MD-100 - MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK.pdf
PDF 297 KB Posted
- Attached to
- CATH LAB Federal contract opportunity
- Solicitation number
- 36C24720B0024
About this file
This document includes mechanical drawings and specifications for the demolition and replacement of ductwork and piping in a cardiac cath lab. The project involves removing the existing air handling unit, computer room air handler, ductwork, piping, and terminal boxes serving the cath lab spaces. New ductwork, piping, air handling equipment, and terminal boxes will be installed. The project also includes replacing the existing cath lab equipment with a new GE system, Stryker boom, and clean suite ceiling system. The opportunity is available through the Department of Veterans Affairs Veterans Health Administration at the Ralph Johnson VAMC in Charleston, South Carolina. The solicitation number is 36C24720B0024 and bids are due on May 8, 2020.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
12.511.510.59.57.46.1
AA
BB
CC
A
A.8
B
CARDIAC CATH LAB NO. 1
AA205
WARD SUPPLIES
AA204
SCRUB AREA
AA215
SOILED LINEN
AA205A
COMPUTER ROOM
AA219A
CARDIAC CATH LAB NO. 1
CONTROL ROOM
AA219
CARDIAC CATH LAB NO. 2
OBSERVE ROOM
AA223A
CARDIAC CATH LAB NO. 2
MECHANICAL ROOM
AA223B
CARDIAC CATH LAB NO. 2
AA223
SOILED UTILITY
AA237A
SOILED UTILITY
AA221
STORAGE WARD SUPPLIES
AA229
UTILITY ROOM SOILED
AA230
24"x12"
28"x12" 10"x6"
32"x10"
"x
8"
48"x16"
27"x14"
"x
8"
30"x12"
"x
12"x6"
12"x6"
"x
"x
6"
"x
"x
"8" ø
16"x10"
"x
"x
10"x8"
"x
8"
"x1
0"
"x
5"
7" ø
10"x8"
"x
8" ø
7" ø
6"x9"
16"x14"
8"ø
8" x1
0"
10"x12"
7" ø
6"ø
7"ø
22"x8"
"x
8"
14"x4"
30"x8"
6" ø
8" x1
0"
"x
6"8"ø
"x
6"
12"x10"
12"x10"
CFM
CFM
CFM
(E) VAV
BOX
10"ø
CFM
9" ø
CFM
CFM
CFM
8"ø
(E) VAV
BOX
(E) VAV
BOX
CFM
8" ø
CFM
8"x10"7"ø
(E) VAV
BOX
(E) VAV
BOX
CFM
CFM
6" ø
8" x4
CFM
"x
CFM
CFM
CFM
8"ø 6"ø
CFM
CFM
CFM
CFM
"x
4"
14"x4"
CFM
CFM
CFM
12"x10"
14"x4"CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
EXISTING COMPUTER ROOM AHU TO BE
DEMOLISHED. REMOVE ALL REFRIGERANT PIPING UP
TO ROOF MOUNTED CONDENSER UNIT.
THIS PROJECT SHALL BE PHASED. ALL WORK EXTERNAL TO THE CATH
LAB TO BE COMPLETED IN PHASES 1-3 . ALL WORK INSIDE THE CATH
LAB SHALL BE DONE IN PHASE 4. CONTRACTOR TO COORDINATE WITH
OWNER.
PHASE 4 LIMITS
PHASE 4
LIMITS
PHASE 1
SYMBOLS LEGEND
EXISTING DUCT TO REMAIN
NEW DUCTWORK
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
MANUAL VOLUME DAMPER
FIRE DAMPER
FIRE SMOKE DAMPER
FSD
FD
CONNECT TO EXISTING
TRANSFER ARROW
SMOKE DAMPER
SD
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION
PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL
REFERENCE ONLY.
B. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH
THE OWNERS REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE
OF TWO WEEKS. THIS TIME LENGTH MAY BE LONGER OR SHORTER
FOR SOME SHUTDOWNS AND SHALL BE AT THE OWNERS DISCRETION.
C. PROVIDE ESCUTCHEON PLATES WHERE DUCTS PENETRATE CEILINGS
OR WALLS IN AREAS EXPOSED TO VIEW. ESCUTCHEONS FOR DUCTS
SHALL BE CONSTRUCTED OF SAME MATERIAL AS DUCT. PIPE
ESCUTCHEONS SHALL BE CHROME-PLATED BRASS.
D. LEAVE A MINIMUM CLEARANCE OF 2 INCHES ABOVE DUCTS INSTALLED
IN RATED PARTITIONS TO ALLOW SPACE FOR THE GENERAL
CONTRACTOR TO SEAL THE WALL ABOVE THE DUCTS. DO NOT INSTALL
FLEXIBLE DUCT THROUGH RATED WALLS, BARRIERS OR PARTITIONS.
E. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED
DAMPERS, FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE
DETECTORS, AND SIMILAR ITEMS REQUIRING MAINTENANCE OR
ADJUSTMENT.
F. MECHANICAL CONTRACTOR SHALL REMOVE INSULATION, REPAIR DUCT
LEAKS, AND RE-INSULATE ALL EXISTING DUCT MAINS.
G. MECHANICAL CONTRACTOR SHALL INSTALL MANUAL VOLUME DAMPERS
ON ALL BRANCH DUCTWORK CONNECTIONS.
H. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW
INSULATION TO MATCH ADJACENT INSULATION AND COVERING.
I. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
J. MECHANICAL CONTRACTOR SHALL RELOCATE EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
K. PROVIDE A PRE-TAB OF ALL AREAS AFFECTED BY AHU 18 BEFORE
REMOVAL OF ANY DUCTWORK. ONCE DEMO HAS BEEN ACCOMPLISHED
AND DUCTWORK, HWH, ETC. IS BLANKED OFF, PERFORM A TAB AFTER
DEMO TO ENSURE FLOW RATES OF CATH LAB #1 AND EVERY OTHER
SUPPLY/RETURN IS WITHIN RANGE. AT END OF INSTALLATION OF NEW
WORK FOR THIS AREA, PERFORM A TAB ON THIS INSTALLATION FOR
THE CARDIAC CATH LAB.
L. ALL HANGARS AND SUPPORTS ASSOCIATED WITH REMOVED
DUCTWORK AND PIPING AS WELL AS ANY ABANDONED HANGERS
WITHIN THE SCOPE OF WORK AREAS SHALL BE REMOVED AND
DISPOSED OF OFF SITE.
GENERAL NOTES
REMOVE EXISTING TERMINAL BOX 18-CV-19. REMOVE DUCTWORK
TO MAIN, CAP AND INSULATE. REMOVE ALL ASSOCATED PIPING
CONNECTIONS, AND CAP AT MAIN.
REMOVE EXISTING TERMINAL BOX. REMOVE DUCTOWRK TO MAIN,
CAP AND INSULATE. REMOVE ALL ASSOCATED PIPING
CONNECTIONS AND CAP AT MAIN.
RELOCATE ALL PIPING, CONDUIT, DUCTWORK, ETC. ABOVE CEILING
IN SHADED AREA TO ACCOMODATE FOR NEW AHU SERVING CATH
LAB 2. CONTRACTOR MAY FIELD VERIFY PRIOR TO PRE-BID.
RELOCATE ALL PIPING, CONDUIT, DUCTWORK, ETC. ABOVE CEILING
(NOTE: VERY CONGESTED AERA) IN SHADED AREA TO
ACCOMODATE FOR NEW OA DUCT. CONTRACTOR MAY FIELD
VERIFY PRIOR TO PRE-BID.
REMOVE AND/OR RELOCATE ALL CONDUITS, PIPING, ETC FROM
ABOVE CEILING IN THIS AREA TO ACCOMODATE NEW DUCTS AND
CEILING SYSTEM.
DEMOLITION KEYED NOTES
DUCT CONTINUES OUTSIDE SCOPE OF THIS PROJECT. NO WORK
REQUIRED EXCEPT TAB MENTIONED IN PARAGRAPH K ABOVE.
EXISTING KEYED NOTES
PROJECT LOCATION:
CARDIAC CATH LAB (2ND FLOOR)
BEE STREET
MAIN HOSPITAL ENTRANCE
BEE STREET/BRAVO STREET
MENTAL HEALTH CLINIC ENTRANCE
N
KEY PLAN
SMOKE TIGHT WALL (EXISTING)
1-HR FIRE RATED WALL (EXISTING)
2-HR FIRE RATED WALL (EXISTING)
WALL RATING LEGEND
LEAD-LINED WALL (EXISTING - MAINTAIN & PATCH AS NEEDED IN RENOVATION)
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Firm License Number: F-0674
Project No. 4415
Charlotte Engineers, LLP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% - CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Megan C. Day, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves
E:
\L oc al
R ev it\
\4
- C E
C en tra l M od el
.rv t
8/
/2
:5 4:
P
M
MD-100
MECHANICAL - SECOND FLOOR - DEMOLITION -
DUCTWORK
CATH LAB SITE PREP at
RALPH JOHNSON VAMC
109 BEE STREET CHARLESTON, SC
534-CSI-555
MAY 08, 2020 GAT ESM
1/8" = 1'-0"1 MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK
Revisions: Date:
ADDENDUM 2 08/12/2020
| Sheets |
| M-004 - MECHANICAL - SCHEDULES |
| M-005 - MECHANICAL - SCHEDULES |
| MD-100 - MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK |
| MD-101 - MECHANICAL - SECOND FLOOR - DEMOLITION - PIPING |
| MH-200 - SECOND FLOOR - NEW WORK - DUCTWORK |
| MP-201 - SECOND FLOOR - NEW WORK - PIPING |
File details come from the government source that posted it. Updated .