MH Domiciliary Kitchen Fans.pdf
PDF 2 MB Posted
- Attached to
- N041--MH Domiciliary Exhaust Hoods Installation
- Solicitation number
- 36C24824Q0829
About this file
This document is a Request for Quotation (RFQ) for the installation of three exhaust hoods at the VA Mental Health Domiciliary VA Nutrition and Food Service main kitchen in San Juan, Puerto Rico. The solicitation is a Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside, with the associated NAICS code of 238220 and a small business size standard of $19 Million. The period of performance is expected to be from April 15, 2024 to April 29, 2024. Quotes must be submitted by 12:00 PM AST on April 11, 2024, and a site visit is scheduled for April 8, 2024 at 2:00 PM. Award will be based on a comparative evaluation of quotes, with options evaluated at the time of award. The contracting office is the Department of Veterans Affairs, Network Contracting Office -8.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MARK: KEF-2
PROJECT: VA MENTAL HEALTH AND RECOVERY FACI...
DATE: 8/18/2021
D Dia.
B Dia.
G
A
C
T Sq.
VCR-D VF
Upblast Centrifugal Exhaust Ventilator Roof Mounted/Direct Drive Electronically Commutated Vari-Flow® Motor
STANDARD CONSTRUCTION FEATURES:
All aluminum housing - Backward inclined all aluminum wheel - Two piece top cap with stainless steel quick release latches - One piece bottom spinning - Welded curb cap corners - Permanently lubricated ball bearing motors - Corrosion resistant fasteners - Transit tested packaging.
Qty Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Power
(HP) FEG
Speed Control
1 135V17D (VF) 960 .250 859 .084 n/a(<1HP) EC
Performance
HP RPM* Volts/Ph/Hz Enclosure RLA
1/8 1725 115/1/60 OPEN -EC 1.9
Motor Information
1 2 3 4 5 6 7 8 LwA dBA Sones
71 68 62 56 56 51 46 41 61 49 5.3
Sound Data Inlet Sound Power by Octave Band v7.6.372.15170 Page 35 of 64
Accessories:
FAN MOUNTED SPEED CONTROL
DISCONNECT NEMA 3 PRE-WIRED
ROOF CURB RCA 18 9.5H -C-T-N
UL762 (327Y-300DEG)
HURRICANE RATED CONSTRUCTION
MIAMI-DADE COUNTY, FL NOA 17-0925.02 / 11-13-2023
TAS-201: Large Missile Impact Test TAS-202: Uniform Static Air Pressure Test TAS-203: Cyclic Wind Pressure Test
FLORIDA PRODUCT APPROVAL, FL11695
WELDED DRAIN CUPLG
TIE-DOWN EYELETS (4)
A 19-1/16 B Dia. 30-3/16
C 28-5/8 D Dia. 20-3/8
G 2 T Sq. 20
Roof Open. Sq.* 15-1/2
Weight(lbs)*** Shipping 100 Unit 82 NOTE: Accessories may affect dimensions shown.
Dimensions (inches)
* Roof opening size for curbs supplied by Cook only.
***Includes fan, motor & accessories.
0.00
0.10
0.20
0.30
0.40
0.50
0.00
.020
.040
.060
.080
.100
0 300 600 900 1200 1500 Flow (CFM)
SP
(i nw c)
Pow er (H
P)
Fan Curve
Fan Curve Legend CFM vs SP CFM vs HP Point of Operation System Curve
Altitude (ft): 62 Temperature (F): 70
*Motor programmed to max speed of 965 RPM.
RLA based on motor manufacturer's data at programmed HP and max RPM.
Motor is electronically protected.
VCR-D VF
MARK: KEF-2
PROJECT: VA MENTAL HEALTH AND RECOVERY FACI...
DATE: 8/18/2021
Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Power
(HP) FEG
OVEL
(fpm)
TSPD
(fpm) SE
Temp (°F)
ALT
(ft)
135V17D (VF) 960 .250 859 .084 n/a(<1HP) 474 3035 45% 70 62
Performance
1 2 3 4 5 6 7 8 LwA dBA Sones
71 68 62 56 56 51 46 41 61 49 5.3
Sound Data Inlet Sound Power by Octave Band
With EC Motor • • Programmed MaxRPM=965
0.00
0.10
0.20
0.30
0.40
0.50
0.00
.020
.040
.060
.080
.100
0 300 600 900 1200 1500 Flow (CFM)
SP
(i nw c)
Pow er (H
P)
Fan Curve Legend CFM vs SP CFM vs HP Point of Operation System Curve v7.6.372.15170 Page 36 of 64
MARK: KEF-1
DATE: 8/18/2021
D Dia.
B Dia.
G
A
C
T Sq.
VCRD-HP VF
Upblast Centrifugal Exhaust Ventilator Roof Mounted/Direct Drive Electronically Commutated Vari-Flow® Motor
STANDARD CONSTRUCTION FEATURES:
All aluminum housing - Backward inclined all aluminum wheel - Two piece top cap with stainless steel quick release latches - One piece bottom spinning - Welded curb cap corners - Permanently lubricated ball bearing motors - Corrosion resistant fasteners - Transit tested packaging.
Qty Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Power
(HP) FEG
Speed Control
1 180VH17D (VF) 2400 1.50 1402 .942 n/a(<1HP) EC
Performance
HP RPM* Volts/Ph/Hz Enclosure RLA
1 1725 208/1/60 OPEN -EC 7.3
Motor Information
1 2 3 4 5 6 7 8 LwA dBA Sones
80 82 77 73 70 72 69 62 78 66 15.6
Sound Data Inlet Sound Power by Octave Band v7.6.372.15170 Page 41 of 64
Accessories:
FAN MOUNTED SPEED CONTROL
DISCONNECT NEMA 3 PRE-WIRED
ROOF CURB RCA 28 9.5H -C-T-N
UL762 (327Y-300DEG)
HURRICANE RATED CONSTRUCTION
MIAMI-DADE COUNTY, FL NOA 17-0925.02 / 11-13-2023
TAS-201: Large Missile Impact Test TAS-202: Uniform Static Air Pressure Test TAS-203: Cyclic Wind Pressure Test
FLORIDA PRODUCT APPROVAL, FL11695
WELDED DRAIN CUPLG
TIE-DOWN EYELETS (4)
A 24-13/16 B Dia. 39-7/16
C 33-3/8 D Dia. 26-1/8
G 3 T Sq. 30
Roof Open. Sq.* 25-1/2
Weight(lbs)*** Shipping 145 Unit 27 NOTE: Accessories may affect dimensions shown.
Dimensions (inches)
* Roof opening size for curbs supplied by Cook only.
***Includes fan, motor & accessories.
0.00
0.40
0.80
1.20
1.60
2.00
0.00
.200
.400
.600
.800
1.00
0 800 1600 2400 3200 4000 Flow (CFM)
SP
(i nw c)
Pow er (H
P)
Fan Curve
Fan Curve Legend CFM vs SP CFM vs HP Point of Operation System Curve
Altitude (ft): 62 Temperature (F): 70
*Motor programmed to max speed of 1407 RPM.
RLA based on motor manufacturer's data at programmed HP and max RPM.
Motor is electronically protected.
VCRD-HP VF
MARK: KEF-1
PROJECT: VA MENTAL HEALTH AND RECOVERY FACI...
DATE: 8/18/2021
Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Power
(HP) FEG
OVEL
(fpm)
TSPD
(fpm) SE
Temp (°F)
ALT
(ft)
180VH17D (VF) 2400 1.50 1402 .942 n/a(<1HP) 621 6606 60% 70 62
Performance
1 2 3 4 5 6 7 8 LwA dBA Sones
80 82 77 73 70 72 69 62 78 66 15.6
Sound Data Inlet Sound Power by Octave Band
With EC Motor • • Programmed MaxRPM=1407
0.00
0.40
0.80
1.20
1.60
2.00
0.00
.200
.400
.600
.800
1.00
0 800 1600 2400 3200 4000 Flow (CFM)
SP
(i nw c)
Pow er (H
P)
Fan Curve Legend CFM vs SP CFM vs HP Point of Operation v7.6.372.15170 Page 42 of 64
MARK: KSF-2
DATE: 8/18/2021
A Sq.
B
T Sq.
C
DKSP-D
Filtered Kitchen Supply Packaged Ventilator Direct Drive
STANDARD CONSTRUCTION FEATURES:
Totally enclosed galvanized cabinet with hooded, filtered intake - Top cap quick release latches - Permanent, one inch, washable, aluminum filters (fiberglass or polyester media available).
Qty Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Input Watts FEG FEI
Speed Control
1 122KSPD 800 .460 1059 175 n/a(<1HP) 1.66 FSC
Performance
Volts/Ph/Hz Enclosure
115/1/60 TEFC -SE
Motor Information
1 2 3 4 5 6 7 8 LwA dBA Sones
66 70 66 61 58 55 52 47 64 53 6.6
Sound Data Inlet Sound Power by Octave Band v7.6.372.15170 Page 43 of 64
Accessories:
BDMI-26 MTR DPR 230V
ROOF CURB RCA 30 9.5H -C+T-N
FILTER BOX W/MERV 8
FAN SPEED CONTROLLER 5 AMP 120 VOLT
A Sq. 32-3/16 B 32-1/4 C 26-3/16 D 25-5/8
T Sq. 32-1/4
Weight(lbs)*** Shipping 354 Unit 246 NOTE: Accessories may affect dimensions shown.
Dimensions (inches)
***Includes fan, motor & accessories.
0.00
0.20
0.40
0.60
0.80
1.00
0.00
0 200 400 600 800 1000 Flow (CFM)
SP
(i nw c)
Input W atts
Fan Curve
Fan Curve Legend CFM vs SP CFM vs Watts Point of Operation
Altitude (ft): 62 Temperature (F): 70
KSP-D
MARK: KSF-2
PROJECT: VA MENTAL HEALTH AND RECOVERY FACI...
DATE: 8/18/2021
Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Input Watts FEG FEI
OVEL
(fpm)
TSPD
(fpm) SE
Temp (°F)
ALT
(ft)
122KSPD 800 .460 1059 175 n/a(<1HP) 1.66 1253 2217 83% 70 62
Performance
1 2 3 4 5 6 7 8 LwA dBA Sones
66 70 66 61 58 55 52 47 64 53 6.6
Sound Data Inlet Sound Power by Octave Band
With Fan Speed Control • • MaxRPM=1089
0.00
0.20
0.40
0.60
0.80
1.00
0.00
0 200 400 600 800 1000 Flow (CFM)
SP
(i nw c)
Input W atts
Fan Curve Legend CFM vs SP CFM vs Watts Point of Operation v7.6.372.15170 Page 44 of 64
MARK: KSF-1
DATE: 8/18/2021
B C
Side Discharge Opening G
T Sq.
A Sq. DH
Bottom DischargeOpening
W
H F
E
E
F
KSP-B
Filtered Kitchen Supply Packaged Ventilator With Filter Box Belt Drive
STANDARD CONSTRUCTION FEATURES:
DWDI blower mounted in a totally enclosed galvanized cabinet with hooded, filtered intake - Insulated top cap with quick release latches - Permanent, one inch, washable, aluminum filters (fiberglass or polyester media available) - Adjustable pitch drives through 5 H.P. - Vibration isolators - Corrosion resistant fasteners - MERV 8 filters in filter box (MERV11 available) - All fans factory adjusted to specified fan
RPM.
Qty Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Power*
(HP) FEG
1 100KSP-B 2040 .500 882 .603 n/a(<1HP)
Performance (*Bhp includes 12% drive loss)
HP RPM Volts/Ph/Hz Enclosure FLA Mounted VFD Rated
3/4 1725 208/3/60 TEFC -SE 3.5 No Yes
Motor Information
1 2 3 4 5 6 7 8 LwA dBA Sones
90 88 74 69 67 65 64 56 76 64 16.3
Sound Data Outlet Sound Power by Octave Band v7.6.372.15170 Page 51 of 64
Accessories:
DRIVES (1.5 SF) @ 882 RPM
DISCONNECT NEMA 1
BDMI-22 MTR DPR 230V
ROOF CURB RCA 26 9.5H -C+T-N
FILTER BOX W/MERV 8
A Sq. 28-3/16 B 27 C 21 x 22-1/4 D 20-1/4 E 7-5/8 F 8-7/16 G 3 H 25-3/4
T Sq. 28-1/8 H x W 11-1/4 x 12-7/8
Roof Open Sq.* 23-1/2 Filter Qty 1
Filters Size 21-3/4 x 27 Box Filter Qty 2
Box Filters Size 25 x 25 x 2
Weight(lbs)*** Shipping 331 Unit 238 NOTE: Accessories may affect dimensions shown.
Dimensions (inches)
* Roof opening size for curbs supplied by Cook only.
***Includes fan, motor & accessories.
0.00
0.25
0.50
0.75
1.00
1.25
0.00
.300
.600
.900
1.20
1.50
0 600 1200 1800 2400 3000 Flow (CFM)
SP
(i nw c)
Pow er (H
P)
Fan Curve
Fan Curve Legend CFM vs SP CFM vs HP Point of Operation System Curve
Altitude (ft): 62 Temperature (F): 70
FLA based on NEC (2017) Table 430.250
KSP-B
MARK: KSF-1
PROJECT: VA MENTAL HEALTH AND RECOVERY FACI...
DATE: 8/18/2021
Catalog Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Power*
(HP) FEG
OVEL
(fpm)
TSPD
(fpm) SE
Temp (°F)
ALT
(ft)
100KSP-B 2040 .500 882 .603 n/a(<1HP) 2050 2309 30% 70 62
Performance (*Bhp includes 12% drive loss)
1 2 3 4 5 6 7 8 LwA dBA Sones
90 88 74 69 67 65 64 56 76 64 16.3
Sound Data Outlet Sound Power by Octave Band
MaxRPM=1419
0.00
0.25
0.50
0.75
1.00
1.25
0.00
.300
.600
.900
1.20
1.50
0 600 1200 1800 2400 3000 Flow (CFM)
SP
(i nw c)
Pow er (H
P)
Fan Curve Legend CFM vs SP CFM vs HP Point of Operation v7.6.372.15170 Page 52 of 64
File details come from the government source that posted it. Updated .