Attachment 2 - 21-306 Lexington Paging Pre-Bid Wall Types.pdf
PDF 23 MB Posted
- Attached to
- Y1DA--596-22-101- Replace Overhead Paging System
- Solicitation number
- 36C24925R0039
About this file
The document is a comprehensive set of architectural and engineering drawings for a Public Address and Mass Notification (PAMNS) system replacement project at the VA Medical Center in Lexington, Kentucky. The project, identified as VA Project Number 596-22-101, involves replacing the existing obsolete overhead paging system across multiple buildings in the Sousley Campus, including Buildings 1, 2, 3, 4, 12, 16, 17, 25, 27, 28, and 29.
The drawings provide detailed floor plans for each building, specifying speaker locations, zones, and technical infrastructure requirements. Key technical specifications include using a Biamp Vocia paging system, installing new speaker assemblies, implementing fiber optic and copper cabling, setting up new equipment cabinets, and ensuring compliance with VA standards, NFPA codes, and Americans with Disabilities Act requirements. The project involves comprehensive wiring, conduit installation, and integration of paging stations across various building floors, with a focus on creating a robust, campus-wide communication system. The design documents are dated February 29, 2024, and prepared by Apogee Consulting Group for the VA Medical Center.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
Engineers Architects U.S. Department of Veterans Affairs 53
G-001
PROJECT COVER SHEET
REPLACE PAGING SYSTEM
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
VA PROJECT #: 596-22-101 APOGEE PROJECT #: 21-306
PROJECT SITE MAP BOWLING PROJECT SITE MAP SOUSLEY
PROJECT IMAGE
PROJECT LOCATION
BOWLING CAMPUS
PROJECT IMAGE
SOUSLEY CAMPUS
PROJECT LOCATION
FEBRUARY 29, 2024
CABLES AND CONNECTORS COLOR LEGEND
TELEPHONE
DESCRIPTION
ITEM JACK CABLE PATCH CABLES I.D. NOTES
DATA/COMPUTER
FIBER - MULTI-MODE
SOUND SYSTEM
WHITE
BLUE
BLACK
N/A
WHITE
BLUE
AQUA
GREEN
WHITE
BLUE
AQUA
N/A
T
C
FO
SS
4 PAIR CABLE
4 PAIR CABLE
6/12/24/36
MULTI COLOR
CONDUCTORS
DUPLEX RECEPTACLE
SIMPLEX RECEPTACLE
EMERGENCY POWER RECEPTACLE
CLEAN RECEPTACLE
SPLIT WIRED RECEPTACLE
HIGH VOLTAGE RECEPTACLE
QUADRUPLEX RECEPTACLE
GFI RECEPTACLE
GFI
DED
DED DUPLEX RECEPTACLE
DED SIMPLEX RECEPTACLE
DED
PP POWER POLE
RECEPTACLES
SURFACE DOOR
SURFACE DOOR
RECESSED
SURFACE
PANELS
SPEAKER 8" ROUND CEILING MOUNTED
SPEAKER 10" x 10" SQUARE CEILING MOUNTED
CEILING TYPE#
#'-#" CEILING HEIGHT
SPEAKER SYMBOL LEGEND
VOLUME CONTROL MOUNTED AT 48"AFF
SPEAKER 10" x 10" WALL MOUNTS
VC
S
S
WALL HORN
LINE TYPE
LEGEND:
CEILING
BOUNDARY
2 x 2 DROP CEILING
HARD CEILING
2 x 4 DROP CEILING
GYP CEILING
UNFINISHED CEILING
1' x 2' METAL PAN CEILING
1' x 1' ACOUSTIC CEILING
PAMN PAMN EQUIPMENT CABINET
PS PAGING STATION
PAGING SYSTEM PHASING
1. INSTALL NEW PAGING HEAD END EQUIPMENT IN ROOMS AS INDICATED ON PLANS.
2. INSTALL NEW PAGING EQUIPMENT IN EACH RACK FOR FLOORS AS SHOWN.
3. INSTALL NEW PAGING BACKBONE CABLING TO THE NEW PAGING EQUIPMENT FROM THE HEAD END
EQUIPMENT.
4. CONNECT AND TERMINATE THE BACK BONE CABLING.
5. INSTALL NEW ZONE AMPLIFIERS IN EACH EQUIPMENT RACK.
6. COORDINATE INTERCONNECTION BETWEEN HEAD END AND ZONE AMPS.
7. INSTALL NEW CABLING AND NEW SPEAKERS.
8. REPLACE/INSTALL CHANGE OVER ALL SPEAKERS TO NEW CABLING.
9. CHANGE OVER ALL SPEAKER CIRCUITS TO NEW SYSTEM.
10. REMOVE ALL OLD PAGING EQUIPMENT.
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
TECHNOLOGY GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA
STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL
LISTING REQUIREMENT AND APPLICABLE BUILDING CODES.
PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION
METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING REQUIREMENTS
FOR TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
COMPLY WITH THE LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING
STANDARD.
COMPLY WITH THE LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS
PATHWAYS AND SPACES.
COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN
ACT".
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY
TESTING AGENCY.
NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE
MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
PROVIDE TIA/EIA CAT 6 COPPER OUTLETS AND CONNECTORS.
ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6 KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED
BY THE VA COR.
LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS
SET FORTH BY THE VA HOSPITAL OIT.
PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.B PARAGRAPH 4.5.6.2.
ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4".
DEVICES PLACED IN INTERCOMMUNICATION ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.
24. CONTRACTOR SHALL USE PRE-ASSEMBLED FIRE SLEEVES OR SHALL USE 3RD-PARTY FIRE PENETRATION INSTALLER
AND INSPECTOR.
25. BASIS OF DESIGN UTILIZED IN THIS DESIGN IS THE BIAMP VOCIA PAGING SYSTEM. ALTERNATES TO THE BASIS OF DESIGN ARE ACCEPTABLE UPON MEETING OR EXCEEDING THE FUNCTIONALITY OF THE SYSTEM AS DESIGNED.
26. CONTRACTOR SHALL TRACK AND NOTE ORDER OF SPEAKERS AND DEVICES IN SPEAKER CIRCUITS, AND PROVIDE
RECORD DRAWINGS INDICATING THE ORDERING OF DEVICES.
27. LIST OF AREAS THAT ARE AFTER HOUR TO BE PROVIDED BY THE VA. CONTRACTOR TO COORDINATE ALL WORK
WITH VA COR AT LEAST THREE WEEKS PRIOR TO WORK.
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
E EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FO FIBER OPTIC
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
IT INTERCOMMUNICATION ROOM
MATV MASTER ANTENNA TELEVISION
MM MULTI MODE FIBER
NAC NETWORK APPLIANCE CIRCUIT PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU RACK POWER DISTRIBUTION UNITS
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
TBB TELECOM BONDING CONDUCTOR
TEL TELEPHONE
TGB TELECOM GROUND BUS BAR
TM TELEMONITORING
TMGB TELECOM MAIN GROUND BUS BAR
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WM WIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
LEGEND
E
D
R
N
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
EXISTING TO BE REPLACED
NEW DEVICES
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
Engineers Architects U.S. Department of Veterans Affairs 53
T-001
TECHNOLOGY GENERAL NOTES,
SYMBOL LEGEND & ABBREVIATIONS
ELECTRICAL SYMBOL NOTES ELECTRICAL GENERAL NOTES
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
FEBRUARY 29, 2024 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
53Engineers Architects U.S. Department of Veterans Affairs
TS-101
BOWLING SITE PLAN
1 BOWLING SITE PLAN
SCALE: 1" = 50
NORTH
PLAN
0 25' 50' 100'
A. PROVIDE NEW 4 STRAND OS2 OUTDOOR FIBER
TO PAMNS EQUIPMENT LOCATED AT EACH
BUILDING IN 2" CONDUIT WITH INNERDUCT, FROM
BUILDING 1 MAIN HEAD END EQUIPMENT RACK.
B. CONTRACTOR SHALL UTILIZE EXISTING BUILDING
PATHWAYS AND BUILDING CONNECTORS FOR
CABLING ORIGINATING AT BUILDING 1.
1. UTILIZE EXISTING INNERDUCT ROUTING
THROUGH TUNNEL TO PROVIDE COVERAGE TO
CHILLER PLANT. REFERENCE T-101A.
2. CHILLER PLANT BUILDING.
U G
T
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGTU
G T
UGT
UGT
UGT
UGT
UGT
UG
T
UG
T
UGT
UGT
UGT
UGT
U G
T U
G T
U G
T U
G T
U G
T U
G T
U G
T U
G T
UGT
UG
T
UG
T
UG
T
UG
T
UG
T
UG
T
UG
T
U G
T
UGT UGT UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
U G
T U
G T
U G
T U
G T
U G
T U
G T
U G
T U
G T
U G
T U
G T
UG
T
U G
T
U G
T
U G
T
U G
T
UGT UGT
UGT UGT UGT UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGT
UGTUGTUGT
UGTUGT
U G
T U
G T
U G
T U
G T
U G
T U
G T
U G
T U
G T
U G
T U
G T
U G
T U
G T
B25
B17
B1
B3
B2
B16
B29B28
B27
B4
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
53Engineers Architects U.S. Department of Veterans Affairs
TS-102
SOUSLEY SITE PLAN
1 SOUSLEY SITE PLAN
SCALE: 1" = 50
NORTH
PLAN
0 25' 50' 100'
A. PROVIDE NEW 4 STRAND OS2 OUTDOOR FIBER
TO PAMNS EQUIPMENT LOCATED AT EACH
BUILDING IN 2" CONDUIT WITH INNERDUCT, FROM
BUILDING 1 MAIN HEAD END EQUIPMENT RACK.
B. CONTRACTOR SHALL UTILIZE EXISTING BUILDING
PATHWAYS AND BUILDING CONNECTORS FOR
CABLING ORIGINATING AT BUILDING 1.
1. FOR BUILDING 12, CONTRACTOR SHALL UTILIZE
EXISTING UNDERGROUND PATHWAY TO PROVIDE
NEW FIBER CONNECTION IN INNERDUCT, FROM
BUILDING 1.
UP
UP DN
GARAGE GATE
UP
MOTOR
CYCLE PARKING
WHEEL
CHAIR PARKING
DN
ATM
DN
RAISED FLOOR
GAS CYL
STORAGE
B005D
HAC
A006F
ELEC.
B009
ELECTRICAL
AU003
ELECTRICAL
AU002ELECTRICAL
AU001
SIGNAL CLOSET
D008
TOILET
FEMALE
B019
PREPARATION STERILIZATION
WORK RM
A005C
STORAGE
A008
FOOD
SERVICING
A006D
CLERK
TYPIST
A011
ASST
CHIEF
A012
CHIEF
A010
PARKING LEVEL A
PA01
MECH RM
D-B038
CORRIDOR
BH005
STORAGE
PA08
OTHER SPACE
PAM03
STORAGE
PA07
ELEVATOR
LOBBY
PA02
ELEVATOR
PAE05
ELEVATOR
PAE04
STAIRWELL
PAS05
EMERGENCY
GENERATOR
D003
TRANSFORMERS &
SWITCHGEAR
D003A
STORAGE
D006STORAGE
D005A
EMS
D005
MECH RM
D004
CORRIDOR
DH001
CORRIDOR
DH002
CORRIDOR
DH004
CORRIDOR
DH003
CORRIDOR
DH003
COMM EQUIP
RM
D007D
TD
D002
ELECTRICAL
D001
STAIR
PAS06 STAIR
PAS07
ELEVATOR
S7
ELEVATOR
S6
STORAGE AREA
PA06
PAINT SHOP
D007C
CARPENTER SHOP
D007
LOCKSMITH
D007B
CHIEF
D007A
CORRIDOR
DH005
STAIR
PAS08
CORRIDOR
BH002
M&O
FORMAN
B013
CHIEF
ELECTRICIAN
B014B
ELECTRIC SHOP
B014C
ELECTRONIC
B014
CORRIDOR
BH003
CORRIDOR
BH003
STORAGE
FLAMMABLE
B016
OFFICE
B017
STAFF
TOILET
B015A
WARE HOUSE
B015
STORAGE
GENERAL
B020
MAIL RM
B015B
EMS EQUIP
B021
TOILET
MALE
B018
SOILED
UTILITY
B022A
CORRIDOR
BH004
OFFICE
B022D
OFFICE
B022E
LOGISTICS SVC
INVENTORY MGMT
B022
OFFICE
B022C
OFFICE
B022B
OFFICE
B022A
EMERGENCY GENERATOR
RM
B037
TRANSFORMER RM
B037A
A/C REFRIGERATION
EQUIP RM
B038
CORRIDOR
BH004
ELECTRICAL DISTRIBUTION
RM
B037B
SVC RM
B039
CORRIDOR
BH006
CORRIDOR
BH006
HAS
B044
HAS
B044C
HAS
B044B
EMS OFFICE
B042A
EMS CHECK IN
B042B
SECY/
RECEPTIONIST
B-042
OFFICE
ASST CHIEF
WORK RM
B-042C
TOILET
B044A
IT
B046
EMS
B043
ELECTRIC
CLOSET
B043A
CHARTING
A032E
HALL
A032
CONFERENCE RM
A032D
RESIDENTS
OFFICE
A032C
SECY
OFFICE
A032B
PM&RS CHIEF'S
OFFICE
A032A
MAIN KITCHEN
B036
DISH
WASHING
A020
CONFERENCE M
A029
BREAK RM
B045A
SUPV OFFICE
B045
SURGICAL PACK
B045C
ENVIRONMENTAL
MGMT SUPPLY
B045D
STORAGE
B045B
MAIN KITCHEN
B036
LINEN
B036D
EMS
B036C
MENS
TOILET
B041
FEMALE
TOILET
B040
CANTEEN STORAGE
B036B
OFFICE
B035
STORAGE
B035A
DAIRY & EGG
REFRIG
B036G
OFFICE SUPVS
B036F
CORRIDOR
AH005
CORRIDOR
AH004
CORRIDOR
AH006
CORRIDOR
AH004
SECY
A028
DIETICIANS
OFFICE
A025A
ASST CHIEF
A027
DIETICIANS
OFFICE
A025EMS
A023
ELECTRIC
CLOSET
AU004
ELEVATOR
LOBBY
A000
ELEVATOR LOBBY
A001
BREAK RM
A021
ELEV
AE004
ELEV
AE005
EQUIP
STORAGE AREA
B001
STORAGE
& ISSUE
B034
OFFICE
A019
ELECTRIC
CLOSET
BU003
EMS
A001B
DUMB
ELEVATOR
SOILED RECEIVING
DECONTAMINATION AREA
B005
MANUAL
CART WASH
B005B
STAIRWELL
BS003HALL
B004
EMS
B005A
WOMENS TOILET
B002
MENS TOILET
B003
STORAGE
B009A
HALL
B006A
CORRIDOR
OX101
BULK
STORAGE
B010
LOGISTICS
STORAGE
B011
ELECTRIC
CLOSET
BU002
UNION OFFICE
B011A
FF: VCT
AC PLUMBING
MACH
B012
OFFICE
B012A
CORRIDOR
BH001
CORRIDOR
AH003
CLEAN RECEIVING
B007
CORRIDOR
AH002
STERILE AND NON-STERILE
STORAGE
A001A
RETAIL STORE
A009
STAIRWELL
PAS04
CORRIDOR
AH001
ELECTRIC
CLOSET
AU005
OFFICE
ASST CHIEF
A003
KITCHEN
A006
OFFICE
CANTEEN
A007
REFR WALK IN
A006B
PREFAB
REFRIG
A006C
FOOD
STORAGE
A006A
SERVING LINE
A005
AU008 AU007 AU006
STAIR
AS002
CAFETERIA
A004A
VCS OFFICE
A004E
VCS OFFICE CHIEF
A004A
STORAGE
A004
STORAGE
A004A
EMS
A004B LOUNGE
A002
LOCKERS
FEMALE
A002A
TOILET &
SHOWERS
A002B
IT CLOSET
A002C
ELEV
P3
ELEV
P2
ELEV
P1
TOILET
A024TELEPHONE EQUIP RM
A022
LOCKERS
A026B
EMS
A026
PHYSICAL
THERAPY
A035
STORAGE
A033
HYDROTHERAPY
A034
RECEPTION
A030
CORRIDOR
AH007
PHYSICAL THERAPY
OUTPATIENT
A036
CORRIDOR
A030A
WAITING AREA
A042
EXAM/EMG
A037
PROVIDER
A038
EXAM
A041
EXAM
A040 PROVIDER
A039
STAIRWELL
AS001
TOILET & SHOWERS
A046
A026A TOILET
FEMALE
A045
OT CLINIC
A044
OT OFFICE
A043
OT OFFICE
A043A
RECEPTION AREA
A050
CORRIDOR
AH009
OFFICE
A070RECEIVING
A071
SVC MGR
A072
CORRIDOR
AH008PGM MGR
A068
OFFICE
A069
COMPUTER RM
A073
CORRIDOR
AH010
SOFTWARE APPL
SUPPORT
A067
APPLICATION
SUPPORT
A066
SYSTEMS
MGR
A065
NETWORKING
MGR
A064
PROG MGR SYST &
NETWORKING
A063
ADP
WORKSHOP
A062
STAIRWELL
AS004
TELECOMM
SVCS
A061
TELECOMM
SVCS
A060
SUPPORT
A059
APPLICATION
SUPPORT
A058
APPLICATION
SUPPORT
A057
OFFICE
A051
PGM
SPECIALISTS
A052
PGMMING &
INFO
A053
PGMMING &
INFO
A054
CONFERENCE
RM
A055
ELECTRICAL
A056
MECHANICAL
B015F
FF: CONC.
PROSTHETICS STORAGE
B015C
FF: VCT
MORGUE
B015A
FF: VCT
LOGISTICS BREAKDOWN
B006B
FF: VCT
PAMNS ZONE 'C'
PAMNS ZONE 'E'
PAMNS ZONE 'E'
PAMNS ZONE 'C'
PAMNS ZONE 'E'
PAMNS ZONE 'L'
PAMNS ZONE 'L'
PAMNS ZONE 'C'
PAMNS ZONE 'H'
PAMNS ZONE 'C'
PAMNS ZONE 'L'
PAMNS ZONE 'C
PAMNS ZONE 'E'
PAMNS ZONE 'L'
PAMNS ZONE 'C'
PAMNS ZONE 'H'
PAMNS ZONE 'P'
PAMNS ZONE 'P'
PAMNS ZONE 'P'
PAMNS ZONE 'C'
PAMNS ZONE 'I' PAMNS ZONE 'C'
PAMNS ZONE 'I'
PAMNS ZONE 'C'
PAMNS ZONE 'P'
PAMNS ZONE 'PDeck'
PAMNS ZONE 'F'
PAMNS ZONE 'C'
PAMNS ZONE 'F'
PAMNS ZONE 'C'
PAMNS ZONE 'K'
PAMNS ZONE 'S'
PAMNS ZONE 'L'
PAMNS ZONE 'C'
PAMNS ZONE 'L'
PAMNS ZONE 'C'
PAMNS ZONE 'K'
PAMNS ZONE 'C'
PAMNS ZONE 'K'
PAMNS ZONE 'PDeck'
SRSR
SR
SR
SR
SR
SR
SR
SR
SR
SRSR
SR
SR
SRSR
SR
SR
SR SR
SR
SRSRSR
SR SR
SR
SR SR SR
SR
SR
SRSR
SR
SR
SR
SR
SR
SR
SR
SR SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SRSR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SRSR
SR
SR
SRSR
SN
SN
SN
SN
SN
SN
SN
SN
SN
SN
SNSN
SN
SN SN
SNSN
SN
SN
SN
SN
SN SN
SN
SN
SN
SNSN
SNSN
SNSN
SN
SN
SNSN
SN
SN
SN
SN
SN
SN
SN
SN
SN
SN
SN
N
N
N
N
N
N N
N
N N
N N
N
N
N
N
N N
SN
SN
SN SN
SNSN
SN
SN
N N
N
N
N
N
N
PS PS PS PS
PS PS PS PS
PS PS
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0" 18'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
S N
S N
S N
S N
S N SN
S N
S N
PAMNS ZONE 'Z'
PAMNS ZONE 'Z'
PAMNS ZONE 'Z'
PAMNS ZONE 'L'
7'7'
7'
7' 7'
7'
7'
7'
7'7'
7'
7'
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATINGS
BUILDING SEPARATION ( >2 HOURS)
3 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1/2 HOUR FIRE BARRIER
SMOKE BARRIER ( >1/2 HOUR)
SMOKE RESISTIVE CONSTRUCTION
X
Engineers Architects U.S. Department of Veterans Affairs
SPEAKER 8" ROUND CEILING MOUNT
SPEAKER 10" X 10" SQUARE CEILING MOUNT
SPEAKER 10" x 10" WALL MOUNT
WALL HORN
CEILING TYPE
CEILING HEIGHT
CEILING TYPE LEGEND
1 2X2 DROP CEILING
2 HARD CEILING
3 2X4 DROP CEILING
4 GYP CEILING
5 UNFINISHED CEILING
6 1' x 2' METAL PAN CEILING 7 1' x 1' ACOUSTIC CEILING
S
S
S
LINE TYPE LEGEND:
CEILING BOUNDARY:
VOLUME CONTROL MOUNTED AT 48"AFFVC
SYMBOL LEGEND
PAGING SYSTEMPS
8 2' x 4' DRY WALL CEILING
T-101A
BOWLING GROUND LEVEL OVERALL
PLAN
1 BOWLING GROUND LEVEL OVERALL PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
1. SPEAKERS IN THIS ZONE WILL HAVE
ANTI-MICROBIAL FACE/BAFFLE.
2. PROVIDE PAGING STATION IN THE PAGING
CENTER AND CONNECT TO THE PAMN SYSTEM
COORDINATE EXACT LOCATION WITH COR
3. UTILIZE EXISTING INNERDUCT FROM ROOM
D007D TO FEED DEVICES LOCATED IN CHILLER
PLANT. INNERDUCT TRAVELS APPROXIMATELY 2
STORIES DOWN PRIOR TO TRAVELLING TO
GROUND FLOOR OFFICE OF CHILLER PLANT.
COORDINATE WORK WITH COR.
T-401
A. ALL EXISTING CONDITIONS ARE BASED ON BEST
AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION.
B. REPAIR/REPLACE ANY DAMAGED CEILING.
C. PROVIDE NEW SPEAKER ASSEMBLY AS SHOWN
AND CONNECT TO EXISTING SPEAKER/PAGING
ZONE.
D. ALL SPEAKERS SHALL BE TAPPED AT 1/2 WATT
UNLESS OTHERWISE NOTED.
E. MINIMUM SPEAKER WIRE SHALL BE 16 AWG.
F. PAGING CABLES SHALL BE INSTALLED IN
CONDUITS IN ALL EXPOSED AREAS (ROOMS WITH
NO CEILINGS) IN ELECTRICAL ROOMS,
MECHANICAL ROOMS, BOILER ROOMS, STORAGE
ROOMS, GARAGES, OUTSIDE AREAS AND STAIRS.
G. ALL PAGING CABLING/CONDUIT SHALL BE
SUPPORTED BY J-HOOKS, IN CABLE TRAY OR AN
APPROVED SUPPORTING SYSTEM.
FEBRUARY 29, 2024
WALL DEVICES
MOUNTED ON
CONCRETE/MASONRY
IN PARKING GARAGE
CONCRETE/
MASONRY
CONCRETE/
MASONRY
GYPSUM
GYPSUM
GYPSUM
CONCRETE
GYPSUM
GYPSUM
GYPSUM
GYPSUM
GYPSUM
GYPSUM
WHEEL CHAIR PARK
HANDICAPPED
PARKING
HANDICAPPED
HANDICAPPED
PARKING PARKING
HANDICAPPED
PARKING
HANDICAPPED HANDICAPPED
PARKING
HANDICAPPED
PARKING
HANDICAPPED
PARKING
HANDICAPPED
PARKING
HANDICAPPED
PARKING PARKING
LEVEL B
VOLUNTEER
PARKING
VOLUNTEER
PARKING
VOLUNTEER
PARKING
VOLUNTEER
PARKING
VOLUNTEER
PARKING
VOLUNTEER
PARKING
VOLUNTEER
PARKING
DOWN
UP
PARKING
DOWN
UP
EMERGENCY
GENERATOR RM
PB01
B038
A/C
REFRIGERATION
EQUIP RM
OTHER SPACE
PB11
TRANSFORMER
RM
B037A
B039
B037
SVC RM
B037B
ELECTRICAL
DISTRIBUTION RM
STAIRWELL
STAIRWELL
AS02
BS03
AS01
STAIRWELL
DENTAL
ORAL
EVAC
UNIT
STAIRWELL
PB09A
PBS05
CHASE
PB03
STORAGE
PB10
ELEV
VESTIBULE
PB02
ELEVATOR
P5
ELEVATOR
P4
PUMP
RM
0-C-1
TC
PB06
EC
PB05
STAIRWELL
PBS06
STAIRWELL
PBS04
UTILITY TUNNEL OTHER SPACE
PB09 PB09
OTHER
SPACE
PB07
FAN RM
PB04
PAMNS ZONE 'PDeck'
PAMNS ZONE 'PDeck'
SN
S
S
N N N
N
NNN
N
N N N
N
N
N
N N N
N
PAMNS ZONE 'B'
PAMNS ZONE 'B'
N
N
N
NN
S
N
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATINGS
BUILDING SEPARATION ( >2 HOURS)
3 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1/2 HOUR FIRE BARRIER
SMOKE BARRIER ( >1/2 HOUR)
SMOKE RESISTIVE CONSTRUCTION
X
Engineers Architects U.S. Department of Veterans Affairs
SPEAKER 8" ROUND CEILING MOUNT
SPEAKER 10" X 10" SQUARE CEILING MOUNT
SPEAKER 10" x 10" WALL MOUNT
WALL HORN
CEILING TYPE
CEILING HEIGHT
CEILING TYPE LEGEND
1 2X2 DROP CEILING
2 HARD CEILING
3 2X4 DROP CEILING
4 GYP CEILING
5 UNFINISHED CEILING
6 1' x 2' METAL PAN CEILING 7 1' x 1' ACOUSTIC CEILING
S
S
S
LINE TYPE LEGEND:
CEILING BOUNDARY:
VOLUME CONTROL MOUNTED AT 48"AFFVC
SYMBOL LEGEND
PAGING SYSTEMPS
8 2' x 4' DRY WALL CEILING
T-101B
BOWLING BASEMENT LEVEL
OVERALL PLAN
1 BOWLING BASEMENT LEVEL OVERALL PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
A. ALL EXISTING CONDITIONS ARE BASED ON BEST
AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION.
B. REPAIR/REPLACE ANY DAMAGED CEILING.
C. PROVIDE NEW SPEAKER ASSEMBLY AS SHOWN
AND CONNECT TO EXISTING SPEAKER/PAGING
ZONE.
D. ALL SPEAKERS SHALL BE TAPPED AT 1/2 WATT
UNLESS OTHERWISE NOTED.
E. MINIMUM SPEAKER WIRE SHALL BE 16 AWG.
F. PAGING CABLES SHALL BE INSTALLED IN
CONDUITS IN ALL EXPOSED AREAS (ROOMS WITH
NO CEILINGS) IN ELECTRICAL ROOMS,
MECHANICAL ROOMS, BOILER ROOMS, STORAGE
ROOMS, GARAGES, OUTSIDE AREAS AND STAIRS.
G. ALL PAGING CABLING/CONDUIT SHALL BE
SUPPORTED BY J-HOOKS, IN CABLE TRAY OR AN
APPROVED SUPPORTING SYSTEM.
FEBRUARY 29, 2024
WALL DEVICES
MOUNTED ON
CONCRETE/MASONRY
IN PARKING GARAGE
CONCRETE/
MASONRY
CONCRETE/
MASONRY
CONCRETE
/MASONRY
DOWN
MOTORCYCLE
MOTORCYCLE
STAIRWELL
PCS04
PARKING
PC01
SUMP
00-C-3
OTHER SPACE
PCM17
FAN RM
00-C-2
STORAGE
PC14
STORAGE
00C6
MECH
RM
PC15
STORAGE
PC16
ELEVATOR
LOBBY
PC02
ELEVATOR
PCE05
ELEVATOR
PCE04
ELEV
EQUIP
00-C-1
STAIR
PCS05
STORAGE
PC05
STORAGE
PC09
MECH RM
PC10
TC
00-D-3
EC
00-D-2STAIR
PCS06
FAN RM
00-D-1
OTHER
SPACE
PCM11
FF:CONCRETE
FF:CONCRETE
FF:VCT
FF:CONCRETE FF:CONCRETE
FF:CONCRETE
FF:VCT
FF:VCT
FF:VCT
FF:CONCRETE
FF:VCT
FF:VCT
FF:CONCRETE
FF:VCT
FF:VCT
FF:CONCRETE
FF:CONCRETE
FF:CONCRETE
FF:CONCRETE
FF:VCT
PAMNS ZONE 'PDeck'
S
S
S
SN
N
N N N
N N N
N
N N N
N
N N N
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATINGS
BUILDING SEPARATION ( >2 HOURS)
3 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1/2 HOUR FIRE BARRIER
SMOKE BARRIER ( >1/2 HOUR)
SMOKE RESISTIVE CONSTRUCTION
X
Engineers Architects U.S. Department of Veterans Affairs
SPEAKER 8" ROUND CEILING MOUNT
SPEAKER 10" X 10" SQUARE CEILING MOUNT
SPEAKER 10" x 10" WALL MOUNT
WALL HORN
CEILING TYPE
CEILING HEIGHT
CEILING TYPE LEGEND
1 2X2 DROP CEILING
2 HARD CEILING
3 2X4 DROP CEILING
4 GYP CEILING
5 UNFINISHED CEILING
6 1' x 2' METAL PAN CEILING 7 1' x 1' ACOUSTIC CEILING
S
S
S
LINE TYPE LEGEND:
CEILING BOUNDARY:
VOLUME CONTROL MOUNTED AT 48"AFFVC
SYMBOL LEGEND
PAGING SYSTEMPS
8 2' x 4' DRY WALL CEILING
T-101C
BOWLING SUB-BASEMENT LEVEL
OVERALL PLAN
1 LOWER LEVEL OVERALL PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
A. ALL EXISTING CONDITIONS ARE BASED ON BEST
AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION.
B. REPAIR/REPLACE ANY DAMAGED CEILING.
C. PROVIDE NEW SPEAKER ASSEMBLY AS SHOWN
AND CONNECT TO EXISTING SPEAKER/PAGING
ZONE.
D. ALL SPEAKERS SHALL BE TAPPED AT 1/2 WATT
UNLESS OTHERWISE NOTED.
E. MINIMUM SPEAKER WIRE SHALL BE 16 AWG.
F. PAGING CABLES SHALL BE INSTALLED IN
CONDUITS IN ALL EXPOSED AREAS (ROOMS WITH
NO CEILINGS) IN ELECTRICAL ROOMS,
MECHANICAL ROOMS, BOILER ROOMS, STORAGE
ROOMS, GARAGES, OUTSIDE AREAS AND STAIRS.
G. ALL PAGING CABLING/CONDUIT SHALL BE
SUPPORTED BY J-HOOKS, IN CABLE TRAY OR AN
APPROVED SUPPORTING SYSTEM.
FEBRUARY 29, 2024
WALL DEVICES
MOUNTED ON
CONCRETE/MASONRY
EXISTING
STAIR
DS108
TOILET
ELEC
B146A
STORAGE
FEMALE
TOILET
CORRIDOR
AS106
OFFICE
NURSE MGR
INPT PHARMACY
IV STORAGETECHNICIAN OFFICE
A-166
VAULT
A-180
B102
SVC ELEV
LOBBY
CORRIDOR
AH101
SUPPLY
B101L
NUCLEAR MED AND
RADIATION SAFETY
ADMIN OFFICE
CORRIDOR
A-151A A-151
A-160
READING RM
A-159
B133D175
A-184
A-184B
C125G
OFFICE
C125
PASSAGE
C125I C129
BH108
CORRIDOR
B101K
B107
B106
SUPV
LAB
BH105
CT SCAN 1
B114
CONFERENCE
CLASS & STUDY
CLINICAL
MICROBIOLOGIST
CORRIDOR
BH103
CORRIDOR
B147A
B148
B141
B140
DRESSING
B137A
VESTIBULE
CH130A
STAFF TLT
CH132AC134
TLT
EXAM / ISO
C130J
EXAM
C125A
TLT
C121C
TRIAGE 01
C121B
STAFF / WORK RM
VASCULAR LAB
D181
RAD STORAGE
EMSCORRIDOR
B138
PATIENT PREP
STORAGE RM
WORK
RM
D191
VASCULAR LAB
D190
SURG CLINIC
CHECK IN
D157
D158 OFFICE
BREAK/
READING
E126
E123
TOILET
CRYOGEN
STORAGE
MRI
E120
COMPUTER RM
E104
SECTION
OFFICE
EM113
D158
D160A
EXAM
D146
EXAM
EXAM
EXAM
CONS
D144
IT EQUIP RM
D112
STAFF TOILET
D111
STAFF TOILET
D108
D107
BREAK RM
D113 D140B
DS107
STAIR
PHYSICIAN
CONSULTANT RM
DU141
EC
DU142
TC
D102C
TOILET
D102D
PATIENT RM
D109
D110
EXAM
D116
CONS
D106
CLEAN SUPPLY D118
EXAM
D104
DIRTY SUPPLY
D120
EXAM
TOILET
D103
EXAM
D101
EXAM
D124
EXAM
D100
MED RECORD
WORK RM
D100A
RECEPTION
INFUSION / CHEMO TREATMENT
DH108
CORRIDOR
D139
CLEAN STOR
SUPPLY RM
D115
PROCEDURE RM
D117
OFFICE D135
EXAM
D133
EXAMD119
EXAM
D121
EXAM
D131
EXAM
D123
EXAM
D129
EXAM
D125
EXAM
D127
EXAM
D143
STORAGE
D136
CAST RM
D145
EXAM
D147
EXAM
D134
EXAM
D132
EXAM
D149
EXAM
D130
EXAM
D151
EXAM
D128
EXAM
D153
EXAM
DH107
CORRIDOR
DH111
CORRIDOR
DH109
CORRIDOR
CH105C
WAITING
CH113
CORRIDOR
CH105
CORRIDOR
C108
TRAVEL
C111
P5
ELEVATOR
P4
ELEVATOR
D102B
TOILET
D102A
PATIENT RM
C109
MENS TOILET
WOMENS
TOILET
C106 C107
EC
C112B
C112A C112 C113A
C113
DIRECTOR OFFICE
C104V1
CUBICLE
C104V2
CUBICLE
C104V3
CUBICLE
C104V4
CUBICLE HEALTH
BENEFITS
CENTER
C104V6
COPY
C104V11 C104V12 C104V13
C104V14
C104V15
C104V19
C104V18
C104U
DECEDENT
AFFAIRS
C104T
OFFICE
C104S
SUPVY MED
SUPPORT
ASST
C104R
PATIENT SUPPORT
PGM SPECIALIST
C104Q
CHIEF AMBULATORY
CARE AND
PROCESSING
C104P
CHIEF HEALTH
INFO MGMT
C104O
HEALTH ADMIN
CHIEF OFFICE C104N
ADMIN
ASST
C104M
ASST CHIEF
HEALTH ADMIN
C104K
CHIEF
OFFICE C104J
UM / UR MGR
OFFICE
CUBICLE
C104H
WORK RM C104
POLICE
C105
HOLDING
C104D
PAT
TOILET C104A
RECEPTION
C104E
STAFF
TOILET
C107
PIV
C104G
BREAK RM
C103
ARMORY
C102
POLICE
C104I
CONFERENCE RM 101
WHEEL CHAIR
STORAGE
C1-1A
VESTIBULE
C110
POLICE
CH101
LOBBY
C113B
E.R. STAFF
C109
EVIDENCE
UP
C139A
D192
TOILET
CORRIDOR
A-191
AS108
PHARMACY OFFICE
A-189
A102
SUPPORT UNIT
ADMINA-190C
PRE-PACK
A164
CORRIDOR
JANITOR
ASSOCIATE CHIEF
OF PHARMACY
OFFICE
BREAK RM
CONFERENCE RM
A190A
STORAGES V
BH102
A-153
WAITING
C126C
EXAM
MENTAL HEALTH
RM
EXAM
E CYL
MED RM
B105
B104
CORRIDOR
BIO MED
ENGG
GLASS WASH
MICROBIOLOGY
LAB
B117
BH104
B144
OUTPATIENT
READING RM
B147
B143
VACANT
B140A
BU106
RESUSCITATION 1 /
ISOEMS
CLEAN UTIL
C136
C125K
STORAGE
C125D
EXAM
PASSAGE
C122
CH121B
EKG/LAB
PASSAGE
EXAM
D183B
D189
D196
WAITING
VESTIBULE
CONFERENCE RM
C107C104E
RECEPTION
C104A
HOLDING
POLICE
WORK RM
UM / UR MGR
OFFICE
C104M
ADMIN
ASST
COPY
C104V6
C104V4
C112A
C107
C109
ELEVATOR
D194
CORRIDOR
ULTRA SOUND
ANGIOGRAPHY
LINEN RM
MRI READING RM
E130
STAIRWELL
PUBLIC TOILET
CAST RM
E128ORTHO STORAGE
PREPARATION
E121
E127
HVAC
MECH/ELEC
CORRIDOR
E119
PROCESSING
ADMIN
OFFICER
E108E110
C111
CORRIDOR
CORRIDOR
DH107
OFFICE
EXAM
EXAM
CONS
D130
D147EXAM
D117
D120
D106
TC
S7
ELEVATOR
S6
D113
ELEC
DN
C109
E128A
A-188
PASSAGE
CH126
CH101C
AH102
CORRIDOR
AH101
CORRIDOR
PATIENT
ADVOCATE
A-190b
MEN
A-179
CLINICAL
PHARMACIST
A-168 A-170
PHARMACY STORAGE
B101B
SURGICAL
PATHOLOGY
B101H
BU101
CORRIDOR
EXAMBREAK RM
A-158
BONE DENSITY
B132
MECH
A-184A
C127
C126D
EXAM
ELEC
BU103
BH107
MECH
HALL WAYSCANNER
RM
CORRIDOR
X-RAY DIAGNOSTIC RM
FILM PROCESSING
AREA
B142
STAFF WORK
C130
C130E
ER OFFICE 2
C141C143
C132D
C128
C125B
SPECIMEN
SOILED UTIL
TRIAGE 02
CH130B
C132A
C121
SOILED UTIL
CS109
ELEVATOR
D195
C114B
RESP
CARE
POLICE
C1-1A
WHEEL CHAIR
STORAGEC104I
C102
ARMORY
C103
BREAK RM C105
SUPVY MED
SUPPORT
ASST
OFFICE
C104T
C104V13C104V12
CUBICLECUBICLE
C104V2
CUBICLE
C104V1
C112B
ELEC
TOILET
E101
MRI RECEPTION
D193
D169
D169a
PROCEDURE RM
E124
E116 E122
RADIOLOGIST
E107
CH105
CH105E
DH110
D161
EXAM
D153
EXAM
D151
D145
D136
D143
D125
D135
D101
ELEVATOR
DU141
DS107
D140B
BREAK RM
D107
D108
STORAGE
EVIDENCE
MALE
TOILET
ADMIN
ASSIST
EXIST WELCOME
DESK
CORRIDOR
CORRIDOR
CORRIDOR A-190
A-175
A-178
MED MGMT
SPECIALIST
A-163
A-167
PHARMACY
ADAPC
RESIDENTS
A-166
PATHOLOGY LAB
CORRIDOR SOILED
A146
CONFERENCE RM
BREAK RM
B108
BREAK RM
B101G
STORAGE
B101ISUPV
ELEC
AU-105
A-150
FILE RM
A-152B
MENS
RESTROOM
A-156
VIEWING RM
A-185
STORAGE
DECONTAM
TOILET
ON CALL
C125F
C130A
CH125H
NOUR
PREP
C125J
STAIR
CS104
OFFICE
B103
ELEC
BS103
B128
B150A
B152A
LAB INFO
MGR
B113B
MEDIA
PREPARATION
B114D
CHIEF
PATHOLOGY SVC
B118B121
B153
CORRIDOR
BH106
STORAGE
PASSAGE
CH121
ISO
RESUSCITATION 2 /
CH140
EXAM / ISO
C130H
C140 C144
C131
EXAM
C130K
C125E
C125C
EXAM
C124
C123SUB-WAITING
C121DC121A
C132C
EC
CU100
P7
EXAM
C114C
CH104
C104G
PIV
STAFF
TOILET
C104
C104J C104K
CHIEF HEALTH
INFO MGMT
C104P
C104Q
DECEDENT
AFFAIRS
C104V15
C104V3
CORRIDOR
D186
CONTROL
D188A
D180
E129
D156A
STAFF RM
PHYSICISTS
OFFICE & LAB
E125MRI READING
STAFF RADIOLOGIST
OFFICE
D166
SUPV MRI
TECH
E103
CHIEF OF
RADIOLOGY
E109E112
CORRIDOR
DH112
C108
CORRIDOR
MECH
D154A
OFFICE
EXAM
D154
EXAM
D150
EXAM
D127
D119
D139
DH108
D100
D124
EXAM
D103
D118
CONS
D116
D110
D109
D102C
PHYSICIAN
CONSULTANT RM
D111
STAFF TOILET
UP
DN
B140A
TOILET
E106
E105
CORRIDOR
CH102A
EXAM / ISO
C130I
C113B
CHIEF
TECHNOLOGIST
EH102
BMS CLOSET
A178
ANTEROOM
ACOS AMB
CARE
INVESTIGATION DRUGS SVC
PGME MGR
A-162
A-165
A-167A
CHIEF
A-169
CRITICAL CARE
PHARMACY
SPECIALIST OFFICE
A-171
IN-VITRO COUNTING
HIGH/LOW
STAIR
A147
B101A
B107A
OFFICE
STORAGE
EMS CLOSET
B101D
A-150A
HOT LAB
A-155
A-157
KITCHEN
B133A
B133B
PHARMACY WAITING
A-186
A-184C
EXAM
C130B
PASSAGE
CH125B
CLEAN UTILITY
C130D
CH132
CORRIDOR
BH109
STORAGE
BLOOD BANK MED
DIRECTOR
LAB MGR /
CHIEF
MED TECH
CLINICAL
CHEMIST
BU102
STAIR
CONTROL RM
PCR RM
ANCILLARY
TESTING COORD
B116B119B-120
RADIOLOGY SVC
SUPPLY RM RADIOGRAPHIC
RADIOGRAPHIC AND
FLUOROSCOPIC
RADIO/FLOUR
B137
WAITING
CH120
ENTRANCE
CH139
C130F
PASSAGE
C142
EMPLOYEE TRAINING
RM
EXAM
CART STORAGE
TLT
EXAM
CH125A
EXAM
C133
ELEVATOR
P6
EC
D183A
EXAMC114
CH104A
CH101
C110
CHIEF
OFFICE
PATIENT SUPPORT
PGM SPECIALIST
C104V11
CUBICLE
C113A
ELEVATOR
P5
CH118
D172
E100
D194
PRE-OP
ASSESSMENT
CH114
CAST RM
CAST RM
DRESS
EM115
X-RAY
E118E117
LIBRARY
STAFF
RADIOLOGIST
E111
DH111
EXAM
EXAM
D152
D162
D163
D132
D129D123
D131D121
D133
OFFICE
D115
D100A
D102D
D112
BU102
B139B
DRESSING
B139A
TOILET
B137B
A-152B
STAFF
TOILET
VASCULAR LAB
E102
CORRIDOR
CH102
C114A
EH103
A-177
AH103
AS107
A177
A103
A-190a
A-177a
WOMEN
A-176
MGR
CMOP
FORMULARY MGRPHARMACY
OPERATION
MGR
A-172
A-173
A174
AS102
1B-1
BH101
B101J
ELECTRIC
CLOSET
B104
PROVIDER
WORK RM
AH102
CORRIDOR
A-152A
WAITING
A-152
WOMENS
RESTROOM
A-154
SUPPLY
VACANT
B131
LOUNGE
STAFF
TOILET
B133A
C126A
PHYS
WORK
C130C
STAFF WORK
CH125
PASSAGE
LINE ITEM
MGR OFFICE
FEMALE
TOILET
B127
CORRIDOR
MALE TOILET
B126
B125
B152
B113
B114C
PATHOLOGY
B115
PATHOLOGISTCHIEF
PATHOLOGIST
UPS
RM
VACANT
CONTROL RM
B147B
X-RAY
RADIOGRAPHIC AND
FLUOROSCOPIC
B139
C138OFFICE 3
ER NURSE MGR
C137
IT
PASSAGETLT/SHWR
EMS
CH121A
PASSAGEC132B
EXAM
IT
C135
STAIRWELL
SPEC COLLECT
BREAK RM
LOBBY
POLICE
PAT
TOILET
C104H
CUBICLE
ASST CHIEF
HEALTH ADMIN
C104N
HEALTH ADMIN
CHIEF OFFICE
C104O
CHIEF AMBULATORY
CARE AND
PROCESSING
C104R
C104S
C104U
C104V17
C104V18
C104V19
C104V16
C104V14
C104C
C113
CANTEEN
HASC112
EMS
C106
C110A
D102AD102B
P4
B134C
D173
OFFICE- CHIEF VASCULAR
LAB TECH
D171
DS108
PRE-OP
ASSESSMENT
EC
D155
D156
D193
SVC
OFFICE
D185
DRESSING/
RESTROOM
D168A
TOILET
DRESS
TOILET
D165
EMS CLOSET
E114
EH104
STAFF
RADIOLOGIST
STAFF
RADIOLOGIST
FISCAL
CH113
WAITINGCH105C
CORRIDOR
DH109
D160
D148
D128
D149
D134
EXAM
CH100
D124A
D104
SOILED UTILITY
D164
DU142
EC
D140
STAIR
BREAK ROOM
D140A
UROLOGY
EMS
C104V7 C104V5
C104V20 C104V19 C104V18
C110
D126B
SURGERY
D137
D168
CONFERENCE
BH103
CORRIDOR
DH116
CORRIDOR
DH116A
CORRIDOR
B136
MECH. SHAFT B135
STORAGE
D137
EQUIPMENT
B134A
CHEST X-RAY
B134
CHEST X-RAY
B134B
OFFICE
D175A
RADIOLOGY
LOBBY
D180A
CONTROL RM
CH118
CORRIDOR
TOILET
B134D
RADIOLOGY
WAITING
BH103
B142
INPATIENT
HOLDING
BAY 3
B146E
INPATIENT
HOLDING
BAY 3
B146D
INPATIENT
HOLDING
BAY 3
B146C
OFFICE
B101F
STORAGE
B101C
OFFICE
B101E
RADIOLOGY
STORAGE
B146F
DRESSING
RM
B146H
DRESSING
RM
DRESSING RM
ALCOVE
B146G
DRESSING
RM
B14JG
INPATIENT
OBSEVATION
B146B
RECEPTION
B146B
HOT LAB
OFFICE
B132A
DOSE
B122A
DOSE
B122B
HOT LAB
B122C
TOILET
B122D
B122A
WAITING
C1-5D
WORK RM
D155
SURGERY
CLINIC
SURGERY
CLINIC
SURGERY
CLINIC
B144
X-RAY
DIAGNOSTIC
RM
BH105
CORRIDOR
PAMNS ZONE '1S'
PAMNS ZONE '1A'
PAMNS ZONE '1B'
PAMNS ZONE '1A'
PAMNS ZONE '1A'
PAMNS ZONE '1B'
PAMNS ZONE '1R'
PAMNS ZONE '1R'
PAMNS ZONE '1R'
PAMNS ZONE '1N'
PAMNS ZONE '1L'
PAMNS ZONE '1A'
PAMNS ZONE '1L'
PAMNS ZONE '1N'
PAMNS ZONE '1A'
PAMNS ZONE '1R'
PAMNS ZONE '1A'
PAMNS ZONE '1E'
PAMNS ZONE '1A'
PAMNS ZONE '1E'
PAMNS ZONE '1E'
PAMNS ZONE '1X'
PAMNS ZONE '1X'
PAMNS ZONE '1A'
PAMNS ZONE '1X'
SS
SS
S
S
S
S
SR
SR
SRSR
SR
SRSR
SR
SR
SR SR
SR
SR SR
SR
SR SR
SRSR
SR SR
SR
SR
SR
SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR SR
SR
SR
SR
SR
SR SR SR SR
SRSR
SRSR
SR
SRSR
SR
SRSR
SR
SR SR
SR
SR
SRSR
SR
SR
SR
SR SR SR
SR SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SRSR SRSR
SR
SR
SR
SRSRSR
SR
SR
SR
PAMNS ZONE '1A'SR
SR
SR
SR
SR
SR
PAMNS ZONE '1A'
SR
SR
SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR SRSR
SR
SR
SR
SR
SR
SR
SR
SR
SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SN
SN
S S
S S
SN
SN
SN
SN
SN
SN
SN
SN
N
N
N
N
SD
SD SD SN SN SD SD
SD
SD
SN
SN
SD
SD
SN
SN
SR
SN
SR
SN
SN
SN
SD
SN
SR
SD
SN
SDSN
SN
SR SD SN
SN
SD
SR
SN
SN
SRSN
SN
SRSN
SR
SN
SN
SNSN
SN
SN
SR SR SR
SN
SD
SR SR
SNSNSN
SN
SN
SD
SD
SNSNSNSD
SN
SN
SN
SN SN
SN SN SN SN
SN
SN
SN
SNSNSN SN
SN
PAMNS ZONE '1P'
PAMNS ZONE '1N'
PAMNS ZONE '1M'
PAMNS ZONE '1M'
SN
SN
SN
9'-0"
9'-0"
9'-6"
9'-6"
9'-6"
9'-6"
9'-6"
8'-0"
8'-0"
8'-0"
8'-6"
8'-0"
8'-0"
8'-0"
8'-0"
9'-0"
8'-0"
8'-0"
8'-0"
9'-0"
8'-0"
8'-6"
8'-6"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-6"
8'-6"
8'-6" 18'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
S N
SN
SN
SN
SN
SN
PRIVATE
A132
PRIVATE
A131
PRIVATE
A130 PRIVATE
A127
PRIVATE
A126
PRIVATE
A122
OFFICE
A121
OFFICE
A120
SE
MI
-P
RI
VA
TE
A1
29 SEMI-PRIVATE
A128
TOILET
A130A
TOILET
A131A
TOILET
A132A
TOILET
A127A
TOILET
A126A
TOILET
A124A
TOILET
A122A
TOILET
A121A
TOILET
A120A
GROUP
ROOM
A143
TOILET
A128A
TOILET
A129A
SECLUSION
ANTEROOM
A136A
TOILET
A136B
SECLUSION
ROOM
A136
CONSULT
A137
STAFF
STATION
A141
EXAM
ROOM
A108
CLEAN
UTILITY
A109
SOILED
UTILITY
A110
GROUP
ROOM
A111
LAB
SOILED
A107
LAB
CLEAN
ROOM
A105
PATIENT
TOILET
A112
CLOSET
A113
STORAGE
A103
TOILET
A102
ELECTRICAL
AU104
OFFICE:
PROGRAM
MGR.
A133
OFFICE:
HEAD
NURSE
A134
OFFICE
A124
LAUNDRY
A123
MULTI-PURPOSE
ROOM
A115
BREAK
ROOM
A119JAN.
A117
CO
RR
ID
OR
A1
DAY/DINING
ROOM
A125
SALLY
PORT
ENTRY
A101
STAIR
AS101
MED
ROOM
A142
TOILET
A106
ELEC.
A114
ANTEROOM
A106A
STAFF
TOILET
A118
CORRIDOR
ELEC
AU101
ELEC
AU102
ELEC
AU103
WAITING
A100
SRL
OFFICE
A138
PCR 1
A139A PCR 2
A139B
PCR 3
A139C
IFA SCOPE
A139D
SEROLOGY
LAB
A139
SRL
TESTING
B111
SUPV
SEROLOGY
LAB
B111A
BCE
CO-ORDER
B112
STERILIZER
B113A
GLASS
WASH
B113
MICROBIOLOGY
LAB
B114
LAB
B114B
PRIVATE
B114A
LAB MED
MGR.
B113B
SIM.
SIM.
PRIVATE
A125A
LOCKERS
A100-B
LOCKERS
A100-C
ANTEROOM
A100-A
OFFICE
B129H
OFFICE
B129G
OFFICE
B129F
OFFICE
B129E
CLOSET
B129D
OFFICE
B129C
OFFICE
B129B
ST
UD
EN
TS
B1
L
SHARED
OFFICE
B129J
PANTRY
B129K
CORRIDOR
B129
CLOSET
B129A
PAMNS ZONE '1A'
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATINGS
BUILDING SEPARATION ( >2 HOURS)
3 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1/2 HOUR FIRE BARRIER
SMOKE BARRIER ( >1/2 HOUR)
SMOKE RESISTIVE CONSTRUCTION
Engineers Architects U.S. Department of Veterans Affairs
SPEAKER 8" ROUND CEILING MOUNT
SPEAKER 10" X 10" SQUARE CEILING MOUNT
SPEAKER 10" x 10" WALL MOUNT
WALL HORN
CEILING TYPE
CEILING HEIGHT
CEILING TYPE LEGEND
1 2X2 DROP CEILING
2 HARD CEILING
3 2X4 DROP CEILING
4 GYP CEILING
5 UNFINISHED CEILING
6 1' x 2' METAL PAN CEILING 7 1' x 1' ACOUSTIC CEILING
S
S
S
LINE TYPE LEGEND:
CEILING BOUNDARY:
VOLUME CONTROL MOUNTED AT 48"AFFVC
SYMBOL LEGEND
PAGING SYSTEMPS
8 2' x 4' DRY WALL CEILING
T-111
BOWLING FIRST FLOOR OVERALL
PLAN MENTAL HEALTH
1 BOWLING FIRST FLOOR OVERALL PLAN MENTAL HEALTH
SCALE: 1/8" = 1' 0"
NORTH
TRUE
8 16 320
A. ALL EXISTING CONDITIONS ARE BASED ON BEST
AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION.
B. REPAIR/REPLACE ANY DAMAGED CEILING.
C. PROVIDE NEW SPEAKER ASSEMBLY AS SHOWN
AND CONNECT TO EXISTING SPEAKER/PAGING
ZONE.
D. ALL SPEAKERS SHALL BE TAPPED AT 1/2 WATT
UNLESS OTHERWISE NOTED.
E. MINIMUM SPEAKER WIRE SHALL BE 16 AWG.
F. PAGING CABLES SHALL BE INSTALLED IN
CONDUITS IN ALL EXPOSED AREAS (ROOMS WITH
NO CEILINGS) IN ELECTRICAL ROOMS,
MECHANICAL ROOMS, BOILER ROOMS, STORAGE
ROOMS, GARAGES, OUTSIDE AREAS AND STAIRS.
G. ALL PAGING CABLING/CONDUIT SHALL BE
SUPPORTED BY J-HOOKS, IN CABLE TRAY OR AN
APPROVED SUPPORTING SYSTEM.
T-401
FEBRUARY 29, 2024
Gypsum
Gypsum
Gypsum
Gypsum
Gypsum
Gypsum
Gypsum
DN
UP
UPDN
DN
UP
DN
ROOF OF FIRST
FLOOR BELOW
ROOF OF GROUND
FLOOR BELOW
CARD CATALOGRE
FE
RE
NC
E
UP
UP
BABY CHANGING
STATION
S
S D
W
D
W
ELEC
AU203
ELEC
AU202
ELEC
AU201
ELEC
AU206
ELEC
AU207
ELEC
AU208
ELECTRIC
CLOSET
A205A
STAFF TOILET
D227
STORAGE
C223B
CORRIDOR
BH205
ELEC
BU203
TOILET
A271B
STORAGE
CH2-12A
CORRIDOR
BH212
CORRIDOR
AH202
CORRIDOR
AH205
CORRIDOR
AH206A
CORRIDOR
AH203
CORRIDOR
AH206
CORRIDOR
AH207
LOBBY
AH200
CORRIDOR
AH209
CORRIDOR
AH208
CORRIDOR
AH201
CORRIDOR
AH211
CORRIDOR
AH210
SEMI-PRIVATE
RM
A257
CCU1
A258
CCU2
A259
CCU3
A260
CARDIAC
PROCEDURE RM
A261
SEMI-PRIVATE
RM
A256
SHOWER
A269
TOILET
A257A
TOILET
A256A
NURSE
STATION
A267
NURSES
WORK RM
A268
NOURISHMENT
CENTER
A267C
EMS
A270
STAIRWELL
AS202
CCU4
A262
CCU5
A263
CCU6
A264
IT CLOSET
A265 STRESS LAB
A266
SOILED UTILITY
A267B
CLEAN
UTILITY
A267A
BREAK
A267D
NURSE
COORD OFC
A274
TOILET
A251
EMS
A252
HEART STATION
SUPV OFFICE
A272
LOCKER
A271A
NURSE
LOUNGE
A271
CONFERENCE RM
A255
VISITOR WAITING
A254
STOR
A255
TOILET
A255A
ECHO LAB
A250
ECHO LAB
A249
CORRIDOR
AH211A
CONTROL RM
A248A
PHONO
CARDIOLOGY
A248
EC
AU205
CARDIO CASE
MGR OFFICE
A276A
CARDIO
OFFICE
A276
HEART STATION
A245
HEART STATION
WORK RM
A244
PACEMAKER
A247
EKG COMPUTER
A247A
EEO ADMIN
OFFICE
A277
CARDIOLOGY
DOCTOR OFFICE
A246
IT CLOSET
A243
CATH LAB
OFFICE
A242 CATH LAB 1
A235
EQUIP
RM
A235BELEVATOR
P1
ELEVATOR
P2
ELEVATOR
P3
CATH
STORAGE
A235A
STAFF
OFFICE
A231A
BREAK
RM
A231
STAFF
CORRIDOR
A232
CONTROL
A234
CATH LAB 2
A233
CATH STORAGE
A233A
CLEAN
HOLDING
A230
SOILED
LINEN
A229
EQUIP
RM
A233B
CONSULT
A225
CLEAN
UTILITY
A226
STAIRWELL
AS201
RECEPTION/
BUSINESS
A214
FILE
A214A
STRETCHER
STORAGESTAFF TOILET
A228
PATIENT CARE
STAFF WORKROOM
A227
PHYSICIAN
WORK RM
A222
CONSULT
A241
JANITOR
A240 TOILET
A239 CLEAN STOR
A238
PREPARATION/HOLDING
A237
READING/
VIEWING
A236
BREAK RM
A224
PROCEDURE
A223
PATIENT
TOILET
A223A
SOILED
HOLDING
A223B
EXAMINATION/
TREATMENT
A221
EXAMINATION
A220
EXAMINATION
A219
EXAMINATION
A218
EXAMINATION
A217
EXAMINATION
A216
EXAMINATION
A215
CLINIC C
WAITING
A211
GROUP CLINIC RM
A210
EMS
A212
PATIENT
TOILET
A213
CORRIDOR
AH204
WC STORAGE
A211A
TOILET
A207A
EC
AU204
LAB
A207
SVC
LOBBY
A201
ELEVATOR
S5
ELEVATOR
S4
WAITING
A205
PHARMACY
A204
EQUIP STOR
A202
MECH
RM
B234
CLEAN
UTILITY
A202 STAFF
TOILET
A206A
STORAGE
A248B
MECH
RM
A273 SOCIAL
WORKER
B247
VENDING RM
B250 ENTRY
B200
CORRIDOR
C212
CORRIDOR
BH202
TOILET
B248
TOILET
B249
CORRIDOR
BH201
CLINIC A
WAITING AREA
B201
EXAM
B207
EXAM
B208
EXAM
B209
EXAM
B210
EXAM
B211
EXAM
B212
RECEPTION/
BUSINESS
B202
CHECK
OUT
B202A
STOR
B203
CORRIDOR
C2B4
STAFF
TOILET
B205HAC
B204
PATIENT
TOILET
B206
STAFF
CORRIDOR
BH203
PATIENT
CARE
B217
PHYSICIAN
WORK RM
B218
PHYSICIAN
WORK RM
B219
NURSE
WORK RM
B220
SOILED
HOLDINGS
B245
PROCEDURE
B244
PATIENT
TOILET
B244A
PATIENT
TOILET
B243
EXAM
B242
STAIRWELL
BS203
WORK
RM
B239
CORRIDOR
BH206
RECEPTION/
BUSINESS
B237
CLINIC B
WAITING
B238
ELECTRIC
CLOSET
BU201
STOR
A203
CHECK
OUT
B237A
COPY RM
B236
CORRIDOR
BH207
CONSULT
B235
STAFF
LOCKER
A206
WARFARIN
CLINIC
B234
NURSE MGR
OFFICE
B233
EXAM
B232
EXAM
B231
EXAM
B230
EXAM
B229
EXAM
B228
EXAM
B227
EXAM
B226
EXAM
B225
EXAM
B224
EXAM
B223
TREATMENT
B222
SUPPLY
B221
EXAM
B216
EXAM
B215
EXAM
B214
EXAM
B213
CORRIDOR
CH218
COMPUTER
TRAINING
D205
CLASSROOM
D206
LEARNING
OFFICER OFFICE
D207
ACOS OFF
D208
LEARNING
RESOURCE
CENTER OFFICE
D203A
CORRIDOR
C221
TRAINING
INSTRUCTOR
LPIS FACILITY
CO-ORDINATOR
OFFICE
D204
STORAGE
D201B
CORRIDOR
DH223
LRC OFFICE
D203
FEM TOILET
D202
STORAGE
D205A
VESTIBULE
DH220
STORAGE
PROJ
D201AAUDITORIUM
D201
CONTROL RM
C205
CORRIDOR
CH206
CORRIDOR
CH207
EC
CU208
PREPARATION/
WORK AREA
C206
LIBRARY
C209 M TOILET
D200
STORAGE
C210
LIBRARY
RECEPTION
C211D
CONFERENCE
C211A
STORAGE
CH205 OFFICE
C211B
VISUAL INFO OFFICE
C207
TELEMEDICINE
DISTANCE
LEARNING A
C204
CORRIDOR
CH204
CORRIDOR
CH203
INFO
C201
LOBBY
CH201
CORRIDOR
DH229
EMS
D228
STAFF TOILET
D226
CORRIDOR
DH228
CORRIDOR
DH230
EC
DU230
EC
DU229
STAIRWELL
DS207
ELEVATOR
S6
ELEVATOR
S7 IT
D231
CORRIDOR
DH231
CORRIDOR
DH226
CORRIDOR
DH224
CORRIDOR
DH225
CORRIDOR
DH227
TOILET
D211
STORAGE
D212
TRAINEES
D214
AUDIOLOGY
EXTERN
D216
AUDIO
D217
AUDIO
D219
AUDIOLOGY
D210
VOICE
LABORATORY
D213
SP PATH
D215
TREATMENT RM
D218
PM&R
CO-ORDR
D220
OFFICE
D221A
EXAM
D221
ROTARY CHAIR
D221B
CORRIDOR
CH211
CORRIDOR
DH232
AMPUTEE
PGM
OFFICE
D222
SOUND SUITE (VV)
D223
CONTROL
D223A
CONTROL
D224A
SOUND SUITE (VV)
D224
AUDIOLOGY
CO-ORDR
D225
CLERICAL REC
D209
WAITING
DH224A
CORRIDOR
CH212
STAFF DEV
SPECIALIST OFFICE
C203A
PATIENT SAFETY
FELLOWS
OFFICE
C203B
SIM CTR
TRAINING RM
C203C
LIBRARY
C203
MULTI PURPOSE
C203D
STAFF
DEVELOPMENT
SPECIALIST OFFICE
C203E
STORAGE
D236
CORRIDOR
DH233
STAIRWELL
DS208
CORRIDOR
C234
REPAIR AND DEVELOPMENT
D232
SEC/WAIT
D230
SUPV BIO MED
OFFICE
D234
INDUSTRIAL HYGIENIST
OFFICE
D235
STORAGE
D232A
OFFICE RM
D238
WORK RM
D237
MECH SHAFT
DU202
STORAGE
D232D
MECH SHAFT
DU201
CORRIDOR
CH215
CORRIDOR
CH214
CORRIDOR
CH217
CORRIDOR
CH216
ORAL SURGY
C235
ORAL SURGY
C238
RECOVERY
C239
TOILET
LOCKER RM
C241
OPERATORY
C261
DENTAL LAB
C260
STORAGE
C236
STORAGE
C237
OFFICE RM
C234
CONFERENCE RM
C232
INSTRUMENT
STORAGE
C240
CHIEF
OFFICE
C233
STOR
C228 TOILET
C227
OFFICE
C242
X-RAY
C244
X-RAY
C246
SUPPLY
C248
GENERAL
C245
TREATMENT
OPERATORY
C243
EC
C257
GENERAL
C255
GENERAL
C253
PROSTHETICS
LAB
C259
SOLID
C258
OPERATORY
C256
OPERATORY
C254
DENTISTS
OFFICE
C252
EMS
C231
DATA
ENTRY
C251
HYGIENE
OPERATOR
C250
HYGIENE
OPERATOR
C249
EXAM
OPERATOR
C247
WAITING
C229B
SECY/CLERICAL
C229
OFFICE
C230
CORRIDOR
CH213
RECORDS
C225
STAIRWELL
CS204
SUPER OFFICE
C226A
WAITING
EMS
C224
WORK AREA/STORAGE
C223E
C223F
RECEPTION
C223
TOILET
C223C
IT
CU222
WAITING
C223A
OFFICE CHIEF
C223D
ELEVATOR
P6
ELEVATOR
P7
ELEVATOR
(FUTURE)
CE208
EC
CU200
STAIRWELL
CS209
SCREENING
C271
WAITING RM
C270
SCREENING
C272
OPTICAL
SCREENING
C273
MENS
TOILET
C212
WOMENS
TOILET
C213
RECEPTION WORKSPACE
C270B
CORRIDOR
TECH WORK
AREA
C297
EXAM RM
C294
EXAM RM
C293
EXAM RM
C290
EXAM RM
C289
RECEPTION
C270A
EXAM RM
C292
EXAM RM
C295
EXAM RM
C296
CLINIC
DIRECTOR
C274
VISUAL
FIELD
C276
SPECIAL TESTING
C277
YAG LASER
C280
ARGON LASER
C281
EXAM RM
C291
SOILED SPD
C285A
CLEAN SPD
C285
OFFICE
C288
VIST
COORD
C287
VISIT DOC OFFICE
C286
CASE MGR
C284
OPTICAL
SHOP
C275
PHOTO
RM
C278
PROCEDURE RM
C279
CLIN DIR OFFICE
C282
WORK AREA / KITCHENETTE
C283
STOR
C229A
PAMNS ZONE '2L'
PAMNS ZONE '2Y'
PAMNS ZONE '2L'
PAMNS ZONE '2Y'
PAMNS ZONE '2A'
PAMNS ZONE '2A'
PAMNS ZONE '2S'
PAMNS ZONE '2S'
PAMNS ZONE '2L'
PAMNS ZONE '2L'
PAMNS ZONE '2A'
PAMNS ZONE '2R'
PAMNS ZONE '2P'
PAMNS ZONE '2A'
PAMNS ZONE '2P'
PAMNS ZONE '2R'
PAMNS ZONE '2A'
PAMNS ZONE '2D'
PAMNS ZONE '2A'
PAMNS ZONE '2E'
PAMNS ZONE '2A'
PAMNS ZONE '2A'
PAMNS ZONE '2U'
PAMNS ZONE '2A'
PAMNS ZONE '2U'
PAMNS ZONE '2H'
PAMNS ZONE '2B'
PAMNS ZONE '2B'
PAMNS ZONE '2B'
PAMNS ZONE '2H'
PAMNS ZONE '2A'
PAMNS ZONE '2H'SRSR
SR
SR
SR
SR SR SR
SR
SR SR SR
SR
SR SR
SR
SR
SRSR
SR
SR
SR
SR
SRSR
SR
SR
SRSR
SR
SR
SR
SR
SR
SR
SR
SR
SRSRSR
SR
SRSR
SR
SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SN
VC
N
S
N
S
N S
N S
N
S
N
S
SN
SN
VC
VC
SN
SN
SN
SN
SN
SN
SN
SN
SN
SN
VC
VC
SN
SN SN SN
SN
SN
SN SN
SN
SNSNSN
SN
SN
SN
SN
SN
SN
SN
SD
SD
SD
SN
SR
SNSN
SN
SD
SN
SD SN
SD
SN
SN
SD N
SD
SD
SD
SN
SD
SD
SD
SN
PAMNS ZONE '2H'
SN
8'-0"
8'-0"
8'-0"
9'-5"
8'-0"
9'-5"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-5"
8'-5"
9'-6"
9'-6"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
9'-0"
8'-0"
8'-0" 18'-0"
9'-0"
9'-0"
9'-0"
9'-0"
SN
9'-0"
8'-0"
9'-6"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
9'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
S N
S N
S N
SN
S N S N
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
DECEMBER 1, 2023 HTJDM
REPLACE OBSOLETE
OVERHEAD
PAGING SYSTEM
596-22-101
VA MEDICAL CENTER LEXINGTON
1101 VETERANS DRIVE
LEXINGTON, KENTUCKY 40502
21-306
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATINGS
BUILDING SEPARATION ( >2 HOURS)
3 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1/2 HOUR FIRE BARRIER
SMOKE BARRIER ( >1/2 HOUR)
SMOKE RESISTIVE CONSTRUCTION
Engineers Architects U.S. Department of Veterans Affairs
SPEAKER 8" ROUND CEILING MOUNT
SPEAKER 10" X 10" SQUARE CEILING MOUNT
SPEAKER 10" x 10" WALL MOUNT
WALL HORN
CEILING TYPE
CEILING HEIGHT
CEILING TYPE LEGEND
1 2X2 DROP CEILING
2 HARD CEILING
3 2X4 DROP CEILING
4 GYP CEILING
5 UNFINISHED CEILING
6 1' x 2' METAL PAN CEILING 7 1' x 1' ACOUSTIC CEILING
S
S
S
LINE TYPE LEGEND:
CEILING BOUNDARY:
VOLUME CONTROL MOUNTED AT 48"AFFVC
SYMBOL LEGEND
PAGING SYSTEMPS
8 2' x 4' DRY WALL CEILING
T-121
BOWLING SECOND FLOOR OVERALL
PLAN
1 BOWLING SECOND FLOOR OVERALL PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
A. ALL EXISTING CONDITIONS ARE BASED ON BEST
AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION.
B. REPAIR/REPLACE ANY DAMAGED CEILING.
C. PROVIDE NEW SPEAKER ASSEMBLY AS SHOWN
AND CONNECT TO EXISTING SPEAKER/PAGING
ZONE.
D. ALL SPEAKERS SHALL BE TAPPED AT 1/2 WATT
UNLESS OTHERWISE NOTED.
E. MINIMUM SPEAKER WIRE SHALL BE 16 AWG.
F. PAGING CABLES SHALL BE INSTALLED IN
CONDUITS IN ALL EXPOSED AREAS (ROOMS WITH
NO CEILINGS) IN ELECTRICAL ROOMS,
MECHANICAL ROOMS, BOILER ROOMS, STORAGE
ROOMS, GARAGES, OUTSIDE AREAS AND STAIRS.
G. ALL PAGING CABLING/CONDUIT SHALL BE
SUPPORTED BY J-HOOKS, IN CABLE…
This is the start of the file's text. The full file is on GovTribe.