Attachment 2 - E601 - ELECTRICAL DETAILS.pdf

PDF 2 MB Posted

Attached to
Z2DA--603-23-2-2318-0001 - Replace ORs 1-3 Supply Heads
Solicitation number
36C24923R0032
Issued by

About this file

This document provides details for a federal construction solicitation to replace supply heads in operating rooms 1 through 3 at the Robley Rex VA Medical Center in Louisville, Kentucky. The solicitation is set aside 100% for Service-Disabled Veteran-Owned Small Businesses between $500,000 and $1 million in project value. The selected contractor will be responsible for all labor, materials, equipment, transportation, and supervision to complete demolition, general construction, HVAC, plumbing, building envelope, electrical and finish work. The anticipated completion schedule is 270 calendar days from notice to proceed. Offerors must be verified as SDVOSBs by the VA's Center for Veterans Enterprise and registered in the System for Award Management by the time of proposal submission. Questions must be submitted in writing to the contracting officer.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NURSE

DESK

NURSE

DESK

PACS PC

(J1)

TOUCH

PANEL

A1

T1

V1

LEVITON

BOX

SURGICAL

LIGHT

CONTROLLER

SURGICAL

LIGHT MOUNT

SURGICAL

LIGHT HEAD

SURGICAL LIGHT

HEAD IN-LIGHT

CAM

SURGICAL

DISPLAY

SURGICAL

DISPLAY

ANESTHESIA

BOOM

VITALS/HEMO

VIDEO

GUEST

UNIVERSAL

PORT

PERFUSION

BOOM

VIDEO GUEST

UNIVERSAL

PORT

B1 C1 C2

K1

N3 N2

1-1/2"C1-1/2"C1-1/2"C1"C

1"C2"C 1" PASS THRU

(FOR DATA JACK)

1-1/4"C V1

REQUIRES DEDICATED

EMERGENCY BACKUP

120V ON 20 AMP POWER

(NOT BY STERIS)

1-1/4"C

1-1/4"C

JUNCTION BOX SCHEDULE

J-BOX # SIZE TYPE MOUNTING

A1

T1

12"H x 12"W x 4"D PULL BOX IN WALL

24"H x 24"W x 8"D NEMA 1, SCREW COVER ABOVE CEILING

JUNCTION BOX SCHEDULE NOTES

• ALL BOXES ARE PROVIDED BY THE CLIENTS CONTRACTOR UNLESS

NOTED OTHERWISE.

• MOUNTING REQUIREMENTS SHOWN ARE THE DEFAULT REQUIREMENTS

UNLESS OTHERWISE NOTES/DETAILED.

• ALL BOXES AND COVER PLATES ARE PROVIDED BY THE CLIENTS

CONTRACTOR UNLESS OTHERWISE NOTED.

• MOUNTING REQUIREMENTS SHOWN ON CONTRACTOR SUPPLIED BACK

BOXES AND POWER PANELS DIAGRAM ARE THE DEFAULT REQUIREMENTS

UNLESS OTHERWISE NOTED.

• BOXES/OUTLETS/RECEPTACLES LOCATED ABOVE THE CEILING MUST BE

WITHIN 18 INCHES OF THE CEILING AND BE ACCESSIBLE FROM THE

SPACE BELOW; CLIENT/GENERAL CONTRACTOR TO PROVIDE SUITABLE

CEILING ACCESS PANELS AT DEVICE LOCATIONS.

• T1 JUNCTION BOX - 24" x 24" x 8" (PROVIDED AND MOUNTED VERTICALLY

NOT BY STERIS); ALL FIELD CONDUITS AND 2" AND 1" CONDUIT TO (A1)

STERIS INTEGRATION BOX ATTACH TO JUNCTION BOX (T1); CEILING

ACCESS REQUIRED FOR SERVICE ACCESS; ALL CONDUIT TO ENTER T1

BOX ANYWHERE EXCEPT FOR THE BACK SIDE; T1 BOX SHOULD NOT BE

HIGHER THAN 12' ABOVE FINISHED FLOOR;

NOT TO BE LOCATED DIRECTLY ABOVE NURSE DESKS OR ANY OTHER

FIXED EQUIPMENT.

CONDUIT NOTES

• IF A DIRECT CONNECTION IS NEEDED BETWEEN TWO PIECES OF

EQUIPMENT, CONDUIT MUST BE RUN.

• EXACT CONDUIT PATH DETERMINED BY ELECTRICAL CONTRACTOR.

• CONDUIT SHOULD NOT EXCEED 50'.

• MUST BE A PULLBOX FOR EVERY 270 DEGREE OF CONDUIT BEND.

• ALL CONDUITS SHOULD BE PROVIDED WITH PULL STRINGS AND MUST

HAVE INSULATED BUSHINGS ON ALL OPEN ENDS.

• USE OF FLEXIBLE CONDUIT IS NOT ACCEPTABLE.

• STERIS WILL NOT BE RESPONSIBLE FOR FIRE STOPPING IN ANY FORM.

N2 4-11/16" x 2-1/8"D SINGLE GANG MUD RING IN WALL

N3 4 GANG SWITCH / OUTLET BOX IN WALL

INTEGRATION EQUIPMENT

LEGEND DESCRIPTION RESPONSIBILITY

STERIS iQ2800 INTEGRATION RACK STERIS

WALL MOUNTED 12x12x4" JUNCTION BOX AT NURSE DESK STATION REQUIRED FOR iQ2800 RACK ELECTRICAL CONTRACTOR

A1

B1 SURGICAL LIGHT MOUNT STERIS

C1 ANESTHESIA BOOM STERIS

C2 PERFUSION BOOM STERIS

J1 WALL MOUNTED TOUCH PANEL STERIS

K1 SURGICAL LIGHT CONTROLLER STERIS

WALL MOUNTED 4 11/16" JUNCTION BOX WITH SINGLE

GANG MUD RING (USED FOR TOUCH PANEL)N2 ELECTRICAL CONTRACTOR

N3 WALL MOUNTED 4 GANG JUNCTION BOX (USED FOR PACS) ELECTRICAL CONTRACTOR

24" H x 24" W X 8" D ABOVE CEILING JUNCTION BOX

(NOT BY STERIS)T1 ELECTRICAL CONTRACTOR

V1 LEVITON BOX FOR STERIS POWER DISTRIBUTION ELECTRICAL CONTRACTOR

NOTE:

A. "CLIENTS CONTRATOR" MEANS ELECTRICAL CONTRACTOR.

A1

T1

N2

FLOOR

CEILING

N3 V1

LEVITON BOX 47605-21x & 47605-21S COVER

FOR STERIS POWER DISTRIBUTION

(CONTRACTOR PROVIDED AND INSTALLED)

CONTRACTOR PROVIDED AND INSTALLED

JUNCTION BOX (REQUIRED FOR iQ2800 RACK)JUNCTION BOX FOR TOUCH PANEL

(CONTRACTOR PROVIDED AND INSTALLED)

4 GANG SWITCH BOX USED FOR PACS

(CONTRACTOR PROVIDED AND INSTALLED)

JUNCTION BOX

(CONTRACTOR PROVIDED AND INSTALLED)

JUNCTION BOX SHOULD NOT BE HIGHER THAN 12' ABOVE FINISHED FLOOR

SURGE PROTECTOR LEV 47605-DP

20A - 120V

20A DOUBLE DUPLEX

ISOLATED CIRCUIT

AND GROUND

EXISTING NURSE DESK

A

B O

V E

F

IN

IS

H

E D

F L

O O

R

20A DUPLEX

ISOLATED GROUND

A

B O

V E

F

IN

IS

H

E D

F L

O O

R

GCX VERTICAL RAIL & ARTICULATED TV ARM.

PROVIDE BLOCKING.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

T-691

A u to d e s k D o c s /L o u is v ill e V

A

R e p la c e

O R

A n e s th e s ia

S u p p ly

H e a d s /F

F E

L o u is v ill e

R e p la c e

O R

A n e s th e s ia

B

M E

P rv t

/1

/2

:2

:1

P

M

E601

ELECTRICAL DETAILS

Owner

11/15/2022 JB IA

REPLACE OR 1-3 ANESTHESIA

SUPPLY HEADS

603-22-101

LOUISVILLE, KENTUCKY

BID DOCUMENTS

ROBLEY REX

VA MEDICAL

CENTER

LIGHTING FIXTURE SCHEDULE

IMAGE MARK DESCRIPTION

MOUNTING

LOAD

(VA) LUMINOUS FLUX

COLOR

TEMPERATURE CRI Comments

S-SURFACE

R-RECESSED

SM-STEM MTD

WM-WALL MTD

C-CHAIN MTD

UC-UNDER CAB

CS-CEIL SURFACE

A 2'x4' & 2'X2' LED LIGHT WITH WHITE AND INDIGO DISINFECTION MODES. INTEGRAL ALUMINUM

HEATSINK AND ANTI-MICROBIAL FINISH ON EXPOSED SURFACES. INTEGRAL WITH EMERGENCY

BATTERY PACK. 120V. 0-10V DIMMING.

R 150 10080 lm 4000 K 90 OWNER

FURNISHED /

CONTACTOR

INSTALLED

B 2'x2' LED LIGHT WITH GREEN LED CIRCUIT. INTEGRAL ALUMINUM HEATSINK AND ANTI-MICROBIAL

FINISH ON EXPOSED SURFACES. INTEGRAL WITH EMERGENCY BATTERY PACK. 120V. 0-10V

DIMMING.

R 86 5180 lm 4000 K 90 OWNER

FURNISHED /

CONTACTOR

INSTALLED

NTS

HARMONY INTEGRATION SYSTEM WIRING DIAGRAM

NEW NEW NEW

NTS

CONTRACTOR SUPPLIED BACK BOXES AND POWER PANELS

No. Revisions: Date:

BID DOCUMENTS 11/15/2022

1 REVISION #1 03/10/2023

Notes:

Total Est. Demand: 41 A

Total Conn.: 41 A

Total Est. Demand: 4960 VA

Power 3600 VA 100.00% 3600 VA Total Conn. Load: 4960 VA

Other 1360 VA 100.00% 1360 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 41 A

Total Load: 4960 VA

11 STERIS INTEGRATION RACK iQ2800 (A1) 20 A 1 200 VA 0 VA 1 20 A SPARE 12

9 TOUCH PANEL SCREEN (J1) 20 A 1 100 VA 500 VA 1 20 A POWER DISTRIBUTION JUNCTION BOX (T1) 10

7 SURGICAL LIGHTING CONTROLLER (K1) 20 A 1 200 VA 360 VA 1 20 A LEVITON JUNCTION BOX (V1) 8

5 OR-1 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-1 ANESTHESIA BOOM 6

3 OR-1 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-1 ANESTHESIA BOOM 4

1 OR-1 ANESTHESIA BOOM 20 A 1 720 VA 720 VA 1 20 A OR-1 ANESTHESIA BOOM 2

CKT Circuit Description Trip Poles

A

Poles Trip Circuit Description CKT

1. OWNER FURNISHED AND CONTRACTOR INSTALLED

2. ISOLATION PANELS HAVE 2-POLE BREAKERS, OPENING BOTH NEUTRAL AND HOT WIRES.

3. THERE IS A 7.5KVA 208V-1PH - 120V-1PH ISOLATION TRANSFORMER INCLUDED IN ENCLOSURE.

Notes:

Enclosure: Type 1 MCB Rating: 50 A

Mounting: Flush Wires: 2 Mains Rating: 100 A

Supply From: Phases: 1 Mains Type: MCB

Location: OR-1 C-408 Volts: 120 Single Phase A.I.C. Rating: 10,000 A

Branch Panel: IPP408-2

Notes:

Total Est. Demand: 30 A

Total Conn.: 30 A

Total Est. Demand: 3600 VA

Total Conn. Load: 3600 VA

Power 3600 VA 100.00% 3600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 30 A

Total Load: 3600 VA

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 OR-2 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-2 ANESTHESIA BOOM 6

3 OR-2 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-2 ANESTHESIA BOOM 4

1 OR-2 ANESTHESIA BOOM 20 A 1 720 VA 720 VA 1 20 A OR-2 ANESTHESIA BOOM 2

CKT Circuit Description Trip Poles

A

Poles Trip Circuit Description CKT

1. OWNER FURNISHED AND CONTRACTOR INSTALLED

2. ISOLATION PANELS HAVE 2-POLE BREAKERS, OPENING BOTH NEUTRAL AND HOT WIRES.

3. THERE IS A 7.5KVA 208V-1PH - 120V-1PH ISOLATION TRANSFORMER INCLUDED IN ENCLOSURE.

Notes:

Enclosure: Type 1 MCB Rating: 50 A

Mounting: Flush Wires: 2 Mains Rating: 100 A

Supply From: Phases: 1 Mains Type: MCB

Location: OR-2 C-406 Volts: 120 Single Phase A.I.C. Rating: 10,000 A

Branch Panel: IPP406-2

Notes:

Total Est. Demand: 30 A

Total Conn.: 30 A

Total Est. Demand: 3600 VA

Total Conn. Load: 3600 VA

Power 3600 VA 100.00% 3600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 30 A

Total Load: 3600 VA

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 OR-3 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-3 ANESTHESIA BOOM 6

3 OR-3 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-3 ANESTHESIA BOOM 4

1 OR-3 ANESTHESIA BOOM 20 A 1 720 VA 720 VA 1 20 A OR-3 ANESTHESIA BOOM 2

CKT Circuit Description Trip Poles

A

Poles Trip Circuit Description CKT

1. OWNER FURNISHED AND CONTRACTOR INSTALLED

2. ISOLATION PANELS HAVE 2-POLE BREAKERS, OPENING BOTH NEUTRAL AND HOT WIRES.

3. THERE IS A 7.5KVA 208V-1PH - 120V-1PH ISOLATION TRANSFORMER INCLUDED IN ENCLOSURE.

Notes:

Enclosure: Type 1 MCB Rating: 50 A

Mounting: Flush Wires: 2 Mains Rating: 100 A

Supply From: Phases: 1 Mains Type: MCB

Location: OR-3 C-404 Volts: 120 Single Phase A.I.C. Rating: 10,000 A

Branch Panel: IPP404-2

Panel 4BEMG-A Panel 4BEMG-A Panel 4BEMG-A

1 1 1

11/15/2022

Sheets
E601 - ELECTRICAL DETAILS

File details come from the government source that posted it. Updated .