Bowling ONE-LINE E-602-1.pdf

PDF 231 KB Posted

Attached to
H361--LEX Triannual Energy Study and ARC Flash Testing
Solicitation number
36C24927Q0038
Issued by

About this file

This document is a Building 1 Electrical One-Line diagram for the Lexington-Cooper EHRM Infrastructure Design project located at 1101 Veterans Drive, Lexington, Kentucky 40502, prepared by the U.S. Department of Veterans Affairs Construction and Facilities Management.

The diagram illustrates the complete electrical distribution system for Building 1, including two 1000 kW / 1250 kVA generators with associated automatic transfer switches (ATS) for critical and normal power circuits, four transformers (T1-T4 ranging from 1000-1500 kVA), multiple switchboards and distribution panels serving telecom and data center loads, and uninterruptible power supply (UPS) systems with capacities of 112.5 kVA each. Key electrical components include main service buses, critical power bus duct risers, fire suppression systems, and computer room air conditioning (CRAC) units. The design specifies new equipment shown in bold lines and existing equipment in light lines, with provisions for removal of outdated ATS-UPS systems post-implementation. The contractor must perform short-circuit, coordination, and arc-flash study calculations per specification section 260573, provide advanced utility metering systems to capture voltage, current, and power data reporting including peak demand data and data center electrical load data, and coordinate with the mechanical contractor's building management system points list. Equipment includes ABB Entelliguard R retrofill breakers to replace existing GE breakers and floor-mounted Unistrut frames for panel mounting.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

E

L

N

E

L

N

E

L

N

E

L

N

E

L

UPS-MBC-TC

GROUND FLOORGROUND FLOOR

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

FOURTH FLOOR

FIFTH FLOOR

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

FOURTH FLOOR

FIFTH FLOOR

SIXTH FLOOR SIXTH FLOOR

600AF

600AT

NDP-1 208/120V 400A

NPLIT-1-A104

NPLIT-1-A243

NPLIT-1-A345

NPLIT-1-A450

NPLIT-1-AU547

NPLIT-1-A627

100A 400A

MCB

NPLIT-1-A002C

200A

NF DISC.

T-1-EC

112.5 kVA

ECDP-1 208/120V 400A

100A 400A

MCB

CPLIT-1-A104

CPLIT-1-A243

CPLIT-1-A345

CPLIT-1-A450

CPLIT-1-AU547

CPLIT-1-A627

CPLIT-1-A002C

100A 100A 100A 100A 100A 100A 100A 100A 100A 100A 100A

(BUILDING 1 - TR CRITICAL POWER)

(BUILDING 1 - TR NORMAL POWER)

250A 250A

250A 250A

DC T-UPS 1DC T-UPS 2

T-UPS 1

112.5 kVA

T-UPS 2

112.5 kVA

400A 350A

400A 350A

DC MBP-TC DC UPS 2

UPS-2

400A 350A

400A 350A

DC UPS-1

DC LDC

UPS-1 UPS-LDC

600AF

600AT

HCDP1-EHRM

600A 480/277V

ECDP1

DATA CENTER

NEW UPS-B

T-1-EC

200-2

T-1-NP

112.5 kVA

400-1 400-1

DATA CENTER

UPS-B BYPASS

200A

NF DISC.

HNDP1-EHRM

600A 480/277V

400AF

200AT

LSI

DATA CENTER NEW UPS-A

200-2

DATA CENTER

UPS-A BYPASS

100-1

100-1

100-1

100-1

100-1

100-1

100-1

100-1

100-1

100-1

100-1

100-1

100-1

60A60A

CPLIT-1-B046

CPLIT-1-B125

SPD

60A

NPLIT-1-B046

60A60A

NPLIT-1-B125

200-2 200-2

200-2

400AF

200AT

LSI

250AF

175AT

LSI

400AF

200AT

LSI

400AF

200AT

LSI

250AF

175AT

LSI

200-2 200-2

200-2

400-1

SPD

M

SPD

M

M

M M M

M M MM

SPD

M

SPD

M

SPD

M

SPD

M

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

SPD

M

GENERATOR #1

1000 kW

1250 kVA

1600AF

1520AT

L,S,I

GENERATOR #2

1000 kW

1250 kVA

TEMP

GENERATOR

1600AF

1520AT

L,S,I

1600AF

1520AT

L,S,I

ESB

800AF

600AT

L,S,I

TRS

600A

ATS FIRE

BRANCH

FIRE PUMP

MOTOR

FIRE MONITOR

400AF

400AT

L,S,I

ATS LS

DPLS

400A

1600AF

1000AT

L,S,I

800AF

600AT

L,S,I

ATS CRITICAL

ATS-EQUIP

SBC

300AF

210AT

L,S

T-CPH

600AF

300AT

L,S

600AF

480AT

L,S

1600AF

1280AT

L,S,I

CRITICAL POWER

BUS DUCT RISER

TOWER BLDG 1 MV SWG BUS 1

MAIN BLDG 1A MV SWG A

TOWER BLDG 1 MV SWG BUS 2

MAIN BLDG 1A MV SWG B

T4 1500 kVA

T1 1500 kVA

MAIN SERVICE BUS 2 MAIN SERVICE BUS 1

T3 1000 kVA

T2 1000 kVA

SBD

1600AF

1600AT

L,S

1600AF

1600AT

L,S

SBG

SBB

2000AF

2000AT

L,S

SBA

1600AF

800AT

L,S

SBH

SBF

600AF

600AT

L,S,I

600AF

600AT

L,S,I

600AF

600AT

L,S,I

800AF

920AT

L,S

400AF

560AT

L,S

400AF

165AT

L,S, I

800AF

400AT

L,S, I

1600AF

800AT

L,S, I

MCB T-PPP T-SBL T-SBK T-PEE LE-1 SBJ

T-CPK

LG T-PDD

MCC MCA LF T-PFF T-PCC

600AF

210AT

1600AT

800AF

SBE

600AF

160AT

600AF

200AT

HEMG HEMG-1 T-EPB

A

B U

S D

U C

T R

IS

E

R

ELC

T-A

100 A

100 A

225 A

BUS DUCT CONTINUES

EH1 480/277V 400A

T-EL

150A 30A

ATS-UPS

250A

150A 15A

225 A

50A

H2 480/277V 400A

CRAC-2 INDOOR CRAC-2 OUTDOOR

50A 50A 15A 15A

CRAC-1

INDOOR

CRAC-3

INDOOR

CRAC-1

OUTDOOR

CRAC-3

OUTDOOR

GGG

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

E-602-1

BKM

BUILDING 1 - ELECTRICAL ONE-LINE

BKM5/16/23

NOT TO SCALE

BUILDING 1 - ELECTRICAL ONE LINE

ELECTRICAL KEYED NOTES

1. EXISTING ELECTRICAL EQUIPMENT FED FROM ATS-UPS

(SHOWN DASHED) SHALL BE REMOVED AFTER NEW UPS

DISTRIBUTION IS FULLY FUNCTIONAL. COORDINATE WITH

PHASING PLAN AND OWNER.

2. IN EXISTING EMERGENCY CRITICAL POWER 480/277V

SWITCHGEAR SBC SECTION, UTILIZE EXISTING GE

480/277V, 600A FRAME BREAKER AS INDICATED IN ORDER

TO SERVE NEW CRITICAL POWER FEED FOR TR ROOM

DISTRIBUTION. ADJUST TRIP SETTING AS REQUIRED. SEE

ONE-LINE.

3. IN EXISTING NORMAL POWER 480/277V SWITCHGEAR,

PROVIDE ABB ENTELLIGUARD R RETROFILL BREAKER

WHICH IS INTERCHANGEABLE WITH GE BREAKERS.

RETROFILL BREAKER TO FIT IN EXISTING SPACE AS

INDICATED IN ORDER TO SERVE NEW NORMAL POWER

FEED FOR TR ROOM DISTRIBUTION.

4. PROVIDE FLOOR-MOUNT UNISTRUT FRAME AND

HARDWARE NECESSARY TO MOUNT NEW NORMAL AND

CRITICAL POWER DISTRIBUTION PANELS. SEE ONE-LINE.

5. EXISTING ATS-UPS SHALL BE LEFT IN PLACE FOR

POTENTIAL FUTURE RE-USE. COORDINATE WITH OWNER.

6. DISCONNECT POWER TO EXISTING CRACS BEING

REPLACED AND PROVIDE NEW BREAKER TO FEED NEW

CRAC AS SHOWN. SEE EQUIPMENT DATA SCHEDULE AND

PLANS.

7. K13 TRANSFORMER SHALL BE GROUNDED PER

GROUNDING DETAIL.

8. DATA CENTER K13 TRANSFORMER SHALL BE GROUNDED

PER GROUNDING DETAIL.

ELECTRICAL GENERAL NOTES

1. EXISTING EQUIPMENT IS SHOWN "LIGHT". NEW

EQUIPMENT AND FEEDERS ARE SHOWN "BOLD".

2. SUCCESSFUL ELECTRICAL EQUIPMENT VENDOR SHALL

PERFORM SHORT-CIRCUIT, COORDINATION, AND ARC-

FLASH STUDY CALCULATIONS FOR NEW EQUIPMENT

BEING PROVIDED. SEE SPECIFICATION SECTION 260573

FOR FURTHER DETAIL. PROVIDE STUDY SUBMITTAL

DOCUMENTING FINDINGS, BREAKER TYPES, TRIP

SETTINGS AND AIC RATINGS.

ELECTRICAL METERING NOTE

1. FOR ADVANCED UTILITY METERING IN BUILDING 1,

PROVIDE METERING SYSTEMS, COMMUNICATION

NETWORK, AND INTERFACE REQUIRED FOR ELECTRICAL

VOLTAGE, CURRENT, AND POWER DATA

REPORTING. REPORTING SHALL INCLUDE PEAK DEMAND

DATA, TELECOM PANEL ELECTRICAL DATA, TELECOM

DISTRIBUTION PANEL ELECTRICAL DATA, DATA CENTER

ELECTRICAL LOAD DATA, AND OTHER REQUIRED

ELECTRICAL DATA. COORDINATE REPORT DATA WITH

MECHANICAL CONTRACTOR BMS POINTS LIST. SEE

ADVANCED METERING SPECIFICATIONS FOR FURTHER

DETAIL.

VHALEXMessnT Cloud+

VHALEXMessnT Cloud+ New breaker located inside of SBC

VHALEXMessnT Cloud+

VHALEXMessnT Cloud+ Critical ATS

File details come from the government source that posted it. Updated .