CLC Phase 2 - One Line Diagram.pdf
PDF 185 KB Posted
- Solicitation number
- 36C24927Q0038
About this file
This document is a Single-Line Diagram for Buildings 204 and 205 of a construction project for the U.S. Department of Veterans Affairs. The drawing, dated December 18, 2020, is part of 100% Construction Documents for the "Construct Replacement CLC - Long Term Rehab" project located in Lexington, Kentucky. The diagram illustrates the electrical distribution system including a 500 kVA pad-mount transformer (12.47 kV to 208Y/120V), a 400 kW diesel generator set, multiple automatic transfer switches (ATS) rated at 400A, 600A, and 800A with bypass isolation and open transition capabilities, and a comprehensive network of panelboards, disconnects, and protective devices. Key components include the 205 Main Distribution Panel (2000A), 205 Metering Panel (400A), 205 Normal Distribution Panel (600A), and 205 Equipment Distribution Panel (800A).
The system incorporates multiple load centers and branch circuits serving various building loads including elevator systems, air handling units, emergency generator hookups, and portable generator docking stations. Surge protective devices (SPD) are distributed throughout the system for equipment protection. The feeder schedule specifies cable sizes ranging from #2 copper for 100-amp circuits to 4-set configurations of 600 kCMIL copper for 2000-amp service. The fault current schedule documents available short-circuit amperage ratings at 45 reference points throughout the distribution system, with ratings ranging from 1,001 kAIC to 32,042 kAIC. The design includes grounding systems with main ground bars, water main connections, UFER foundation grounding, building steel integration, and lightning protection provisions. The project was prepared by Heapy, Inc., serving as consultant and architect/engineer of record, with project number 2019-05137.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E N E N E N E N
G
N
G
REMOVABLE
BUS LINK
SW BD
METERING
K
K
EN
M
A
M
G
GFP
K
VFD
E N
N
G
REMOVABLE
BUS LINK
SW BD
METERING
100A/3P 100A/3P
'GC1'
'1C3' '1N1' '1N2' '1N3' '1N4'
'GLS1'
100A/3P 100A/3P 100A/3P 100A/3P 100A/3P
'GEQ1'
'205 CDP', 400A, 208Y/120V, 3PH, 4W
'205 MDP', 2000A, 208Y/120V, 3PH, 4W
2000A/3P 225A/3P 400A/3P 600A/3P
500KVA
12.47kV -
208Y/120V-3PH
PAD-MOUNT TX
5.75%
'205-N-ATS'
600A - 208/120V - 4P
BYPASS ISOLATION
OPEN TRANSITION
400kW /500kVA 208/120V
DIESEL GEN-SET
1600A FEEDER
TAPPING W IREW AY
225A/3P
LSI
400A/3P
LSI
600A/3P
LSI
LOAD BANK
SPD
100% RATED
1600A 3P BREAKER
'205-CR-ATS'
400A - 208/120V - 4P
BYPASS ISOLATION
OPEN TRANSITION
'205-LS-ATS'
225A - 208/120V - 4P
BYPASS ISOLATION
OPEN TRANSITION
'1LS1' '1LS2'
'1C1'
'GN1'
'1EQ1'
SPD SPD SPD
SPD
SPD SPD
SPD SPD
60A/3P 60A/3P
8 8 8 8 8 8 8 8
100A/3P
'GN2'
100A/3P
4 98 19 20
6 7
MAIN GROUND BAR W ITH
STAND OFF ISOLATORS
W ATER
MAIN
UFER
FOUNDATION
GROUND
BUILDING
STEEL
LIGHTNING
PROTECTION
MAIN TR CLOSET
GROUND BAR
EXISTING PAD MOUNTED SWITCH
PRIMARY SW ITCH
EXISTING LOAD - 398kVA (32A AT 12.47kV) NEW LOAD - 375kVA (30A AT 12.47kV)
TOTAL - 773kVA (62A AT 12.47kV)
LSI
60A/3P
LSI
LSI LSI
50A/3P
MVP-1
60E
'205-EQ-ATS'
800A - 208/120V - 4P
BYPASS ISOLATION
OPEN TRANSITION
SPD
28 29
'205 NDP', 600A, 208Y/120V, 3PH, 4W
800A/3P
LSI
800A/3P
LSI
225A/3P 100A/3P
SPD
60A/3P
30 '205 EQDP', 800A, 208Y/120V, 3PH, 4W
ELEV-1
150A/3P
ACCU-205-G
175A/3P
ACCU-205-1
175A/3P
ACCU-204-1
0 0 0 0
PORTABLE
GENERATOR
PADMOUNT 1600A DUAL
PURPOSE DOCKING STATION
50A/3P
EHU-205-G
50A/3P 50A/3P
0 0 0
EHU-205-1 EHU-204-1
EXISTING FEED TO
BUILDING 201 & 202
13 15
18 22 23
24 25 26 27
33 34 35 36 37 38 39
50A/3P
AHU-205-G-RF
35A/3P
AHU-205-G-SF
50A/3P
AHU-205-1-RF
0 0 0
90A/3P
AHU-205-1-SF
50A/3P 90A/3P
0 0 0
AHU-204-1-RF AHU-204-1-SF
40 41 42 43 44 45
FROM EXISTING
TRANSFORMER PMT-9
N G
100% RATED
ELECTRICAL SINGLE-LINE LEGEND
TRANSFORMER
VOLTAGE TERMINATION - PRIMARY
SURGE PROTECTIVE DEVICE
AUTOMATIC TRANSFER SW ITCH
GENERATOR
ELECTRIC METER
EQUIPMENT GROUND
GROUND FAULT PROTECTOR
EQUIPMENT MULTIMETER
EQUIPMENT POTENTIAL TRANSFORMER
PANELBOARD BREAKER
DELTA SYMBOL
DISCONNECT
EQUIPMENT AMMETER
EQUIPMENT CURRENT TRANSFORMER
EQUIPMENT W YE SIDE OF TRANSFORMER W ITH GROUND
KEYED INTERLOCK
MOTOR
MOTOR STARTER
MOTOR STARTER AND DISCONNECT
PANELBOARD - MAIN LUG ONLY
PANELBOARD - DOUBLE SET OF LUGS
PANELBOARD - MAIN BREAKER
SHORT CIRCUIT FAULT LOCATION
VARIABLE FREQUENCY DRIVE
VOLTAGE TERMINATION - SECONDARY
AUTOMATIC TRANSFER SW ITCH - BYPASS
BUS LINK
OR
BUSSING
SW ITCHBOARD ENCLOSURE
INTEGRATED EQUIPMENT ENCLOSURE
EXISTING CONDUIT & W IRE TO REMAIN
CONDUIT & W IRE TO BE REMOVED
CONDUIT & W IRE
EQUIPMENT SW ITCHBOARD METER
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO. STATE COA FIRM NO.
SD SCHEMATIC DESIGN 07.31.2020
DD DESIGN DEVELOPMENT 09.30.2020
95% CONSTRUCTION DOCUMENTS 11.23.2020
100% CONSTRUCTION DOCUMENTS 12.18.2020
/1
/2
:4
:2
A
M
Construct Replacement CLC - Long Term Rehab
12.18.2020
SINGLE LINE
E300
W JFMSG
000-00-000
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
596-333
2019-05137 01528
SINGLE-LINE DIAGRAM - BUILDING 204 & 205
0 REFER TO MOTOR SCHEDULE OR PANEL SCHEDULE FOR FEEDER SIZE
1 15 KV EPR 3 - #2/0 CU., 1 - #1 CU. GND. 600V, IN 4" C.
2 2000A: 5 SETS 4 - 600 kCMIL CU., IN 4"C.
3 1600A: 4 SETS 4 - 600 kCMIL CU., 1 - #4/0 CU. GND., IN 4"C.
4 800A: 2 SETS OF 4 - 500 kCMIL CU., 1 - #1/0 CU. GND., IN 4"C.
5 600A: 2 SETS OF 4 - 350 kCMIL CU., 1 - #1 CU. GND., IN 3"C.
6 400A: 4 - 500kCMIL CU., 1 - #3 CU. GND., IN 4"C.
7 225A: 4 - #4/0 CU., 1 - #4 CU. GND., IN 2.5"C.
8 100A: 4 - #2 CU., 1 - #8 CU. GND., IN 1.25"C.
REF.
POINT DESCRIPTION
MIN. EQUIP.
RATING
AVAILABLE SHORT
CIRCUIT AMPS
1 EM BUSWAY 10kAIC 8,034
2 205 MDP 42kAIC 32,042
3 LATS-EM 42kAIC 7,536
4 LATS-NORM 42kAIC 24,834
5 GLS1 24kAIC 19,691
6 1LS1 10kAIC 8,986
7 1LS2 10kAIC 3,394
8 CATS-EM 42kAIC 7,805
9 CATS-NORM 42kAIC 28,643
10 CDP 42kAIC 25,790
11 GC1 24kAIC 17,222
13 1C1 24kAIC 10,510
15 1C3 10kAIC 3,508
18 MVP-1 10kAIC 5,344
19 N-ATS-EM 42kAIC 7,805
20 N-ATS-NORM 42kAIC 28,623
21 NDP 42kAIC 25,757
22 GN1 24kAIC 17,205
23 GN2 24kAIC 17,195
24 1N1 18kAIC 10,504
25 1N2 18kAIC 10,498
26 1N3 10kAIC 3,507
27 1N4 10kAIC 3,496
28 EQ-ATS-EM 42kAIC 7,898
29 EQ-ATS-NORM 42kAIC 29,895
30 EQDP 42kAIC 27,841
31 GEQ1 20kAIC 17,881
32 1EQ1 10kAIC 3,519
33 ELEV-1 10kAIC 6,222
34 ACCU-205-G 5kAIC 3,585
35 ACCU-205-1 5kAIC 3,578
36 ACCU-203-1 5kAIC 3,024
37 EHU-205-G 5kAIC 1,452
38 EHU-205-1 5kAIC 1,438
39 EHU-203-1 5kAIC 1,356
40 AHU-205-GRF 5kAIC 1,447
41 AHU-205-GSF 5kAIC 2,257
42 AHU-205-1RF 5kAIC 1,001
43 AHU-205-1SF 5kAIC 3,562
44 AHU-203-1RF 5kAIC 1,447
45 AHU-203-1SF 5kAIC 3,562
FEEDER SCHEDULEFAULT CURRENT SCHEDULE
NOTES:
1. PROVIDE NEW MEDIUM VOLTAGE FUSE IN EXISTING PAD-MOUNTED GEAR.
2. CONTACTS FOR LOAD BANK DUMP CIRCUITRY.
3. LOAD BANK DUMP BOX.
4. PROVIDE GROUNDING FOR SEPERATELY DERIVED SYSTEM.
Revisions Date