About this file

This document contains specifications for roof accessories for a construction project to renovate Building 39 for Transportation and Grounds at the Lexington VA Medical Center. Key requirements include equipment supports fabricated from galvanized steel with internal insulation and wood nailers; low silhouette gravity ventilators constructed of aluminum not exceeding 12 inches in height; and a metal grating roof walkway system consisting of galvanized steel grating in 2-foot widths and 10- to 12-foot lengths with support framing, brackets, and safety railings as required. Finish colors must be selected by the owner. The related federal contract opportunity is solicitation number 36C24921R0056 from the Department of Veterans Affairs Veterans Health Administration for project number 596-19-102.

View the file

Other files

File Type Posted
09 3013 TILING.pdf PDF
A-401 Revised.pdf PDF
CU 001 CU 002 CU 003.pdf PDF
A-601 Revised.pdf PDF
36C24921R0056 0002.docx DOCX document
Roof Pictures.pdf PDF
Solicitation Questions and Answers.pdf PDF
36C24921R0056 0001.docx DOCX document
Site Visit Sign-In Sheet.pdf PDF
Project Drawings 3 of 3.pdf PDF
Project Specifications.pdf PDF
Project Drawings 1 of 3.pdf PDF
Pricing Schedule.xlsx XLSX spreadsheet
Project Drawings 2 of 3.pdf PDF
Past Performance Questionnaire.pdf PDF
Statement of Work.pdf PDF
36C24921R0056_1.docx DOCX document
Wage Determination KY20210090 01-15-2021.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LXVA 190206 Lexington VA Medical Center 596-19-102 Bid Documents, 11-16-2020 Renovate B-39 for Transportation & Grounds

01-01-21

07 72 00 - 1

SECTION 07 72 00

ROOF ACCESSORIES

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies equipment supports; gravity ventilators; and metal grating roof walkway system.

1.2 RELATED WORK

A. Section 07 21 13, THERMAL INSULATION: General insulation.

B. Section 07 22 00, ROOF AND DECK INSULATION: Rigid insulations for roofing.

C. Section 07 92 00, JOINT SEALANTS: Sealant material and installation.

1.3 QUALITY ASSURANCE

A. Provide roof accessories that are the products of manufacturers regularly engaged in producing the kinds of products specified.

B. For each accessory type provide the same product made by the same manufacturer.

C. Assemble each accessory to the greatest extent possible before delivery to the site.

1.4 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Samples: Submit representative sample panel of color anodized aluminum not less than 101 x 101 mm (4 x 4 inches). For extrusions, submit width not less than section to be installed. Show coating with integral color and texture and include manufacturer's identifying label.

C. Shop Drawings: Each item specified showing design, details of construction, installation and fastenings.

D. Manufacturer's Literature and Data: Each item specified.

E. Certificates: Stating that aluminum has been given specified thickness of anodizing.

1.5 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extend referenced. The publications are referenced in the text by the basic designation only.

B. ASTM International (ASTM):

01-01-21

07 72 00 - 2

A653/A653M-20...........Steel Sheet, Zinc-Coated (Galvanized) or Zinc-

Iron Alloy-Coated (Galvannealed) By the Hot-Dip

Process

B209-14.................Aluminum and Aluminum-Alloy Sheet and Plate

B209M-14................Aluminum and Aluminum-Alloy Sheet and Plate

(Metric)

B221-14.................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes

B221M-13................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)

C726-17.................Mineral Wool Roof Insulation Board

C1289-19................Faced Rigid Cellular Polyisocyanurate Thermal

Insulation Board

D1187/D1187M-97(2018)...Asphalt-Base Emulsions for Use as Protective

Coatings for Metal

C. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06 Series.......Metal Finishes Manual

D. American Architectural Manufacturers Association (AAMA):

2603-20.................Performance Requirements and Test Procedures for Pigmented Organic Coatings on Aluminum

Extrusions and Panels (with Coil Coating

Appendix).

2605-20.................Performance Requirements and Test Procedures for Superior Performing Organic Coatings on

Architectural Extrusions and Panels (with Coil

Coating Appendix).

611-14..................Anodized Architectural Aluminum

621-02..................High Performance Organic Coatings on Coil

Coated Architectural Hot Dipped Galvanized

(HDG) and Zinc-Aluminum Coated Steel Substrates

E. American Society of Civil Engineers (ASCE):

ASCE/SEI 7-16...........Minimum Design Loads and Associated Criteria for Buildings and Other Structures

F. U.S. Occupational Safety and Health Standards (OSHA):

29 CFR 1910 Subpart D... Walking-Working Surfaces (1910.21-1910.30)

PART 2 - PRODUCTS

01-01-21

07 72 00 - 3

2.1 MATERIALS

A. Aluminum, Extruded: ASTM B221M (B221).

B. Aluminum Sheet: ASTM B209M (B209).

C. Galvanized Sheet Steel: ASTM A653/A653M; G-90 coating.

D. Asphalt Coating: ASTM D1187/D1187M, Type I, quick setting.

2.2 EQUIPMENT SUPPORTS

A. Supported Load Capacity as indicated by Drawings.

B. Fabricate equipment supports from 1.3 mm (0.0516 inch) thick galvanized ASTM A653/A653M steel fabricate with welded corners and with seams joined by continuous water and air tight welds.

C. Equipment supports to be internally reinforced with angles 1.22 m (48 inches) on center.

D. Form exterior curb with integral base.

E. Use galvanized steel liners for curbs having inside dimension over

305 mm (12 inches).

F. Internally insulate with 38 mm (1-1/2 inch) glass-fiber board insulation (ASTM C726).

G. Fabricate curb with a minimum height of 203 mm (8 inches) above roof surface.

H. Attach preservative treated wood nailers to top of curb. Provide 50 mm

(2 inch) by 50 mm (2 inch) minimum nominal size on curb with openings and 50 mm (2 inch) thick, width of curb up to 305 mm (12 inches) on equipment support curbs.

I. Make size of supports suit size of equipment furnished, with height as shown on construction documents, but not less than 203 mm (8 inches) above roof surface.

J. Top of Equipment Supports: Level with pitch built into curb when deck slopes. Equip supports with water diverter or cricket on side that obstructs water flow.

K. Finish: to be selected by the Owner during shop drawing verification.

SPEC WRITER NOTE: Use following article for gravity type ventilators not connected to ducts. All ventilators, mechanical and gravity, that are connected to ducts are specified in Mechanical Specifications. Coordinate finish/color.

01-01-21

07 72 00 - 4

2.3 LOW SILHOUETTE GRAVITY VENTILATORS (REFER TO MECHANICAL SPECIFICATIONS)

A. Fabricate base of 1 mm (0.04 inch) thick aluminum, and vent of 0.8 mm

(0.032 inch) thick aluminum.

1. Height not to exceed 305 mm (12 inches) above top of roof curb.

2. Design ventilators to withstand 137 Km (85 miles) per hour wind velocity.

3. Provide ventilators with a removable 18 by 18 mesh by 0.28 mm (0.11 inch) diameter aluminum wire cloth insect screen.

B. Construct damper of the same material as the ventilator and design to completely close opening or remain wide open. Hold damper in closed position by a brass chain and catch. Extend chains 305 mm (12 inches) below and engage catch when damper is closed.

2.4 METAL GRATING ROOF WALKWAY SYSTEM

A. Provide metal grating roof walkway system consisting of prefabricated pans, of 14 gauge, galvanized (G-90 Coating) steel grating with slip resistant surface.

B. Grating units to be in 610 mm (2 foot) widths and in 3048 to 3658 mm (10 to 12 foot long) sections as required.

C. Provide complete with support framing, brackets, connectors, nosings and other accessories as required for complete roof walkway system.

1. Include support stands at minimum 1524 mm (5 feet) on center to hold planks a minimum of 228 mm (9 inches) above roof surface.

2. Provide wind restraint attachment to roof structure of size and spacing required to meet wind uplift requirements.

D. Include step units, nosings framing and connectors to provide changes in elevation as required. Comply with ASCE 7 and 29 CFR 1910.23.

E. Equip walkways with safety railings where required by 29 CFR 1910.23.

F. Provide neoprene rubber pads having a shore A hardness of 80 to 90-

Durometer under each support, or bearing surface.

G. Finish: to be selected by the Owner during shop drawing review.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install roof specialties where indicated on construction documents.

B. Secure with fasteners in accordance with manufacture's printed installation instructions and approved shop drawings unless shown otherwise.

01-01-21

07 72 00 - 5

C. Coordinate to install insulation where shown; see Section 07 21 13, THERMAL INSULATION and Section 07 22 00, ROOF AND DECK INSULATION.

D. Comply with section 07 92 00, JOINT SEALANTS to install sealants where required by manufactures installation instructions require sealant.

E. Coordinate with roofing work for installation of items in sequence to prevent water infiltration.

1. After completion of base flashing bend down cap flashing flange and secure to blocking with screws.

2. Install expansion joint cover with 6 mm (1/4 inch) wide space at end joints and tension bars at 610 mm (24 inches) on center.

3. Install cover plates with formed aluminum flashing concealed and centered on joint. Flashing to lap cover not less than 101 mm

(4 inches).

F. Equipment Supports: Do not anchor to insulating concrete or metal deck.

Anchor only to building structure as per manufacturers recommendations.

3.2 PROTECTION OF ALUMINUM

A. Provide protection for aluminum against galvanic action wherever dissimilar materials are in contact, by painting the contact surfaces of the dissimilar material with two (2) coats of asphalt coating

(complete coverage), or by separating the contact surfaces with a preformed neoprene tape having pressure sensitive adhesive coating on side.

B. Paint aluminum in contact with wood, concrete and masonry, or other absorptive materials, that may become repeatedly wet, with two coats of asphalt coating.

3.3 ADJUSTING

A. Adjust roof hatch hardware to operate freely and so that cover will operate without binding, close tightly at perimeter, and latch securely.

3.4 PROTECTION

A. Protect roof accessories from damage during installation and after completion of the work from subsequent construction.

- - - E N D - - -

SECTION 07 72 00 ROOF ACCESSORIES
PART 1 - GENERAL
1.1 DESCRIPTION
1.2 RELATED WORK
1.3 QUALITY ASSURANCE
1.4 SUBMITTALS
1.5 APPLICABLE PUBLICATIONS
PART 2 - PRODUCTS
2.1 MATERIALS
2.2 EQUIPMENT SUPPORTS
2.3 LOW SILHOUETTE GRAVITY VENTILATORS (Refer to Mechanical specifications)
2.4 METAL GRATING ROOF WALKWAY SYSTEM
PART 3 - EXECUTION
3.1 INSTALLATION
3.2 PROTECTION OF ALUMINUM
3.3 ADJUSTING
3.4 PROTECTION

File details come from the government source that posted it. Updated .