S06_RFI UPDATE ACM Survey Report - JAHVA Building 1 FOR REF ONLY.pdf

PDF 22 MB Posted

Attached to
Y1DA--FY23: NRM-Tier 1 (PROJ: 673-21-148) BB - Renovate Bldg 1 - 5 South to Private Patient Rooms
Solicitation number
36C24823R0199
Issued by

About this file

This document provides details on a federal contract opportunity to renovate Building 1 at a Veterans Affairs medical center. The solicitation number is 36C24823R0199 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8. It seeks to convert five floors of the building from general medical/surgical beds to private patient rooms as part of Project 673-21-148. Interested parties should respond with pricing and qualification information by the specified due date to be considered for the award, which is expected to be granted in the following fiscal year for the renovation work. Key requirements include converting existing bed space and support areas to modernized private inpatient rooms while maintaining compliance with VA design guidelines.

View the file

Other files

File Type Posted
36C24823R0199 0007.docx DOCX document
S06_673 21 148_VA Tampa_5South_DRAWINGS_BidSet_REV1_20231106.pdf PDF
S06_673 21 148_VA Tampa_5South_SPECS_BidSet_REV1_20231106.pdf PDF
36C24823R0199 0006.docx DOCX document
S06_RFI UPDATE List-Description of Bid-Proposal Items and any associated alternate deductive_110723.docx DOCX document
S06_673-21-148_VA Tampa_5South_SPECS_BidSet_REV1_20231106.pdf PDF
S06_673-21-148_VA Tampa_5South_DRAWINGS_BidSet_REV1_20231106.pdf PDF
36C24823R0199 0005.docx DOCX document
S05_RFI 36C24823R0199 BB Renovate 5 South Private Patient Rooms UPDATED 11 3.xlsx XLSX spreadsheet
S06_RFI UPDATE CCTV Riser Diagram_110723.pdf PDF
S06_RFI UPDATE CCTV Riser Diagram.pdf PDF
P01_673-21-148 BB SOW REV.docx DOCX document
S06_RFI UPDATE 22 00 97 5th Floor Asbestos and Lead Survey Report REV 1 2023 10 05.pdf PDF
S05_RFI_36C24823R0199_BB Renovate 5 South Private Patient Rooms UPDATED 10.27.xlsx XLSX spreadsheet
S06_RFI UPDATE 673-21-148 VA Tampa 5South DRAWINGS BidSet REV1 2023 10 27.pdf PDF
36C24823R0199 0004.docx DOCX document
S06_RFI UPDATE List-Description of Bid-Proposal Items and any associated alternate deductive.docx DOCX document
S06_RFI UPDATE 673-21-148 VA Tampa 5South SPECS BidSet REV1 2023 10 30.pdf PDF
36C24823R0199 0003.docx DOCX document
RFI Spreadsheet.xlsx XLSX spreadsheet
36C24823R0199 0002.docx DOCX document
S04_673_21_148 Construction Site Visit Attendance.pdf PDF
36C24823R0199 0001.docx DOCX document
S02_RFP Attachment_Price Matrix.xlsx XLSX spreadsheet
S02_RFP Attachment_VA LOS_JAN 2023_DEVIATION.pdf PDF
S02_RFP Attachment_WD FL20230208_13Jan2023.pdf PDF
S02_RFP Attachment_Instructions to Offerors.docx DOCX document
S02_RFP Attachment_RFI Spreadsheet.xlsx XLSX spreadsheet
S02_RFP Attachment_Past Performance Questionnaire.pdf PDF
36C24823R0199_2.docx DOCX document
S02_RFP Attachment_5S Site Map.pdf PDF
S02_RFP Attachment_673_21_148_VA Tampa_5South_SPECS_BidSet_REVISED.pdf PDF
S02_RFP Attachment_673_21_148_VA Tampa_5South_DRAWINGS_BidSet_REV.pdf PDF
S02_RFP Attachment_Experience Information Sheet.docx DOCX document
S02_RFP Attachment_EMR.docx DOCX document
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Asbestos AHERA Survey Report

Performed at:

Building 1

James A. Haley VA Medical Center 13000 Bruce B. Downs Blvd

Tampa, FL 33612

Report Prepared For:

Biosphere International 13139 W. Linebaugh Ave

Tampa, Florida 33626

Report Prepared By:

OHC Environmental Engineering, Inc.

101 South Hoover Blvd., Suite 101 Tampa, Florida 33609

OHC Project #170161-AS

May 28, 2018

James A. Haley VA Medical Center Asbestos AHERA Survey

OHC Project No. 170161-AS i

May 28, 2017

Ronnie King Biosphere International 13139 W. Linebaugh Ave., Tampa, FL 33626

Re: Asbestos AHERA Survey

James A. Haley VA Medical Center 13000 Bruce B. Downs Blvd., Dear Mr. King, OHC Environmental Engineering, Inc. (OHC) is pleased to present the report for the Asbestos NESHAP Survey performed from November 27, 2017 to April 9, 2018. These services were conducted in Building 1 at the James A. Haley VA Medical Center located at 13000 Bruce B.

Downs Boulevard in Tampa, Florida.

If we can be of further assistance or if you should have any questions, please do not hesitate to contact us at your convenience.

Sincerely, Report Prepared by:

Kirill Smirnov Industrial Hygienist

Report Reviewed by:

Cristina Jones Project Manager

James A. Haley VA Medical Center ii

ASBESTOS NESHAP SURVEY

OHC PROJECT NO. 170161-AS

CLIENT NAME: Biosphere International

PROJECT NAME: JAHVA Building 1

PROJECT ADDRESS: James A. Haley VA Medical Center 13000 Bruce B. Downs Blvd., DATE OF SURVEY: November 2017-April 2018

CONSULTING FIRM: OHC Environmental Engineering, Inc.

101 South Hoover Blvd., Suite 101 Tampa, Florida 33609

SURVEYOR: Kirill Sminov

OHC PROJECT MANAGER: Cristina Jones

FLAC:

James F. Rizk

FLAC #ZA0000060

James A. Haley VA Medical Center iii

TABLE OF CONTENTS

1.0 INTRODUCTION

2.0 SCOPE OF WORK

3.0 EXECUTIVE SUMMARY

4.0 ASBESTOS SURVEY

4.1 Asbestos Survey Results

4.2 Asbestos Sampling Methods

4.3 Regulatory Requirements

4.4 Statutory Requirements

5.0 OBSERVATIONS

6.0 LIMITATIONS

7.0 DOCUMENT CONTENT

APPENDIX A: Photographs – Basement, Floors 3-7, and Penthouse

APPENDIX B: Photographs – Ground, First & Second Floors

APPENDIX C: Sampling Locations

APPENDIX D: Analytical Results – Basement, Floors 3-7, and Penthouse

APPENDIX E: Analytical Results – Ground, First & Second Floors

APPENDIX F: Consultant & Laboratory Credentials

James A. Haley VA Medical Center

1.0 INTRODUCTION

OHC Environmental Engineering, Inc., (OHC), was contracted by Ronnie King of Biosphere International to perform an Asbestos Survey in compliance with the National Emission Standard for Hazardous Air Pollutants (NESHAP) regulation for asbestos (40 CFR 61 Subpart M). The survey was performed throughout Building 1 at the James A.

Haley VA Medical Center in Tampa, Florida. A representative from OHC, Mr. Kirill Smirnov, visited the area from November 27th of 2017 to April 9th of 2018, to perform these services. This survey is limited to the identification and collection of Asbestos Containing Material (ACM) throughout all levels of Building 1 only.

2.0 SCOPE OF WORK

The scope of work for this survey included the following:

• A site visit and thorough NESHAP inspection by an Asbestos Hazard Emergency Response Act (AHERA) accredited asbestos building inspector working under the supervision of a Florida Licensed Asbestos Consultant (LAC) to identify suspect Asbestos Containing Material (ACM)

• Sampling, labeling and analyzing of accessible suspect ACM to be disturbed

• Preparation of a comprehensive report documenting the location and content of all materials sampled and analyzed, which includes suspect ACM and the category and assessment of identified hazardous materials

3.0 EXECUTIVE SUMMARY

Based on the results of the Polarized Light Microscopy (PLM), Asbestos Containing Materials (ACM) does exist within the scope of this survey, as indicated in Tables 1 and 2 below.

James A. Haley VA Medical Center

TABLE 1: ASBESTOS SURVEY RESULTS

BASEMENT, FLOORS 3-7, AND PENTHOUSE

JAMES A. HALEY VAMC – BUILDING 1

HSA Sample

ID

Sample Location

Material Description

Approx.

Quantity Result Category

10A Penthouse

White wrap on pipes and insulation 500 LF 15% Chrysotile – mastic

NF-II

(TSI) 10B Penthouse

10C Penthouse

40A Basement

Brown baseboard with tan mastic 300 LF 2% Chrysotile – texture

NF-II

(Misc) 40B Basement

40C Basement

76A

9x9 cream floor tile with olive streaks and black mastic. By

Elevator 3 left corner.

9x9 cream floor tile with olive streaks and black mastic

50,000 SF

3% Chrysotile – tile

8% Chrysotile – mastic

NF-I

(Misc)

76B In 7B-721B 76C By 7B-728 76D 5th floor lobby 76E 3rd floor lobby

80A 7B-721B Red 9x9 tile with black mastic in front of fire apparatus closets

1,000 SF

NF-I

(Misc)

80B 7A-718B

80C 7B-721B

82A Inside 7B-721B

Drywall with joint compound 40,000 SF 2% Chrysotile – joint compound

NF-II

(Misc)

82B Inside

82C Location above ceiling tile.

82D In 6B-624

82E Above ceiling on

82F 5A-502A

82G Above ceiling on

82H Inside 4B-421

82I Above ceiling on 4th floor

82J Behind chair left of 3B-305, inside damaged wall.

82K Above ceiling on 3rd

James A. Haley VA Medical Center

83A

Across from employee restroom by nurses station, next to water fountain

12x12 tile with gray-blue pattern and yellow mastic

20,000 SF

<1% Chrysotile −

Black/Yellow Mastic

OSHA Rules Apply

83B By stairwell door next to 7A-747B

83C By 7A-736 entrance to the right.

84A By South wing entrance on 7th floor

12x12 gray tile with gray and beige streaks and yellow and black mastics

15,000 SF 5% Chrysotile −

NF-I

(Misc)

84B By 7A-723 entrance.

84C Inside 7A-702A fire apparatus.

84D Across from 6A-

84E Left of 6A-648C.

By stairwell door.

85A 7A-722B

12x12 faded red tile in front of fire apparatus closet 1,000 SF 5% Chrysotile − mastic

NF-I

(Misc)

85B By 7A-702A 85C By 7A-702A 85D Inside 6A-648C 85E Inside 6A-625C

88A 7A-736

12x12 white tile with gray streaks 200 SF 4% Chrysotile − mastic

NF-I

(Misc) 88B 7A-736 88C 7A-736

89A By 7A-733

Gray fire proofing 30000 SF 4% Chrysotile RACM (Surfacing)

89B By 7A-733 89C By 7A-722D 89D By 7A-722D 89E By 7A-735

96A In front of elevators 10 and 11.

12x12 blue tile with black mastic 700 SF 6% Chrysotile − mastic

NF-I

(Misc) 96B In front of elevators 10 and 11.

96C In front of elevators 10 and 11.

James A. Haley VA Medical Center

96D Behind chairs left of elevator 10 on 3rd floor

96E Behind chairs right of elevator 11 on 3rd floor

97A Outside of doorway 7B- 705C

12x12 tan floor tile with white and beige streaks. Black/yellow mastic.

60,000 SF 8% Chrysotile − mastic

NF-I

(Misc)

97B In 7B-705. Left side by cubicles.

97C In 7B-705. 2ft from doorway.

97D

6th floor elevator 10 lobby, left corner by the chairs when facing elevators.

97E To the right of

6th floor elevator 11.

97F To the right of

5th floor elevator

97G Left of doorway 5B-539

99 99A Across from 7B- 704B

12x12 pink tile with brown streaks and yellow with black mastic

500 SF 3% Chrysotile – black mastic

NF-I

(Misc)

101A By 7B-725 Gold mastic on metal ductwork 3,000 SF 5% Chrysotile − mastic

NF-II

(Misc) 101B By elevator 3 on

5th floor 101C By 4A-459

114A

Left of the 6th floor elevator 5 if facing the doors 9x9 tan floor tile with white and brown streaks and black mastic

50,000 SF

15% Chrysotile –

NF-I

(Misc) 114B By 6B-625 door.

114C

Wall opposite 6A-634, corner before elevator lobby.

James A. Haley VA Medical Center

116A

Left of the 6th floor elevator 10 if facing the doors, by the corner. 12x12 tan floor tile with large beige and gray streaks.

Tan/black mastic

20,000 SF 7% Chrysotile − mastic

NF-I

(Misc) 116B By 6B-603 doorway.

116C Inside 6B-624

116D Left of Elevator 10 on 4th floor

116E Inside 4B-421

120A By 6A-625C 12x12 white tile with gray speckles and black mastic

10,000 SF 4% Chrysotile –

NF-I

(Misc) 120B

Across from 6A- 619, by clean linen closet.

120C By 6A-602A

125A Left of elevator 5 on 6th floor. Brown fire proofing in the middle of 6th floor

2,000 SF 7% Chrysotile RACM (Surfacing) 125B Left of elevator 5 on 6th floor.

125C By elevator 3 on 6th floor.

144A 4B-415

Black mastic on fire closet pipes 400 SF 2% Chrysotile – mastic

NF-II

(Misc)

144B 7A-718B 144C 6th fire closet 144D 5th fire closet 144E 3A-348C

147A Left of elevator 5, on 3rd floor 9x9 tan floor tile with brown streaks and black mastic

30,000 SF

10% Chrysotile –

NF-I

(Misc) 147B By 3B-301

147C In 3B-312B

150A 3rd floor

Gray tile with dark yellow mastic 250 SF 3% Chrysotile − mastic

NF-I

(Misc)

150B 3rd floor

150C 3rd floor

James A. Haley VA Medical Center

TABLE 2: ASBESTOS SURVEY RESULTS

GROUND, FIRST AND SECOND FLOORS

JAMES A. HALEY VAMC – BUILDING 1

HSA Sample

ID

Sample Location

Material Description

Approx.

Quantity Result Category

2A Inside 2D-217A

9x9 tile with brown streak and black mastic

50,000 SF

4% Chrysotile −

10% Chrysotile −

NF-I

(Misc)

2B Left of elevator 3 on 2nd floor

2C By 2D-255C, left of exit sign

2D 1B-156B, behind right double door

2E 1C-101B fire closet

3A Inside 2D-217A

Drywall with joint compound 45,000 SF 2% Chrysotile – joint compound

NF-II

(Misc)

3B Inside 2A-239 3C Inside 2B-207C

3D Above ceiling on 1st

3E Above ceiling on 1st

3F Above ceiling on ground floor

3G Above ceiling on ground floor

4A Inside 2D-217A

Red 9x9 tile with black mastic 1,000 SF

8% Chrysotile -

NF-I

(Misc)

4B Inside 2A-213B 4C Inside 2B-203B

4D In 1D-158 fire closet

4E In 1C-101B

6A Right of 2A- 215C

Dark tan vinyl tile with black accent tiles, two layers of tile underneath, and yellow and black mastic

400 SF 4% Chrysotile – black mastic

NF-I

(Misc) 6B In 2A-215 behind left wall

6C Right of stage, by exit door

8A By entrance to 2A-213B

9x9 tan tile with white streaks, black mastic

40,000 SF

4% Chrysotile –

5% Chrysotile –

NF-I

(Misc)

8B Left of 2A-221

8C Right of 2B- 201D

8D 1D-158 fire closet

8E Across from 1C- 101A

James A. Haley VA Medical Center

9A In 2B-203B 9x9 cream tile with olive streaks and black mastic

40,000 SF

2% Chrysotile –

NF-I

(Misc) 9B

By 2C-213, behind double door 9C In 2C-260A

10A Across from 2B-

9x9 black tile with white streaks and black mastic

1,500 SF

6% Chrysotile –

NF-I

(Misc)

10B Behind left hemodialysis door

10C Behind left ambulatory door

10D Right double door by 1C-102

10E Left double door by 1B-104

12A Right of elevator 11, behind chairs

12x12 white tile with beige splatters and yellow mastic 25,000 SF 2% Chrysotile – mastic

NF-I

(Misc)

12B Left of elevator

12C Right of 11, behind chairs

12D Ground floor by elevators

13A By elevator 10, 11 lobby, 2nd floor 12x12 blue tile with light blue speckles and black mastic

500 SF 3% Chrysotile – mastic

NF-I

(Misc) 13B

By vending machines, pharmacy pickup, 1st floor

13C By Elevator 3 on ground floor

15A By stair exit, next to 2A-228

12x12 cream tile with apricot streaks and yellow mastic

10,000 SF

NF-I

(Misc)

15B Inside GD-018A 15C Inside GD-010B

15D GA-024A

15E Inside GA-009A

18A Intersection by 2A-218

Gray fire proofing 80,000 SF 8% Chrysotile RACM (Surfacing)

18B By 2C-276D 18C By 2C-230 18D Cafeteria dining

18E Auditorium – by

TV

James A. Haley VA Medical Center

18F 1st floor by elevator lobby

18G 1st floor by elevator lobby

18H 1st floor

18I Ground floor by police entrance

18J Ground floor by walkway to garage

21A By 2C-222D Beige duct joint filling mastic 1,000 SF 6% Chrysotile – mastic

NF-II

(Misc) 21B Ground floor

22A IN 2C-222A

12x12 pink tile with black mastic 3,000 SF 15% Chrysotile – black mastic

NF-I

(Misc) 22B Left of 2c-222 entrance

22C By double doors next to ward entrance

23A By the exit to crosswalk 12x12 orange-tan tile with beige speckles and yellow mastic

500 SF 10% Chrysotile – black mastic

NF-I

(Misc) 23B By the exit-left side

23C By exit no smoking sign

27A By 2C-258

Gold mastic on ductwork 3,000 SF 4% Chrysotile – mastic

NF-II

(Misc)

27B By 2C-248 27C In 2D-204 27D 1st

32A In 2A-213B

Gray hard mastic on black pipe joints 500 SF 2% Chrysotile – mastic

NF-II

(Misc)

32B In 2D- 255A 32C In 2C-201B 32D 1st floor 32E Ground floor

33A 2C-222 by door

12x12 tan tile with beige and gray splatters, gray mastic 2,000 SF 6% Chrysotile – black mastic

NF-I

(Misc)

33B Right of TV, by chairs

33C Right of coffee machine

33D Dental waiting – behind chairs

33E By 1A-157 behind chairs

37 37A By entrance SICU hallway

12x12 blue tile with orange and blue streaks 4,000 SF 8% Chrysotile – black mastic

NF-I

(Misc)

James A. Haley VA Medical Center

38A By 2B-216

Silver wrap with pink insulation 5,000 LF 8% Chrysotile – wrap

NF-II

(TSI) 38B 1st floor

38C Ground floor

57A Chapel on 2nd floor, by entrance

White popcorn ceiling 400 SF 5% Chrysotile RACM

(Surfacing) 57B

Chapel on 2nd floor, by entrance

57C

Chapel on 2nd floor, by entrance

58A In 1B-109A 12x12 red tile on top of beige tile with yellow and black mastics

700 SF

NF-I

(Misc)

58B In 1B-122A

58C BY GA-024A

58D By GD-018A

59A In 1B-109A 12x12 White tile with gray and tan speckles, yellow mastic

5,000 SF

NF-I

(Misc)

59B In 1B-155A 59C Ground floor 59D Ground floor

62A In waiting lobby by windows 12x12 light pink tile with orange and blue speckles on beige tile with yellow and black mastic

400 SF

NF-I

(Misc) 62B In waiting lobby by windows

62C In waiting lobby by windows

63A Dental office suites – by entrance door 12x12 Gray tile with gray speckles. Yellow with dark beige mastic

200 SF 7% Chrysotile – black mastic

NF-I

(Misc) 63B

Dental office suites – by equipment cart

63C Dental office suites – by the hallway corner

69A ER lobby Green tile on top of beige tile. Yellow mastic.

500 SF

beige tile

7% Chrysotile –

NF-I

(Misc)

69B ER lobby

69C ER lobby

70 70A

In the basement, on the outside of ground floor pool

Brown pool mastic covering 1,500 SF 3% Chrysotile – mastic

NF-II

(Misc)

James A. Haley VA Medical Center

70B

In the basement, on the outside of ground floor pool

70C

In the basement, on the outside of ground floor pool

72A Safety office Gray vinyl panels on tile, yellow mastic 400 SF beige tile

7% Chrysotile –

NF-I

(Misc)

72B Safety office

72C Safety office

73A Ground floor Hard black-brown mastic inside fire closets on walls

300 SF 4% Chrysotile – mastic

NF-II

(Misc) 73B Ground floor

NF-I = Category I Non-friable ACM NF-II = Category II Non-Friable ACM RACM = Regulated Asbestos-Containing Materials

4.0 ASBESTOS SURVEY

The Environmental Protection Agency defines Asbestos Containing Material (ACM) as any material or product that contains more than one percent (1%) asbestos. Based on the observations and the laboratory analysis of the samples collected from the site, ACM does exist within the scope of this survey.

4.1 Asbestos Survey Results

Tables 3 and 4 below summarize the samples of suspect ACM collected. Note that samples in RED are considered asbestos-containing materials (ACM). Please refer to Appendix A of this report for photos of the materials sampled, Appendix B for asbestos sampling locations, and Appendix C for complete laboratory analytical results.

List of Abbreviations:

F Friable HSA Homogenous Sampling Area LF Linear Feet Mod Moderate NAD No asbestos Detected NF Non-Friable SF Square Feet

James A. Haley VA Medical Center

TABLE 3: ASBESTOS SAMPLING RESULTS

JAMES A. HALEY VA MEDICAL CENTER – TAMPA, FL

BUILDING 1

HSA Sample ID Location Color Material Description Asbestos Content Quantity Cond. PFD Friable or NF

1A 1B 1C

Penthouse White

Cloth wrap and pink insulation between large round ducts

NAD 500 LF Fair High NF

2A 2B 2C

Penthouse Pink Pink wrap with black insulation and mastic NAD 500 LF Fair High F

3A 3B 3C

Penthouse Blue Blue wrap with black insulation and mastic NAD 500 LF Fair High F

4A 4B 4C

Penthouse White Mastic on pipe ends and junctions

NAD 400 SF Fair High NF

5A 5B 5C

Penthouse Yellow

Yellow wrap with yellow insulation on pipes

NAD 500 LF Fair High NF

6 6A Penthouse Black Black gaskets on valves NAD 50 SF Fair Mod. NF

7A 7B 7C 7D 7E

Penthouse Gray Gray fire proofing NAD 5000 SF Good High F

James A. Haley VA Medical Center

8A 8B 8C

Penthouse Gray Gray Mastic on

HVAC unit doors

NAD 100 SF Fair Mod. NF

9A 9B 9C

Penthouse White

White wrap and insulation on large rectangular HVAC ducts

NAD 500 SF Fair High NF

10A 10B 10C

Penthouse White

White wrap on pipes and insulation with mastic

15% Chrysotile -mastic 500 LF Fair Mod. NF

11A 11B 11C

Penthouse Silver Silver wrap with yellow insulation.

NAD 500 LF Fair Mod. NF

12A 12B 12C

Penthouse Black Black foam insulation on pipes

NAD 200 LF Fair Mod. NF

13A 13B 13C

Penthouse Yellow Yellow paper wrap with yellow insulation.

NAD 500 LF Fair Mod. NF

14A 14B 14C

Penthouse Gray Gray mastic on metal ducts NAD 100 SF Fair Mod. NF

15 15A Penthouse Off-white Hard packing material on pipe elbows

NAD 100 SF Fair Mod. F

16 16A Penthouse White White mastic on metal ducts NAD 50 SF Fair Mod. NF

17 17A Penthouse Brown and silver

Brown and silver pipe joint mastic NAD 50 SF Fair Mod. NF

James A. Haley VA Medical Center

18 18A Penthouse White White mastic between HVAC unit metal seams

NAD 50 SF Fair Mod. NF

19 19A Penthouse Gray

Gray Wrap with silver and white wrap backing and insulation on HVAC units

NAD 800 SF Fair Mod. NF

20 20A Penthouse White White mastic on silver wrap with Brown insulation

NAD 100 SF Fair Mod. NF

21A 21B 21C

Penthouse Orange Orange gasket NAD 5 SF Good Mod. F

22A 22B 22C

Penthouse Black Black foam insulation NAD 200 LF Fair Mod. NF

23A 23B 23C

Penthouse Yellow Yellow insulation in metal pipes

NAD 500 LF Fair Mod. NF

24A 24B 24C

Penthouse Red Red fire proofing (caulking) NAD 50 SF Good Mod. NF

25 25A Penthouse Black Black foam insulation NAD 200 LF Fair Mod. NF

26 26A Penthouse White White mastic on red pipes NAD 50 SF Good Mod. NF

27 27A Penthouse Green Green mastic NAD 50 SF Fair Mod. NF 28 28A Penthouse Gray Gray mastic NAD 50 SF Good. Mod. NF

James A. Haley VA Medical Center

29A 29B 29C

Inside double door area in the basement by the office area

Pink Pink on top of gray fire proofing

NAD 100 SF Good High F

30A 30B 30C 30D 30E

Basement Gray Gray fire proofing NAD 30000 SF Good High F

31A 31B 31C

Next to entrance to the pipe area in basement Blue

Blue fire proofing on top of gray NAD 100 SF Good High F

32A 32B 32C

By unloading ramp in the basement

Dark gray Darker gray fire proofing NAD 100 SF Good High F

33A 33B 33C

Basement White

Large chilled water return pipes; Paper wrap and yellow insulation

NAD 2000 LF Fair Mod. NF

34 34A Basement White

Large chilled water return pipes inside main pipe area. Paper wrap with black insulation and mastic.

NAD 2000 LF Fair Mod. F

35 34A Basement White

GO PSI UP

paper pipe wrap and yellow insulation with

NAD 2000 LF Fair Mod. NF

James A. Haley VA Medical Center

36 36A Basement White

30 LBS MP RET

and 30 PSI GO STEAM pipe paper wrap and yellow insulation

NAD 2000 LF Fair Mod. NF

37A 37B 37C

Basement White

Chilled water return pipes with paper wrap and black insulation with mastic

NAD 2000 LF Fair Mod. F

38 38A Basement White

Chilled water return pipes with paper wrap and yellow insulation

NAD 2000 LF Fair Mod. NF

39 39A Basement White-gray

Hard gray surfacing material on 12 inch pipe

NAD 200 LF Good Low F

40A 40B 40C

Basement offices area Brown Brown baseboard with tan mastic 2% Chrysotile -texture 300 LF Good Mod. NF

41 41A Basement Gray Gray baseboard with tan mastic NAD 300 LF Good Mod. NF

42A 42B 42C

Basement White Drywall with joint compound NAD 15000 SF Fair Mod. F

43A 43B 43C

Basement Beige and brown

Beige and Brown tile with streaks and gray and black mastics.

NAD 400 SF Good Mod. NF

James A. Haley VA Medical Center

44A 44B 44C

Basement White 2x4 with 2x2 random squiggly line ceiling tile

NAD 700 SF Good Mod. F

45A 45B 45C

Basement Red Red fire stop NAD 200 SF Good Low NF

46A 46B 46C

Basement Gray Linoleum stone pattern tile on top of HSA43

NAD 300 SF Good Mod. NF

47A 47B 47C

Basement White White mastic on ductwork NAD 100 SF Good Low NF

48A 48B 48C

Basement Silver Silver duct wrap with yellow insulation

NAD 400 LF Fair Mod. NF

49 49A Basement Silver Silver duct wrap with pink insulation

NAD 200 LF Good Mod. NF

50A 50B 50C

Basement Orange Orange gaskets on blue pipe valves

NAD 25 SF Good Low NF

51A 51B 51C

Basement Gray Gray mastic on metal ducts NAD 250 SF Good Low NF

52A 52B 52C

Basement Silver Silver duct wrap with white insulation

NAD 200 LF Good Mod. NF

53A 53B 53C

Basement Gray with white streaks

12x12 gray Tile with white streaks and

NAD 300 SF Good Mod. NF

James A. Haley VA Medical Center

54A 54B 54C

Basement Black Black foam wrap on pipes NAD 200 LF Fair Mod. NF

55A 55B 55C

Basement White Wrap with mastic and green insulation

NAD 250 LF Good Low NF

56A 56B 56C

Basement Silver

Silver wrap on large rectangular HVAC duct with yellow insulation

NAD 100 LF Good Low NF

57A 57B 57C

Basement White

White cloth wrap and yellow insulation on large HVAC duct

NAD 400 LF Good Mod. NF

58A 58B 58C

Basement Gray Gray fire proofing inside DB-xx Area

NAD 1000 SF Good Mod. F

59A 59B 59C

Basement Gray

Gray compacted fire proofing on columns and ceiling

NAD 10000 SF Good High F

60A 60B 60C 60D 60E

Basement Green/gra y

Green on gray fire proofing NAD 1000 SF Good Mod. F

Basement Dark green

Dark green wrap and yellow insulation on condensate pipe.

NAD 400 LF Good Low NF

James A. Haley VA Medical Center

Basement Yellow Yellow wrap and yellow insulation on steam pipes

NAD 400 LF Good Low NF

Basement Gray Gray mastic on metal ducts NAD 150 SF Good Low NF

Basement Red Red fire caulking NAD 100 SF Good Low NF

65 65A Basement White

White insulation material beneath metal sheet wrap on steam tank

NAD 400 SF Good Low NF

66 66A Basement Yellow Yellow mastic on round metal pipes

NAD 100 SF Good Low NF

67A 67B 67C

Basement White

Wrap with yellow insulation on large round pipes

NAD 2000 LF Good Mod. NF

68A 68B 68C

Basement White

Wrap with yellow insulation on small round pipes

NAD 2000 LF Good Mod. NF

69A 69B 69C

Basement White

White cloth wrap with yellow insulation on Rectangular HVAC ducts

NAD 500 LF Good Mod. NF

James A. Haley VA Medical Center

70A 70B 70C

Basement Silver

Silver duct wrap with yellow insulation and mastic

NAD 500 LF Good Mod. NF

71A 71B 71C

Basement Red Gasket on steam tank NAD 25 SF Good Low NF

72A 72B 72C

Basement Blue Blue wrap on pipe with yellow insulation

NAD 300 LF Fair Mod. NF

73A 73B 73C

Basement White Water line white wrap with yellow insulation NAD 300 LF Fair Mod. NF

74A 74B 74C

Basement White White wrap with black insulation NAD 500 LF Good Mod. F

75A 75B 75C

Basement Black Black wall covering material NAD 2000 SF Fair Mod. NF

76A 76B 76C 76D 76E

Present in hallways and rooms

Cream with olive streaks

9x9 cream floor tile with olive streaks and black mastic

3% Chrysotile - tile;

8% Chrysotile -

50000 SF Good High NF

James A. Haley VA Medical Center

77A 77B 77C 77D 77E 77F 77G 77H 77I

Rooms and hallways Blue

4 inch blue baseboard with yellow mastic

NAD 5000 LF Good Mod. NF

78A 78B 78C 78D 78E 78F 78G 78H 78I 78J 78K

Rooms and hallways Gray

4 inch gray baseboard with yellow mastic

NAD 10000 LF Fair Mod. NF

79A 79B 79C 79D 79E 79F 79G 79H 79I 79J 79K

Rooms and hallways Gray

6-inch gray baseboard with

NAD 5000 LF Good Mod. NF

James A. Haley VA Medical Center

80A 80B 80C

Hallways Red

Red 9x9 tile with black mastic in front of fire apparatus closets

3% Chrysotile - tile;

8% Chrysotile -mastic 1000 SF Good Low NF

81A 81B 81C 81D 81E

Above ceiling in hallways and rooms, and in fire closets

Red Red fire caulking NAD 700 SF Good Low NF

82A 82B 82C 82D 82E 82F 82G 82H 82I 82J 82K

Hallways and rooms White Drywall with joint compound 2% Chrysotile 40000 SF Good Low F

83A 83B 83C

7A hallways Gray-blue

12x12 tile with gray-blue pattern and yellow mastic

<1% Chrysotile 2000 SF Good High NF

84A 84B 84C 84D 84E

In hallways Gray

12x12 gray tile with gray and beige streaks and yellow and black mastics

5% Chrysotile -mastic 15000 SF Good Mod. NF

James A. Haley VA Medical Center

85A 85B 85C 85D 85E

In front of fire apparatus closets Red

12x12 faded red tile in front of fire apparatus closet

5% Chrysotile -mastic 1000 SF Good Low NF

86 86A Inside 7A-718B White

White mastic on black pipe inside fire apparatus closets

NAD 10 SF Fair Low NF

87A 87B 87C

In 7A-736 Brown Brown 4 inch baseboard with yellow mastic

NAD 200 LF Fair Mod. NF

88A 88B 88C

In 7A-736 White 12x12 white tile with gray streaks

4% Chrysotile -mastic 200 SF Good Mod. NF

89A 89B 89C 89D 89E

7th Floor Gray Gray fire proofing 4% Chrysotile 30000 SF Good Mod. F

90A 90B 90C

7th Floor White Paper wrap with yellow insulation and mastic NAD 10000 LF Fair Low NF

91A 91B 91C 91D 91E 91F 91G

Above ceiling in rooms and hallways

Silver Silver duct wrap with mastic and pink insulation

NAD 10000 LF Good Low NF

James A. Haley VA Medical Center

92A 92B 92C 92D 92E

Above ceiling in rooms and hallways

Silver

Silver duct wrap with yellow insulation and mastic

NAD 50000 LF Fair Low NF

93A 93B 93C

7th floor hallways and rooms White

2x4 ceiling tile with large squiggly holes and pinholes

NAD 30000 SF Fair Mod. F

95A 95B 95C 95D 94E

In hallways and rooms White

2x4 ceiling tile with small squiggly lines and pinholes

NAD 50000 SF Fair Mod. F

95A 95B 95C

In hallways and rooms White

Ceiling tile with long squiggly lines and varying size pinholes

NAD 20000 SF Fair Mod. F

96A 96B 96C 96D 96E

Patches in hallways Blue 12x12 blue tile with black mastic 6% Chrysotile -mastic 700 SF Good High. NF

97A 97B 97C 97D 97E 97F 97G

In hallways and rooms

Tan with white and beige streaks

12x12 tan floor tile with white and beige streaks. Yellow mastic

8% Chrysotile -mastic 60000 SF Good High NF

James A. Haley VA Medical Center

98A 98B 98C

7B-715

Blue with a multicolor ed pattern

Blue carpet with multicolored pattern with mastic and vapor barrier

NAD 300 SF Good Mod NF

99 99A Across from 7B- 704B Pink

12x12 pink tile with brown streaks and yellow with black mastic

3% Chrysotile – black mastic 500 SF Good High NF

100A 100B 100C

7th Floor – 7A Light green

12x12 light green tile with mastic NAD 2000 SF Good Mod NF

101A 101B 101C

On metal ducts above the ceiling

Gold on the outside, silver metallic on the inside

Gold mastic on metal ductwork

5% Chrysotile -mastic 3000 SF Good Low NF

102A 102B 102C 102D 102E 102F 102G

Hallways and rooms

White with blue gray streaks

White tile with blue-gray streaks and yellow mastic. Unclear ON what type of tile.

NAD 20000 SF Good Mod. NF

103A 103B 103C 103D 103E

Rooms Gray-blue 4-inch gray-blue baseboard with

NAD 5000 LF Fair Mod. NF

James A. Haley VA Medical Center

104A 104B 104C

In 7B-714 Faded green

4-inch faded green baseboard with yellow mastic

NAD 400 LF Good Mod. NF

105A 105B 105C 105D 105E

Stairwells Blue

Blue with black and white speckles stairwell covering with yellow mastic

NAD 5000 SF Good High NF

106A 106B 106C

In rooms - 7B-

White with blue and brown speckles

White tile with blue and brown speckles and yellow mastic and black mastic

NAD 1000 SF Good Mod NF

107A 107B 107C

In rooms - 7B- 703 Beige

Beige baseboard with yellow mastic NAD 500 LF Good Mod NF

108A 108B 108C

In rooms - 7A-

Beige with blue and red speckles

12x12 beige tile with blue and red speckles and yellow mastic

NAD 1000 SF Good Mod. NF

109A 109B 109C

In rooms - 7A- 717 Brown

4-inch brown baseboard with beige mastic NAD 400 LF Good Mod. NF

110A 110B 110C

In rooms - 7A- 717 Brown

4-inch brown baseboard with beige mastic (same as HSA

109)

NAD 400 LF Good Mod. NF

James A. Haley VA Medical Center

111A 111B 111C 111D 111E 111F 111G 111H 111I 111J 111K

Electric closets Beige Beige fire proofing in electric closets

NAD 7000 SF Good Mod. F

112A 112B 112C 112D 112E 112F 112G 112H 112I 112J 112K

Electric closets Gray Gray fire proofing in electric closets

NAD 7000 SF Good Mod. F

113A 113B 113C

On ducts above ceiling Gray Gray mastic on ducts NAD 5000 SF Good Low NF

114A 114B 114C

In hallways

Tan with white and brown streaks

9x9 tan floor tile with white and brown streaks and black mastic

3% Chrysotile – tile;

15% Chrysotile –

50000 SF Good High NF

James A. Haley VA Medical Center

115A 115B 115C 115D 115E

Above rooms – 7A Gray

Gray fire proofing above patient rooms

NAD 5000 SF Good Mod. F

116A 116B 116C 116D 116E

Hallways and rooms

Tan with large beige and gray streaks

12x12 tan floor tile with large beige and gray streaks

7% Chrysotile -mastic 20000 SF Good High NF

117A 117B 117C 117D 117E

Above rooms on 6th floor Pale green

Pale green fire proofing above rooms on 6th floor

NAD 5000 SF Good Mod. F

118 118A In 6B-616G Beige Beige mastic on ducts on 6th floor NAD 300 SF Good Low NF

119A 119B 119C

6B-616G and 6B- 616M Cream

Cream mastic on ducts and on attached to fire proofing at seams on 6th floor

NAD 400 SF Good Mod. NF

120A 120B 120C

Hallways – 6A White with gray speckles

12x12 white tile with gray speckles and black mastic

4% Chrysotile – black mastic 10000 SF Good High NF

121A 121B 121C

Hallways 6ht floor – 6B Purple Purple baseboard with beige mastic NAD 1000 LF Good Mod. NF

James A. Haley VA Medical Center

122A 122B 122C 122D 122E

In rooms Gray Gray door caulking NAD 3000 LF Good Low NF

123 123A By elevators 10 and 11 on 6th floor Blue Blue wallpaper with mastic NAD 500 SF Fair Low NF

124 124A By elevators 10 and 11 on 7th floor Cream Cream wallpaper with beige mastic NAD 500 SF Fair Low NF

125A 125B 125C

6th Floor Brown

Brown fire proofing in the middle of 6th floor

7% Chrysotile 2000 SF Good Mod. F

126A 126B 126C

Hallways and rooms White

2x2 ceiling tile with squiggly lines and pinholes

NAD 5000 SF Fair Mod. F

127A 127B 127C 127D 127E

6th Floor White

2x2 ceiling tile with long squiggly lines and pinholes

NAD 5000 SF Fair Mod. F

128A 128B 128C

6th Floor Gray Gray fire proofing NAD 25000 SF Good Mod. F

129A 129B 129C

6th Floor Silver Mastic on silver duct wrap with yellow insulation NAD 2000 SF Good Low NF

James A. Haley VA Medical Center

130A 130B 130C

6th Floor White

Paper wrap on pipe with mastic and yellow insulation

NAD 7000 LF Fair Mod. NF

131A 131B 131C

6th Floor Yellow

Yellow insulation on ducts with no wrap

NAD 4000 LF Good Mod. NF

132A 132B 132C

5B rooms Black Black sink undercoating NAD 2000 SF Good Low F

133 133A In 5B-524 Gray Gray sink undercoating NAD 2000 SF Good Low F

134A 134B 134C

5B hallways White White baseboard with beige mastic NAD 500 LF Good Mod. NF

135A 135B 135C

5B Hallways Cream Cream wallpaper with mastic and vapor barrier NAD 20000 SF Fair Mod. NF

135A 135B 135C

5B Above ceiling Silver Silver wrap with white mastic and white insulation

NAD 1000 LF Good Low NF

137A 137B 137C 137D 137E

Above ceiling in hallways and rooms White

Paper wrap with silver backing and yellow insulation

NAD 5000 LF Fair Mod. NF

James A. Haley VA Medical Center

138A 138B 138C 138D 138E 138F 138G

Above ceiling in hallways and rooms

Gray with green

Gray with green fire proofing NAD 10000 SF Good Mod. F

139A 139B 139C

5B Hallways White 2x2 white ceiling tile with dark specks

NAD 2000 SF Fair Mod. NF

140 140A Elevators 10 and 11 on 4th floor White

White caulking around elevator doors NAD 500 LF Fair Low NF

141A 141B 141C

4B Hallways and rooms

Pale light green

Pale light green baseboard with beige mastic NAD 500 LF Good Mod. NF

142A 142B 142C

In electrical closets Gray

Gray wall material in electric closets NAD 5000 SF Good Low F

143A 143B 143C

In 4B-417i Pink Pink insulation beneath black plastic covering NAD 700 LF Good Low NF

144A 144B 144C 144D 144E

Fire apparatus closets Black Black mastic on fire closet pipes 2% Chrysotile 400 SF Fair Low NF

145 145A 4A-448B Pale red Pale red fire proofing (caulking)

NAD 5000 SF Good Low NF

James A. Haley VA Medical Center

146A 146B 146C 146D

Hallways Cream Wallpaper in hallways NAD 20000 SF Good Low NF

147A 147B 147C

Hallways Tan

9x9 tan floor tile with brown streaks and black mastic

3% Chrysotile – tile;

10% Chrysotile – mastic 30000 SF Good High NF

148A 148B 148C

In 3 North Gray and purple

Wallpaper with gray and purple pattern in 3 North

NAD 5000 SF Good Low NF

149A 149B 149C

3rd Floor pipe room Silver Silver wrap with brown insulation NAD 700 LF Fair Mod. NF

150A 150B 150C

3rd Floor pipe room Gray

Gray tile with dark yellow mastic

3% Chrysotile -mastic 250 SF Fair High NF

151A 151B 151C

3rd Floor pipe room White Paper wrap with black insulation NAD 1000 LF Fair Mod. NF

152A 152B 152C

3rd Floor pipe room White Elbow wrap with black insulation NAD 800 SF Good Low F

153A 153B 153C

3rd Floor pipe room Gray

Hard packing material on blue pipe elbows NAD 500 SF Good Low F

154A 154B 154C

3rd Floor pipe room Blue

Blue paper wrap with black

NAD 1000 LF Fair Mod. NF

James A. Haley VA Medical Center

155A 155B 155C

3rd Floor pipe room Blue Blue wrap with black insulation NAD 1000 LF Fair Mod. F

156A 156B 156C

3rd Floor pipe room White

White paper wrap with yellow insulation NAD 1200 LF Fair Mod. NF

157A 157B 157C

3rd Floor pipe room White

Smooth white paper wrap with yellow insulation

NAD 800 LF Fair Mod. NF

158A 158B 158C

3rd Floor pipe room White

White paper wrap with yellow insulation on 1-inch pipe

NAD 300 LF Good Mod. NF

159A 159B 159C

3rd Floor pipe room White Cloth wrap with black insulation NAD 3000 SF Good Mod. F

160A 160B 160C

3rd Floor pipe room White Cloth wrap with yellow insulation NAD 500 LF Good Mod. NF

161A 161B 161C

3rd Floor pipe room Yellow

Smooth yellow wrap with yellow insulation NAD 800 LF Fair Mod. NF

162A 162B 162C

3rd Floor pipe room Silver Silver wrap with yellow insulation NAD 1000 LF Fair Mod. NF

163A 163B 163C 163D 163E

3rd Floor pipe room Gray Gray fireproofing NAD 5000 SF Good Mod. F

James A. Haley VA Medical Center

TABLE 4: ASBESTOS SAMPLING RESULTS

JAMES A. HALEY VA MEDICAL CENTER – TAMPA, FL

BUILDING 1 – GROUND, 2ND, AND 3RD FLOORS

HSA Sample ID Location Color Material Description Asbestos Content Quantity Cond. PFD Friable or NF

1A 1B 1C 1D 1E 1F 1G

Hallways and rooms Gray

4-inch gray baseboard with beige mastic with yellow tint

NAD 15000 LF Good High NF

2A 2B 2C 2D 2E

Hallways and rooms Tan

9x9 tile with brown streak and black mastic

4% Chrysotile - tile;

10% Chrysotile -mastic 50000 SF Good High NF

3A 3B 3C 3D 3E 3F 3G

Hallways and rooms White Drywall with joint compound 2% Chrysotile 45000 SF Good Mod. F

4A 4B 4C 4D 4E

In front of fire apparatus closets Red Red 9x9 tile with black mastic

3% Chrysotile - tile;

8% Chrysotile -

1000 SF Good Mod. NF

James A. Haley VA Medical Center

5A 5B 5C 5D 5E 5F 5G

Above the ceiling in hallways and rooms, and in fire closets

Red Red fire stop NAD 1200 SF Good Low NF

6A 6B 6C

In the auditorium on 2nd floor

Dark tan with black accents

Dark tan vinyl tile with black accent tiles, two layers of tile underneath, and yellow and black mastic

4% Chrysotile - black mastic 400 SF Good High NF

7A 7B 7C 7D 7E

In the auditorium on 2nd floor Black

Black decorative baseboard with beige mastic NAD 400 LF Good Low NF

8A 8B 8C

In hallways and rooms

Tan with white streaks

9x9 tan tile with white streaks, black mastic

4% Chrysotile - tile;

5% Chrysotile -mastic 40000 SF Good High NF

9A 9B 9C

In hallways and rooms

Cream with olive streaks

9x9 cream tile with olive streaks and black mastic

2% Chrysotile - tile;

8% Chrysotile -mastic 40000 SF Good High NF

10A 10B 10C

In hallway junctions

Black with white streaks

9x9 black tile with white streaks and black mastic

4% Chrysotile - tile;

6% Chrysotile -mastic 1500 SF Good High NF

11A 11B 11C

In hallways and rooms Gray

6-inch baseboard with yellow-beige mastic

NAD 2500 LF Good Mod. NF

James A. Haley VA Medical Center

12A 12B 12C

In hallways White with beige splatters

12x12 white tile with beige splatters and yellow mastic

2% Chrysotile – mastic 25000 SF Good High NF

13A 13B 13C

Patches in hallways

Blue with light blue speckles

12x12 blue tile with light blue speckles and black mastic

3% Chrysotile -mastic 500 SF Good High NF

14A 14B 14C

In fire closets Gray Gray plaster inside fire closets NAD 700 SF Good Mod. F

15A 15B 15C 15D 15E

In hallways and rooms

Cream with apricot streaks

12x12 cream tile with apricot streaks and yellow mastic

2% Chrysotile - tile;

4% Chrysotile -mastic Good High NF

16A 16B 16C 16D 16E

In hallways and rooms White

2x4 ceiling tile with squiggly holes and pinholes

NAD Fair Mod. F

17A 17B 17C 17D 17E

Above ceiling in hallways and rooms Silver

Round duct wrap with mastic and yellow insulation NAD 10000 LF Good Mod. NF

James A. Haley VA Medical Center

18A 18B 18C 18D 18E 18F 18G 18H 18I 18J

Above ceiling in hallways and rooms Gray Gray fire proofing 8% Chrysotile 80000 SF Good Mod. F

19A 19B 19C

Above ceiling in hallways and rooms White

Paper pipe wrap with silver backing and yellow insulation

NAD 10000 LF Fair Mod. NF

20A 20B 20C 20D

Above ceiling in hallways and rooms White Pipe elbow mastic NAD 3000 SF Fair Mod. NF

21A 21B 21C

Above ceiling in hallways and rooms Beige Beige duct joint filling mastic 6% Chrysotile 1000 SF Good Low NF

22A 22B 22C

In hallways and rooms Pink 12x12 pink tile with black mastic 15% Chrysotile – black mastic 3000 SF Good High NF

23A 23B 23C

By crosswalk to USF exit

Orange-tan with beige speckles

12x12 orange-tan tile with beige speckles and yellow mastic

10% Chrysotile – black mastic 500 SF Good High NF

24 24A By crosswalk to USF exit Yellow

12x12 yellow tile with yellow

NAD 50 SF Good Mod. NF

James A. Haley VA Medical Center

25A 25B 25C

In hallways and rooms

Dark green

4-inch dark green baseboard with yellow mastic

NAD 500 LF Good Mod. NF

26A 26B 26C 26D 26E 26F 26G

Above ceiling in hallways and rooms Silver

Silver wrap with mastic and yellow insulation square/rectangula r ducts

NAD 10000 LF Good Mod. NF

27A 27B 27C 27D

Above ceiling in hallways and rooms Gold Gold mastic on ductwork 4% Chrysotile 3000 SF Good Low NF

28A 28B 28C

In hallways and rooms Cream

Cream seamless floor with leveler and mastic NAD 500 SF Good High NF

29 29A Entrance to 2D- 219B hallway Gray

12x12 gray tile with yellow mastic on HSA8 NAD 150 SF Good High NF

30A 30B 30C

In hallways and rooms

Tan with brown streaks

9x9 tan tile with brown streaks.

Black mastic.

NAD 10000 SF Good High NF

31 31A In 2C-242A Wood pattern

Vinyl wood pattern with yellow mastic NAD 500 SF Good Mod. NF

32A 32B 32C

In fire closets Gray Gray hard mastic on black pipe joints

2% Chrysotile 500 SF Good Low NF

James A. Haley VA Medical Center

33A 33B 33C

In hallways and rooms

Tan with beige and gray splatters

12x12 tan tile with beige and gray splatters, gray mastic

6% Chrysotile – black mastic 2000 SF Good High NF

34 34A 2C-424 Beige

Beige vinyl floor tile with beige, blue, red dot pattern with beige mastic

NAD 300 SF Good Mod. NF

35 35A In stairwells Blue Blue vinyl stair covering NAD 3000 SF Good High NF

36 36A Cafeteria on 2nd floor Wood

Vinyl wood pattern flooring with gray mastic

NAD 300 SF Good High NF

37 37A By entrance to SICU hallway

Blue with orange and blue streak

12x12 blue tile with orange and blue streaks

8% Chrysotile – black mastic 4000 SF Good High NF

38A 38B 38C

Above ceiling in hallways and rooms Silver Silver wrap with pink insulation 8% Chrysotile – wrap 5000 LF Good Low NF

39A 39B 39C

Above ceiling in hallways and rooms

Gray with green

Gray with green fireproofing NAD 10000 SF Good Mod. F

40A 40B 40C

Hallways and rooms White

Ceiling tile with small and large pinholes NAD 80000 SF Fair Mod. F

41A 41B 41C

In hallways and rooms Cream Cream baseboard with beige mastic NAD 2000 LF Good Mod. NF

James A. Haley VA Medical Center

42A 42B 42C

In hallways Beige Wallpaper with gray mastic NAD 10000 SF Good Mod. NF

43A 43B 43C

In hallways Yellow Yellow mastic behind white wall panels

NAD 10000 SF Good Low NF

44A 44B 44C

Cafeteria on 2nd floor Black Black baseboard with beige mastic NAD 150 LF Good Mod. NF

45A 45B 45C

In hallways Beige Textured, beige wallpaper NAD 5000 SF Good Mod. NF

46 46A In 2B-225A Gray and white

20x20 vinyl gray and white tile.

Black mastic

NAD 400 SF Good High NF

47A 47B 47C

Library Beige and gray/blue

Beige and gray/ blue vinyl tile in library w/ beige mastic

NAD 400 SF Good Mod. NF

48A 48B 48C

Electrical closets Beige Beige fireproofing in electrical closets

NAD 10000 SF Good Mod. F

49A 49B 49C

Electrical closets Painted gray

Painted gray fireproofing in electrical closets NAD 10000 SF Good Mod. F

50A 50B 50C

Electrical closets White with gray speckles

12x12 white with gray speckles tile in electric closets

NAD 5000 SF Good Mod. NF

51A 51B 51C

Electrical closets and rooms and hallways Dark blue

Dark blue baseboard with

NAD 3000 LF Good Low NF

James A. Haley VA Medical Center

52A 52B 52C

Patient library Dark brown

Dark brown baseboard with beige mastic NAD 500 LF Good Mod NF

53A 53B 53C

2C-242 Light gray Light gray baseboard with beige mastic

NAD 400 LF Good Mod NF

54 54A In FDb-2A-237-1

Blue with red and orange speckles

Blue carpet with red and orange speckles. Green mastic.

NAD 300 SF Good Mod. NF

55A 55B 55C 55D 56E

Hallways Clear Clear mastic behind gray wall panels

NAD 1000 SF Good Low NF

56 56A Corner across from 2D-220 White White baseboard with clear mastic NAD 200 LF Good Mod. NF

57A 57B 57C

Chapel on 1st floor White White popcorn ceiling 5% Chrysotile 400 SF Good Low F

58A 58B 58C

Hallways by fire closets Red

12x12 red tile on top of beige tile with yellow and black mastics

4% Chrysotile – beige tile; 10% Chrysotile – mastic 700 SF Good Mod. NF

59A 59B 59C 59D

Hallways and rooms

White with gray and tan speckles

12x12 White tile with gray and tan speckles, yellow mastic

3% Chrysotile – tile;

10% Chrysotile – mastic 5000 SF Good High NF

60A 60B 60C

Hallways Pale orange

Pale orange baseboard with

NAD 600 LF Good Mod. NF

James A. Haley VA Medical Center

61A 61B 61C

Lab area White White sink undercoating NAD 300 SF Good Low NF

62A 62B 62C

Waiting lobby on 1st floor Light pink

12x12 light pink tile with orange and blue speckles on beige tile with yellow and black mastic

4% Chrysotile – beige tile; 8% Chrysotile – mastic 400 SF Good High NF

63A 63B 63C

By dental office suites Gray

12x12 gray tile with gray speckles, yellow and beige/black mastics

7% Chrysotile – black mastic 200 SF Fair Mod. NF

64 64A 64B In fire closets Soft yellow Soft yellow mastic on pipes NAD 100 SF Fair Low NF

65 65A 1st floor reception area

Gray with pearl speckles

Gray terrazzo flooring with pearl speckles and yellow mastic

NAD 500 SF Good High NF

66 66A Dining room on ground floor Black

Black baseboard in dining area on ground floor.

Beige mastic.

NAD 150 LF Fair Mod. NF

67A 67B 67C

In hallways Brown Brown baseboard with beige mastic NAD 700 LF Fair Mod. NF

68A 68B 68C

In mail room Beige with gray streaks

Beige tile with gray streaks in mail room.

Yellow mastic

NAD 300 SF Fair High NF

James A. Haley VA Medical Center

69A 69B 69C

ER Lobby Green Green tile on top of beige tile.

Yellow mastic.

3% Chrysotile – beige tile; 7% Chrysotile -mastic 500 SF Fair High NF

70A 70B 70C

Pool in the basement Brown Brown pool mastic covering 3% Chrysotile – mastic 1500 SF Fair Low NF

71A 71B 71C

SPD office

Beige with blue and pink splatters

12x12 beige tile with blue and pink splatters.

Yellow mastic.

NAD 400 SF Fair High NF

72A 72B 72C

Safety office Gray Gray vinyl panels on tile, yellow mastic

2% Chrysotile – beige tile; 7% Chrysotile -mastic 400 SF Good Mod. NF

73A 73B 73C

Fire closets Black

Hard black-brown mastic inside fire closets on walls

4% Chrysotile 300 SF Fair Low F

74A 74B 74C

Safety office Pink-beige Pink-beige baseboard with yellow mastic

NAD 250 LF Good Mod. NF

75A 75B 75C

First floor lab Light blue

Light blue fireproofing above lab area on first floor

NAD 1000 SF Good Mod. F

James A. Haley VA Medical Center

4.2 Asbestos Sampling Methods

The surveyor conducted a visual inspection of every safe and reasonably accessible room and space of the building and identified homogeneous areas based on the texture, appearance, and use of suspect ACM. Bulk samples of all friable and non-friable suspect ACM were collected, as well as a representative number of samples from each homogeneous area following the EPA's simplified random sampling method (EPA560/585-030a). Good Industrial Hygiene practices were followed when collecting bulk samples in order to minimize fiber release. Every precaution was taken to prevent asbestos exposure to the surveyor, the building occupants, and the public.

All sample locations were logged with an appropriate description and the locations were marked on any available drawings. A unique sequential numbering system was used to identify each area. Each bulk sample was placed in a labeled bag, which was immediately marked with its sample number. A chain of custody form was submitted with each sample group for analysis and signed by the receiving laboratory personnel who handled the samples. The samples were analyzed by EMSL Analytical, a National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory, for asbestos content.

4.3 Regulatory Requirements

Demolition: According to NESHAP, 40CFR61 Subpart M, demolition is defined as the wrecking or taking out of any load-supporting structural member of a facility together with any related handling operations or the intentional burning of any facility.

The final NESHAP Rule provides classification for regulated asbestos containing material as follows:

• Friable asbestos material;

• Category I non-friable ACM that has become friable;

• Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading; or

• Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by forces expected to act upon the material in the course of demolition or renovation operations.

If the total asbestos content is determined to be trace to 10%, the owner must either assume that the material contains greater than 1% asbestos and treat the material as regulated asbestos-containing material (RACM) or have the material verified/quantified by point counting. If after point counting, the material is quantified as 1% or less, it is not regulated by the NESHAP.

The Occupational Safety and Health Administration (OSHA) considers material that contains any amount of asbestos as asbestos-containing and requires compliance with OSHA regulations. The demolition of a structure with materials present that contain any amount of asbestos is considered by OSHA as an asbestos

James A. Haley VA Medical Center abatement, and all applicable OSHA rules must be complied with during the demolition.

Notification: Notification is required to the local regulatory agency:

1. Ten (10) working days prior to a demolition.

2. Ten (10) working days prior to a renovation operation, if the amount of asbestos material removed or impacted is greater than 160 SF on all building components (i.e. floor tile, mastic, GWBS, etc.) or 260 LF on pipes.

3. One (1) day prior to demolition, if the building has been condemned and is structurally unsound as determined by the appropriate agency.

Notification must be sent by certified mail with return receipt or hand delivered to the Georgia Environmental Protection Division. The demolition contractor must wait ten (10) working days (Monday – Friday) from the postmarked date of mailing or the date of hand delivery to commencement of demolition. Any change to the start date of the demolition requires notification to the agency by phone, followed by a written revision to the Notification Form.

4.4 Statutory Requirements

The regulatory agency responsible for the oversight of the rules pertaining to asbestos-containing building materials (ACBM) is the Environmental Protection Agency (EPA). The regulations state that prior to demolition or renovation, a facility survey must be conducted in accordance to section 40 CFR 61-M National Emission Standards for Hazardous Air Pollutants; Asbestos NESHAP Revisions, Final Rule.

Enforcement of these rules was passed on to the states. In the State of Georgia they are enforced by the Environmental Protection Division. Some counties have developed an enforcement division to carry out the responsibilities and have developed environmental and asbestos ordinances with which compliance is required.

5.0 OBSERVATIONS

• Loose fireproofing observed on top of most ceiling tiles and HVAC ducts on all floors.

James A. Haley VA Medical Center

6.0 LIMITATIONS

The materials sampled in this survey were subject to accessibility. This survey is limited to the Building 1 only located at the James A. Haley VA Medical Center in Tampa, Florida.

OHC warrants that the investigations and methodology reflect the prevailing standard of work practices in the environmental consulting field. If it is expected that materials outside the scope of this survey are to be disturbed, they must be presumed ACM until the materials can be analyzed by an accredited asbestos building inspector.

• Elevator shafts were not sampled due to confined space restrictions

• AC units were active during the time of the survey, therefore, any insulation within in these units was not sampled.

• Tile of different colors in the middle of hallways were not sampled due to trip hazards as per discussion with James Watson, CIH, in the Safety Department of the James A. Haley VAMC.

• Some confined areas were not accessible above the ceiling due to size restrictions of the mobile containment unit.

• Time limitations were encountered when checking areas where patients were constantly present.

• Some materials, including terrazzo flooring on the 1st floor and white panels on walls, could not be sampled without significantly damaging these materials. The materials were sampled where already damaged or broken.

7.0 DOCUMENT CONTENT

This document has been prepared for the exclusive use by Biosphere International and the Veterans Health Administration. The knowledge of the consultant is based upon current information and research. If local knowledge indicates error, omissions, or inaccuracy, please notify the consultant.

James A. Haley VA Medical Center

APPENDIX A:

PHOTOGRAPHS

BASEMENT, FLOORS 3-7,

AND PENTHOUSE

James A. Haley VA Medical Center

[HSA-1] No Asbestos Detected Cloth wrap and pink insulation between large round ducts

[HSA-2] No Asbestos Detected Pink wrap with black insulation and mastic

James A. Haley VA Medical Center

[HSA-3] No Asbestos Detected Blue wrap with black insulation and mastic

[HSA-4] No Asbestos Detected Mastic on pipe ends and junctions

James A. Haley VA Medical Center

[HSA-5] No Asbestos Detected Yellow wrap with yellow insulation on pipes

[HSA-6] No Asbestos Detected Black gaskets on valves

James A. Haley VA Medical Center

[HSA-7] No Asbestos Detected Gray fire proofing

[HSA-8] No Asbestos Detected Gray Mastic on HVAC unit doors

James A. Haley VA Medical Center

[HSA-9] No Asbestos Detected White wrap and insulation on large rectangular HVAC ducts

[HSA-10] 15% Chrysotile - mastic White wrap on pipes and insulation with mastic

James A. Haley VA Medical Center

[HSA-11] No Asbestos Detected Silver wrap with yellow insulation.

[HSA-12] No Asbestos Detected Black foam insulation on pipes

James A. Haley VA Medical Center

[HSA-13] No Asbestos Detected Yellow paper wrap with yellow insulation.

[HSA-14] No Asbestos Detected Gray mastic on metal ducts

James A. Haley VA Medical Center

[HSA-15] No Asbestos Detected Hard packing material on pipe elbows

[HSA-16] No Asbestos Detected White mastic on metal ducts.

James A. Haley VA Medical Center

[HSA-17] No Asbestos Detected Brown and silver pipe joint mastic

[HSA-18] No Asbestos Detected White mastic between HVAC unit metal seams

James A. Haley VA Medical Center

[HSA-19] No Asbestos Detected Gray Wrap with silver and white wrap backing and…

This is the start of the file's text. The full file is on GovTribe.