This document is a HazMat-Universal Waste Inspection Report for the Tampa VA Medical Center and Brooksville VA Clinic, conducted by Castle Hill Associates from January 29 to March 15, 2024. The comprehensive inspection surveyed multiple buildings for universal waste materials as defined by the EPA, including mercury-containing fluorescent light tubes, PCB ballasts, lead and nickel-cadmium batteries, mercury/sodium high-pressure light bulbs, CFCs in water coolers and A/C units, and mercury thermostats and switches.
The report details universal waste quantities by building and floor, with significant findings across 15 different buildings. Notable quantities include 114 mercury-containing fluorescent light tubes, 57 PCB ballasts, 187 lead and nickel-cadmium batteries, and 32 mercury/sodium high-pressure light bulbs in the main medical center building. The Brooksville Clinic location also had substantial universal waste, with 540 fluorescent light tubes, 270 PCB ballasts, and 36 backup light batteries. The inspection was performed by Brett Brumbaugh, a Registered Environmental Property Assessor (REPA) and Certified Environmental & Safety Compliance Officer (CESCO), who visually identified and inventoried the waste materials without sampling.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HAZMAT-UNIVERSAL WASTE INSPECTION
LOCATION:
TAMPA VA MEDICAL CENTER
BROOKSVILLE VA CLINIC
VA SUNSHINE HEALTHCARE NETWORK
INSPECTION DATES:
JANUARY 29 - MARCH 15, 2024
CONTRACTOR:
CASTLE HILL ASSOCIATES, LLC
1197 FARNSWORTH RD. SUITE E
WATERVILLE, OH 43566
567-952-0212
HazMat-Universal Waste Inspection Report January-March 2024 Tampa VA Medical Center, Tampa, FL / Brooksville VA Clinic, Brooksville, FL
TABLE OF CONTENTS
1. INSPECTION SCOPE OF WORK & SUMMARY
2. UNIVERSAL WASTE FINDINGS & INVENTORY BY BUILDING
3. TYPICAL PHOTOGRAPHS OF UNIVERSAL WASTE COMPONENTS
APPENDICES
Appendix A - Inspector Certifications
INSPECTION SCOPE OF WORK & SUMMARY
A survey for the potentially hazardous wastes, which are typically described as “Universal Wastes” was conducted from January 29 - March 15, 2024 for the Department of Veterans Affairs at the Tampa VA Medical Center in Tampa, FL and the Brooksville VA Clinic in Brooksville, FL by Castle Hill Associates.
The details of the project are as follows:
Building Name: Tampa VA Medical Center Address: 13000 Bruce B Downs Blvd., Tampa, FL 33612 Inspector: Brett Brumbaugh, REPA, CESCO
Building Name: Brooksville VA Clinic Address: 14540 Cortez Blvd., Brooksville, FL 34613 Inspector: Brett Brumbaugh, REPA, CESCO
The survey was conducted in accordance with current federal environmental standards for these materials.
Universal waste is defined by the United States Environmental Protection Agency in 40 CFR 273.912.
These wastes are a category of hazardous waste that contains very common materials found in buildings.
Universal waste includes batteries, fluorescent lamps, mercury components (ballasts, thermostats, switches, etc.), CFC refrigerants, and hydraulic oils found in building components. These waste materials were determined by the EPA to pose a lower immediate risk to people and the environment compared to other hazardous wastes.
The suspect universal waste materials and components were not sampled as part of this inspection, but were visually identified and inventoried as required by the US EPA hazardous material regulations. In addition, no soil sampling or sub-surface investigation was conducted for components such as underground storage tanks (USTs), healthcare chemicals, cleaning chemicals, or previous hazardous materials dumping or disposal. Also, asbestos containing materials and lead-based paint were surveyed and reported as separate reports.
The identified Universal Wastes were inventoried by component and quantity in each building along with a breakdown of each component per floor on the following page. In addition, a typical photo of each Universal Waste component is included in Appendix A.
The inspection was conducted and the report was prepared by Brett Brumbaugh of Castle Hill Associates who has been conducting hazardous materials surveys since 1987. He is a registered environmental property assessor (REPA) and a certified environmental and safety compliance officer (CESCO) through the NREP (National Registry of Environmental Professionals).
Inspector Signature:
Brett L. Brumbaugh, REPA, CESCO NREP Registered Environmental Property Assessor (REPA #5866) NREP Certified Environmental & Safety Compliance Officer (CESCO #123337)
INSPECTION FINDINGS
BUILDING 1
Universal Waste Material Quantity
Mercury containing fluorescent light tubes (4’ and 8’ tubes) 114 tubes
PCB containing fluorescent light fixture ballasts 57 each
Lead & Ni-Cd Batteries in backup lighting fixtures & exit lights 187 each
Mercury/Sodium high-pressure light bulbs 32 bulbs
Hydraulic oils in door closers 90 each
CFCs in water coolers/fountains 58 each
Mercury containing HVAC switches and thermometers 44 each
UNIVERSAL WASTE QUANTITIES BY FLOOR
Area/Floor Fluor. Tubes PCB Ballasts Exit/Backup
Lights Hg/Sodium
Bulbs Hydraulic Closers
Water Cooler CFCs
Exterior 32
Ground 60 30 25 14 25
First 54 27 58 27 12
Second 44 18 6
Third 12 6 3
Fourth 12 7 3
Fifth 12 1 3
Sixth 12 8 3
Seventh 12 9 3
TOTALS 114 57 187 32 90 58
BUILDING 2
Universal Waste Material Locations Quantity
Mercury/Sodium high-pressure light bulbs Exterior 8 bulbs
BUILDING 19
Mercury containing fluorescent light tubes (4’ and 8’ tubes) All floors 40 bulbs
PCB containing fluorescent light fixture ballasts All floors 20 each
Lead & Ni-Cd Batteries in backup lights & exit lights All floors 6 each
Mercury/Sodium high-pressure light bulbs Exterior 12 each
Mercury Thermostats G003 1 each
BUILDING 23
Mercury/Sodium high-pressure light bulbs Exterior 2 each
BUILDING 24
Mercury containing fluorescent light tubes (4’ and 8’ tubes) Interior 26 bulbs
PCB containing fluorescent light fixture ballasts Interior 13 each
BUILDING 30
Lead & Ni-Cd Batteries in backup lights & exit lights Ground-3rd floor 40 each
CFCs in water coolers/fountains Ground-3rd floor 8 each
Mercury/Sodium high-pressure light bulbs Exterior 6 each
BUILDING 32
Lead & Ni-Cd Batteries in backup lights & exit lights Ground-3rd floor 64 each
CFCs in water coolers/fountains Ground-3rd floor 16 each
BUILDING 36
Lead & Ni-Cd Batteries in backup lights & exit lights 1st floor 6 each
CFCs in water coolers/fountains 1st floor 2 each
BUILDING 38
Lead & Ni-Cd Batteries in backup lights & exit lights Ground-3rd floor 48 each
CFCs in water coolers/fountains Ground-3rd floor 16 each
Mercury/Sodium high-pressure light bulbs Exterior 8 each
BUILDING 39
Lead & Ni-Cd Batteries in backup lights & exit lights 1st floor 3 each
BUILDING 41
Lead & Ni-Cd Batteries in backup lights & exit lights 1st and 2nd floors 20 each
CFCs in water coolers/fountains 1st and 2nd floors 2 each
Mercury/Sodium high-pressure light bulbs Exterior 4 each
BUILDING 42
Lead & Ni-Cd Batteries in backup lights & exit lights 1st floor 12 each
BUILDING 54
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 24 each
CFCs in water coolers/fountains Interior 5 each
Mercury/Sodium high-pressure light bulbs Interior/Exterior 28 each
BUILDING 55
Lead & Ni-Cd Batteries in backup lights & exit lights All levels 42 each
Mercury/Sodium high-pressure light bulbs Exterior 8 each
BUILDING 56
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 4 each
Mercury/Sodium high-pressure light bulbs Interior/Exterior 2 each
BUILDING 68
Lead & Ni-Cd Batteries in backup lights & exit lights 1st & 2nd floors 24 each
CFCs in water coolers/fountains Interior 4 each
Mercury/Sodium high-pressure light bulbs Exterior 4 each
BUILDING T33
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 7 each
CFCs in A/C Units Exterior 1 each
BUILDING T43
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 4 each
BUILDING T49
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 2 each
BUILDING T61
Mercury containing fluorescent light tubes (4’ and 8’ tubes) Interior 32 bulbs
BUILDING T62
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 10 each
BUILDING T73
BUILDING T74
BUILDING T75
BUILDING T76
BUILDING T77
BUILDING T78
BUILDING T80
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 18 each
CFCs in water coolers/fountains Interior 2 each
BUILDING T81
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 18 each
BUILDING T82
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 18 each
BUILDING T83
Lead & Ni-Cd Batteries in backup lights & exit lights Interior 18 each
BUILDING T99
BROOKSVILLE CLINIC
Mercury containing fluorescent light tubes (4’ and 8’ tubes) 1st and 2nd floors 540 bulbs
PCB containing fluorescent light fixture ballasts 1st and 2nd floors 270 each
Lead & Ni-Cd Batteries in backup lights & exit lights 1st and 2nd floors 36 each
CFCs in water coolers/fountains Interior 3 each
TYPICAL PHOTOGRAPHS OF UNIVERSAL WASTE MATERIALS
Photo 1 Mercury containing fluorescent light tubes
Photo 2 Hydraulic oil in door closer
Photo 3 CFCs in drinking fountains
Photo 4 Exit light fixture batteries
Photo 5 Hg/Sodium light bulbs in exerior fixtures
Photo 6 Mercury thermostats
Photo 7 Mercury gauges
Photo 8 CFC in drinking fountains
Photo 9 Batteries in backup lighting fixtures and exit lights
Photo 10 Hg/Sodium light bulbs in exerior fixtures
Photo 11 Exterior A/C units on trailers
Photo 12 Exterior A/C units on trailers
APPENDIX A
INSPECTOR CERTIFICATIONS