Attachment 0004- RFI List 2- 679-19-101 with VA responses.pdf
PDF 1 MB Posted
- Attached to
- 679-19-101 Correct Critical Access and ADA Deficiencies B61 Federal contract opportunity
- Solicitation number
- 36C24726R0069
About this file
This is a Request for Information (RFI) response document for VA Project #679-19-101, specifically RFI List #2, containing the Department of Veterans Affairs' responses to contractor inquiries marked in red.
The document addresses two key questions from previous RFI submissions. Question 1 clarifies construction fencing requirements, referencing Specification 01 00 00 Section 1.6.H, which mandates that contractors provide a chain link construction fence with a minimum height of 2.1 meters (seven feet) around the construction area. The VA directs contractors to consult the provided project drawings to identify the designated construction area where fencing is required. Question 2 responds to a previous inquiry about an acceptable construction condition by sharing an attached photograph (referenced as attachment 0004A) that was previously submitted by an offeror. The photograph depicts an active construction site showing excavated trenches at a residential property with wooden safety railings and surveying equipment. The VA's response confirms that the referenced condition shown in the photograph would be acceptable if it meets the project requirements and shares this image with all bidders to ensure equitable information distribution among all competing offerors.
View the file
Other files for this federal contract opportunity
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI List #2 Project #679-19-101
VA Contracting Responses are in red
1. In RFI List #3, Question 3 requests that the VA provide missing information regarding where construction fencing is required; however, no information was provided in the response. Will the VA please provide this information? - Spec 01 00 00 1.6.H states, “Before construction operations begin, Contractor shall provide a chain link construction fence, 2.1m (seven feet) minimum height, around the construction area indicated on the drawings”. Please refer to the provided drawings for the designated construction area where fencing is required.
2. In RFI List #3, Question 10, the offeror attached a picture for reference to their question. The VA responded by confirming that the referenced condition would be acceptable if it meets requirements. Will the VA please share the attached picture with all bidders so that all offerors are receiving the same information, especially since the VA confirmed that the referenced condition would be acceptable?
– Please see attachment 0004A for full-size referenced photo. Photo is also attached below.