This is a summary of a federal contract solicitation and related asbestos and lead survey report. The solicitation number is 36C24823R0199 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8 for project Y1DA--FY23: NRM-Tier 1 (PROJ: 673-21-148) BB - Renovate Bldg 1 - 5 South to Private Patient Rooms. The opportunity type is a solicitation. The 15MB PDF file is an asbestos and lead survey report for the 5th floor of a building undergoing renovation from semi-private to private patient rooms. Response is due by October 5, 2023. The solicitation involves renovations that require an asbestos and lead survey of the affected areas to ensure worker and patient safety during the project.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos NESHAP & Lead Survey
Performed at:
James A. Haley VA Hospital
Building 1 - 5th Floor
13000 Bruce B. Downs Blvd.
Tampa, FL 33612
Report Prepared For:
AESUS
1050 E. Southern Ave, Suite D
Tempe, AR 85282
Report Prepared By:
OHC Environmental Engineering, Inc.
101 South Hoover Blvd, Suite 101
Tampa, Florida 33609
OHC Project #220097-AS
June 10th, 2022
Building 1 5th Floor South Wing
Limited Asbestos & Lead Survey
OHC Project No. 220097-AS
PROJECT INFORMATION
OHC PROJECT #: 220097-AS
CLIENT NAME: Veterans’ Health Administration
CLIENT CONTACT: Mr. Orlando Gonzalez
PROJECT LOCATION: Building 1 - 5th Floor
13000 Bruce B. Downs Blvd.
Tampa, FL 33612
SERVICES: Asbestos & Lead Survey
DATE OF SURVEY: May 24th-26th 2022
OHC SURVEYOR: Nick Foster
REPORT REVIEWED BY:
Cristina Jones, CPH, MPH
OHC Operations Manager
LICENSED CONSULTANT:
James F. Rizk, CIH
FLAC #ZA0000060
TABLE OF CONTENTS
1.0 INTRODUCTION
2.0 BUILDING DESCRIPTION
3.0 EXECUTIVE SUMMARY
3.1 Asbestos Survey Results
3.2 Lead Survey Results
4.0 ASBESTOS SURVEY
4.1 Asbestos Survey Results
4.2 Asbestos Sampling Methods
4.3 Regulatory Requirements
4.4 Statutory Requirements
5.0 LEAD SURVEY
5.1 Lead Survey Results
5.2 Lead Sampling Methods
5.3 Standards for Lead-Containing Paint
6.0 OTHER OBSERVATIONS
7.0 CONCLUSIONS & RECOMMENDATIONS
8.0 LIMITATIONS
9.0 DOCUMENT CONTENT
APPENDIX A: Asbestos & Lead Sampling Locations
APPENDIX B: Photographs of Materials Sampled for Asbestos
APPENDIX C: Photographs of Materials Sampled for Lead
APPENDIX D: Asbestos Laboratory Analytical Results
APPENDIX E: Lead Laboratory Analytical Results
APPENDIX F: Consultant & Laboratory Credentials
1.0 INTRODUCTION
OHC Environmental Engineering, Inc., (OHC), was contracted by Mr. Orlando Gonzales of AESUS to perform an asbestos survey in compliance with the National Emission
Standard for Hazardous Air Pollutants (NESHAP) regulation for asbestos (40 CFR 61
Subpart M). In addition, a survey for lead-containing paint (LCP) was performed in the areas to be disturbed. The surveys were conducted for the upcoming renovations of the 5th
Floor of the James A. Haley Veterans Hospital Building 1. Representatives from OHC and certified AHERA building inspectors, Nick Foster, and Tom Martinelli, visited the site on
May 24th to the 26th of 2022, to perform these services.
2.0 BUILDING DESCRIPTION
The 5th Floor of the James A. Haley Building 1 that was within the scope of this survey is comprised of patient rooms, a nursing station and offices, GI area, and break rooms that make up approximately a 9,943 SF area. The survey was limited to the Acute Care 5 South wing. The building is estimated to have been built in the 1970’s. The building is constructed on concrete slab at grade. Interior walls are drywall on metal studs. Floors are covered with vinyl floor tiles. Ceilings are a suspended tile system. This survey was conducted to verify conclusions in a previous asbestos survey performed by OHC in May of 2018 (OHC Project
#170161-AS).
TABLE 1: 2022 ASBESTOS SURVEY RESULTS
JAMES A. HALEY VAMC – BUILDING 1-5th Floor Acute Wing South
HSA
Sample
ID
Sample
Location
Material
Description
Approx.
Quantity Result Category
4 097-4A
Wall Cavity
Behind Access
Panel in HVAC
Room in 5A-516
Loose Brown
Fireproofing <1 SF 15% Chrysotile Friable
11 097-11C 5 South Entry
Door
White Interior Door
Caulking 50 LF <1% Chrysotile NF/I
14 097-14A Fire closet
5A-525C
Black Mastic on
Walls 5 SF 2% Chrysotile NF/II
097-15A Day Room
5A-507 White VCT with
Blue Streaks and
Black/Beige Mastic
9,943 SF
<1%-3%
Chrysotile
NF/I
097-15B Storage Room
5A-519
097-16A 5A-507
GWBS 14,000 SF 2% Chrysotile NF/II 097-16B 5A-516
097-16C Hallway East of
Nurses Station
Follow up inspection:
TABLE 1-Cont.: MATERIALS SAMPLED FOR ASBESTOS
HSA
Sample
ID
Sample Location
Material
Description Result
Category
097-20A
Room 5A-516 Behind
Wall Panel (H.A.C.
Room) Loose Brown
Fireproofing within Wall
Cavities and on Top of
Lockers
Loose Fireproofing:
3% - 8% Chrysotile
Assume there is loose fireproofing in all drywall cavities.
Friable
Class I 097-20B
Room 5A-525B
(Electrical Room)
097-20C Room 5A-521a
(Restroom)
097-20D Room 5A-512 (Electrical
Room)
097-20E Room 5A-513 (Staff
Room)
PACM PACM Restrooms in 5 South Black Mirror
Mastic
PACM
NF/II
PACM PACM Fire Dampers Mastic PACM N/F/II
3.0 EXECUTIVE SUMMARY
3.1 Asbestos Survey Results
Based on the results of the Polarized Light Microscopy (PLM) laboratory analysis, asbestos-containing materials (ACM) are present, as indicated in Table 1 and 2.
TABLE 2: ASBESTOS CONTAINING MATERIALS
HSA Sample ID Material Description Material
Locations
Estimated
Quantity
(5th Floor
South)
Lab Result
NESHAP
Cat.
OSHA Class
May
#82
May
#16
82F, 82G, 16A, 16B, 16C
Drywall Joint
Compound
Throughout 5th
Floor 14,000 SF 2% Chrysotile NF-I, Class I
May
#97
97F, 97G Yellow/Black Mastic
Under Floor Tile
Throughout 5th
Floor 9,943 SF 8% Chrysotile NF-I, Class I
May
#101
101B Gold Mastic on Duct
Ducts Above
Suspended
Ceilings
450 LF 5% Chrysotile NF-I, Class I
May
#144
May
#14
144D, 14A Black Mastic on Walls and Pipes
Fire Closet 5A-
525c 5 SF 2% Chrysotile NF-I, Class I
May
#4
4A Loose Brown
Fireproofing
Behind Wall
Cavity in H.A.C.
Room 5A-516
< 1 SF
15%
Chrysotile
RACM
May
#11
11C White Interior
Caulking
5th Floor South
Wing Entry
Doors
50 LF
< 1%
Chrysotile NF-I, Class I
May
#15
15A, 15B
White VCT with Blue
Streaks and Black
Mastic
Throughout 5th
Floor 9,943 SF 3% Chrysotile NF-I, Class I
3.2 Lead Survey Results
Based on the laboratory analysis of paint chip samples, lead does exist within the scope of this survey, as indicated in table 1 below.
TABLE 3: LEAD CONTAINING MATERIALS
Sample ID Material
Locations Material Description
Total
Quantities Result Category
097-Pb1
Doorway to Day
Room 5A-530
Brown Paint on Metal
Door Frame
Every
Doorway in
Hall
0.55% wt LBP
097-Pb4
Lockers in
Hallway (Linen
Storage)
Brown Paint on Metal
Lockers
43 Lockers <0.013% wt LCP
097-Pb7
Room 519
Light Blue Glazing on
Bathroom Wall Tiles
50 SF 0.510% wt LBP
097-Pb9
Wall Panels in IT and Cable Closets
Gray Paint on Wooden
Panels 50 SF 0.30% wt LCP
4.0 ASBESTOS SURVEY
Based on the laboratory analysis of the samples collected, ACM does exist within the scope of this survey.
4.1 Asbestos Survey Results
The Environmental Protection Agency defines asbestos-containing material
(ACM) as any material or product that contains more than one percent (1%) asbestos. Table 4 below summarizes the samples of suspect ACM collected from the site. The table describes the homogenous sampling area (HSA), sample ID, sample location, material description, quantity, condition, friability, and the laboratory analytical result. Please refer to the Appendices at the end of this report for photographs of the materials sampled and official laboratory analytical results.
LEGEND:
▪ NAD = No Asbestos Detected
▪ ### = the material contains asbestos and requires compliance with NESHAP and OSHA
▪ * = Quality Control sample to ensure the reliability of laboratory analytical procedures
TABLE 4: MATERIALS SAMPLED FOR ASBESTOS
HSA Sample ID Sample Location Material
Description
Quantity, Condition, Friability
Results
097-1A Above Ceiling in Room 5A-
507 Day Room
Green
Fireproofing
10,000 SF
Good
Yes
NAD
097-1B Ceiling of H.A.C. Room 5A-
097-1C Hallway Outside of Room
5A-505
097-2A Wall Cavity Behind Access
Panel in Bathroom 5A-521a
Plaster on Walls
800 SF
Good
No
NAD
097-2B Wall Cavity Behind Access
Panel in H.A.C. Room 5A-
097-2C Interior Wall Plaster Inside
Room 5A-516
097-3A Wall Cavity Behind Access
Panel in Bathroom 5A-521a White Mastic on
Copper Pipe
10 LF
Fair
No
NAD
097-4A* Wall Cavity Behind Access
Panel in H.A.C. Room 5A-
Loose Brown
Fireproofing
< 1SF
Poor
Yes
15%
Chrysotile
097-5A Floor of H.A.C. Room 5A-
1x1 Blue Green
Floor Tile
50 SF
Good
No
NAD
097-6A Walls of H.A.C. Room 5A-
Light Gray Wall
Tile, Gray Grout, Tan Mastic
50 SF
Good
No
NAD
097-7A
Walls of H.A.C. Room 5A-
516 Pink Wall Tile
50 SF
Good
No
NAD
097-8A Walls of H.A.C. Room 5A-
Texture on Walls
200 SF
Good
No
NAD
097-8B Walls of H.A.C. Room 5A-
097-8C Walls of H.A.C. Room 5A-
097-9A
Floor of Bathroom 5A-521a
Floor Tile with
Gray Grout
250 SF
Good
No
NAD
097-10A By Sink in Day Room 5A-507 White Wall Tile, White Grout, White Mastic
30 SF
Good
No
NAD
097-11A Day Room Door 5A-507
White Interior
Door Caulking
100 LF
Good
No
< 1%
Chrysotile 097-11B Day Room Sink 5A-507
097-11C 5 South Wing Entry Doors
097-12A Bathroom 5A-527 Tan Speckled
Floor Coating
100 SF
Good
No
NAD
097-13A Bathroom 5A-527 Cream Colored
Rectangular Wall
Tiles
200 SF
Good
No
NAD
097-14A Fire Closet 5A-525c Black Mastic on
Walls
5 SF
Good
No
2% Chrysotile
097-15A* Day Room Floor 5A-507 White VCT with
Blue Streaks and
Black/Beige
Mastic
1000 SF
Good
No
<1% - 3%
Chrysotile
097-15B Storage Room 5A-519 Floor
097-15C Hallway East of Nurses
Station
097-16A By Door to Day Room 5A-
GWBS
10,000 SF
Good
No
2% Chrysotile 097-16B By Door to Room 5A-516
097-16C Hallway East of Nurses
Station
097-17A Locker Outside Room 5A-529 Paneling Inside
Locker Doors
43 Lockers
Good
No
NAD 097-17B Locker Outside Room 526
097-17C Locker Outside Room 520
097-18A Bathroom 5A-521a Pink Wall Tile, White Grout, Gray
Mastic
250 SF
Good
No
NAD
097-19A Above Ceiling in Hallway
Outside of 5A-525c Gray Fireproofing
10,000 SF
Good
Yes
NAD
097-19B Above Ceiling Outside
Bathroom in Room 5A-519
4.2 Asbestos Sampling Methods
Asbestos sampling was conducted in accordance with NESHAP (40 CFR 61, Subpart
M) protocol for the commencement of demolition/renovation activities. The surveyor conducted a visual inspection of every safe and reasonably accessible room and space of the building. Materials sampled were grouped into Homogenous Sampling Areas
(HSA) based on the texture, color, use, age, condition, and every other visual appearance to identify suspect ACM. Materials containing asbestos are grouped into the following categories:
• Regulated ACM (RACM): Refers to friable manufactured ACM or a
Category I non-friable ACM that has become friable; or a Category I Non-
Friable ACM that will be or has been subjected to sanding, grinding, cutting or abrading; or a Category II Non-Friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations.
• Category I Non-Friable ACM: Refers to asbestos containing packing, gaskets, resilient floor coverings (including mastics), and asphalt roofing products containing more than 1% asbestos.
• Category II Non-Friable ACM: Refers to any material that is not a
Category I Non-Friable ACM that contains greater than 1% asbestos.
Bulk samples of all friable and non-friable suspect ACM were collected, as well as a representative number of samples from each homogeneous area following the EPA's simplified random sampling method (EPA560/585-030a). Good Industrial Hygiene practices were followed when collecting bulk samples to minimize fiber release.
Every precaution was taken to prevent asbestos exposure to the surveyor, the building occupants, and the public. All sample locations were logged with an appropriate description and the locations were marked on any available drawings. A unique sequential numbering system was used to identify each area. Each bulk sample was placed in a labeled bag, which was immediately marked with its sample number. Strict
Chain-of-Custody protocols were followed and signed by the receiving laboratory personnel who handled the samples. The samples were analyzed via PLM EPA-600 by an AIHA and NVLAP Accredited laboratory. Quality control samples were analyzed by EMSL Analytical in Tampa, Florida for Quality Control procedures during the analysis of asbestos content. The purpose is to monitor the performance of the laboratories where samples are being analyzed to provide competence and reliability assurance.
4.3 Regulatory Requirements
Demolition: According to NESHAP, 40CFR61 Subpart M, demolition is defined as the wrecking or taking out of any load-supporting structural member of a facility together with any related handling operations or the intentional burning of any facility.
The final NESHAP Rule provides classification for regulated asbestos containing material as follows:
• Friable asbestos material;
• Category I non-friable ACM that has become friable;
• Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading; or
• Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by forces expected to act upon the material during demolition or renovation operations.
If the total asbestos content is determined to be trace to 10%, the owner must either assume that the material contains greater than 1% asbestos and treat the material as regulated asbestos-containing material (RACM) or have the material verified/quantified by point counting. If after point counting, the material is quantified as 1% or less, it is not regulated by the NESHAP. The Occupational
Safety and Health Administration (OSHA) considers material that contains any amount of asbestos as asbestos-containing and requires compliance with OSHA regulations. The demolition of a structure with materials present that contain any amount of asbestos is considered by OSHA as an asbestos abatement, and all applicable OSHA rules must be complied with during the demolition.
Notification: Notification is required to the local regulatory agency:
1. Ten (10) working days prior to a demolition.
2. Ten (10) working days prior to a renovation operation, if the amount of asbestos material removed or impacted is greater than 160 SF on all building components (i.e. floor tile, mastic, GWBS, etc.) or 260 LF on pipes.
3. One (1) day prior to demolition if the building has been condemned and is structurally unsound as determined by the appropriate agency.
Notification must be sent by certified mail with return receipt or hand delivered to the Florida Department of Environmental Protection. The demolition contractor must wait ten (10) working days (Monday – Friday) from the postmarked date of mailing or the date of hand delivery to commencement of demolition. Any change to the start date of the demolition requires notification to the agency by phone, followed by a written revision to the Notification Form.
4.4 Statutory Requirements
The regulatory agency responsible for the oversight of the rules pertaining to asbestos-containing building materials (ACBM) is the Environmental Protection Agency
(EPA). The regulations state that prior to demolition or renovation a facility survey must be conducted in accordance with section 40 CFR 61-M National Emission
Standards for Hazardous Air Pollutants; Asbestos NESHAP Revisions, Final Rule.
Enforcement of these rules was passed on to the states. In the State of Florida, they are enforced by the Department of Environmental Protection (DEP). Some counties have developed an enforcement division to carry out the responsibilities of the DEP and have developed environmental and asbestos ordinances with which compliance is required.
5.0 LEAD SURVEY
Based on the laboratory analysis of paint chip samples, lead does exist in the areas to be disturbed.
5.1 Lead Survey Results
Table 5 below summarizes the materials tested for lead and includes their color, substrate, description and location, and lead content. Please refer to the Appendices at the end of this report for photographs of the materials sampled and official laboratory analytical results.
LEGEND:
▪ ### = the sample that contains Lead at levels that will require compliance with
EPA and OSHA.
▪ NLD = No Lead Detected (< reporting limit)
▪ BLC = Below Levels of Concern (0.009% wt and below)
▪ LCP = Lead-Containing Paint (0.01-0.49% wt)
▪ LBP = Lead-Based Paint (0.50% wt and above)
TABLE 5: MATERIALS SAMPLED FOR LEAD
Sample ID Sample Location Material Description Quantity Lab Result Category
097-Pb1 Doorway to Day
Room 5A-530
Brown Paint on
Metal Door Frame
Every Door
Frame in Hall 0.55% wt LBP
097-Pb2 Inside Day
Room 5A-530
Beige Paint on
Drywall
Throughout
5th Floor <0.0087% wt NLD
097-Pb3 Inside Day
Room 5A-530
Blue Paint on
Drywall
300 SF
<0.0090% wt NLD
097-Pb4 Lockers in
Hallways (Linen
Storage)
Brown Paint on
Metal Lockers
43 Lockers
<0.013% wt LCP
097-Pb5 Room 519 Old
Patient Room
Converted to
Storage
White Paint on
Drywall
500 SF
<0.0084% wt NLD
097-Pb6 Room 519 Old
Patient Room
Converted to
Storage
Green Paint on
Drywall
400 SF
<0.0090% wt NLD
097-Pb7 Room 519 Old
Patient Room
Converted to
Storage
Light Blue Glazing on Bathroom Wall
Tile
50 SF
0.510% wt LBP
097-Pb8 Patient Shower
Room
Dark Gray Paint on
Bathroom Wall and
Floor Tile in
Showers
50 SF
<0.0080% wt NLD
097-Pb9 Wall Panels in
IT and Cable
Closet
Gray Paint on
Wooden Panels
50 SF
0.30% wt LCP
097-Pb10 Pink Paint on walls in room
5A-529
Pink Paint on Dry wall
1500 SF
<0.0084% wt NLD
097-Pb11 Nurse Managers
Office
Light Blue Glazing on Bathroom Wall
Light Blue Paint on
Drywall
500 SF
<0.0099% wt NLD
097-Pb12 Patient
Restroom 5A-
527 Floor
Coating
Speckled Flooring with Coating
100 SF
<0.0080% wt NLD
097-Pb13 Patient
Restroom 5A-
521a Wall Tile
Pink Wall Tiles 200 SF
<0.005% wt NLD
097-Pb14 Bathroom 5A-
521a Floor
2x2 White Floor
Tile (Painted Gray)
250 SF
<0.005% wt NLD
097-Pb15 Day Room 5A-
4x4 White Wall Tile 30 SF <0.005% wt NLD
5.2 Lead Sampling Methods
All samples were collected by a trained Lead-Containing Paint inspector, placed in a sterile bag, and appropriately labeled. Strict Chain-of-Custody protocols were followed and signed by the receiving laboratory personnel who handled the samples.
All samples were analyzed via Flame Atomic Absorption Spectroscopy (FAAS) by
EMSL Analytical in Pineville, NC. The ceramic tile samples were analyzed via X-ray fluorescence by EMSL Analytical in Cinnaminson, NJ.
5.3 Standards for Lead-Containing Paint
There is presently no standard on the level of lead in paint other than the HUD guidelines of 0.5% by weight or 1.0 mg/cm2, which is used as a threshold for remedial action. OSHA, on the other hand, does not recognize these criteria. The consumer product safety commission has established a level of 0.06% as a threshold for lead-free paint. Any levels of lead in paint are considered lead-containing paint
(LCP). OSHA’s standards for lead are based on the potential for human exposure by means of inhalation and ingestion. Therefore, any substrate with any level of
LCP could cause health concerns when the paint is disturbed. Performing activities could create airborne exposures of lead above the PEL. Any persons performing any lead activities such as LCP renovation, repair, painting, or maintenance that may disturb the paint must be certified by EPA to perform these activities in accordance with the Renovation, Repair, and Painting (RRP) rule 40 CFR 745
Subpart E.
6.0 OBSERVATIONS
• Observation holes were cut through the drywall walls on the north, east and west sides of sixth west floor to expose the exterior perimeter walls. No suspect materials were observed from the observation hole areas.
• Asbestos containing fireproofing was removed from the ceiling deck and building systems from above the suspended ceiling system several years ago. Certain small areas were reportedly inaccessible and could not be removed (i.e., in between ductwork and ceiling, certain inaccessible beam areas, etc.) After the abatement, non-asbestos pale green containing fireproofing was re-applied to these areas. Therefore, if these inaccessible areas exist in the Fifth-floor South area, they were not visible at the time of the survey.
• No fireproofing was observed and sampled from the pipe chase access doors in the patient rooms. Fireproofing can be located there resulting from the previous abatement and re-spray application process allowing fireproofing to possibly get in between the walls of various rooms. It is not known if this fireproofing exists within the inaccessible walls of other rooms on the 5th floor South other than the small sample found in H.A.C. Room 5A-
516.
• All pipe insulation was observed to be non-suspect fiberglass or foam glass insulation with non-asbestos containing white mastic applied to some of the joints and fittings.
• All mastic under the vinyl floor tile on the sixth floor should be considered to contains asbestos, according to the May 2018 survey results.
• No electrical wiring sampled as all electricity was live at the time of sampling. Visible wiring insulation appeared to be non-suspect plastic or rubber.
7.0 CONCLUSIONS
Based on the results of the PLM analysis from the May 2108 survey and the most recent sampling event, ACM is present within the 5th Floor South wing of Building 1. The materials identified are listed in Tables 1 & 2. These materials will require removal by a licensed asbestos contractor under full containment, with oversight and monitoring by
OHC’s Industrial Hygienist. An abatement plan/specification for removal is recommended.
8.0 LIMITATIONS
The materials sampled in this survey were subject to accessibility and issues listed in
Section 6.0. This survey is limited to the Building 1 - 5th Floor South wing at 13000 Bruce
B. Downs Blvd in Tampa, Florida. OHC warrants that the investigations and methodology reflect the prevailing standard of work practices in the environmental consulting field. If it is expected that materials outside the scope of this survey are to be disturbed, they must be presumed ACM until the materials can be analyzed by an accredited asbestos building inspector.
9.0 DOCUMENT CONTENT
This document has been prepared for exclusive use by Ms. Kara Sikorski Chaput and the
James A. Haley Veterans Hospital. The knowledge of the consultant is based upon current information and research. If local knowledge indicates error, omissions, or inaccuracy, please notify the consultant.
APPENDIX A
ASBESTOS & LEAD
SAMPLING LOCATIONS
APPENDIX B
PHOTOGRAPHS OF MATERIALS
SAMPLED FOR ASBESTOS
1 Room 5A-507 Day Room Green Fireproofing [NAD]
2 Bathroom 5A-521a White Plaster on Walls [NAD]
3 Bathroom 5A-521a White Mastic on Copper Pipe [NAD]
4 Wall Cavity Behind Access Panel in H.A.C. Room 5A-516 Loose Brown Fireproofing [15% Chrysotile]
5 Floor of H.A.C. Room 5A-516 Blue and Green Floor Tile [NAD]
6 Walls of H.A.C. Room 5A-516 Light Gray Wall Tile, Gray Grout, and Beige Mastic [NAD]
7 Walls of H.A.C. Room 5A-516 Wall Tile [NAD]
8 Walls of H.A.C. Room 5A-516 Texture on Walls [NAD]
9 Floor of Bathroom 5A-521a Painted Floor Tile with Gray Grout [NAD]
10 Day Room 5A-507 by Sink White Wall Tile, White Grout, and White Mastic [NAD]
11 Day Room Door 5A-507 White Interior Caulking [Sample 097-11C <1% Chrysotile]
12 Bathroom 5A-527 Tank Speckled Floor Coating [NAD]
13 Bathroom 5A-527 Cream Colored Rectangular Wall Tile [NAD]
14 Fire Closet 5A-525c Black Mastic on Walls [2% Chrysotile]
15 Day Room Floor 5A-507 White VCT with Blue Streaks and Black/Tan Mastic [3% Chrysotile - Black Mastic]
16 Day Room 5A-507 by Door GWBS [2% Chrysotile - Joint Compound]
17 Locker Outside Room 5A-529 Interior Paneling [NAD]
18 Bathroom 5A-521a Pink Wall Tile, White Grout, Gray Mastic [NAD]
19 Above Ceiling in Hallway Outside of 5A-525c Gray Fireproofing [NAD]
APPENDIX C
PHOTOGRAPHS OF MATERIALS
SAMPLED FOR LEAD
20 Doorway to Day Room 5A-530 Brown Paint on Metal Door Frame [0.55% wt LBP]
21 Inside Day Room 5A-530 Beige Paint on Drywall [<0.0087% wt NLD]
22 Inside Day Room 5A-530 Blue Paint on Drywall [<0.0090% wt NLD]
23 Lockers in Hallways (Linen Storage) Brown Paint on Metal Lockers [<0.13% wt LCP]
24 Room 519 Old Patient Room Converted to Storage White Paint on Drywall [<0.0084% wt NLD]
25 Room 519 Old Patient Room Converted to Storage Green Paint on Drywall [<0.0090% NLD]
26 Room 519 Old Patient Room Converted to Storage Light Blue Glazing on Tile [0.51% wt LBP]
27 Patient Shower Room Dark Gray Paint on Bathroom Wall and Floor Tile [<0.0080% wt NLD]
28 Wall Panels in IT and Cable Closets Gray Paint on Wooden Panels [0.30% wt LCP]
29 Room 5A-529 Pink Paint on Drywall [<0.0084% NLD]
30 Nurse Managers Office Light Blue Paint Drywall [<0.0099% wt NLD]
31 Patient Restroom 5A-527 Floor Coating Speckled Floor [<0.0080% wt NLD]
32 Patient Restroom 5A-521a Wall Tile Pink Glazing [<0.005% wt NLD]
33 Bathroom 5A-521a White Floor Tile Painted Gray [<0.005%wt NLD]
34 Day Room 5A-507 White Wall Tile Glazing [<0.005%wt NLD]
APPENDIX D
ASBESTOS LABORATORY
ANALYTICAL RESULTS
APPENDIX E
LEAD LABORATORY
ANALYTICAL RESULTS
APPENDIX F
CONSULTANT & LABORATORY
CREDENTIALS
----- END OF REPORT -----