This electrical drawing package outlines the scope of work for a Cath Lab site prep project at the Ralph Johnson VAMC in Charleston, South Carolina. Key elements of the project include removing existing Cath Lab equipment and replacing it with a new GE system, Stryker boom, and Cleansuite ceiling system. The work will be conducted in four phases with all wall and ceiling devices in certain areas to remain unless noted. New electrical panels, circuit breakers, conduits and other infrastructure will be installed to support the new medical equipment. The project is being undertaken by the Department of Veterans Affairs and managed by the Veterans Health Administration VISN 7.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EP
O
EP
O
J
J
J
CR
CR
CR
PP
PP
PP
J
J
J
CR
CR
CR
J
J
J
J
ATS LL
ATS LS
SWBD HDCC
SWBD HDLS SWBD 2HEDP1
NEW NORMAL ISO PANEL
2INP1
NEW CRITICAL ISO PANEL
2ICP2
NEW CRITICAL ISO PANEL
2ICP1
ATS EE
PANEL A PANEL CCB
PANEL HA
PANEL LSA
PANEL HCCC
PANEL 2LE-AA231 PANEL 2HE-AA231
EX
EX
EX
EX
EX
EX
7 8
CRITICAL ISO PANEL #2
MCC-EA SEC.1-4
NEW AHU-16
480V, 3P
MCA: 25A
MOCP: 30A
30A, 3P, FPN, NEMA 1
30A, 3P, FPN, NEMA 1
2HEDP1-26
NEW AHU-15
480V, 3P, 4.1HP
MCA: 5A
MOCP: 15A
EXEX
EX
H-1 480V, 3P
MCA: 14A
MOCP: 20A
30A, 3P, FPN, NEMA 1
MCC-EA SEC.2-2
CAV-1
120V, 1P
PHASE 3
PHASE 1-3
PHASE 4 LIMITS
PHASE 4
LIMITS
PHASE 1
PHASE 2
2INP1-1
2INP1-2
2ICP1-1
2ICP1-22ICP1-3
2ICP1-4
2ICP2-1
2ICP2-2,3 2INP1-4
2INP1-3
MCC-EA
MCC-NA
175A FED
FROM
2HEDP1
APPROXIMATE LOCATION OF JOHNSON CONTROLS PANEL IN ICU ROOM A247
CONDUIT PROPOSED CONDUIT RUN IS APPROXIMATELY 250'.
EX
2INP1-5
2L12-23
2LE9CC-16
2LE9CC-11
2L12-29
2ICP1-5
EX
EX
EX
EX
EX
EX
EX
EX
STRYKER ITEM E
ANESTHESIA BOOM
STRYKER
ITEM B
SURGICAL
LIGHT
STRYKER ITEM D
TANDEM EQUIPMENT/
MONITOR BOOM
2ICP2-4,5,6,7,8,9
2ICP2-10,11,12,13,14,15
2INP1-6
2ICP1-6 2ICP1-7
GENERAL NOTES
A. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
LOCATION OF CEILING FIXTURES.
B. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION
PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR
GENERAL REFERENCE ONLY.
C. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
D. COORDINATE LIGHT FIXTURE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLANS PRIOR TO
INSTALLATION.
E. CONNECT ALL UNSWITCHED LIGHT FIXTURES AND EXIT
SIGNS AHEAD OF ANY LOCAL SWITCHING AND/OR DIMMERS.
F. CONNECT ALL NEW EXIT SIGNS TO EXISTING LIFE-SAFETY
LIGHTING CIRCUIT HLSA-1.
J. WORK RELATED TO NEW AND REPLACED CORRIDOR DOORS
TO BE A PART OF PHASES 1, 2, AND 3 AS SHOWN. ALL WIRE,
CONDUIT, AND POWER CONNECTIONS OUTSIDE OF CATH
LAB 2 INCLUDING AHU CONNECTIONS AND INSTALLATION OF
NEW ISOLATED POWER PANELS TO BE COMPLETED DURING
PHASES 1-3. WORK INSIDE THE CATH LAB TO BE A PART OF
PHASE 4.
PROVIDE NEW 480V, 150A, 3P ENCLOSED CIRCUIT BREAKER WITH LOCK-OUT/TAG-OUT CAPABILITY.
NEW CEILING MOUNTED LIGHT AND HVAC COMBINATION SYSTEM. COORDINATE WITH VENDOR
DRAWINGS FOR EXACT REQUIREMENTS. COORDINATE WITH UNISTRUT LAYOUT AND STRUCTURAL
STEEL. CONTRACTOR TO PROVIDE NEW 480V CRITICAL CIRCUIT FROM PANEL HCCC.
PROVIDE JUNCTION BOX IN CEILING FOR STRYKER BOOM. COORDINATE WITH FINAL VENDOR
DRAWINGS FOR EXACT CIRCUIT REQUIREMENTS. SEE PROJECT COVER SHEET, REF 3, 4, 5, & 6.
ALL WALL AND CEILING DEVICES IN THIS AREA ARE EXISTING UNLESS OTHERWISE NOTED.
NO WORK IN THIS AREA UNLESS OTHERWISE NOTED.
PROVIDE NEW FUSED DISCONNECT SWITCH SERVING NEW AHU. REFER TO MECHANICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE NEW 100A, 3P SHUNT TRIP CIRCUIT BREAKER WITH INTEGRAL 120V SHUNT TRIP CIRCUIT.
WIRE TO EXISTING EPOS TO MAKE SYSTEM COMPLETE AND FUNCTIONAL.
PROVIDE NEW DISCONNECT SWITCH TO SERVE NEW CHILLED WATER SYSTEM. SEE MECHANICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
ALL EXISTING CRITICAL (RED) RECEPTACLES AND IN WALL DEVICES TO BE RE-WIRED TO NEW CRITICAL ISOLATION PANEL 1ICP1. EXISTING CONDUIT AND WALL BOX TO BE RE-USED. WIRING TO
BE REPLACED ENTIRELY.
ALL NEW CEILING DEVICES INCLUDING BOOMS TO BE WIRED TO NEW CRITICAL ISOLATION PANEL
2ICP1.
PROVIDE JUNCTION BOX ABOVE ACCESSIBLE CEILING FOR 24V CONNECTION TO PACS SYSTEM.
PROVIDE NEW DISCONNECT SWITCH TO SERVE HUMIDIFER. REFER TO MECHANICAL DRAWINGS
FOR ADDITIONAL INFORMATION.
NOT USED
ABOVE COUNTER DUPLEX RECEPTACLES TO BE REPLACED WITH QUAD RECEPTACLES.
PROVIDE 2#10, 1#10G IN 3/4"C FOR NEW LIGHT SIGNALING BOX. COORDINATE JUNCTION BOX
LOCATION WITH EQUIPMENT VENDOR.
CONTRACTOR TO COORDINATE WITH MECHANICAL INSTALLER IN THIS AREA TO RELOCATE
EXISTING ELECTRICAL CONDUIT AND DEVICES THAT ARE REQUIRED TO BE RELOCATED FOR
MECHANICAL EQUIPMENT INSTALLATION.
LOCATION OF RELOCATED MEDGAS ZONE VALVE BOX. COORDINATE WITH MEDGAS INSTALLER TO
RECONNECT LOCAL MEDGAS ALARM STATION CIRCUIT FOR NEW MED GAS VALVE BOX.
LOCATION SHOWN FOR AHU IS APPROXIMATE. COORDINATE WITH COR AND GE EQUIPMENT
INSTALLER TO ENSURE CORRECT SPACING AND CLEARANCE FOR ALL EQUIPMENT TO BE
INSTALLED IN THIS LOCATION.
PROVIDE NEW DEDICATED RECEPTACLE TO POWER NEW EQUIPMENT. COORDINATE CIRCUIT
SELECTION AND LOCATION WITH COR PRIOR TO INSTALLATION. CONNECT WITH 2#12AWG, 1#12G IN 3/4"C.
NEW WORK KEYED NOTES
DRAWINGS. SEE SCHEDULE FOR TYPE (*).
CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON
LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,
LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.
CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT*
LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.
SEE SCHEDULE FOR TYPE (*).*
HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.* * *
LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).
SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).
SINGLE POLE SWITCH, MOUNTED 42" AFF TO CENTER OF DEVICE.S
EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED
OTHERWISE. CONNECT UNSWITCHED.
DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 42" AFF TO CENTER OF OUTLET
OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES
OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY
DUPLEX RECEPTACLE, MOUNTED 42" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH
INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
POWER SYSTEM.
CONNECTED TO THE EMERGENCY POWER SYSTEM.
JUNCTION OR PULL BOX. W = WEATHERPROOF.J
FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.15
PANELBOARD SURFACE MOUNTED.
PANELBOARD FLUSH MOUNTED.
PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.PP
CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.CR
EMERGENCY SYSTEM OFF PUSH BUTTONEPO
DD FIRE ALARM DUCT MOUNTED SMOKE DETECTOR.
SYMBOLS LEGEND
RL = EXISTING DEVICE TO BE RELOCATED.
DASHED SYMBOLS INDICATE EXISTING DEVICES.
RLD = RELOCATED DEVICE SHOWN IN FINAL LOCATION.
RM = EXISTING DEVICE TO REMAIN.
RM
RM
RV = EXISTING DEVICE TO BE REMOVED.
RP = EXISTING DEVICE TO BE REPLACED WITH NEW DEVICE.
EX = EXISTING DEVICE
PROJECT LOCATION:
CARDIAC CATH LAB (2ND FLOOR)
BEE STREET
MAIN HOSPITAL ENTRANCE
BEE STREET/BRAVO STREET
MENTAL HEALTH CLINIC ENTRANCE
N
KEY PLAN
SMOKE TIGHT WALL (EXISTING)
1-HR FIRE RATED WALL (EXISTING)
2-HR FIRE RATED WALL (EXISTING)
WALL RATING LEGEND
LEAD-LINED WALL (EXISTING - MAINTAIN & PATCH AS NEEDED IN RENOVATION)
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Firm License Number: F-0674
Project No. 4415
Charlotte Engineers, LLP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% - CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Megan C. Day, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves
D :\l oc al re vi t m od el s\
\4
- C
E C en tra l M od el .rv t 8/
/2
:4
5:
P M
EP-201
ELECTRICAL - SECOND FLOOR - POWER &
SYSTEMS
CATH LAB SITE PREP at
RALPH JOHNSON VAMC
109 BEE STREET CHARLESTON, SC
534-CSI-555
MAY 08, 2020 CLH JCE
1/8" = 1'-0"1 ELECTRICAL - FIRST FLOOR - NEW WORK - POWER & SYSTEMS
Revisions: Date:
ADDENDUM 2 08/12/2020
| Sheets |
| ED-100 - ELECTRICAL - SECOND FLOOR - DEMOLITION |
| EP-201 - ELECTRICAL - SECOND FLOOR - POWER & SYSTEMS |