This document is a Building 1 Electrical One-Line diagram for the Lexington-Cooper EHRM Infrastructure Design project located at 1101 Veterans Drive, Lexington, Kentucky 40502, prepared by the U.S. Department of Veterans Affairs Construction and Facilities Management.
The diagram illustrates the complete electrical distribution system for Building 1, including two 1000 kW / 1250 kVA generators with associated automatic transfer switches (ATS) for critical and normal power circuits, four transformers (T1-T4 ranging from 1000-1500 kVA), multiple switchboards and distribution panels serving telecom and data center loads, and uninterruptible power supply (UPS) systems with capacities of 112.5 kVA each. Key electrical components include main service buses, critical power bus duct risers, fire suppression systems, and computer room air conditioning (CRAC) units. The design specifies new equipment shown in bold lines and existing equipment in light lines, with provisions for removal of outdated ATS-UPS systems post-implementation. The contractor must perform short-circuit, coordination, and arc-flash study calculations per specification section 260573, provide advanced utility metering systems to capture voltage, current, and power data reporting including peak demand data and data center electrical load data, and coordinate with the mechanical contractor's building management system points list. Equipment includes ABB Entelliguard R retrofill breakers to replace existing GE breakers and floor-mounted Unistrut frames for panel mounting.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
E
L
N
E
L
N
E
L
N
E
L
N
E
L
UPS-MBC-TC
GROUND FLOORGROUND FLOOR
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
SIXTH FLOOR SIXTH FLOOR
600AF
600AT
NDP-1 208/120V 400A
NPLIT-1-A104
NPLIT-1-A243
NPLIT-1-A345
NPLIT-1-A450
NPLIT-1-AU547
NPLIT-1-A627
100A 400A
MCB
NPLIT-1-A002C
200A
NF DISC.
T-1-EC
112.5 kVA
ECDP-1 208/120V 400A
100A 400A
MCB
CPLIT-1-A104
CPLIT-1-A243
CPLIT-1-A345
CPLIT-1-A450
CPLIT-1-AU547
CPLIT-1-A627
CPLIT-1-A002C
100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A
(BUILDING 1 - TR CRITICAL POWER)
(BUILDING 1 - TR NORMAL POWER)
250A 250A
250A 250A
DC T-UPS 1DC T-UPS 2
T-UPS 1
112.5 kVA
T-UPS 2
112.5 kVA
400A 350A
400A 350A
DC MBP-TC DC UPS 2
UPS-2
400A 350A
400A 350A
DC UPS-1
DC LDC
UPS-1 UPS-LDC
600AF
600AT
HCDP1-EHRM
600A 480/277V
ECDP1
DATA CENTER
NEW UPS-B
T-1-EC
200-2
T-1-NP
112.5 kVA
400-1 400-1
DATA CENTER
UPS-B BYPASS
200A
NF DISC.
HNDP1-EHRM
600A 480/277V
400AF
200AT
LSI
DATA CENTER NEW UPS-A
200-2
DATA CENTER
UPS-A BYPASS
100-1
100-1
100-1
100-1
100-1
100-1
100-1
100-1
100-1
100-1
100-1
100-1
100-1
60A60A
CPLIT-1-B046
CPLIT-1-B125
SPD
60A
NPLIT-1-B046
60A60A
NPLIT-1-B125
200-2 200-2
200-2
400AF
200AT
LSI
250AF
175AT
LSI
400AF
200AT
LSI
400AF
200AT
LSI
250AF
175AT
LSI
200-2 200-2
200-2
400-1
SPD
M
SPD
M
M
M M M
M M MM
SPD
M
SPD
M
SPD
M
SPD
M
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
SPD
M
GENERATOR #1
1000 kW
1250 kVA
1600AF
1520AT
L,S,I
GENERATOR #2
1000 kW
1250 kVA
TEMP
GENERATOR
1600AF
1520AT
L,S,I
1600AF
1520AT
L,S,I
ESB
800AF
600AT
L,S,I
TRS
600A
ATS FIRE
BRANCH
FIRE PUMP
MOTOR
FIRE MONITOR
400AF
400AT
L,S,I
ATS LS
DPLS
400A
1600AF
1000AT
L,S,I
800AF
600AT
L,S,I
ATS CRITICAL
ATS-EQUIP
SBC
300AF
210AT
L,S
T-CPH
600AF
300AT
L,S
600AF
480AT
L,S
1600AF
1280AT
L,S,I
CRITICAL POWER
BUS DUCT RISER
TOWER BLDG 1 MV SWG BUS 1
MAIN BLDG 1A MV SWG A
TOWER BLDG 1 MV SWG BUS 2
MAIN BLDG 1A MV SWG B
T4 1500 kVA
T1 1500 kVA
MAIN SERVICE BUS 2 MAIN SERVICE BUS 1
T3 1000 kVA
T2 1000 kVA
SBD
1600AF
1600AT
L,S
1600AF
1600AT
L,S
SBG
SBB
2000AF
2000AT
L,S
SBA
1600AF
800AT
L,S
SBH
SBF
600AF
600AT
L,S,I
600AF
600AT
L,S,I
600AF
600AT
L,S,I
800AF
920AT
L,S
400AF
560AT
L,S
400AF
165AT
L,S, I
800AF
400AT
L,S, I
1600AF
800AT
L,S, I
MCB T-PPP T-SBL T-SBK T-PEE LE-1 SBJ
T-CPK
LG T-PDD
MCC MCA LF T-PFF T-PCC
600AF
210AT
1600AT
800AF
SBE
600AF
160AT
600AF
200AT
HEMG HEMG-1 T-EPB
A
B U
S D
U C
T R
IS
E
R
ELC
T-A
100 A
100 A
225 A
BUS DUCT CONTINUES
EH1 480/277V 400A
T-EL
150A 30A
ATS-UPS
250A
150A 15A
225 A
50A
H2 480/277V 400A
CRAC-2 INDOOR CRAC-2 OUTDOOR
50A 50A 15A 15A
CRAC-1
INDOOR
CRAC-3
INDOOR
CRAC-1
OUTDOOR
CRAC-3
OUTDOOR
GGG
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
569A4-22-700100% CONSTRUCTION
DOCUMENTS
LEXINGTON-COOPER EHRM
INFRASTRUCTURE DESIGN
1101 VETERANS DRIVE
LEXINGTON, KY 40502
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
St. Louis
6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com
E-602-1
BKM
BUILDING 1 - ELECTRICAL ONE-LINE
BKM5/16/23
NOT TO SCALE
BUILDING 1 - ELECTRICAL ONE LINE
ELECTRICAL KEYED NOTES
1. EXISTING ELECTRICAL EQUIPMENT FED FROM ATS-UPS
(SHOWN DASHED) SHALL BE REMOVED AFTER NEW UPS
DISTRIBUTION IS FULLY FUNCTIONAL. COORDINATE WITH
PHASING PLAN AND OWNER.
2. IN EXISTING EMERGENCY CRITICAL POWER 480/277V
SWITCHGEAR SBC SECTION, UTILIZE EXISTING GE
480/277V, 600A FRAME BREAKER AS INDICATED IN ORDER
TO SERVE NEW CRITICAL POWER FEED FOR TR ROOM
DISTRIBUTION. ADJUST TRIP SETTING AS REQUIRED. SEE
ONE-LINE.
3. IN EXISTING NORMAL POWER 480/277V SWITCHGEAR,
PROVIDE ABB ENTELLIGUARD R RETROFILL BREAKER
WHICH IS INTERCHANGEABLE WITH GE BREAKERS.
RETROFILL BREAKER TO FIT IN EXISTING SPACE AS
INDICATED IN ORDER TO SERVE NEW NORMAL POWER
FEED FOR TR ROOM DISTRIBUTION.
4. PROVIDE FLOOR-MOUNT UNISTRUT FRAME AND
HARDWARE NECESSARY TO MOUNT NEW NORMAL AND
CRITICAL POWER DISTRIBUTION PANELS. SEE ONE-LINE.
5. EXISTING ATS-UPS SHALL BE LEFT IN PLACE FOR
POTENTIAL FUTURE RE-USE. COORDINATE WITH OWNER.
6. DISCONNECT POWER TO EXISTING CRACS BEING
REPLACED AND PROVIDE NEW BREAKER TO FEED NEW
CRAC AS SHOWN. SEE EQUIPMENT DATA SCHEDULE AND
PLANS.
7. K13 TRANSFORMER SHALL BE GROUNDED PER
GROUNDING DETAIL.
8. DATA CENTER K13 TRANSFORMER SHALL BE GROUNDED
PER GROUNDING DETAIL.
ELECTRICAL GENERAL NOTES
1. EXISTING EQUIPMENT IS SHOWN "LIGHT". NEW
EQUIPMENT AND FEEDERS ARE SHOWN "BOLD".
2. SUCCESSFUL ELECTRICAL EQUIPMENT VENDOR SHALL
PERFORM SHORT-CIRCUIT, COORDINATION, AND ARC-
FLASH STUDY CALCULATIONS FOR NEW EQUIPMENT
BEING PROVIDED. SEE SPECIFICATION SECTION 260573
FOR FURTHER DETAIL. PROVIDE STUDY SUBMITTAL
DOCUMENTING FINDINGS, BREAKER TYPES, TRIP
SETTINGS AND AIC RATINGS.
ELECTRICAL METERING NOTE
1. FOR ADVANCED UTILITY METERING IN BUILDING 1,
PROVIDE METERING SYSTEMS, COMMUNICATION
NETWORK, AND INTERFACE REQUIRED FOR ELECTRICAL
VOLTAGE, CURRENT, AND POWER DATA
REPORTING. REPORTING SHALL INCLUDE PEAK DEMAND
DATA, TELECOM PANEL ELECTRICAL DATA, TELECOM
DISTRIBUTION PANEL ELECTRICAL DATA, DATA CENTER
ELECTRICAL LOAD DATA, AND OTHER REQUIRED
ELECTRICAL DATA. COORDINATE REPORT DATA WITH
MECHANICAL CONTRACTOR BMS POINTS LIST. SEE
ADVANCED METERING SPECIFICATIONS FOR FURTHER
DETAIL.
VHALEXMessnT Cloud+
VHALEXMessnT Cloud+ New breaker located inside of SBC
VHALEXMessnT Cloud+
VHALEXMessnT Cloud+ Critical ATS