This document provides details for a federal construction solicitation to replace supply heads in operating rooms 1 through 3 at the Robley Rex VA Medical Center in Louisville, Kentucky. The solicitation is set aside 100% for Service-Disabled Veteran-Owned Small Businesses between $500,000 and $1 million in project value. The selected contractor will be responsible for all labor, materials, equipment, transportation, and supervision to complete demolition, general construction, HVAC, plumbing, building envelope, electrical and finish work. The anticipated completion schedule is 270 calendar days from notice to proceed. Offerors must be verified as SDVOSBs by the VA's Center for Veterans Enterprise and registered in the System for Award Management by the time of proposal submission. Questions must be submitted in writing to the contracting officer.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NURSE
DESK
NURSE
DESK
PACS PC
(J1)
TOUCH
PANEL
A1
T1
V1
LEVITON
BOX
SURGICAL
LIGHT
CONTROLLER
SURGICAL
LIGHT MOUNT
SURGICAL
LIGHT HEAD
SURGICAL LIGHT
HEAD IN-LIGHT
CAM
SURGICAL
DISPLAY
SURGICAL
DISPLAY
ANESTHESIA
BOOM
VITALS/HEMO
VIDEO
GUEST
UNIVERSAL
PORT
PERFUSION
BOOM
VIDEO GUEST
UNIVERSAL
PORT
B1 C1 C2
K1
N3 N2
1-1/2"C1-1/2"C1-1/2"C1"C
1"C2"C 1" PASS THRU
(FOR DATA JACK)
1-1/4"C V1
REQUIRES DEDICATED
EMERGENCY BACKUP
120V ON 20 AMP POWER
(NOT BY STERIS)
1-1/4"C
1-1/4"C
JUNCTION BOX SCHEDULE
J-BOX # SIZE TYPE MOUNTING
A1
T1
12"H x 12"W x 4"D PULL BOX IN WALL
24"H x 24"W x 8"D NEMA 1, SCREW COVER ABOVE CEILING
JUNCTION BOX SCHEDULE NOTES
• ALL BOXES ARE PROVIDED BY THE CLIENTS CONTRACTOR UNLESS
NOTED OTHERWISE.
• MOUNTING REQUIREMENTS SHOWN ARE THE DEFAULT REQUIREMENTS
UNLESS OTHERWISE NOTES/DETAILED.
• ALL BOXES AND COVER PLATES ARE PROVIDED BY THE CLIENTS
CONTRACTOR UNLESS OTHERWISE NOTED.
• MOUNTING REQUIREMENTS SHOWN ON CONTRACTOR SUPPLIED BACK
BOXES AND POWER PANELS DIAGRAM ARE THE DEFAULT REQUIREMENTS
UNLESS OTHERWISE NOTED.
• BOXES/OUTLETS/RECEPTACLES LOCATED ABOVE THE CEILING MUST BE
WITHIN 18 INCHES OF THE CEILING AND BE ACCESSIBLE FROM THE
SPACE BELOW; CLIENT/GENERAL CONTRACTOR TO PROVIDE SUITABLE
CEILING ACCESS PANELS AT DEVICE LOCATIONS.
• T1 JUNCTION BOX - 24" x 24" x 8" (PROVIDED AND MOUNTED VERTICALLY
NOT BY STERIS); ALL FIELD CONDUITS AND 2" AND 1" CONDUIT TO (A1)
STERIS INTEGRATION BOX ATTACH TO JUNCTION BOX (T1); CEILING
ACCESS REQUIRED FOR SERVICE ACCESS; ALL CONDUIT TO ENTER T1
BOX ANYWHERE EXCEPT FOR THE BACK SIDE; T1 BOX SHOULD NOT BE
HIGHER THAN 12' ABOVE FINISHED FLOOR;
NOT TO BE LOCATED DIRECTLY ABOVE NURSE DESKS OR ANY OTHER
FIXED EQUIPMENT.
CONDUIT NOTES
• IF A DIRECT CONNECTION IS NEEDED BETWEEN TWO PIECES OF
EQUIPMENT, CONDUIT MUST BE RUN.
• EXACT CONDUIT PATH DETERMINED BY ELECTRICAL CONTRACTOR.
• CONDUIT SHOULD NOT EXCEED 50'.
• MUST BE A PULLBOX FOR EVERY 270 DEGREE OF CONDUIT BEND.
• ALL CONDUITS SHOULD BE PROVIDED WITH PULL STRINGS AND MUST
HAVE INSULATED BUSHINGS ON ALL OPEN ENDS.
• USE OF FLEXIBLE CONDUIT IS NOT ACCEPTABLE.
• STERIS WILL NOT BE RESPONSIBLE FOR FIRE STOPPING IN ANY FORM.
N2 4-11/16" x 2-1/8"D SINGLE GANG MUD RING IN WALL
N3 4 GANG SWITCH / OUTLET BOX IN WALL
INTEGRATION EQUIPMENT
LEGEND DESCRIPTION RESPONSIBILITY
STERIS iQ2800 INTEGRATION RACK STERIS
WALL MOUNTED 12x12x4" JUNCTION BOX AT NURSE DESK STATION REQUIRED FOR iQ2800 RACK ELECTRICAL CONTRACTOR
A1
B1 SURGICAL LIGHT MOUNT STERIS
C1 ANESTHESIA BOOM STERIS
C2 PERFUSION BOOM STERIS
J1 WALL MOUNTED TOUCH PANEL STERIS
K1 SURGICAL LIGHT CONTROLLER STERIS
WALL MOUNTED 4 11/16" JUNCTION BOX WITH SINGLE
GANG MUD RING (USED FOR TOUCH PANEL)N2 ELECTRICAL CONTRACTOR
N3 WALL MOUNTED 4 GANG JUNCTION BOX (USED FOR PACS) ELECTRICAL CONTRACTOR
24" H x 24" W X 8" D ABOVE CEILING JUNCTION BOX
(NOT BY STERIS)T1 ELECTRICAL CONTRACTOR
V1 LEVITON BOX FOR STERIS POWER DISTRIBUTION ELECTRICAL CONTRACTOR
NOTE:
A. "CLIENTS CONTRATOR" MEANS ELECTRICAL CONTRACTOR.
A1
T1
N2
FLOOR
CEILING
N3 V1
LEVITON BOX 47605-21x & 47605-21S COVER
FOR STERIS POWER DISTRIBUTION
(CONTRACTOR PROVIDED AND INSTALLED)
CONTRACTOR PROVIDED AND INSTALLED
JUNCTION BOX (REQUIRED FOR iQ2800 RACK)JUNCTION BOX FOR TOUCH PANEL
(CONTRACTOR PROVIDED AND INSTALLED)
4 GANG SWITCH BOX USED FOR PACS
(CONTRACTOR PROVIDED AND INSTALLED)
JUNCTION BOX
(CONTRACTOR PROVIDED AND INSTALLED)
JUNCTION BOX SHOULD NOT BE HIGHER THAN 12' ABOVE FINISHED FLOOR
SURGE PROTECTOR LEV 47605-DP
20A - 120V
20A DOUBLE DUPLEX
ISOLATED CIRCUIT
AND GROUND
EXISTING NURSE DESK
A
B O
V E
F
IN
IS
H
E D
F L
O O
R
20A DUPLEX
ISOLATED GROUND
A
B O
V E
F
IN
IS
H
E D
F L
O O
R
GCX VERTICAL RAIL & ARTICULATED TV ARM.
PROVIDE BLOCKING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
T-691
A u to d e s k D o c s /L o u is v ill e V
A
R e p la c e
O R
A n e s th e s ia
S u p p ly
H e a d s /F
F E
L o u is v ill e
R e p la c e
O R
A n e s th e s ia
B
M E
P rv t
/1
/2
:2
:1
P
M
E601
ELECTRICAL DETAILS
Owner
11/15/2022 JB IA
REPLACE OR 1-3 ANESTHESIA
SUPPLY HEADS
603-22-101
LOUISVILLE, KENTUCKY
BID DOCUMENTS
ROBLEY REX
VA MEDICAL
CENTER
LIGHTING FIXTURE SCHEDULE
IMAGE MARK DESCRIPTION
MOUNTING
LOAD
(VA) LUMINOUS FLUX
COLOR
TEMPERATURE CRI Comments
S-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE
A 2'x4' & 2'X2' LED LIGHT WITH WHITE AND INDIGO DISINFECTION MODES. INTEGRAL ALUMINUM
HEATSINK AND ANTI-MICROBIAL FINISH ON EXPOSED SURFACES. INTEGRAL WITH EMERGENCY
BATTERY PACK. 120V. 0-10V DIMMING.
R 150 10080 lm 4000 K 90 OWNER
FURNISHED /
CONTACTOR
INSTALLED
B 2'x2' LED LIGHT WITH GREEN LED CIRCUIT. INTEGRAL ALUMINUM HEATSINK AND ANTI-MICROBIAL
FINISH ON EXPOSED SURFACES. INTEGRAL WITH EMERGENCY BATTERY PACK. 120V. 0-10V
DIMMING.
R 86 5180 lm 4000 K 90 OWNER
FURNISHED /
CONTACTOR
INSTALLED
NTS
HARMONY INTEGRATION SYSTEM WIRING DIAGRAM
NEW NEW NEW
NTS
CONTRACTOR SUPPLIED BACK BOXES AND POWER PANELS
No. Revisions: Date:
BID DOCUMENTS 11/15/2022
1 REVISION #1 03/10/2023
Notes:
Total Est. Demand: 41 A
Total Conn.: 41 A
Total Est. Demand: 4960 VA
Power 3600 VA 100.00% 3600 VA Total Conn. Load: 4960 VA
Other 1360 VA 100.00% 1360 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 41 A
Total Load: 4960 VA
11 STERIS INTEGRATION RACK iQ2800 (A1) 20 A 1 200 VA 0 VA 1 20 A SPARE 12
9 TOUCH PANEL SCREEN (J1) 20 A 1 100 VA 500 VA 1 20 A POWER DISTRIBUTION JUNCTION BOX (T1) 10
7 SURGICAL LIGHTING CONTROLLER (K1) 20 A 1 200 VA 360 VA 1 20 A LEVITON JUNCTION BOX (V1) 8
5 OR-1 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-1 ANESTHESIA BOOM 6
3 OR-1 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-1 ANESTHESIA BOOM 4
1 OR-1 ANESTHESIA BOOM 20 A 1 720 VA 720 VA 1 20 A OR-1 ANESTHESIA BOOM 2
CKT Circuit Description Trip Poles
A
Poles Trip Circuit Description CKT
1. OWNER FURNISHED AND CONTRACTOR INSTALLED
2. ISOLATION PANELS HAVE 2-POLE BREAKERS, OPENING BOTH NEUTRAL AND HOT WIRES.
3. THERE IS A 7.5KVA 208V-1PH - 120V-1PH ISOLATION TRANSFORMER INCLUDED IN ENCLOSURE.
Notes:
Enclosure: Type 1 MCB Rating: 50 A
Mounting: Flush Wires: 2 Mains Rating: 100 A
Supply From: Phases: 1 Mains Type: MCB
Location: OR-1 C-408 Volts: 120 Single Phase A.I.C. Rating: 10,000 A
Branch Panel: IPP408-2
Notes:
Total Est. Demand: 30 A
Total Conn.: 30 A
Total Est. Demand: 3600 VA
Total Conn. Load: 3600 VA
Power 3600 VA 100.00% 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 30 A
Total Load: 3600 VA
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 OR-2 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-2 ANESTHESIA BOOM 6
3 OR-2 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-2 ANESTHESIA BOOM 4
1 OR-2 ANESTHESIA BOOM 20 A 1 720 VA 720 VA 1 20 A OR-2 ANESTHESIA BOOM 2
CKT Circuit Description Trip Poles
A
Poles Trip Circuit Description CKT
1. OWNER FURNISHED AND CONTRACTOR INSTALLED
2. ISOLATION PANELS HAVE 2-POLE BREAKERS, OPENING BOTH NEUTRAL AND HOT WIRES.
3. THERE IS A 7.5KVA 208V-1PH - 120V-1PH ISOLATION TRANSFORMER INCLUDED IN ENCLOSURE.
Notes:
Enclosure: Type 1 MCB Rating: 50 A
Mounting: Flush Wires: 2 Mains Rating: 100 A
Supply From: Phases: 1 Mains Type: MCB
Location: OR-2 C-406 Volts: 120 Single Phase A.I.C. Rating: 10,000 A
Branch Panel: IPP406-2
Notes:
Total Est. Demand: 30 A
Total Conn.: 30 A
Total Est. Demand: 3600 VA
Total Conn. Load: 3600 VA
Power 3600 VA 100.00% 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 30 A
Total Load: 3600 VA
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 OR-3 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-3 ANESTHESIA BOOM 6
3 OR-3 ANESTHESIA BOOM 20 A 1 540 VA 540 VA 1 20 A OR-3 ANESTHESIA BOOM 4
1 OR-3 ANESTHESIA BOOM 20 A 1 720 VA 720 VA 1 20 A OR-3 ANESTHESIA BOOM 2
CKT Circuit Description Trip Poles
A
Poles Trip Circuit Description CKT
1. OWNER FURNISHED AND CONTRACTOR INSTALLED
2. ISOLATION PANELS HAVE 2-POLE BREAKERS, OPENING BOTH NEUTRAL AND HOT WIRES.
3. THERE IS A 7.5KVA 208V-1PH - 120V-1PH ISOLATION TRANSFORMER INCLUDED IN ENCLOSURE.
Notes:
Enclosure: Type 1 MCB Rating: 50 A
Mounting: Flush Wires: 2 Mains Rating: 100 A
Supply From: Phases: 1 Mains Type: MCB
Location: OR-3 C-404 Volts: 120 Single Phase A.I.C. Rating: 10,000 A
Branch Panel: IPP404-2
Panel 4BEMG-A Panel 4BEMG-A Panel 4BEMG-A
1 1 1
11/15/2022
| Sheets |
| E601 - ELECTRICAL DETAILS |
File details come from the government source that posted it. Updated .