This federal contract opportunity notice seeks complete site preparation services for the first floor of Building 1A at the Memphis VA Medical Center in Memphis, Tennessee. The scope of work includes demolition and removal of existing structures as well as furnishing all labor, materials, and services to prepare the site for operations. The requirement has an estimated value between $250,000 and $500,000 and falls under NAICS code 236220 for commercial and institutional building construction. The solicitation will utilize the LPTA source selection process and is a 100% SDVOSB set-aside. Interested parties must have an active registration in both the CVE and SAM databases. The point of contact for written questions is the contracting officer, with the solicitation, project name, and number required in the email subject line. Questions will only be accepted once the solicitation is released on or around June 4, 2021.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
E-001A
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
ELECTRICAL GENERAL NOTES:
1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:
A. NFPA 70-2020 (NATIONAL ELECTRICAL CODE)
B. ANSI C2-2017 (NATIONAL ELECTRICAL SAFETY CODE)
C. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.
D. PG-18-10 VA ELECTRICAL DESIGN MANUAL
2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40%
FULL.
3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND
CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL
DESCRIPTIONS INDICATED.
5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.
6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.
7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE
RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE
ROUGHING-IN.
9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA
COMPENSATION WILL BE GRANTED.
10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM THE
EXISTING SHALL BE REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.
11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND
SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE
CONTRACTOR'S RESPONSIBILITY.
14. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY
MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/8” IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN
WITH AN INDELIBLE MARKER.
17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.
ELECTRICAL ABBREVIATIONS:
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS
THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE
DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT
SYSTEM HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY
SYSTEM
HWRP
HWSP
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UPS
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
XFMR
Z
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR
SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNINTERRUPTIBLE POWER SUPPLY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
TRANSFORMER
IMPEDANCE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
E-001
ELECTRICAL GENERAL NOTES AND
ABBREVIATIONS
EOFK
NOTE:
1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS
PROJECT.
WIRE SIZE FOR ALL 277V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 170 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 280 FT
AND GREATER THAN OR EQUAL TO 170 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 440 FT
AND GREATER THAN OR EQUAL TO 280 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 700 FT
AND GREATER THAN OR EQUAL TO 440 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
WIRE SIZE FOR ALL 120V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT
AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT
AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT
AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
NOTES:
1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.
ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,
DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT
IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF
EACH:
EXISTING EQUIPMENT
NEW OR RELOCATED EQUIPMENT
HATCH INDICATES EQUIPMENT TO BE DEMOLISHED
REVISIONS DATE
1/2
B
W
SB
M
M
2/60/40/1
60/40/3/3R
40/3/3R
CB
T
M
EM
J J
J
G
G4
A
AE
M
X X
C
D a b
LUMINAIRES
LUMINAIRE AND OUTLET BOX. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
LUMINAIRE AND OUTLET BOX WIRED FOR
MULTILEVEL SWITCHING, LOWER CASE LETTER
INDICATES SWITCHLEG DESTINATION.
LUMINAIRE AND OUTLET BOX, WITH PROVISIONS
FOR EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED EXIT SIGN AND
OUTLET BOX. PROVIDE NUMBER OF ARROWS
AND FACES INDICATED. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNT AT 96" ABOVE FINISHED FLOOR.
RECESSED OR PENDANT MOUNTED LUMINAIRE
AND OUTLET BOX. LETTER INDICATES LUMINAIRE
TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED LUMINAIRE AND
OUTLET BOX WITH PROVISIONS FOR
EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
EMERGENCY LIGHT UNIT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
REMOTE HEAD OR FLOOD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
WALL WASH DOWNLIGHT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POLE MOUNTED LUMINAIRE. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POST-TOP OR BOLLARD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
EQUIPMENT
MOTOR, HORSEPOWER AS INDICATED
MOTORIZED DAMPER
3-POLE COMBINATION MAGNETIC MOTOR
STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/
NEMA ENCLOSURE) NF = NONFUSED
DISCONNECT SWITCH, (SWITCH AMPS/ FUSE
SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-
FUSED
INDIVIDUALLY MOUNTED CIRCUIT BREAKER,
(CIRCUIT BREAKER SIZE/ POLES/ NEMA
ENCLOSURE)
DRY TYPE TRANSFORMER, KVA AS INDICATED
METER
ELECTRONIC METER
PANELBOARD, SEE SCHEDULES
DISTRIBUTION PANELBOARD, SEE SCHEDULES
EQUIPMENT AS INDICATED
CEILING OR WALL MOUNTED JUNCTION BOX
PULL OR JUNCTION BOX
CEILING MOUNTED BLUE LIGHT SYSTEM
ROTATING BEACON
WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE
DROP CEILING
BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT
48" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
WHITE NOISE ROTARY VOLUME CONTROL;
MOUNT 48" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE.
CR
ST
TR
M
R
LA-1,3,5
WIRING DEVICES
LOW VOLTAGE ON/OFF WALL SWITCH, WALL
MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE
DIMMER CONTROL WITH DIMMABLE FIXTURES
INTEGRAL WITH SWITCH.
CEILING MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR
CEILING MOUNTED DUAL TECHNOLOGY
VACANCY SENSOR
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOELECTRIC CELL
WIRING
CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5
ADJACENT TO ARROW INDICATES HOMERUN OF
CIRCUITS, 1,3,5 TO PANEL LA. MARKS ACROSS
RACEWAY INDICATE THE NUMBER OF PHASE
CONDUCTORS AND NEUTRAL IN RACEWAY.
GROUND CONDUCTORS ARE INDICATED BY
LONGER HASHMARKS. NO MARKS ACROSS
RACEWAY INDICATES 2#12 CONDUCTORS AND 1
#12 GROUND CONDUCTOR. CONDUCTOR SIZE #
12 UNLESS INDICATED OTHERWISE. MINIMUM
RACEWAY SIZE SHALL BE 3/4"
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR
ABOVE FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
PLUG-IN BUSWAY, UNLESS INDICATED
OTHERWISE
SURFACE METAL RACEWAY OR MULTIOUTLET
ASSEMBLY AS INDICATED
LADDER TYPE CABLE TRAY (SIZE AS INDICATED
ON PLAN)
DUCTBANK, TEXT INDICATES QUANTITY AND
SIZE OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)
LIGHTNING PROTECTION
3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG
GROUND ROD TEST WELL
BARE COPPER GROUND CONDUCTOR, 1/0
UNLESS INDICATED OTHERWISE.
4/0 BARE COPPER GROUND CONDUCTOR
LIGHTNING PROTECTION SYSTEM AIR TERMINAL
LIGHTNING PROTECTION ROOF CONDUCTOR
ELECTRICAL CONNECTION
SITE
ELECTRICAL MANHOLE
ELECTRICAL HANDHOLE
PAD MOUNTED TRANSFORMER
POWER POLE
DOWN GUY AND ANCHOR (QUANTITY AS
INDICATED)
2W4"
WIRING DEVICES
SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE.
DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"
ABOVE FINISHED FLOOR OR ABOVE COUNTER
TOP/BACKSPLASH
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
18" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 48" ABOVE FINISHED FLOOR OR
ABOVE COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX GFI RECEPTACLE, NEMA
5-20R, MOUNTED CONCEALED BEHIND ELECTRIC
WATER COOLER
FLOOR BOX WITH DUPLEX RECEPTACLE NEMA
5-20R. PROVIDE FIRE RATED POKE THRU
DEVICES ON ALL FLOORS ABOVE GROUND
LEVEL.
SPECIAL RECEPTACLE, NEMA TYPE AS
INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
CEILING BOX WITH DUPLEX RECEPTACLE, NEMA
5-20R
RECEPTACLE WP = IN-USE WEATHER PROOF
SUBSCRIPTS TR = TAMPER RESISTANT
TV = TELEVISION, MOUNT AT 60" ABOVE
FINISHED FLOOR
AFCI = ARC FAULT CIRCUIT INTERRUPTER
FLOOR BOX SUITABLE FOR CONCRETE FLOOR
POUR; TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE
WITH HINGED ACCESS TO RECEPTACLES AND
JACKS RECESSED BELOW COVER IN FLOOR
BOX. PROVIDE 8" FIRE RATED POKE THRU
ABOVE GROUND FLOOR.
WALL SWITCH, AC TYPE, SPST, MOUNT 48"
ABOVE FINISHED FLOOR
WALL SWITCH, AC TYPE, DPDT, MOUNT 48"
ABOVE FINISHED FLOOR
3-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
4-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
SLIDE DIMMER, MOUNT 48" ABOVE FINISHED
FLOOR
MOTOR RATED DISCONNECT SWITCH WITH
THERMAL OVERLOADS, SINGLE POLE SINGLE
THROW, MOUNT ON UNIT, UNLESS INDICATED
OTHERWISE.
WALL MOUNTED, DUAL TECHNOLOGY VACANCY
SWITCH, MOUNT 48" ABOVE FINISHED FLOOR
WALL MOUNTED, DUAL TECHNOLOGY
OCCUPANCY SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
ELECTRICAL LEGEND
D
M
V
O
LV
OS
DS
PE
5-30R
EWC
ONE-LINE
TRANSFORMER
CURRENT TRANSFORMER
FUSE
ELECTRICAL CONNECTION
CIRCUIT BREAKER
SWITCH
SURGE ARRESTORS
SEPARABLE CONNECTION
DRY TYPE TRANSFORMER, K-4 RATED, KVA AS
INDICATED
GROUND
SCHEMATIC
PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)
CONTROL RELAY COIL
SHUNT TRIP COIL
TIME DELAY RELAY COIL
MOTOR STARTER COIL
SW
S
S
S
S
S
S
S
S
S
VS
D
F
G
H
P
J
LP
TV
COMMUNICATIONS
COAXIAL CABLE TELEVISION OUTLET WALL MOUNTED
60" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
COMMUNICATIONS COMBINATION VOICE/DATA OUTLET
(TWO VOICE & TWO DATA JACKS) MOUNT 18" ABOVE
FINISHED FLOOR, UNLESS INDICATED OTHERWISE
COMMUNICATIONS VOICE OUTLET MOUNT 48" ABOVE
FINISHED FLOOR, UNLESS INDICATED OTHERWISE
COMMUNICATIONS COMBINATION VOICE/DATA OUTLET
(ONE VOICE & TWO DATA JACKS), MOUNT 18" ABOVE
FINISHED FLOOR, UNLESS INDICATED OTHERWISE
FLOOR BOX SUITABLE FOR CONCRETE FLOOR POUR;
TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE WITH
HINGED ACCESS TO RECEPTACLES AND JACKS
RECESSED BELOW COVER IN FLOOR BOX. PROVIDE 8"
FIRE RATED POKE THRU ABOVE GROUND FLOOR.
COAXIAL CABLE TELEVISION OUTLET CEILING MOUNTED
WALL MOUNTED JUNCTION BOX FOR VOICE/DATA
CONNECTION TO MODULAR WORKSTATION FURNITURE.
CEILING MOUNTED PA SPEAKER, ONE WAY TYPE
WALL MOUNTED PA SPEAKER, ONE WAY TYPE; MOUNT
120" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
CLOSED CIRCUIT TELEVISION CAMERA
CONTROL STATION
WALL SWITCH, AC TYPE, SINGLE POLE SINGLE THROW,
MOUNT 48" ABOVE FINISHED FLOOR
LOW VOLTAGE ON/OFF WALL SWITCH, MOUNT 48"
ABOVE FINISHED FLOOR. PROVIDE DIMMER CONTROL
WITH DIMMABLE FIXTURES INTEGRAL WITH SWITCH.
WIRING
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR ABOVE
FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW GRADE
OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
LADDER TYPE CABLE TRAY (SIZE AS INDICATED)
WELDED WIRE BASKET TYPE CABLE TRAY (SIZE AS
INDICATED)
ELECTRONIC SECURITY
ACCESS CONTROL JUNCTION BOX
BALANCED MAGNETIC DOOR CONTACT
ELECTRIC STRIKE
SEISMIC VIBRATION SENSOR
CARD READER
ELECTRIC LOCKSET
ELECTRIC HINGE
MOTION DETECTION SENSOR
INTRUSION DETECTION SYSTEM PANEL
ACCESS CONTROL SYSTEM PANEL
INFRARED REQUEST TO EXIT
KEY PAD
MAGLOCK
DOOR RELEASE
BIOMETRIC READER
HIGH SECURITY SWITCH
TELECOMMUNICATIONS LEGEND
DC
ES
S
CR
EL
EH
M
IDS
IR
KP
ML
DR
AC
BR
LV
J
HSS
ACS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
E-002
ELECTRICAL LEGEND
EOFK
NOTE:
1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.
F
G
11 11.5 12
E.6
E
IMAGE
G109
ELEC
G108
STAFF T.
D101
SOIL HOLD
D103
EXERCISE
D104
CARDIAC NUCLEAR
IMAGE
D102
IMAGE
D100
CORR.
C1-11
CORR.
C1-11
EXAM
D105
PAT. DOSE
D107
CONFERENCE
D106
CORR.
C1-12
2 3 4
PLAN LEGEND
AREA OF WORK
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
ED101
FIRST FLOOR ELECTRICAL
DEMOLITION PLAN
EOFK
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
SCALE: 1/4" = 1'-0"F1
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
SCALE: = 1'-0"
0 4 84
1/4"
KEYPLAN
REVISIONS DATE
KEYNOTES:
1. EXISTING ELECTRICAL DEVICES AND COMPONENTS ON THE
WALL TO BE DEMOLISHED IN ROOM D102 ARE EXISTING TO BE
RELOCATED AND SHALL BE REMOVED AND KEPT IN A SAFE
LOCATION DURING DEMOLISHING AND SHALL BE REINSTALLED
ON NEW WALL. PROVIDE ALL WIRING, CONDUIT AND OTHER
APPURTENANCES NEEDED FOR A COMPLETE REINSTALLATION.
ELECTRICAL CONTRACTOR SHALL MAKE SURE ALL
REINSTALLED ELECTRICAL EQUIPMENT AND DATA DEVICES ARE
IN GOOD WORKING CONDITION AFTER REINSTALLATION.
2. AREA OF RENOVATION. DISCONNECT AND DEMOLISH ALL
CONNECTIONS TO THE EXISTING NUCLEAR MEDICINE MACHINE
SYSTEM, POWER DISTRIBUTION UNIT, UPS, AND MAIN
DISCONNECT PANEL. ALL WIRING AND CONDUITS ASSOCIATED
WITH DEMOLISHED EQUIPMENT SHALL BE REMOVED BACK TO
SOURCE. ALL OTHER ELECTRICAL EQUIPMENT INCLUDING
RECEPTACLES AND MECHANICAL EQUIPMENT CONNECTIONS
TO REMAIN. ALL TELECOM, WIRELESS ACCESS POINTS, NURSE
CALL AND PUBLIC ADDRESS SYSTEM SHALL REMAIN, BE
PRESERVED AND PROTECTED DURING CONSTRUCTION.
3. DEMOLISH ALL EXISTNG PATHWAYS BETWEEN THE EXISTING
NUCLEAR MEDICINE MACHINE SYSTEM, POWER DISTRIBUITON
UNIT, UPS, AND MAIN DISCONNECT PANEL.
4. DEMOLISH ALL LIGHT FIXTURES IN RENOVATION AREA.
PRESERVE EXISTING CIRCUIT TO BACKBOX ABOVE CEILING.
PROTECT DURING CONSTRUCTION.
D
D
3D 3D D a a aa a b a b
A1E A1
A1 A1E
A1E
A1E
WL
a b
B
BE
BE
B B
B c c c ccc c
F
G
11 11.5 12
E.6
E
TYP.
5 5
TYP.
IMAGE
G109
IMAGE
D100
CARDIAC NUCLEAR
IMAGE
D102
ELEC
G108
CORR.
C1-11
CORR.
C1-11
STAFF T.
D101
SOIL HOLD
D103
EXERCISE
D104
EXAM
D105
PAT. DOSE
D107
CONFERENCE
D106
CORR.
C1-12
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
E-101
FIRST FLOOR ELECTRICAL LIGHTING
PLAN
EOFK
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. WIRE EXIT SIGNS AHEAD OF ALL LOCAL SWITCHING.
KEYNOTES:
1. RE-USE EXISTING LIGHTING CIRCUIT PRESERVED DURING
DEMOLITION TO CONNECT TO NEW LIGHT FIXTURE.
2. POWER NEW EMERGENCY LIGHT FIXTURES FROM EXISTING
EMERGENCY PANEL IC11 IN ELECTRICAL ROOM G108. PROVIDE
2#12, 1#12G IN 1/2" CONDUIT, A 20A CIRCUIT BREAKER AND ALL
WIRING AND ACCESSORIES AS REQUIRED FOR A COMPLETE
INSTALLATION.
3. DOOR SWITCH WITH NO/NC CONTACTS. CONNECT TO SPECT-CT
SYSTEM CONTROL CIRCUIT. SPECT-CT SHOULD SHUT OFF
UPON OPENING OF THE ENTRANCE DOOR. PROVIDE A 1/2"
CONDUIT WITH PULL STRING BETWEEN CT PDU AND DOOR
SWITCH.
4. WARNING LIGHT WITH WORDING "X-RAY IN USE, DO NOT
ENTER". PROVIDE INTERFACE WITH SPECT-CT CONTROLLER
VIA INTERFACE RELAY. PROVIDE FOR AUTOMATIC
ILLUMINATION OF X-RAY WARNING LIGHT WHILE THE SPECT-CT
IS IN OPERATION. PROVIDE A 1/2" CONDUIT WITH PULL STRING
BETWEEN CT PDU AND WARNING LIGHT CONTROLLER.
5. EXIT LIGHTING FIXTURES ARE EXISTING TO REMAIN AND ONLY
SHOWN FOR REFERENCE.
6. COORDINATE FINAL LOCATION OF DOWNLIGHTS AND DIMMER
SWITCH WITH COR PRIOR TO INSTALLATION.
DEDUCTIVE ALTERNATE #1:
7. DEDUCT COSTS FOR MATERIALS AND LABOR TO PROVIDE SIX
NEW DIMMABLE FLUSH MOUNTED DOWNLIGHTS B/BE AND
CIRCUIT TO EXISTING LOCAL LIGHTING CIRCUIT.
SCALE: 1/4" = 1'-0"F1
FIRST FLOOR ELECTRICAL LIGHTING PLAN
LUMINAIRE SCHEDULE
FIXTUR
E DESCRIPTION LAMP LUMENS CRI CCT
VOLTAGE
WATTAGE MOUNTING MANUFACTURER NOTES
A1 2'X4' LED FLAT PANEL TROFFER LED 4950 80 3500 UNV 41 W GRID RECESSED CREE C-TR-C-FP24-50L-35K-WH 1,2,3
A1E 2'X4' LED FLAT PANEL TROFFER LED 4950 80 3500 UNV 41 W GRID RECESSED CREE C-TR-C-FP24-50L-35K-WH 1,2,3
B 6" LED RECESSED FLAT PANEL DOWNLIGHT LED 3000 80 3500 UNV 28 W RECESSED COOPER LDS6B-30-D010/EU6B-3040-35/6LBS-1-LI 1,2,3
BE 6" LED RECESSED FLAT PANEL DOWNLIGHT LED 3000 80 3500 UNV 28 W RECESSED COOPER LDS6B-30-D010/EU6B-3040-35/6LBS-1-LI 1,2,3
WL X-RAY ON WARNING LIGHT LED N/A N/A N/A UNV 10 W WALL: 9' AFF KENALL METMDU-MW-R-XIU-DNE-DT 1
NOTES:
1. DESIGN BASIS SHOWN FOR REFERENCE ONLY. FIXTURES OF EQUAL QUALITY AND PERFORMANCE ARE ACCEPTABLE. ALL FIXTURES MUST BE EQUAL IN MATERIAL, QUALITY, WARRANTY, PHOTOMETRIC, SIZE AND FINISH.
2. VERIFY CEILING TYPES WITH ARCHITECTURAL DRAWINGS PRIOR TO ORDERING.
3. 'A1E' AND 'BE' FIXTURES SHALL BE CIRCUITED TO EMERGENCY LIGHT FIXTURE CIRCUITS AS SHOWN ON DRAWING. SEE KEYNOTE #2 FOR MORE INFORMATION.
SCALE: = 1'-0"
0 4 84
1/4"
SCALE: 1/4" = 1'-0"F5
PHOTOMETRIC PLAN
KEYPLAN
REVISIONS DATE
POINT BY POINT PHOTOMETRIC CALCULATIONS
Calculation Points Name Average Maximum Minimum Avg/Min Max/Min
Image Room 39 fc 52 fc 14 fc 2.7 3.7
R A
IL F
O
R S
E R
V
IC
E (P
R E
F E
R A
B
LY
A V
O
ID
T O
R O
U T
E C
A B
LE
S
B E
LO
W
IT
Limited
Standard
J
R A
IL F
O
R S
E R
V
IC
E (P
R E
F E
R A
B
LY
A V
O
ID
T O
R O
U T
E C
A B
LE
S
B E
LO
W
IT
Limited
Standard
6kVA UPS XFMR
MAIN DISCONNECT PANEL (MDP)
CT PDU
POWER INPUT DISTRIBUTION BOX
XELERIS WORKSTATION
CT CONSOLE AND COMPUTER
6kVA UPS 1C11-51C11
1C11-2
1C11-4
ELEC
G108
CORR.
C1-11
STAFF T.
D101
SOIL HOLD
D103
EXERCISE
D104
EXAM
D105
PAT. DOSE
D107
CARDIAC NUCLEAR
IMAGE
D102
CONFERENCE
D106
CORR.
C1-12
IMAGE
D100
IMAGE
G109
1C11-2
F
G
E.6
11.5
1C11
BCU-1
VAV-1
F
G
11 11.5 12
E.6
ELEC
G108
CORR.
C1-11
STAFF T.
D101
IMAGE
D100
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
E-111
FIRST FLOOR ELECTRICAL POWER
PLAN
EOFK
SHEET NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO ARCHITECTURAL DRAWINGS AND PRE-INSTALL
MANUAL FOR EXACT EQUIPMENT LOCATIONS, PATHWAY
LOCATIONS, AND PATHWAY MAX DISTANCES PRIOR
TO INSTALLATION.
3. ELECTRICAL CONTRACTOR SHALL PROVIDE PULLSTRING IN
ALL CONDUIT RUNS AND PATHWAYS.
4. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL CORE
HOLE DRILLING THROUGH THE FLOOR WITH THE
CONTRACTING OFFICER REPRESENTATIVE PRIOR TO
DRILLING.
KEYNOTES:
1. PROVIDE A 2" CONDUIT BELOW FLOOR. ROUTE CONDUIT ON
STRUT MOUNTED ABOVE CEILING ON FLOOR BELOW.
2. PROVIDE A 2-1/2" CONDUIT BELOW FLOOR. ROUTE CONDUIT ON
STRUT MOUNTED ABOVE CEILING ON FLOOR BELOW.
3. PROVIDE A 3-1/2" CONDUIT BELOW FLOOR. ROUTE CONDUIT ON
STRUT MOUNTED ABOVE CEILING ON FLOOR BELOW.
4. POWER FOR NEW VACUUM, MEDICAL AIR AND O2 OUTLET. SEE
P-101 FOR MORE INFORMATION.
5. 12" X 16" X 4" BOX FOR CT POWER DISTRIBUTION UNIT.
6. 12" X 12" X 6" BOX BELOW FLOOR.
7. EXISTING VAV BOX.
8. 6" X 6" X 4" BOX FOR 6KVA NUCLEAR UPS.
9. 10" X 3 1/2" FLUSH WALL DUCT WITH MINIMUM 2 DIVIDERS.
10. PROVIDE A 4" CONDUIT BELOW FLOOR. ROUTE CONDUIT ON
STRUT MOUNTED ABOVE CEILING ON FLOOR BELOW.
11. PROVIDE 4#2 & A DEDICATED 1#2 GROUND IN A 2" CONDUIT
LOCATED ABOVE CEILING AND TERMINATE IN THE GE
PROVIDED MAIN DISCONNECT PANEL ON 90A/3P MCB.
12. PROVIDE 2" CONDUIT WITH PULL STRING ROUTED TO PANEL
MCC 1-N3 LOCATED IN ROOM D115. APPROXIMATELY 190' AWAY.
13. 3/4" CONDUIT RUN ABOVE THE CEILING.
14. X-RAY ROOM WARNING LIGHT CONTROL PANEL.
15. X-RAY ON LAMP (L1) 24V. PROVIDE 120V POWER WARNING
LIGHT FROM THE NEAREST RECEPTACLE CIRCUIT FEEDING
THE NUCLEAR MEDICINE ROOM.
16. EMERGENCY POWER OFF PUSHBUTTON.
17. PROVIDE 2#12, 1#12G IN 1/2" CONDUIT, A 15A CIRCUIT BREAKER
AND ALL WIRING AND ACCESSORIES AS REQUIRED TO
CONNECT BLOWER COIL UNIT (BCU-1) TO PANEL 1C11 IN
ELECTRICAL ROOM G108. UNIT COMES WITH INTEGRAL
DISCONNECT SWITCH. CONNECT PER MANUFACTURER'S
RECOMMENDATIONS.
18. REPLACE EXISTING FEEDER CONDUCTORS WITH NEW
CONDUCTORS SPECIFIED ON SHEET E-001. COORDINATE
BREAKER SIZE WITH GENERAL ELECTRIC PRIOR TO
INSTALLATION. COORDINATE OUTAGE WITH VA COR PRIOR TO
INSTALLATION.
19. PROVIDE A 2" CONDUIT BETWEEN POWER INPUT DISTRIBUTION
BOX AND MAIN DISCONNECT PANEL.
SCALE: 1/4" = 1'-0"F1
FIRST FLOOR ELECTRICAL POWER PLAN
SCALE: = 1'-0"
0 4 84
1/4"
TOTAL EST. DESIGN...
TOTAL EST. DEMAND... 48.1 A
TOTAL CONN. CURRENT: 48.1 A
TOTAL EST. DEMAND LOAD: 40.00 kVA
Power 40.00 kVA 40.00 kVA TOTAL CONN. LOAD: 40.00 kVA
LOAD CLASSIFICATION: CONNECTED LOAD ESTIMATED DEMAND PANEL TOTALS
NOTES:
16 SPECT-CT 3 90 A 40.0 kVA
15 EXISTING -- -- 0.0 kVA
14 EXISTING -- -- 0.0 kVA
13 EXISTING -- -- 0.0 kVA
12 EXISTING -- -- 0.0 kVA
11 EXISTING -- -- 0.0 kVA
10 EXISTING -- -- 0.0 kVA
9 EXISTING -- -- 0.0 kVA
8 EXISTING -- -- 0.0 kVA
7 EXISTING -- -- 0.0 kVA
6 EXISTING -- -- 0.0 kVA
5 EXISTING -- -- 0.0 kVA
4 EXISTING -- -- 0.0 kVA
3 EXISTING -- -- 0.0 kVA
2 EXISTING -- -- 0.0 kVA
1 EXISTING -- -- 0.0 kVA
CKT CIRCUIT DESCRIPTION # OF POLES TRIP RATING Load
SCCR RATING: EXISTING
WIRES: 4
ENCLOSURE: NEMA 1 PHASES: 3
MOUNTING: Surface VOLTAGE: 480Y/277
LOCATION: CORR. C1-11 MAINS RATING: PANEL
DISTRIBUTION PANEL: MCC 1-N3
KEYPLAN
SCALE: 1/4" = 1'-0"F4
FIRST FLOOR ELECTRICAL HVAC POWER PLAN
TV
TV TV
MAX.
6"
MAX.
6"
AV
MAX.
12"
" DATA
OUTLET
MAX.
12"
" POWER
RECEPTACLE
T-STAT
T $
LIGHT
SWITCH
OR OS
SWITCH
VOICE
OUTLET
MAX.
6"
12" MAX.
PROJECTOR
MOMENTARY
TOGGLE
SWITCH
18" MAX. 6"
~ M A
R K
E R
B O
A R
D
6" MIN.
POWER
RECEPTACLE
6" MIN.
6" MIN.
FLOOR
CEILING
FACEPLATE COLOR PER
SPECIFICATION 26 27 26
PNL-CKT
CLEAR LABEL TAPE WITH
TYPED, BLACK LETTERING
DESIGNATING PANEL AND
CIRCUIT NUMBER.
PROVIDE RECEPTACLES IN THE
FOLLOWING COLORS:
• WHITE: NORMAL POWER
• RED: GENERATOR POWER
• BLUE: UPS POWER
PROVIDE DURABLE
WIRE MARKERS OR
TAGS INSIDE THE
OUTLET BOX.
INSTALL GROUND PIN
ON TOP
FACEPLATE COLOR PER
SPECIFICATION 26 09 23
PNL-CKT
CLEAR LABEL TAPE WITH
TYPED, BLACK LETTERING
DESIGNATING PANEL AND
CIRCUIT NUMBER.
PROVIDE DURABLE
WIRE MARKERS OR
TAGS INSIDE THE
OUTLET BOX.
J-BOX 3'-0" MAX.
DISTANCE FROM
CENTER OF LIGHT
FIXTURE
T-BAR RUNNER
SUPPORT CONDUIT
10'-0" O.C.
FLEX WITH
GROUND WIRE
EARTHQUAKE
CLIP
#12 STEEL WIRE
(TYPICAL)
THREADED ROD
FROM STRUCTURE
DO NOT SECURE TO
CEILING SUPPORT
WIRES
LUMINAIRE REQUIREMENTS:
1. HOUSING & FINISH - DURABLE ALUMINUM CONSTRUCTION. WHITE POLYESTER
POWDER-COAT SEALED, MAINTENANCE-FREE FIXTURE DESIGN.
2. REFLECTORS - PRECISION ENGINEERED ACRYLIC LENS AND POLYMETHYL
METHACRYLATE (PMMA) DIFFUSER PREVENTS HOT SPOTS, SHADOWS AND
GLARE, WHILE PROVIDING UNIFORM ILLUMINATION.
3. LAMPS - LED LAMP TO HAVE 3500K KELVIN COLOR TEMPERATURE OF LIGHT
WITH A CRI OF 80 OR GREATER AND AN L80 OF 50,000 HOURS OR GREATER.
4. DRIVER - 120-277VAC, 50/60HZ ELECTRICAL INPUT (PF ≥ 0.9, THD < 20%).
MINIMUM 85% ELECTRICAL EFFICIENCY. SERVICEABLE, CONSTANT-CURRENT
MULTI-CHANNEL PROGRAMMABLE DRIVER WITH DUAL ANALOG (0-10V)
CONTROL INPUTS FOR INTENSITY AND CCT. LINEAR INTENSITY AND CCT
ADJUSTMENT PROFILES WITH 1-100% RANGE AND DIM-TO-DARK CAPABILITIES
ON INTENSITY.
5. CERTIFICATION - FIXTURE MUST BE DLC QUALIFIED (DESIGN LIGHT
CONSORTIUM) AND UL LISTED.
6. WARRANTY - PROVIDE A MINIMUM 10-YEAR WARRANTY BY MANUFACTURER.
PROVIDE IES FILE AND PROVIDE SPECIFICATION SHEET FOR REVIEW.
7. FIXTURE TYPES -
TYPE 'A1' - 4950 LUMENS, 2' X 4', RECESSED
TYPE 'A1E' - 4950 LUMENS, 2' X 4', RECESSED, ON EMERGENCY CIRCUIT
1. HOUSING - HIGH IMPACT, INJECTION MOLDED POLYCARBONATE.
HOUSING PROVIDED WITH CANOPY MOUNTING AND WIREWAY DRILL
POINTS TOP AND SIDE – SEE CROSS SECTION/DETAILS. CLOSED CELL
DIE-CUT NEOPRENE GASKET SEALS HOUSING TO CANOPY.
2. FINISH - UV-STABILIZED, HIGH IMPACT, INJECTION MOLDED CLEAR
POLYCARBONATE. NOMINAL THICKNESS .120". CORROSION RESISTANT
PHILLIPS HEAD FASTENERS SECURE SHIELD TO HOUSING.
CONTINUOUS CLOSED CELL SILICONE GASKET SEALS SHIELD TO
HOUSING.
3. REFLECTOR - HIGH IMPACT, INJECTION MOLDED POLYCARBONATE
CANOPY COVER WITH HEAVY GAUGE GALVANIZED STEEL MOUNTING
PLATE WITH INTEGRAL 1/4-20 THREADED STUDS. CANOPY MOUNTING
PLATE PROVIDED WITH FOUR-POINT MOUNTING HOLES, ONE WIREWAY
HOLE AND TEMPORARY JUNCTION BOX MOUNTING HOLES. CLOSED
CELL DIE-CUT NEOPRENE GASKET SEALS CANOPY TO MOUNTING
SURFACE.
4. LENS AND FRAME - LEGEND ILLUMINATED BY INTERNAL HIGH OUTPUT
LEDS. LETTERING HEIGHT AND STROKE DETERMINED BY LEGEND
OPTION. POLYCARBONATE RED, GREEN OR BLUE FILTER PANELS.
STENCIL IS 18-GAUGE LASER CUT STEEL WITH TGIC POLYESTER
POWDER COAT FINISH TO MATCH HOUSING.
5. LAMP SOCKET - ELECTRICAL COMPONENTS MOUNTED TO REMOVABLE
HIGH IMPACT, INJECTION MOLDED POLYCARBONATE CHASSIS. DRILL
POINTS PROVIDED FOR OPTIONAL CONDUIT ENTRY.
6. LAMPS - 624nm RED LED LIGHT SOURCE.
7. CERTIFICATION - UL AND CUL LISTED FOR WET LOCATION. MEETS OR
EXCEEDS UL48. NSF2 SPLASH/NON-FOOD ZONE.
8. FIXTURE TYPES -
TYPE 'WL' - 9.55" X 14", WALL MOUNTED, 9'AFF
LUMINAIRE REQUIREMENTS:
LUMINAIRE REQUIREMENTS:
6"
NOMINAL
7" NOMINAL
1. HOUSING & FINISH - PAINTED DIE CAST ALUMINUM, SPUN
ALUMINUM OR NONCONDUCTIVE INJECTION MOLDED
LOWER REFLECTOR WITH A LENSED UPPER OPTICAL
CHAMBER PROVIDING SUPERIOR LUMEN OUTPUT WITH
MINIMAL SOURCE BRIGHTNESS.
2. REFLECTORS - HIGH-EFFICIENCY MIXING CHAMBER
DESIGN WITH REGRESSED DIFFUSED TEMPERED-GLASS
LENS PRODUCES UNIFORM LIGHT OUTPUT. ROUND
APERTURE.
3. LAMPS - LED LAMP TO HAVE 3500K KELVIN COLOR
TEMPERATURE OF LIGHT WITH A CRI OF 80 OR GREATER
AND AN L70 OF 60,000 HOURS OR GREATER.
4. DRIVER - FIXTURE TO HAVE A DIGITALLY ADDRESSABLE
DRIVER OR LOW VOLTAGE DIGITAL ADDRESSABLE
CONTROL DEVICE. LED DRIVER TO BE 120-277 VOLT.
FIXTURE SHALL HAVE 0 TO 10 VOLT DIMMING, 1-100%.
5. CERTIFICATION - FIXTURE SHALL BE UL LISTED.
6. WARRANTY - PROVIDE A MINIMUM 10-YEAR WARRANTY BY
MANUFACTURER.
7. FIXTURE TYPES -
TYPE B - 6" DIA. - 3000 LUMENS
TYPE BE - 6" DIA. - 3000 LUMENS, ON EMERGENCY CIRCUIT
SCALE: N.T.S.D1
MOUNTING HEIGHT DETAIL
SHEET NOTES:
SCALE: N.T.S.B1
RECEPTACLE DETAIL (TYP.)
SCALE: N.T.S.B4
LIGHT SWITCH DETAIL (TYP.)
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC - MEMPHIS, TENNESSEE
COMPLETE SITE PREP FIRST
FLOOR BUILDING 1A,
SPECT-CT
APRIL 20, 2021
BID DOCUMENTS 614-19-116
1A
E-501
ELECTRICAL DETAILS
EOFK
SCALE: N.T.S.F1
RECESSED LAY-IN FIXTURE MOUNTING DETAIL
SCALE: N.T.S.D4
2'X4' LED FLAT PANEL TROFFER
SCALE: N.T.S.D7
X-RAY WARNING LIGHT FIXTURE
SCALE: N.T.S.F4
6" RECESSED LED DOWNLIGHT