004 FA-100 BUILDING 2 FA PLANS - DEMOLITION - NEW WORK - Amendment 00001 - Attachment 3.pdf

PDF 3 MB Posted

Attached to
Amendment 0001 - 36C24726Q0772 - Project 557-23-103 | Replace Building 2 and Building 4 Generators | Construction
Solicitation number
36C24726Q0772
Issued by

About this file

This document is a set of Bid Documents/Existing Conditions and Demolition Plans for a federal construction project at the VA Dublin Healthcare System in Dublin, Georgia. The project, numbered D.L.E. 557-23-103 (Drawing FA-100), involves the replacement of Building 2 and Building 4 generators at 1826 Veterans Boulevard, Dublin, GA 31021. The project is under the Office of Construction and Facilities Management, U.S. Department of Veterans Affairs, with an issue date of June 15, 2026.

The drawing set includes detailed architectural and engineering plans for Building 2 basement fire detection system demolition and existing conditions. The plans depict the basement layout with current fire alarm control panel locations, existing fire detection devices, and proposed demolition requirements. The document provides a Fire Alarm System Input/Output Matrix detailing device compatibility and connections across multiple buildings. Key plan sheets include the Building 2 Basement Fire Detection Demolition Plan, Building 2 FACP Existing Location Plan, and Building 2 Basement Key Plan. The Architect/Engineer of Record is NBM (Northeast Infrastructure, LLC), located in Honesdale, Pennsylvania, with consulting services from Calibre Engineering located in Highlands Ranch, Colorado. General demolition notes specify contractor responsibilities for system removal, proper disposal, safety protocols, and restoration procedures.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

V.A.C.

BUILDING 2 BASEMENT FIRE

DETECTION EXISTING CONDITIONS

AND DEMOLITION PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1826 VETERANS BLVD.

DUBLIN, GA 31021

Revisions: Date:

VA DUBLIN HEALTHCARE SYSTEM

D.L.E.

557-23-103

FA-100

REPLACEMENT OF

BUILDING 2 & 4 GENERATORS

BID DOCUMENTS R1

06/15/2026(502) 836-4232

10901 FRONT BEACH ROAD, SUITE 1415

PANAMA CITY BEACH, FL 32407

www.force-protect.com

(303) 730-0434

8822 RIDGELINE BLVD #310

HIGHLANDS RANCH, CO 80129

www.calibre-engineering.com

34 BROWN STREET

HONESDALE, PA 18431

OFFICE : (570) 253-0846

WWW.NEINFRA.COMNortheast Infrastructure, LLC

X

AutoCAD SHX Text

UP

AutoCAD SHX Text

IT CLOSET

AutoCAD SHX Text

STORAGE BM123

AutoCAD SHX Text

ELEC BM124

AutoCAD SHX Text

ELEC BM124A

AutoCAD SHX Text

CORRIDOR CRB5-2

AutoCAD SHX Text

FIRE CLOSET BM127G

AutoCAD SHX Text

ELEVATOR D-2

AutoCAD SHX Text

STAIR D-2 STB4-2

AutoCAD SHX Text

REFRIGERATION COMPRESSOR ROOM BM121

AutoCAD SHX Text

HD

AutoCAD SHX Text

HD

AutoCAD SHX Text

HD

AutoCAD SHX Text

MECH ROOM BM104

AutoCAD SHX Text

MECH ROOM BM103B

AutoCAD SHX Text

MECH ROOM BM103

AutoCAD SHX Text

FACP

AutoCAD SHX Text

CORRIDOR CRB1-2

AutoCAD SHX Text

EXISTING FIRE ALARM CONTROL PANEL

AutoCAD SHX Text

FACP

AutoCAD SHX Text

BUILDING 2 BASEMENT CORRIDOR

AutoCAD SHX Text

EXISTING DEVICES

AutoCAD SHX Text

BUILDING 2 BASEMENT ELEC. ROOM BM124A

AutoCAD SHX Text

HD

AutoCAD SHX Text

HD

AutoCAD SHX Text

HD

AutoCAD SHX Text

BUILDING 2 BASEMENT ELEC. ROOM BM124A

AutoCAD SHX Text

BUILDING 2 BASEMENT ELEC. ROOM BM124A

AutoCAD SHX Text L

AutoCAD SHX Text

LAWRENCE J. MARCHETTI

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text Y

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text V

AutoCAD SHX Text M

AutoCAD SHX Text P

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text No. PE051700E

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text M

AutoCAD SHX Text W

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DETECTION DEMOLITION PLAN

AutoCAD SHX Text 1/4"=1-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 2 BASEMENT FIRE

AutoCAD SHX Text

FA-100

AutoCAD SHX Text N

AutoCAD SHX Text

PROJECT NORTH

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

BASEMENT KEY PLAN

AutoCAD SHX Text 1/64"=1'-0"

AutoCAD SHX Text

BUILDING 2

AutoCAD SHX Text N

AutoCAD SHX Text

PROJECT NORTH

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

FACP EXISTING LOCATION PLAN

AutoCAD SHX Text 1/4"=1-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 2 BASEMENT

AutoCAD SHX Text

FA-100

AutoCAD SHX Text N

AutoCAD SHX Text

PROJECT NORTH

AutoCAD SHX Text

GENERAL DEMOLITION NOTES

AutoCAD SHX Text 1.

AutoCAD SHX Text FIRE ALARM DETECTION DEVICES LOCATED WITHIN ROOMS 124 AND 124A SHALL BE DEMOLISHED AS INDICATED. THE EXISTING FIRE ALARM CONTROL PANEL (FACP) SHALL REMAIN IN SERVICE AND SHALL NOT BE REPLACED.

AutoCAD SHX Text 2.

AutoCAD SHX Text FOLLOWING DEMOLITION OF THE FIRE ALARM DETECTION DEVICES IN ROOMS 124 AND 124A, THE CONTRACTOR SHALL REPROGRAM THE EXISTING FACP AND ALL ASSOCIATED SYSTEM LOGIC AS REQUIRED AND REMOVE EXISTING DEVICES FROM PANEL PROGRAM.

AutoCAD SHX Text 3.

AutoCAD SHX Text THE CONTRACTOR SHALL ENSURE THAT ALL REMAINING FIRE ALARM SYSTEM FUNCTIONS AND DEVICES CONTINUE TO OPERATE PROPERLY AND IN FULL COMPLIANCE WITH NFPA 72 AND VA REQUIREMENTS. THE FIRE ALARM SYSTEM SHALL BE LEFT COMPLETE, FULLY OPERATIONAL, AND FREE OF TROUBLE, SUPERVISORY, OR FAULT CONDITIONS AT THE COMPLETION OF DEMOLITION AND CONSTRUCTION.

AutoCAD SHX Text 4.

AutoCAD SHX Text ALL WORK, INCLUDING DEMOLITION, REPROGRAMMING, TESTING, AND RESTORATION OF SYSTEM OPERATION, SHALL BE PERFORMED BY A FACTORY-AUTHORIZED FIRE ALARM CONTRACTOR. ALL REQUIRED COORDINATION WITH THE VA, FIRE PROTECTION, AND FACILITY ENGINEERING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

AutoCAD SHX Text 5.

AutoCAD SHX Text THE CONTRACTOR SHALL PERFORM ALL REQUIRED TESTING AND VERIFICATION NECESSARY TO CONFIRM PROPER SYSTEM OPERATION FOLLOWING REPROGRAMMING AND SHALL PROVIDE DOCUMENTATION AND AS-BUILT RECORDS AS REQUIRED.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

FIRE ALARM

AutoCAD SHX Text

DEMOLITION RISER DIAGRAM

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

AutoCAD SHX Text

FA-100

AutoCAD SHX Text

RISER DIAGRAM LEGEND

AutoCAD SHX Text

18AWG UTP SOLID IN 3/4" CONDUIT

AutoCAD SHX Text

GENERAL LEGEND

AutoCAD SHX Text

DEMOLITION

AutoCAD SHX Text

SYMBOLS

AutoCAD SHX Text

HEAT DETECTOR

AutoCAD SHX Text

FIRE ALARM CONTROL PANEL

AutoCAD SHX Text

SMOKE DETECTOR

AutoCAD SHX Text

VALVE TAMPER SWITCH

AutoCAD SHX Text

WATERFLOW SWITCH

AutoCAD SHX Text

HD

AutoCAD SHX Text

FACP

AutoCAD SHX Text S

AutoCAD SHX Text

TS

AutoCAD SHX Text

WS

AutoCAD SHX Text

GENERAL DEMOLITION NOTES

AutoCAD SHX Text 1.

AutoCAD SHX Text THIS SYSTEM SHALL CONFORM TO THE PROJECT SPECIFICATIONS AND REFERENCES CONTAINED THEREIN.

AutoCAD SHX Text 2.

AutoCAD SHX Text ALL EQUIPMENT AND SYSTEM COMPONENTS FURNISHED AND INSTALLED SHALL BE NEW AND LISTED BY UL FOR THEIR INTENDED USE. THE EQUIPMENT AND SYSTEM COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS, THE MANUFACTURERS. RECOMMENDATIONS, AND WITHIN THE LIMITATIONS OF THE UL LISTINGS. ALL EQUIPMENT SHALL BE THE STANDARD PRODUCT OF A SINGLE MANUFACTURER. EVIDENCE OF UL LISTING IS REQUIRED.

AutoCAD SHX Text 3.

AutoCAD SHX Text

ALL WIRING SHALL CONFORM TO NFPA 70- NATIONAL ELECTRICAL CODE 2026.

AutoCAD SHX Text 4.

AutoCAD SHX Text

ALL SMOKE DETECTORS SHALL BE LOCATED AT LEAST 3-FEET FROM AIR SUPPLY DIFFUSERS.

AutoCAD SHX Text 5.

AutoCAD SHX Text ALL REQUIRED MANUAL FIRE ALARM BOXES SHALL BE LOCATED ON THE LATCH SIDE OF EXIT DOORS.

AutoCAD SHX Text 6.

AutoCAD SHX Text ALL INITIATING DEVICE CIRCUITS (IDC) AND SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS "B", PER NFPA-72 2025 NATIONAL FIRE ALARM CODE AND VA FIRE PROTECTION ENGINEERING DESIGN MANUAL (VAFPDM).

AutoCAD SHX Text 7.

AutoCAD SHX Text ALL NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE CLASS "B", 2-WIRE CIRCUITS AS DESCRIBED IN NFPA-72.

AutoCAD SHX Text 8.

AutoCAD SHX Text

POWER FOR FACP SHALL BE SUPPLIED BY A DEDICATED BRANCH CIRCUIT.

AutoCAD SHX Text 9.

AutoCAD SHX Text POWER LIMITED FIRE ALARM (PLFA) CIRCUITS SHALL BE INSTALLED IN CONFORMANCE WITH ARTICLE 760 OF THE NATIONAL ELECTRICAL CODE (NFPA 70).

AutoCAD SHX Text 10.

AutoCAD SHX Text ADDRESSABLE MONITORING MODULES SHALL BE PROVIDED TO MONITOR THE STATUS OF WATERFLOW SWITCHES, TAMPER SWITCHES AND PRESSURE SWITCHES.

File details come from the government source that posted it. Updated .