A - BLDG 5 BASEMENT

15 KVA - B16 - BLDG 16 RM 1E

75 KVA - B3A - OUTSIDE N. E. OF BLDG 3

75 KVA - 203 - BLDG 2 OUTSIDE West

112.5 KVA - B6 - OUTSIDE N. E. BLDG 6

??? KVA - ??? - BLDG 1 Outside A155

GROUNDING SYSTEM TESTING

1. Outdoor Transformers total of 9

2. Bldg 2

3. Bldg 3

4. Bldg 4

5. Bldg 5

6. Bldg 6

7. Bldg 7

8. Bldg 16

9. Bldg 17

10. T-4

11. T-5

12. T-6

13. Room 42 & 42A

LOW VOLTAGE BREAKERS

277/480V Main Panel 120/208V Main Panel 3 Generator Breaker See All Panels tab

DP BLDG 1 RM A155 277/480V #22

DP-1 BLDG 1 RM 42 208/120V #02

DP-1E BLDG 1 RM 27 208/120V #02

DP-2 BLDG 1 RM 42 208/120V #05

DP-3 BLDG 1 RM 42 208/120V #12

DP-3A BLDG 1 RM 42 208/120V #15 ESS-P #2,4,6

DP-4 BLDG 1 RM 48 208/120V #10

DP-5 BLDG 1 RM 4 208/120V #04

DP-6 BLDG 1 RM 269 208/120V #04

DP-9 BLDG 1 RM B607 208/120V #16

DP-TELE A BLDG 1 RM 57 208/120V #07 ESS-P #20,22,24

DP-TELE B BLDG 1 RM 57 208/120V #07 ESS-P #20,22,24

EM-1 BLDG 1 Hall by 176 208/120V #01 ESS-P #1,3,5

EM-1A BLDG 1 RM A155 208/120V #01 ESS-P #1,3,5

EM-2 BLDG 1 Hall by 242 208/120V #01 ESS-P #1,3,5 EM-3 BLDG 1 Hall by 3157 208/120V #01 ESS-P #1,3,5

EM-4 BLDG 1 RM 4310 208/120V #01 ESS-P #1,3,5

EM-5 BLDG 1 Hall by 529 208/120V #01 ESS-P #1,3,5

EM-B BLDG 1 RM 42 208/120V #01 ESS-P #1,3,5

EMP BLDG 1 RM 42 208/120V #01 ESS-P #1,3,5

EQ-1 BLDG 1 Hall by 139 208/120V #14 ESS-P #13,15,17

EQ-1A BLDG 1 RM A155 277/480V #04 GEN #1

EQ-2 BLDG 1 Hall by 242 208/120V #14 ESS-P #13,15,17

EQ-2A BLDG 1 RM 261 208/120V #14 ESS-P #13,15,17

EQ-3 BLDG 1 Hall by 3153 208/120V #14 ESS-P #13,15,17

EQ-4 BLDG 1 RM 4321 208/120V #14 ESS-P #13,15,17

EQ-5 BLDG 1 Hall by 526A 208/120V #14 ESS-P #13,15,17

EQ-B BLDG 1 RM 42 208/120V #14 ESS-P #13,15,17

EQ-DP-B BLDG 1 RM 42 208/120V #08 GDP-2 #8,10,12

EQ-HDP-2 BLDG 1 RM 250 277/480V #17 GDP-2

EQ-HDP-B BLDG 1 RM 42A 277/480V #17 GDP-2

EQ-HPP-3 BLDG 1 RM 399 277/480V #04 GEN #1

EQ-HPP-4 BLDG 2 Outside West 277/480V #04 GEN #1

EQ-KP-B BLDG 1 RM 12 208/120V #08 GDP-2 #8,10,12

EQ-LPP-4 BLDG 2 Outside West 277/480V #04 GEN #1

EQP BLDG 1 RM 42 208/120V #14 ESS-P #13,15,17

EQ-PH BLDG 1 RM 600 208/120V #14 ESS-P #13,15,17

EQ-PP-11 BLDG 1 RM 600 208/120V #11 ESS-P #14,16,18

EQ-PP-B BLDG 1 RM 42 277/480V #17 GDP-2

EQ-USP BLDG 1 RM 29 277/480V #17 EQ-PP-B #8,10

ESS-P BLDG 1 RM 42 208/120V GEN #2

GDP-2 and GDP-2A BLDG 1 RM 42A 277/480V GEN #3 HAZMAT GROUNDS (North) 208/120V AEP X-former

ISO POWER BLDG 1 RM 3235 208/120V #06 ESS-P #8,10,12

ISO POWER BLDG 1 RM 3232 208/120V #06 ESS-P #8,10,12

ISO POWER BLDG 1 RM 3218 208/120V #06 ESS-P #8,10,12

ISO POWER BLDG 1 RM 3214 208/120V #06 ESS-P #8,10,12

LP-5A BLDG 1 Hall by 535 208/120V #10 LP-5B BLDG 1 Hall by 503 208/120V #05 LP-5C BLDG 1 Hall by 523 208/120V #02 LP-5D BLDG 1 Hall by 519 208/120V #02 LP-BA BLDG 1 Hall by 57 208/120V #10

LP-BA-A BLDG 1 RM 57 208/120V #10

LP-BB BLDG 1 Hall by 49 208/120V #10 LP-BC BLDG 1 Hall by 42 208/120V #05 LP-BD BLDG 1 Hall by 36 208/120V #02

LP-BE BLDG 1 RM 2 208/120V #05

LP-BF BLDG 1 Hall by 4 208/120V #04

LP-E1 BLDG 1 RM 42 208/120V #01 ESS-P #1,3,5

LP-E2 BLDG 1 Hall by 192 208/120V #01 ESS-P #1,3,5 LPL BLDG 1 Hall by 28 208/120V #12

LP-OIT-BE BLDG 1 RM 53 208/120V #16

LP-OR BLDG 1 Hall by 3217 208/120V #09

LV BLDG 2 RM 101 277/480V #04 GEN #1

LVA BLDG 2 RM 101 277/480V #04 GEN #1

MCC BLDG 2 RM 101 277/480V #04 GEN #1

MCC-1 BLDG 1 RM A155 277/480V #04 GEN #1

MDP-AMB BLDG 1 RM A155 277/480V #22

MDP-MRI BLDG 17 RM 102 277/480V #23 GDP-2A

MDP-OR BLDG 1 Hall by 3217 208/120V #09 MDP-TRAILORS GROUNDS (North) 208/120V AEP X-former

Panel A BLDG 17 RM 102 277/480V #23 GDP-2A

PP1 BLDG 6 BASEMENT 277/480V #07 GDP-2A

PP-1 BLDG 1 RM 48 208/120V #14 ESS-P #13,15,17

PP-10 BLDG 1 RM 399 277/480V #19 GDP-2

PP-10A BLDG 1 RM 399 277/480V #19 GDP-2

PP-16 BLDG 16 RM 1E 277/480V #05 GDP-2A

PP1A BLDG 6 Hall by 101 277/480V #07 GDP-2A PP2 BLDG 6 Hall by 101 277/480V #07 GDP-2A PP-2 BLDG 1 Hall by 50 208/120V #12 PP-2BA BLDG 1 Hall by 253 208/120V #10 PP3 BLDG 6 NE Outside 277/480V #07 GDP-2 PP-3 BLDG 1 Hall by 263 208/120V #12

PP-4 BLDG 1 RM 38 208/120V #14 ESS-P #13,15,17

PP-5 BLDG 5 BASEMENT 277/480V #07 GDP-2A

PP-6 BLDG 1 RM 12 208/120V #12

PP-6B BLDG 1 RM 12 208/120V #12

PP-7A BLDG 7 BASEMENT 277/480V #07 GDP-2A

PP-7B BLDG 7 BASEMENT 277/480V #07 GDP-2A

PP-9 BLDG 1 SUB BASE 208/120V #14 ESS-P #13,15,17

PP-A BLDG 1 RM 42 277/480V #03

TRANSFORMER T-CRDP1 BLDG 1 RM 41 277/480V #11 GDP-2 75KVA

TRANSFORMER T-PP9 BLDG 1 SUB BASE 208/120V #14 ESS-P #13,15,17 30KVA

TRANSFORMER TS-203 BLDG 2 Outside West 277/480V #04 GEN #1 75KVA TRANSFORMER T-TRAILOR GROUNDS (North) 208/120V AEP 112.5KVA