This document provides details of a federal contract opportunity for complete site preparation work on the first floor of Building 1A at the Memphis VA Medical Center in Memphis, Tennessee. The work includes demolition and removal of existing structures as well as furnishing labor, materials, and performing all work required by the specifications and drawings. The requirement has an estimated value between $250,000 and $500,000. The NAICS code applicable is 236220 for commercial and institutional building construction. The small business size standard is $39.5 million. This will be procured using FAR Part 15 with a lowest price technically acceptable source selection. The requirement is a 100% set-aside for service-disabled veteran-owned small businesses. Offerors must be listed in the Center for Verification and Evaluation database and have an active SAM registration. Questions must be submitted in writing by email to the contracting officer by June 4, 2021, when the solicitation is planned for release.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
M-001A
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
GENERAL MECHANICAL NOTES
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS MADE. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. ALL TRANSITIONS, ELBOWS, ETC.
REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER
TRADES SHALL BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED
OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
3. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.
4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, UNIFIED FACILITIES
CRITERIA, AND INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.
5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING
REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.
6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT
BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.
7. COORDINATE WALL PENETRATIONS WITH THE GENERAL CONTRACTOR.
8. CAULK WITH SILICONE ALL GAPS BETWEEN WALL, CEILING AND FLOOR OPENINGS AND HVAC EQUIPMENT PENETRATIONS.
PATCH LARGE GAPS BEFORE CAULKING IS APPLIED.
9. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE PRESSURE
CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.
10. VOLUME DAMPERS SHALL BE PROVIDED AT EACH NEW MAIN BRANCH TAKE-OFF AND IN SUCH OTHER LOCATIONS WHERE
REQUIRED TO PROPERLY BALANCE THE SYSTEM.
11. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE INSTALLED.
12. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL 45° AND 90° SQUARE ELBOWS. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS
TYPE.
13. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET
CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
14. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH.
BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE
CRUSHED OR DISTORTED IN ITS FINAL CONFIGURATION.
15. ROUND DUCTWORK CONNECTIONS BETWEEN MAIN DUCT AND TERMINAL UNITS SHALL BE RIGID DUCT OF THE SAME DIAMETER
AS TERMINAL UNIT INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
16. PROVIDE SHEET METAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT.
TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT CONNECTORS SHALL BE USED ON FINAL CONNECTION TO
AIR HANDLING EQUIPMENT.
17. DIMENSIONS SHOWN FOR DIFFUSERS AND GRILLES ARE NECK DIMENSIONS.
18. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY ARCHITECTURAL REFLECTED
CEILING PLAN.
19. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS.
ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.
21. SUPPLY AND RETURN DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 90.1.
22. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY. REFER TO
SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
23. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWINGS BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE
PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
24. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.
25. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
26. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
M-001
MECHANICAL GENERAL NOTES,
SCHEDULES, & DESIGN CRITERIA
ANCH
NOTES:
1. EXISTING EQUIPMENT IS SHOWN WITH THIN LINEWORK.
2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK
AND DASHED.
3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD
LINEWORK.
4. BELOW IS AN EXAMPLE OF EACH:
EXISTING EQUIPMENT
EQUIPMENT TO BE DEMOLISHED
NEW OR RELOCATED EQUIPMENT
AIR DEVICE SCHEDULE
MARK TYPE REMARKSFINISHDAMPERNC
AIR FLOW
MAX
APD
IN.WG
MOUNTING MODULE SIZE
IN.x IN.
NECK SIZE
IN.x IN.
SQUARE PLAQUE FACE
NOTES:
1. PROVIDE SQUARE TO ROUND ADAPTER.
2. SEE DETAILS B4 AND B7 IN M-501 SHEET FOR DAMPER IN BRANCH FOR DUCT SERVING EACH DIFFUSER.
3. CONTRACTOR TO PROVIDE APPROPRIATE TRANSITION FROM THE NEW AIR DEVICES TO THE EXISTING DUCTWORK.
4. COORDINATE SHIELDING WITH ARCHITECTURAL. REFER TO DIV 13 49 00 FOR MORE INFORMATION.
SERVICE
SD-1 0.100 CEILING 24 x 24 23 OBD WHITESUPPLY 1,2,3REFER TO PLANSREFER TO PLANS
EG-1 0.088 CEILING 24 x 24 23 OBD WHITEEXHAUST REFER TO PLANSREFER TO PLANSLOUVERED FACE 1,3
EXISTING VAV SCHEDULE
MARK LOCATION
FIRST
FLOOR
SERVICE
VAV-1(E) D100
INLET DIA
(IN)
MAX
COOLING
(CFM)
BASIS OF DESIGN NOTES
EXISTING
BLOWER COIL UNIT SCHEDULE
MARK LOCATION
FIRST
FLOOR
SERVICE
BCU-1 D100 1"
FAN
DESIGN
CFM
EXT SP RPM MOTOR HP
CHILLED WATER COIL
AIRSIDE
COIL FACE
VEL (FPM)
EAT
DB(F)
LAT
DB(F)
EAT
WB(F)
LAT
WB(F)
WATERSIDE
EWT(F) LWT(F) GPM PRESS
DROP
TOTAL
CAP. MBh
SEN CAP.
MBh
ELECTRICAL
VOL Ph Hz MCA
BASIS OF DESIGN OPERATING WEIGHT (LBS) REMARKS
1520 1 450 80 55 67 54 45 61 5.64 7.25 45.26 33 208 1 60 9.66 TRANE BCHD036 176.6
MIN
COOLING
(CFM)
AIRFLOW RANGE
MIN OA
(CFM)
MAX. SP.
LOSS (wg)
HOT WATER HEATING COIL
EAT (F) LAT (F)
FLOW
(GPM)
PIPE SIZE
(IN)
EWT (F) LWT (F)
MIN
HEATING
CAPACITY
(BTUH)
AIR SIDE WATER SIDE
55 75 140401.4
NOTES:
1. PROVIDE UNIT WITH FACTORY MOUNTED VFD TO ADJUST FAN SPEED BASED ON ROOM TEMPERATURE. DISCHARGE AIR TO BE SET AT 55 DEG. F (ADJ).
2. MANUFACTURER PROVIDED STARTER.
3. DISCONNECT PROVIDED BY MANUFACTURER.
4. PROVIDE WITH MERV 13 FILTRATION.
5. PROVIDE FLOAT SWITCH IN AUXILIARY DRAIN PAN TO SHUT DOWN UNIT UPON DETECTION OF WATER.
EXISTING EXISTING EXISTINGEXISTINGEXISTING
PERFORATED FACERR-1 0.088 CEILING 24 x 24 23 OBD WHITERETURN 2,3REFER TO PLANSREFER TO PLANS
EG-2 0.088 WALL 12 X 8 23 OBD WHITEEXHAUST REFER TO PLANSREFER TO PLANSWALL MOUNTED REGISTER 3,4
REVISIONS DATE
GENERAL MECHANICAL ABBREVIATIONS
@ AT
& AND
AFF ABOVE FINISHED FLOOR
A/C ABOVE CEILING
AC AIR CONDITIONER
AD AUTOMATIC DAMPER
ADJ ADJUSTABLE
AFMS AIRFLOW MEASURING STATION
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
AHU AIR HANDLING UNIT
AMB AMBIENT
AMCA AIR MOVEMENT AND CONTROL ASSOCIATION
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING, AND AIR CONDITIONING
ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AUX AUXILIARY
AWS AMERICAN WELDING SOCIETY
AWG AMERICAN WIRE GAUGE
B BOILER
BCU BLOWER COIL UNIT
BD BACKDRAFT DAMPER
BLDG BUILDING
BOD BOTTOM OF DUCT
B/F BELOW FLOOR
B/S BELOW SLAB
BT BUFFER TANK
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CA COMBUSTION AIR INTAKE
CAV CONSTANT AIR VOLUME
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
CONN CONNECT, CONNECTING, CONNECTION
CONT CONTINUED
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DH DEHUMIDIFIER
DIA DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DSS DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
ESP EXTERNAL STATIC PRESSURE
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXST, (E) EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
H HEIGHT
HGRH HOT GAS REHEAT
HP HEAT PUMP
HR HOUR
HSPF HEATING SEASONAL PERFORMANCE FACTOR
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LBF/IN2 POUNDS FORCE PER SQUARE INCH
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MECH MECHANICAL
MFR, MFG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP, MOP MAXIMUM OVER CURRENT PROTECTION
MOD MOTOR OPERATED DAMPER
MSS MANUFACTURER'S STANDARDIZATION SOCIETY
MTD MOUNTED
MUW MAKE-UP WATER (POTABLE/ DOMESTIC)
MVD MANUAL VOLUME DAMPER
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
NO. NUMBER
N.O. NORMALLY OPEN
NPLV NET PART LOAD VALUE
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
QTY QUANTITY
RA RETURN AIR
RG RETURN GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RM ROOM
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
SA SUPPLY AIR
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
SS STAINLESS STEEL
TSTAT THERMOSTAT
TEMP TEMPERATURE
TG TRANSFER GRILLE
THA TOTAL HEAT ABSORPTION
THR TOTAL HEAT REJECTION
TP TEMPERATURE/ PRESSURE TEST PORT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VELO VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
W WATT(S)
W/ WITH
W/O WITHOUT
WB, Twb WET BULB (TEMPERATURE)
WD WIDE, WIDTH
WMS WIRE MESH SCREEN
AIR DISTRIBUTION DEVICE TAGS
DIFFUSER TYPE
A
400 AIRFLOW (CFM), "PLENUM", OR "TRANSFER"
A1
M-501
NORTH
DRAWING REFERENCE KEY
REFER TO
DETAIL NUMBER
SHEET NUMBER OF DETAIL
RE:A1/M-501
NORTH ARROW
A
J
SD
SP
F
CO
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
CONTROL WIRING
STATIC PRESSURE SENSOR
ROUND
FIRESTAT
TEMPERATURE SENSOR
MISCELLANEOUS LEGEND
T
120 VOLT STAND BY POWER JUNCTION
BOX PROVIDED BY THE ELECTRICAL
CONTRACTOR JUNCTION BOX IS
DEDICATED FOR USE BY THE CONTROLS
CONTRACTOR.
VARIABLE FREQUENCY DRIVEVFD
PIPING LEGEND
EXPANSION JOINT
FLEXIBLE CONNECTION
CLEANOUT
WATER METER
FLOOR CLEANOUT
THERMOMETER
PRESSURE REDUCING VALVE
MANUAL AIR VENT
PRESSURE/TEMPERATURE TAP WITH
BALL VALVE
PRESSURE SWITCH
PLUG VALVE
FLOW SWITCH
T&P RELIEF VALVE
AUTOMATIC AIR VENT
PRESSURE GAUGE WITH GAUGE COCK
PS
FS
BUTTERFLY VALVE
STRAINER WITH BLOWDOWN VALVE,
CAP, AND CHAIN
FLOW MEASURING/BALANCING/SHUT-
OFF VALVE
GATE VALVE
CHECK VALVE
BALL VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
DIRECTION OF SLOPE DOWN
ECCENTRIC REDUCER
PIPE FLANGE
PIPE CAP
PIPE GUIDE (PG)
PIPE ANCHOR (PA)X
UNION
TEE OUTLET UP
CONDENSATE DRAIN
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
ELBOW UP
ELBOW DOWN
RISE OR DROP
TEE OUTLET DOWN
M
M
FIRE DAMPER
H
DUCT MOUNTED HUMIDIFIER
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT UP
RETURN AIR DUCT DOWN
30"x14"
SQUARE TO ROUND DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
FLARED SPIN-IN WITH DAMPER AND
FLEX DUCT (DIFFUSER CONNECTION)
ROUND DUCT BRANCH TAKE-OFF FROM
RECTANGULAR MAIN WITH CONICAL TAP
FLEXIBLE DUCT CONNECTION
FLOW ARROW
DUCT SIZE TRANSITION
RECTANGULAR DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
90 DEGREE DUCT ELBOW WITH TURNING VANES
24"Ø
DUCTWORK LEGEND
RETURN AIR DEVICE
ROUND DUCT. DIAMETER INDICATED IN INCHES.
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT (RIGHT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT (LEFT SIDE IS HIGHER)
FD
SD
P - PNEUMATIC-ACTUACTED DAMPER
DAMPER TYPE:
M - MOTORIZED DAMPER (ELECTRIC)
VD
SMOKE DAMPER
VOLUME/BALANCING DAMPER
(LABEL MAY BE OMITTED)
BD
BACKDRAFT DAMPER
(COUNTER-BALANCED UNLESS
OTHERWISE NOTED)
RADIUS DUCT ELBOW - ROUND OR
RECTANGULAR (MIN. 1.5 RADIUS UNLESS
OTHERWISE NOTED)
RECTANGULAR DUCT. SIZE INDICATED IN
INCHES, FIRST NUMBER IS SIDE SHOWN.
DASHED LINES INDICATE ACOUSTICAL LINER
SUPPLY AIR DIFFUSER -
FLOW ARROWS INDICATE AIR PATTERN.
NO FLOW ARROWS SHOWN INDICATES
4-WAY PATTERN.
FSD
COMBINATION
FIRE/SMOKE DAMPER
EXHAUST AIR DEVICE
RC REMOTE CONTROLLER (VRF SYSTEM)
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START/ STOP SWITCH
TH THERMOSTAT/ HUMIDISTAT
HUMIDITY SENSORH
REFRIGERANT HOT GAS
REFRIGERANT LIQUIDRL
HEATING HOT WATER RETURNHWR
HEATING HOT WATER SUPPLYHWS
REFRIGERANT SUCTIONRS
RHG
CD
CHILLED WATER RETURNCHWR
CHILLED WATER SUPPLYCHWS
CONDENSER WATER RETURNCWR
CONDENSER WATER SUPPLYCWS
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT (RIGHT SIDE IS HIGHER)
DUCT SIZE TRANSITION RECTANGULAR TO
ROUND
30"/14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES,
FIRST NUMBER IS SIDE SHOWN
RETURN AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT (LEFT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT (RIGHT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT (LEFT SIDE IS HIGHER)
CONNECTION SIZE
(X"xX" INDICATES RECTANGULAR, X"/X"
INDICATES OVAL, X"Ø INDICATES ROUND)
X"xX"
TYP. OF #
TYPICAL OF QUANTITY INDICATED
DP DIFFERENTIAL PRESSURE SENSOR
FLEXIBLE PIPE CONNECTION
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
SKD
DUCT MOUNTED SMOKE DETECTOR
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
M-002
MECHANICAL ABBREVIATIONS AND
LEGENDS
ANCH
33"/14"
25"/14"
42"/14"
16"x10"
26"x14"
VAV-1 (E)
IMAGE
G109
ELEC
G108
STAFF T.
D101
CORR.
C1-11
SOIL HOLD
D103
EXERCISE
D104
EXAM
D105
PAT. DOSE
D107
CONFERENCE
D106
CORR.
C1-12
CARDIAC NUCLEAR
IMAGE
D102
IMAGE
D100
OPERATOR
STATION
D100B
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
MD101
FIRST FLOOR HVAC DEMOLITION PLAN
ANCH
SCALE: 1/4" = 1'-0"F1
FIRST FLOOR HVAC DEMOLITION PLAN
KEYNOTES:#
1. DEMOLISH DUCTWORK AND AIR DEVICE AS INDICATED.
2. DEMOLISH AIR DEVICE AS INDICATED.
3. EXISTING LOW EXHAUST AIR REGISTER TO BE DEMOLISHED AND
REUSE DUCTWORK. INSTALL NEW REGISTER AS SHOWN ON M-101.
4. DEMOLISH EXISTING LOW EXHAUST REGISTER AND DUCTWORK. SEE
M-101 FOR NEW EXHAUST DUCT LOCATION.
5. EXISTING VAV TO REMAIN. REFER TO M-101 AND M-001 FOR MORE
INFORMATION.
6. DEMOLISH EXISITNG TRANSFER GRILLES AND ASSOCIATED
DUCTWORK AS SHOWN.
SHEET NOTES:
1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND
DESIGN CRITERIA.
2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND
LEGENDS.
SCALE: = 1'-0"
0 4 84
1/4"
DEMOLITION WORK
DUCT TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING DUCT TO REMAIN
KEYPLAN
T
T
25"/14"
33"/14"
42"/14"
16"x8"
12"x8"
"x
12"x8"
VAV-1 (E)
14"x6"
16"x10"
16"x8"
"x
"x
"x
"Ø
14"x14"
8"Ø
14"x8"
16"x12"
BCU-1
14"x14"
500 CFM
RR-1
12"x12"
500 CFM
RR-1
8"Ø
200 CFM
SD-1
10"Ø
325 CFM
SD-1
10"Ø
325 CFM
SD-1
10"Ø
400 CFM
SD-1
10"Ø
400 CFM
SD-1
12"x8"
325 CFM
EG-2
12"x8"
125 CFM
EG-2
14"x14"
300 CFM
EG-1
"x
3/4" CHWS
3/4" CHWR
3/4" CD
C H
W
RC
H
W S
C H
W S
C H
W S
C H
W S
C H
W R
C H
W R
C H
W R
C H
W S
C H
W R
CD CD
10"Ø
FLEX
CONNECTOR
IMAGE
G109
ELEC
G108
STAFF T.
D101
CORR.
C1-11
SOIL HOLD
D103
EXERCISE
D104
EXAM
D105
PAT. DOSE
D107
CONFERENCE
D106
CORR.
C1-12
CARDIAC NUCLEAR
IMAGE
D102
IMAGE
D100
OPERATOR
STATION
D100B
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
M-101
FIRST FLOOR HVAC NEW PLAN
ANCH
SCALE: 1/4" = 1'-0"F1
FIRST FLOOR HVAC NEW PLAN
SHEET NOTES:
1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES,
SCHEDULES AND DESIGN CRITERIA.
2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND
LEGENDS.
3. ADJUST AND BALANCE ASSOCIATED AHU AND EXHAUST FAN TO
PROVIDE REQUIRED AIRFLOW TO RESPECTIVE SUPPLY
DIFFUSERS AND EXHAUST GRILLES AS INDICATED.
4. CONTRACTOR TO FIELD VERIFY, LOCATE AND COORDINATE
EXACT LOCATION, SIZE AND ELEVATION OF EXISTING
DIFFUSERS, GRILLES AND ASSOCIATED DUCTWORK.
KEYNOTES:#
1. INSTALL NEW SUPPLY DIFFUSER. BALANCE IT TO THE AIR FLOW AS
INDICATED. ADJUST AIRFLOW PATTERN AS INDICATED BY THE
ARROWS.
2. BALANCE NEW EXHAUST REGISTER TO AIR FLOWS INDICATED.
3. BALANCE NEW RETURN REGISTER TO AIR FLOWS INDICATED.
4. INSTALL NEW EXHAUST REGISTERS LOW ON WALL. MATCH EXISTING
EXHAUST REGISTER ELEVATION. BALANCE TO AIR FLOW AS
INDICATED.
5. INSTALL NEW EXHAUST REGISTER AND ASSOCIATED EXHAUST
DUCTWORK AS SHOWN. BALANCE TO AIR FLOW AS INDICATED. MOUNT
REGISTER AT SAME ELEVATION AS THE REGISTER NOTED IN 4 ABOVE.
6. EXISTING VAV TO REMAIN. BALANCE AIR FLOW TO THIS VAV AS
INDICATED ON THE SCHEDULE ON M-001.
7. INSTALL NEW BLOWER COIL UNIT AND CONTROLS. UNIT SHALL BE AS
SCHEDULED WITH A CHILLED WATER COIL. FAN MOTOR SHALL HAVE A
VFD AND ADJUST FAN SPEED AS NEEDED TO MAINTAIN ROOM
TEMPERATURE. A DUCT MOUNTED SENSOR SHALL MODULATE THE
CHILLED WATER VALVE AS NEEDED TO MAINTAIN 55 DEGREE F
DISCHARGE AIR TEMPERATURE. INSTALL AN AUX. DRAIN PAN UNDER
UNIT AND CHILLED WATER CONTROL VALVE. SEE DETAIL M-001/C5 FOR
CHILLED WATER COIL PIPING AND 2-WAY CONTROL VALVE.
8. INSTALL 3/4" CONDENSATE DRAIN LINE TO THE WALL ABOVE THE
CEILING AND DISCHARGE DRAIN OVER DRAIN. SEE DIV. 22 FOR DRAIN
PIPE.
9. EXTEND 3/4" CHILLED WATER SUPPLY AND RETURN PIPES TO
EXISTING CHILLED WATER LINES IN THE AREA. INSULATE PIPES AS
SPECIFIED.
10. SERVICE SPACE AND COIL PULL FOR BCU-1.
11. HVAC CONTROLLER FOR BCU-1 MOUNTED ABOVE CEILING.
COORDINATE EXACT LOCATION WITH COR.
12. CONTRACTOR TO MAINTAIN WALL RATING OF PIPE PENETRATION.
SCALE: = 1'-0"
0 4 84
1/4"
SEQUENCE OF OPERATION:
1. VAV-1 SHALL MAINTAIN CONSTANT AIR FLOW AS SCHEDULED.
THE ROOM TEMPERATURE SENSOR SHALL MODULATE THE
REHEAT CONTROL VALVE AS NEEDED TO MAINTAIN ROOM
TEMPERATURE SETPOINT.
2. BCU-1 SHALL OPERATE DURING OCCUPIED HOURS AS
DETERMINED BY THE EXISTING BUILDING MANAGEMENT SYSTEM.
A SUPPLY DUCT TEMPERATURE SENSOR SHALL MODULATE THE
CHILLED WATER CONTROL VALVE AS NEEDED TO MAINTAIN 55
DEG. F (ADJ) DISCHARGE AIR TEMPERATURE. A ROOM
TEMPERATURE SENSOR SHALL CONTROL THE FAN VFD AND
ADJUST AIR FLOW AS NEEDED TO MAINTAIN ROOM TEMPERATURE
SETPOINT. UPON FAN REACHING MINIMUM AIR FLOW THE
DISCHARGE AIR TEMPERATURE SHALL RISE 1 DEG. F AT A TIME TO
A MAXIMUM OF 60 DEG. F (ADJ) TO ACHIEVE ROOM TEMPERATURE
SETPOINT. A FLOAT SWITCH IN THE AUX DRAIN SHALL STOP THE
FAN AND ALARM THROUGH THE BUILDING MANAGEMENT SYSTEM
UPON ACTIVATION.
NEW DUCTWORK
NEW PLAN LEGEND
EXISTING DUCT TO REMAIN
KEYPLAN
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS
(TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
AIR SPLIT DUCT TAKE-OFF PLAN
VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER TAKE-OFF
PLAN VIEW
AIR
FLOW
AIR
FLOW
A
IR
F L O
W
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
PROVIDE VOLUME
DAMPER
PROVIDE VOLUME
DAMPER
ADJUSTABLE
METAL ROD
OR LINKAGE
TOP REGISTER
MAIN
SUPPLY
DUCT
VOLUME EXTRACTOR; ADJUSTABLE FROM
FULLY CLOSED POSITION TO CFM NOTED
ON FLOOR PLANS
AIR
FLOW
AIR
FLOW
1/4 W OR 4" MIN.
AIR
FLOW
MAIN SUPPLY
DUCT
A
IR
F L O
W
W
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
M
AX.
M A
X
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
AX.
M A
X
M A
X
M A
X
15°
15°
WALL
ESCUTCHEON TO BE PROVIDED
IN FINISHED AREAS
BACK STOP MATERIAL
SEALANT
PIPE SLEEVE
PER SPECS
CONTINUOUS INSULATION THRU
SLEEVE.
420ONE 1 x 18 GA STRAP36
TWO 1/2. RODS
TWO 3/8. RODS
ONE 1 x 16 GA STRAP
50 700
ONE 1 x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT
HANGER STRAPS OR RODS
MAX. LOAD
LBS.
MAX.
IN.
SPACING
IN. IN.
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
BAND
OVER 50"
HANGER RODS
BAND OF SAME
SIZE AS HANGER
STRAP
LOAD RATED
FASTENERS
50" & UNDER
STRUCTURAL JOIST
1/2" THREADED
ROD (TYP).
1-1/4 X 1-1/4 X 3/16
ANGLE IRON SUPPORTS.
1/2" BOLT AND NUT
W/ 2" 1/2 WASHER.
NUTS AND WASHERS BOTH
SIDES OF ANGLE (TYP).
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L
OR TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
PIPE TO TAIL PIECE
OF SINK. REFER
DETAIL F7 IN P-101
SHEET FOR MORE
DETAILS.
DRAIN
PAN
NOTE:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS
INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE
TO BE CONNECTED.
DIELECTRIC
FITTING
A B
DISCONNECT SWITCH
AIR
FLOW
MOTOR ACCESS PANEL
FILTER
ACCESS
PANEL
3/4" AUXILLARY
DRAIN CONNECTION
RETURN COIL
CONNECTION
SUPPLY COIL
CONNECTION
3/4" MAIN DRAIN
CONNECTION
AIR
FLOW
SEE SPECIFICATIONS FOR
CLAMS AND SEALANT (TYP.)
SUPPORT SADDLE
FROM STRUCTURE
FLEXIBLE DUCT SIZE
SAME AS DIFFUSER
INLET: 5'-0" MAX LENGTH
USE RIGID ELBOWS
FOR CHANGE OF
DIRECTION GREATER
THAN 45O
12"
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
CEILING
VOLUME DAMPER W/
LOCKING QUAD
THERMAL INSULATION
SEE SPECIFICATIONS
CONICAL OUTLET
BRANCH DUCT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
M-501
MECHANICAL DETAILS
ANCH
SCALE: N.T.S.B1
TERMINAL UNIT CHILLED WATER COILS - PIPING CONNECTIONS
SCALE: N.T.S.B4
BRANCH DUCTWORK - TAKEOFFS
SCALE: N.T.S.B7
FLEXIBLE DUCT DETAIL
SCALE: N.T.S.D1
DUCT TRANSITIONS
SCALE: N.T.S.D4
PIPE PENETRATION
SCALE: N.T.S.D7
ROUND DUCT HANGER DETAIL
SCALE: N.T.S.F1
RECTANGULAR DUCT HANGER
SCALE: N.T.S.F4
CONDENSATE DRAIN TRAP
SCALE: N.T.S.F7
BLOWER COIL UNIT DETAIL