539-18-101 ADDENDUM 3 WRITE UP.pdf
PDF 304 KB Posted
- Attached to
- Z1DA--Improve Exhaust System 539-18-101 Federal contract opportunity
- Solicitation number
- 36C25020B0068
About this file
This addendum modifies drawings and specifications for a project to improve exhaust systems at the Cincinnati VA Medical Center. The revisions include changing the outside air supply configuration for several fan coil units by deleting duct connections to return air ducts and adding new duct branches and ceiling diffusers to individual rooms. The schedules are also updated to remove the outside air CFM column from the fan coil unit schedule and add information to the air device schedule.
The related federal contract opportunity is a solicitation to correct fire code deficiencies and interior deficiencies at the Cincinnati VAMC. The project value is between $500,000 and $1,000,000. The solicitation will be set aside for a service-disabled veteran owned small business. Interested offerors must register on the Vendor Information Pages and SAM websites. The NAICS code is 238220 and size standard is $16.5 million. The duration following notice to proceed cannot exceed 180 days. Payment and performance bonds will be required.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25020B0068 0003.docx | DOCX document | |
| 539-18-101 Addendum 3 Dwgs.pdf | ||
| Corbin Russwin Locksets Sole Source Justification Redacted.pdf | ||
| S04 Site Visit Sign in Sheet.pdf | ||
| 01 00 00 ADDENDUM 2.pdf | ||
| Revise Bid Schedule Statement of Bid Items.docx | DOCX document | |
| Addendum 2 Drawings Revisions are clouded.pdf | ||
| 36C25020B0068 0002.docx | DOCX document | |
| Location of temporary door storage.pdf | ||
| Addendum 2 Specifictions Revisons write up.pdf | ||
| 36C25020B0068 0001.docx | DOCX document | |
| 36C25020B0068.docx | DOCX document | |
| 539-18-101 CD Bid Specifications (8-21-2020).pdf | ||
| Wage Determination OH20200082.pdf | ||
| S02 RFI Form.docx | DOCX document | |
| 539-18-101 CD Bid Drawings (8-21-2020).pdf | ||
| S02 Contractor EMR Certification Form.docx | DOCX document |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM
LEVIN PORTER ASSOCIATES, INC.
3011 NEWMARK DRIVE MIAMISBURG, OHIO 45342
O: 937.224.1931 F:937.224.3091 www.levin-porter.com
ADDENDUM NO. 03
September 24, 2020
PROJECT # 539-18-101
IMPROVE EXHAUST SYSTEMS
CINCINNATI VA MEDICAL CENTER
3200 VINE ST
CINCINNATI OH, 45220
LEVIN PORTER ASSOCIATES, INC
3011 NEWMARK DRIVE
MIAMISBURG, OHIO 45342
LPA PROJECT NO. 82146.00
TO ALL BIDDERS:
This addendum including all items listed hereinafter, shall become a part of the documents, shall be taken into account in preparing the proposal, and shall become a part of the contract. The work under each branch shall be in accordance with the original specifications unless excepted in this amendment.
This addendum consists of 2 pages plus 7 (30”x42”) attachments for a total of 9 pages. All changes to drawings shall be shown in clouded areas with an Addendum #3 triangle symbol:
ITEM NO. 1: THE DRAWINGS SHALL BE REVISED AS FOLLOWS:
1.1. Reference: Sheet 1-M102B, SECOND FLOOR PLAN AREA B – REMOVALS &
NEW WORK
A. Revise outside air supply to spaces served by 1-FCU1, 1-FCU2, & 1- FCU3, as follows: delete duct connections to FCU return ducts; provide duct branch & CD2 supply diffuser to each individual room as shown.
Refer to attached revised sheet.
LEVIN PORTER ASSOCIATES, INC.
3011 NEWMARK DRIVE MIAMISBURG, OHIO 45342 2
O: 937.224.1931 F:937.224.3091 www.levin-porter.com
1.2. Reference: Sheet 1-M103B, THIRD FLOOR PLAN AREA B – REMOVALS &
NEW WORK
A. Revise outside air supply to 1-FCU4, as follows: delete duct connection to FCU return duct; provide duct branch & CD2 supply diffuser in Room B314 as shown. Refer to attached revised sheet.
1.3. Reference: Sheet 1-M104A, FOURTH FLOOR PLAN AREA A – REMOVALS &
NEW WORK
A. Revise outside air supply to 1-FCU6, as follows: delete duct connection to FCU return duct; provide duct branch & CD2 supply diffuser to Rooms A425 & A425A as shown. Refer to attached revised sheet.
B. Revise roof demolition to clarify which of two existing condensing units in this area should be removed. Refer to attached revised sheet.
1.4. Reference: Sheet 1-M104D, FOURTH FLOOR PLAN AREA D – REMOVALS &
NEW WORK
A. Revise outside air supply to 1-FCU5, as follows: delete duct connection to FCU return duct; provide duct branch & CD2 supply diffuser to Rooms A458B & A458C as shown. Refer to attached revised sheet.
1.5. Reference: Sheet 1-M105A, FIFTH FLOOR PLAN AREA A – REMOVALS &
NEW WORK
A. Revise outside air supply to 1-FCU8, as follows: delete duct connection to FCU return duct; provide duct branch & CD2 supply diffuser in Room A559 as shown. Refer to attached revised sheet.
1.6. Reference: Sheet 1-M105B FIFTH FLOOR PLAN AREA B – REMOVALS &
NEW WORK
A. Revise outside air supply to 1-FCU7, as follows: delete duct connection to FCU return duct; provide duct branch & CD2 supply diffuser in Room B507 as shown. Refer to attached revised sheet.
1.7. Reference: Sheet M602 SCHEDULES, CONTROLS AND AUTOMATION
A. Revise TWO PIPE FAN COIL UNIT SCHEDULE to delete O.A. CFM column. Refer to attached revised sheet.
B. Revise AIR DISTRIBUTION DEVICES schedule to add CD2 supply diffuser (square plaque diffuser with 12”x12” face) and clarify CD1 supply diffuser has 24”x24” face. Refer to attached revised sheet.
END OF ADDENDUM NO. 03
| PROJECT # 539-18-101 |
| IMPROVE EXHAUST SYSTEMS |
| CINCINNATI VA MEDICAL CENTER |
| 3200 VINE ST |
| CINCINNATI OH, 45220 |
| LPA PROJECT NO. 82146.00 |