Roof Investigation Report - all combined.pdf
PDF 21 MB Posted
- Attached to
- Z1DA--679-23-101 | Special Roofing Replacements
- Solicitation number
- 36C24724R0067
About this file
This document is a Roof Investigation Report related to a federal contract opportunity for Special Roofing Replacements at the Tuscaloosa VA Medical Center.
The contract opportunity, Solicitation Number 36C24724R0067, is for the construction and replacement of roofs on Buildings 1, 4, 5, 12, 17, 18, 61, and 135. The work includes all necessary trades such as carpentry, plumbing, electrical, and HVAC. The contractor must comply with VA safety rules, NFPA, EPA, and NEC codes. The contract performance period is 365 calendar days from the date of award. Key requirements include providing proof of negative tuberculosis tests for all employees, 10-hour OSHA training for subcontractors, and 30-hour OSHA training for the supervisor. The contractor must also obtain a VA identification badge and comply with VA security regulations, including restrictions on photography and video. All VA information must be returned or destroyed upon contract completion.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24724R0067 0003.docx | DOCX document | |
| 36C24724R0067 0002.docx | DOCX document | |
| Pre- Bid Site Visit 6-3-24.pdf | ||
| 36C24724R0067 0001.docx | DOCX document | |
| Attachment 2 - 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING Jan 2023 Dev form.pdf | ||
| Attachment 1 - Experience Modification Rate Form 2022 Revised 2 2 2023.pdf | ||
| UPDATED DBA WAGES AL20240098.pdf | ||
| 36C24724R0067_1.docx | DOCX document | |
| Drawings 679-23-101.pdf | ||
| Specifications - Emergency Roofing Replacement 679-23-101.pdf | ||
| Past Performance Questionnaire.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sep 14, 2023 - 5:39PM
Management Report
VAMC Tuscaloolsa Building 1
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloolsa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com
VAMC Tuscaloolsa Building 1 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 3 Total Sq Ft: 2,893 Map Name Sq Ft Est Install Grade
1 Section 1 509 D
2 Section 2 1,727 D
3 Section 3 657 D
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 1 Size: 509 Overall Grade: D
Inspector:
Core #1 1’ from Drain Concrete
1 1/2” ISO
TPO
Core #2. 8’ from Core #1 Concrete
3 1/2” ISO
TPO
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 509 Overall Grade: D
Inspector:
Overview
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 509 Overall Grade: D
Counter Flashing Detail
Concrete Coping Detail
Coping Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 1 Size: 509 Overall Grade: D
Inspector:
General - (Remedial) Quantity: 1 EA Deficiency:
Core #1 for location Corrective Action:
General - (Remedial) Quantity: 1 EA Deficiency:
Core #2 for location
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 509 Overall Grade: D
Inspector:
General - (Remedial) Quantity: 1 EA Deficiency:
Unsecured lightning Protection cable.
General - Blisters (Remedial)
Deficiency:
Water Blisters in the membrane are due to either air or moisture being caught between the plies of the waterproofing system. As expansion and contraction occur, what was once a small deficiency enlarges greatly, cracks and allows water into the roof system and building.
Corrective Action:
The blister must be X cut, filled with a waterproofing agent and re-sealed per industry standards.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 509 Overall Grade: D
Inspector:
General - Blisters (Remedial) Quantity: 1 EA Deficiency:
Water Blisters in the membrane are due to either air or moisture being caught between the plies of the waterproofing system. As expansion and contraction occur, what was once a small deficiency enlarges greatly, cracks and allows water into the roof system and building.
Corrective Action:
The blister must be X cut, filled with a waterproofing agent and re-sealed per industry standards.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 509 Overall Grade: D
Inspector:
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were wet
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 509 Overall Grade: D
Inspector:
1 - Section 1 (509 Sq Ft ) Grade D Deficiency Qty Emergency Remedial Replacement Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Unsecured lightning Protection... 1 EA $0.00 Blisters 1 EA $0.00 Blisters 1 EA $0.00 Total $0.00 $0.00 $0.00
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 2 Size: 1727 Overall Grade: D
Inspector:
Core #1. 1’ from Drain Concrete
2” ISO
3/4” ISO
3/4” 5 Ply
Core #2. 8’ from Core #1 Concrete
2”ISO
1” ISO
3/4” 5 Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 2 Size: 1727 Overall Grade: D
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 1727 Overall Grade: D
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 1727 Overall Grade: D
Edge Metal Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 2 Size: 1727 Overall Grade: D
Inspector:
General - (Remedial) Quantity: 1 EA Deficiency:
Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 2 Size: 1727 Overall Grade: D
Inspector:
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were wet
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 2 Size: 1727 Overall Grade: D
Inspector:
2 - Section 2 (1,727 Sq Ft ) Grade D Deficiency Qty Emergency Remedial Replacement Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Total $0.00 $0.00 $0.00
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 3 Size: 657 Overall Grade: D
Inspector:
Core #1 1’ from Drain Concrete
2” ISO
1”ISO
3/4” 5 Ply
Core #2. 8’ from Core #1 Concrete
2” ISO
1 1/2” ISO
3/4” 5 Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 3 Size: 657 Overall Grade: D
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 3 Size: 657 Overall Grade: D
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 3 Size: 657 Overall Grade: D
Roof Hatch Detail
Water Supply
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 3 Size: 657 Overall Grade: D
Inspector:
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were Damp
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Budget Matrix Building 1 Tuscaloosa, AL 2893Sq Ft
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Emergency Remedial Replacement 1 - Section 1 (509 Sq Ft) Grade D Projected Replacement: 0 Deficiency Qty Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Unsecured lightning Protection... 1 EA $0.00 Blisters 1 EA $0.00 Blisters 1 EA $0.00 Total $0.00 $0.00 $0.00
2 - Section 2 (1,727 Sq Ft) Grade D Projected Replacement: 0 Deficiency Qty Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Total $0.00 $0.00 $0.00
3 - Section 3 (657 Sq Ft) Grade D Projected Replacement: 0 Deficiency Qty Total $0.00 $0.00 $0.00
Emergency Remedial Replacement Budget Totals $0.00 $0.00 $0.00
Powered by TCPDF (www.tcpdf.org)
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com http://www.tcpdf.org
Sep 21, 2023 - 8:45AM
VAMC Tuscaloosa Building 4
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloosa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
VAMC Tuscaloosa Building 4 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 6 Total Sq Ft: 3,340 Map Name Sq Ft Est Install Grade
1 Section 1 300 C
2 Section 2 370 C
3 Section 3 500 C
4 Section 4 380 C
5 Section 5 540 C
6 Section 6 1,250 C
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 1 Size: 300 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Core #1 Concrete 1/4” Asphalt
2 7/8” ISO
1/2” Perlite 1/2” 5 Ply
Core #2. 8’ from Core #1 Concrete 1/4” Asphalt
2 7/8” ISO
1/2” Perlite 1/2” 5 Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 300 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Overview Dimensions are approx 24.3' x 12'
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 1 Size: 300 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Fish Mouth (Emergency) Quantity: 2 LF Deficiency:
A deficiency in the membrane lap that causes it to fold can cause water to enter.
Corrective Action:
Repair per manufacturers requirements.
General - Debris (Remedial) Quantity: 100 Sq Ft Deficiency:
Debris on membrane is damaging membrane.
Corrective Action:
We will remove and dispose of debris.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 300 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Gutter Clog (Emergency) Quantity: 22 LF Deficiency:
Debris in gutter is inhibiting water flow.
Corrective Action:
We will clean debris and dispose of properly.
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 300 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 300 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Condition Summary Membrane: C Flashings: C Sheet Metal: C Overall: C
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Repair & Monitor
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Core #1 Concrete 1/4” Asphalt
2 7/8 ISO
1/2” Perlite 1/2” 5 Ply Wet
Core#2 Concrete 1/4” Asphalt
2 7/8” ISO
1/2” Perlite 1/2” 5 Ply Wet
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023
Scupper Detail
Counter Flashing, Concrete Coping & Lightning Protection
Pipe Penetration Detail
Exhaust Fan Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Fish Mouth (Emergency) Quantity: 2 EA Deficiency:
A deficiency in the membrane lap that causes it to fold can cause water to enter.
Corrective Action:
Repair per manufacturers requirements.
General - Fish Mouth (Emergency) Quantity: 1 EA Deficiency:
A deficiency in the membrane lap that causes it to fold can cause water to enter.
Corrective Action:
Repair per manufacturers requirements.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Drains/Scupper Open membrane (Emergency) Quantity: 1 EA Deficiency:
Open membrane laps at scupper / drain is open.
Corrective Action:
We will clean prime and seal open laps to ensure water tightness.
General - Debris (Remedial) Quantity: 100 Sq Ft Deficiency:
Debris on membrane is damaging membrane.
Corrective Action:
We will remove and dispose of debris.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 2 Size: 370 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Condition Summary Membrane: C Flashings: C Sheet Metal: C Overall: C
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Core are wet
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 3 Size: 500 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Core #1 1’ from Drain Concrete Asphalt iSO Perlite 5 Ply Wet
Core #2. 8’ from Core #1 Concrete Asphalt
ISO
Perlite 5 Ply Wet
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 3 Size: 500 Overall Grade: C
Inspection Date: 09/11/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 3 Size: 500 Overall Grade: C
Inspection Date: 09/11/2023
Parapet Wall Detail
Coping & Wall Detail
Counter Flashing & Lightning Protection Detail
Roof Hatch Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 3 Size: 500 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Condition Summary Membrane: C Flashings: C Sheet Metal: C Overall: C
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were wet
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 4 Size: 380 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Core #1. 1’ from Scupper. Wet Concrete Asphalt
2 7/8” ISO
1” ISO
1/2” Perlite 3/8” 3 Ply Wet
Core #2. 8’ from Core #1. Wet Concrete Asphalt
2 7/8” ISO
2” ISO
1” ISO
1/2” Perlite 1/2” 3 Ply Wet
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 4 Size: 380 Overall Grade: C
Inspection Date: 09/11/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 4 Size: 380 Overall Grade: C
Inspection Date: 09/11/2023
Concrete Copping & Lightning Protection Detail
Counter Flashing & Parapet Wall Detail
Vent Pipe Penetration Detail
Scupper Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 4 Size: 380 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Debris (Emergency) Quantity: 100 Sq Ft Deficiency:
Debris on membrane is damaging membrane.
Corrective Action:
We will remove and dispose of debris.
General - Pipe Flashing Cracked (Emergency) Quantity: 4 EA Deficiency:
Vent pipe is cracked at base.
Corrective Action:
We will clean and prime the vent base and properly seal to ensure water tightness.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 4 Size: 380 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 4 Size: 380 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Condition Summary Membrane: C Flashings: C Sheet Metal: C Overall: C
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were wet.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 5 Size: 540 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Core #1. 2 ‘ from Drain Wood Asphalt
2” ISO
1/2” Perlite 1/4” 3Ply
Core #2. 8’ from Core #1 Wood Asphalt
2”ISO
1/2” Perlite 5/8” Asphalt 1/4” 3 Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 5 Size: 540 Overall Grade: C
Inspection Date: 09/11/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 5 Size: 540 Overall Grade: C
Inspection Date: 09/11/2023
Drain Detail
Coping & Parapet Wall Detail
Base Flashing Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 5 Size: 540 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Drains/Scupper Open membrane (Emergency) Quantity: 1 EA Deficiency:
Membrane is deteriorated and failing/open at drain.
Corrective Action:
We will clean prime and seal open laps to ensure water tightness.
General - Damaged Flashing (Emergency) Quantity: 5 LF Deficiency:
The existing flashing has been damaged and has failed.
Corrective Action:
Remove the existing flashing and install new, like kind flashing material per manufacturers recommendations and details.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 5 Size: 540 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Damaged Flashing (Emergency) Quantity: 4 LF Deficiency:
The existing flashing has been damaged and has failed.
Corrective Action:
Remove the existing flashing and install new, like kind flashing material per manufacturers recommendations and details.
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 5 Size: 540 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 5 Size: 540 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Condition Summary Membrane: C Flashings: C Sheet Metal: C Overall: C
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Dry Cores
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 6 Size: 1250 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Core #1 1’ from Drain Metal 3” Lightweight Asphalt
2 1/2” ISO
1/2” Perlite 1/4” 3 Ply
Core #2 8’ from Core #1 Metal 3” Lightweight Asphalt
2 1/2” ISO
1/2” Perlite 1/4” 3 Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 6 Size: 1250 Overall Grade: C
Inspection Date: 09/11/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 6 Size: 1250 Overall Grade: C
Inspection Date: 09/11/2023
Base Flashing & Term Bar Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 6 Size: 1250 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Edge Detail/Expansion Joint Separated (Emergency) Quantity: 72 LF Deficiency:
Roof membrane has separated from metal edge.
Corrective Action:
We will remove the loose membrane, secure metal edge joint, clean and prime metal and install new material that extends 3" onto roof to ensure water tightness.
General - Damaged Flashing (Emergency) Quantity: 1 EA Deficiency:
The existing flashing has been damaged and has failed.
Corrective Action:
Remove the existing flashing and install new, like kind flashing material per manufacturers recommendations and details.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 6 Size: 1250 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - Damaged Flashing (Emergency) Quantity: 1 EA Deficiency:
The existing flashing has been damaged and has failed.
Corrective Action:
Remove the existing flashing and install new, like kind flashing material per manufacturers recommendations and details.
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 6 Size: 1250 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 Deficiency:
Core #2 for laction
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 6 Size: 1250 Overall Grade: C
Inspection Date: 09/11/2023 Inspector: William Hall
Condition Summary Membrane: C Flashings: C Sheet Metal: C Overall: C
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were wet
Powered by TCPDF (www.tcpdf.org)
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com
Sep 21, 2023 - 8:57AM
VAMC Tuscaloosa Building 5
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloosa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
VAMC Tuscaloosa Building 5 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 2 Total Sq Ft: 790 Map Name Sq Ft Est Install Grade
1 Section 1 395 D
2 Section 2 395 NA
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 1 Size: 395 Overall Grade: D
Inspection Date: 09/12/2023 Inspector: William Hall
Core #1 Wood 3 layers of felt Copper Sheeting
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 395 Overall Grade: D
Inspection Date: 09/12/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 395 Overall Grade: D
Inspection Date: 09/12/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 395 Overall Grade: D
Inspection Date: 09/12/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 395 Overall Grade: D
Inspection Date: 09/12/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 1 Size: 395 Overall Grade: D
Inspection Date: 09/12/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 395 Overall Grade: D
Inspection Date: 09/12/2023 Inspector: William Hall
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Took one Core because both balconies are the same. Copper sheeting over wood deck, any slope is structural
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 2 Size: 395 Overall Grade: 0
Inspection Date: 09/12/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 395 Overall Grade: 0
Inspection Date: 09/12/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 395 Overall Grade: 0
Inspection Date: 09/12/2023
Powered by TCPDF (www.tcpdf.org)
17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com
Sep 21, 2023 - 6:10PM
VAMC Tuscaloosa Building 12
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloosa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
Sep 21, 2023 - 6:11PM
VAMC Tuscaloosa Building 12 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 1 Total Sq Ft: 6,450 Map Name Sq Ft Est Install Grade
1 Section 1 6,450 D
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023 Inspector: William Hall
Core #1 Wood Felt Paper Slate
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 6450 Overall Grade: D
Inspection Date: 09/15/2023 Inspector: William Hall
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Measurements:
Length of Ridge/Eaves: 121'1" Length of Rake Edge: 26'3" Exposed Eave Width: 18.5"
Powered by TCPDF (www.tcpdf.org)
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com
VAMC Tuscaloosa Building 17
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloosa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
VAMC Tuscaloosa Building 17 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 1 Total Sq Ft: 6,100 Map Name Sq Ft Est Install Grade
1 Section 1 6,100 D
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023 Inspector: William Hall
Core #1 Wood Felt Paper Slate
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023
Ridges to Eve
Length of ridge and sides
Eve Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 6100 Overall Grade: D
Inspection Date: 09/15/2023 Inspector: William Hall
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Measurements:
Length of Ridge/Eaves: 116'6" Length of Rake Edge: 26'3" Exposed Eave Width: 18.5"
Powered by TCPDF (www.tcpdf.org)
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com
Sep 14, 2023 - 5:41PM
VAMC Tuscaloolsa Building 18
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloolsa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
VAMC Tuscaloolsa Building 18 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 2 Total Sq Ft: 6,722 Map Name Sq Ft Est Install Grade
1 Section 1 3,186 D
2 Section 2 3,536 D
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 1 Size: 3186 Overall Grade: D
Inspector:
Core #1 1’ from High Concrete 1/2” Asphalt
2 1/4” ISO
2 1/4” ISO
2 1/4” ISO
1 1/4” ISO
1/2” Composite Board 1/4” 3 Ply Coated
Core #2. 8’ from Core #1 Concrete 1/4” Asphalt
2” ISO
2”ISO
2”ISO
1” Composite Board 1/4” 3Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 3186 Overall Grade: D
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 3186 Overall Grade: D
Pitch Pan Detail
Rail Curb Detail
Counter Flashing over Expansion Joint Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 1 Size: 3186 Overall Grade: D
Inspector:
General - (Remedial) Quantity: 1 EA Deficiency:
Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 3186 Overall Grade: D
Inspector:
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were dry
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 3186 Overall Grade: D
Inspector:
1 - Section 1 (3,186 Sq Ft ) Grade D Deficiency Qty Emergency Remedial Replacement Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Total $0.00 $0.00 $0.00
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023 Inspector: William Hall
Core #1 1’ from Drain Metal 3/4” Perlite 1/2” Asphalt
2” ISO
1/2” Composite Board 1/4” 3 Ply
Core #2. 8’ from Core #1 Metal 3/4” Perlite 1/2” Asphalt
2” ISO
3/4” ISO
1/2” Composite Board 1/4” 3 Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
Sep 14, 2023 - 5:42PM
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023
Curb Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023
Detail
Cricket Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023 Inspector: William Hall
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Cores were Dry
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 2 Size: 3536 Overall Grade: D
Inspection Date: 09/14/2023 Inspector: William Hall
2 - Section 2 (3,536 Sq Ft ) Grade D Deficiency Qty Emergency Remedial Replacement Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Total $0.00 $0.00 $0.00
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Budget Matrix Building 18 Tuscaloosa, AL 6722Sq Ft
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Emergency Remedial Replacement 1 - Section 1 (3,186 Sq Ft) Grade D Projected Replacement: 0 Deficiency Qty Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Total $0.00 $0.00 $0.00
2 - Section 2 (3,536 Sq Ft) Grade D Projected Replacement: 0 Deficiency Qty Core #1 for location 1 EA $0.00 Core #2 for location 1 EA $0.00 Total $0.00 $0.00 $0.00
Emergency Remedial Replacement Budget Totals $0.00 $0.00 $0.00
Powered by TCPDF (www.tcpdf.org)
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com
Sep 21, 2023 - 9:01AM
VAMC Tuscaloosa Building 61
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloosa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
VAMC Tuscaloosa Building 61 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 1 Total Sq Ft: 62,000 Map Name Sq Ft Est Install Grade
1 Section 1 62,000 D
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
Sep 21, 2023 - 9:02AM
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 62000 Overall Grade: D
Inspection Date: 09/15/2023 Inspector: William Hall
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service life remaining F = Less than 1 Year of service life remaining
Recommendations Many soft spots of Decking across all areas. Missing shingles in various spots.
Flashing / sealant at most penetrations / curbs failing cracking. Fasteners at gutters backing out.
Powered by TCPDF (www.tcpdf.org)
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037 roofingsolutionsla.com
VAMC Tuscaloosa Building 135
3701 Loop Road, Tuscaloosa, AL
Prepared For VAMC Tuscaloosa
Powered By
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
VAMC Tuscaloosa Building 135 3701 Loop Road Tuscaloosa, AL 35404
Site Overview
Total Sections: 10 Total Sq Ft: 17,445 Map Name Sq Ft Est Install Grade
1 Section 1 3,000 D
2 Section 2 2,875 D
3 Section 3 400 D
4 Section 4 470 D
5 Section 5 470 D
6 Section 6 7,000 D
7 Section 7 1,300 D
8 Section 8 1,300 D
9 Section 9 400 D
10 Section 10 230 D
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Composition Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
Core #1 by Drain Concrete
2 1/4” ISO
1/2” ISO
1/2” Perlite 1/4” 3 Ply
Core # 2 8’ from core #1 Concrete
2 1/4” ISO
1” ISO
1/2” Perlite 1/4” Ply
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023
Parapet Wall, Lightning Protection & Coping Detail
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Observations (continued) Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
General - Improper Installation (Remedial) Quantity: 1 EA Deficiency:
The original installation of this detail was done improperly and not per industry standards.
Corrective Action:
Remove the existing detail and install a new detail per the industry and manufacturers recommendations and details.
General - Blisters (Emergency) Quantity: 16 EA Deficiency:
Blisters in the membrane are due to either air or moisture being caught between the plies of the waterproofing system. As expansion and contraction occur, what was once a small deficiency enlarges greatly, cracks and allows water into the roof system and building.
Corrective Action:
The blister must be X cut, filled with a waterproofing agent and re-sealed per industry standards.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
General - Improper Installation (Emergency) Quantity: 50 Sq Ft Deficiency:
The original installation of this detail was done improperly and not per industry standards.
Corrective Action:
Remove the existing detail and install a new detail per the industry and manufacturers recommendations and details.
General - Open Flashing (Emergency) Quantity: 4 LF Deficiency:
Open flashings can be caused by membrane shrinkage, insufficient counterflashing or the simple aging and failure of the original flashing to remain adhered to the wall.
Corrective Action:
Depending on the severity of the deterioration of the flashing, they either will need to be removed completely and new flashing installed or the existing flashing must be re-sealed to the wall and the tops of the flashings covered up.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
General - Open Flashing (Emergency) Quantity: 4 LF Deficiency:
Open flashings can be caused by membrane shrinkage, insufficient counterflashing or the simple aging and failure of the original flashing to remain adhered to the wall.
Corrective Action:
Depending on the severity of the deterioration of the flashing, they either will need to be removed completely and new flashing installed or the existing flashing must be re-sealed to the wall and the tops of the flashings covered up.
General - Improper Installation (Emergency) Quantity: 4 LF Deficiency:
The original installation of this detail was done improperly and not per industry standards.
Corrective Action:
Remove the existing detail and install a new detail per the industry and manufacturers recommendations and details.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
General - Open Flashing (Emergency) Quantity: 4 LF Deficiency:
Open flashings can be caused by membrane shrinkage, insufficient counterflashing or the simple aging and failure of the original flashing to remain adhered to the wall.
Corrective Action:
Depending on the severity of the deterioration of the flashing, they either will need to be removed completely and new flashing installed or the existing flashing must be re-sealed to the wall and the tops of the flashings covered up.
General - Open Flashing (Emergency) Quantity: 4 LF Deficiency:
Open flashings can be caused by membrane shrinkage, insufficient counterflashing or the simple aging and failure of the original flashing to remain adhered to the wall.
Corrective Action:
Depending on the severity of the deterioration of the flashing, they either will need to be removed completely and new flashing installed or the existing flashing must be re-sealed to the wall and the tops of the flashings covered up.
Roofing Solutions LLC - Baton Rouge 17260 Jefferson Hwy, Suite D Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
General - Damaged Coping (Emergency) Quantity: 20 LF Deficiency:
The existing edge Metal has been damaged and has failed.
Corrective Action:
Remove the existing coping and install new, like kind coping material per manufacturers recommendations and details.
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Deficiencies (continued) Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
General - (Remedial) Quantity: 1 EA Deficiency:
Baton Rouge LA 70817 P: 2257443912 F: 2257440037
3701 Loop Road Tuscaloosa, AL 35404
Summary Section: Section 1 Size: 3000 Overall Grade: D
Inspection Date: 09/13/2023 Inspector: William Hall
Condition Summary Membrane: D Flashings: D Sheet Metal: D Overall: D
Overall Grade A = 10 Years or more of service life remaining B = 8-10 Years of service life remaining C = 5-7 Years of service life remaining D = 2-4 Years of service…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .