M-005 - MECHANICAL - SCHEDULES.pdf
PDF 230 KB Posted
- Attached to
- CATH LAB Federal contract opportunity
- Solicitation number
- 36C24720B0024
About this file
This document contains mechanical schedules and sequences of operation for an air handling unit to be installed at the Ralph Johnson VAMC as part of a Cath Lab renovation project. Key details include specifications for a Daikin modular air handling unit with a 400 CFM supply fan, 5 ton cooling coil, and 150 MBH hot water heating coil to serve the Cath Lab. The unit will be controlled by the existing Siemens BAS system. Filters, coils, fans, and other components are scheduled with technical details. Sequences of operation are provided for constant volume control of the air handling unit, including discharge air temperature control, static pressure control, and humidification. The related federal contract opportunity is for the Cath Lab renovation project at the Ralph Johnson VAMC, which includes replacement of existing Cath Lab equipment with a new GE system, Stryker boom, and Cleansuite ceiling system.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F
E
D
C
B
A
A
B
C
D
E
F
MIXING SECTION
PRE-FILTER (MERV 8)
COOLING COIL
HEATING COIL
SUPPLY FAN
FINAL FILTER (MERV 17)
SA
RA
OA
PROVIDE 6" ALUMINUM I-BEAMS FOR SUPPORT
CM
CM
TO FIRE
ALARM
SYSTEM
SUPPLY
BAS CONTROL CABINET
OUTSIDE AIR DUCT
AIR HANDLING UNIT CONTROL SCHEMATIC
HS
DP
TS
COOLING
COILFILTER SUPPLY FAN
PRE-
NC
TS-3
L H
DP-1
L
INLET (TYP.)
H
V-2B
DP
FILTER
FINAL
L H
DP-2
SPLL
FLOW SENSOR
ON EACH FAN
CHILLED
WATER
CONTROL
VALVE
HSTS
AIR
BLENDER
TS
HUMIDIFIER
HUMIDIFIER
CONTROL
VALVE
TS
FREEZESTAT
SEQUENCE OF OPERATIONS
AIR HANDLING EQUIPMENT
A. CONSTANT AIR VOLUME AIR HANDLING UNIT - AHU-16 SEQUENCE OF OPERATION
1. THE AHU WILL START ON COMMAND FROM THE BAS, WHEN THE HOA SWITCH IS IN THE
"AUTO" MODE. THE AHU MAY ALSO BE STARTED LOCALLY WHEN THE HOA SWITCH IS
PLACED IN THE "HAND MODE".
2. THE AHU SHALL STOP WHEN COMMANDED BY THE BAS, OR WHEN THE HOA SWITCH IS
PLACED IN "OFF". THE UNIT SHALL SHUT DOWN BY FIRST COMMANDING OFF THE FAN
ECM, WHEN THE FAN IS PROVEN OFF (BY THE CT INPUT) THE UNIT SMOKE DAMPERS
SHALL BE CLOSED, AFTER AN ADJUSTABLE TIME DELAY.
3. THE AHU WILL STOP (FAN OFF) AND AN ALARM BE ROUTED TO THE OPERATORS
WORKSTATION WHEN ANY OF THE FOLLOWING CONDITIONS OCCUR:
a. IF EMERGENCY STOP SWITCH IS IN "PUSHED" POSITION, THEN THE SWITCH MUST BE
MANUALLY "PULLED" IN ORDER TO RESTART AHU. RECONNECT TO THE EXISTING
ESS, IF AVAILABLE.
b. IF THE VAPOR TENSION LOW LIMIT THERMOSTAT ("FREEZESTAT") SENSES A
TEMPERATURE BELOW 35 DEGREES (SHALL REQUIRE A MANUAL RESET)
c. SMOKE MODE - IF THE SMOKE DETECTORS (FURNISHED BY DIVISION 28) INSTALLED
IN THE SUPPLY AIR STREAMS DETECT SMOKE OR A SPACE DETECTOR DETECTS
SMOKE. THE UNIT SHALL BE SHUTDOWN. UNIT SHALL RESTART WHEN THE ALARM
CLEARS.
4. DISCHARGE CONTROL
a. THE DISCHARGE AIR TEMPERATURE SENSOR IS LOCATED AT THE UNIT'S
DISCHARGE PLENUM. CONTROL DISCHARGE AIR TEMPERATURE TO 52 DEGREES F
(ADJUSTABLE), BY MODULATING THE COOLING COIL CONTROL VALVE.
b. AHU COOLING COIL SHALL BE CONTROLLED AS FOLLOWS:
UPON A RISE IN THE SUPPLY AIR TEMPERATURE, THE CONTROL VALVE SHALL BE
MODULATED TOWARD ITS FULL-OPEN POSITION. UPON A FALL IN THE SUPPLY AIR
TEMPERATURE THE CONTROL VALVE SHALL BE MODULATED TOWARDS ITS CLOSED
POSITION. WHEN THE AIR HANDLING UNIT IS SHUTDOWN THE CONTROL VALVE
SHALL CLOSE.
AHU HEATING COIL SHALL BE CONTROLLED AS FOLLOWS:
• UPON FALL IN MIXED AIR TEMPERATURE BELOW 50°F, THE CONTORL VAVLE ON
HEATING COIL SHALL MODULATE TOWARD FULL OPEN POSITION TO MAINTAIN
32°F DISCHARGE AIR TEMPERATURE.
• DEHUMIDIFICATION MODE: UPON CALL FOR HIGH HUMIDITY IN RETURN DUCT
MOUNTED HUMIDITY SENSOR, COOLING COIL SHALL OPERATRE TO FULL OPEN
POSITION AND REHEAT VALVE SHALL MODULATE TO MAINTAIN 52°F DISCHARGE
TEMPERATURE.
• IF WALL THERMOSTAT CALLS FOR HEATING
5. SUPPLY FAN CONTROL
a. MAINTAIN THE SUPPLY AIR DUCT STATIC PRESSURE SENSOR WITH THE LOWEST
READING AT SET POINT. A STATIC PRESSURE TRANSMITTER SHALL BE LOCATED 2/3
DOWN THE LONGEST DUCT. RECONNECT EXISTING.
b. IF THE STATIC PRESSURE SENSOR BECOMES UNRELIABLE, THE CONTROLLER WILL
COMMAND THE SUPPLY FAN VFD TO ITS MINIMUM SPEED AND AN ALARM SHALL BE
ROUTED TO THE OPERATOR'S WORKSTATION.
RESET THE DUCT STATIC PRESSURE SENSOR TO KEEP AT LEAST ONE VAV BOX SUPPLY AIR
DAMPER AT 95% OPEN.
6. HUMIDIFIER CONTROL
a. THE HUMIDIFIER SHALL ONLY BE ENABLED WHEN THE AHU AIRFLOW IS PROVEN.
CONTROL THE HUMIDIFIER BASED ON INPUT FROM A RETURN AIR HUMIDITY SENSOR
WITH AN ADJUSTABLE SETPOINT. INPUT FROM A DISCHARGE HUMIDITY SENSOR
SHALL BE USED TO REDUCE HUMIDIFIER OUTPUT TO PREVENT AIR SATURATION.
HUMIDIFIER CONTROL VALVE SHALL MODULATE TO MAINTAIN SET
POINT.(CUSTOMER ADJUSTABLE).
MANUFACTURER
SERVES
FILTER PRESSURE DROP (INWG) (CLEAN)
FILTER AREA (SQUARE FEET)
FILTER MINIMUM EFFICIENCY
FILTER TYPE
REMARKS:
LOCATION
SYSTEM NO.
REMARKS: BASED ON 180oF EWT AND 160oF LWT.
REMARKS:
REMARKS: FAN SHALL BE PLENUM TYPE.
SQ. FT. FACE AREA MIN.
SENSIBLE LOAD (MBH)
E.A.T. D.B./W.B. (°F) L.A.T. D.B./W.B. (°F)
FINS PER INCH MIN.
SQ. FT. FACE AREA MAX.
FACE VELOCITY MAX.
HEATING CAPACITY (MBH)
L.A.T. D.B. °F E.A.T. D.B. °F
TYPE COIL
TOTAL CFM
ROWS MIN.
TYPE COIL
RPM APPROX.
TYPE DRIVE
HP MIN/VOLT/PH
TOTAL LOAD (MBH)
TOTAL CFM
TOTAL CFM (CFM PER FAN)
EXTERNAL STATIC PRESSURE (IN W.G.)
SYSTEM TYPE
OUTSIDE AIR CFM (MINIMUM/ECONOMIZER)
MODEL NUMBER
ELECTRICAL CHARACTERISTICS
DAIKIN
CONSTANT VOLUME
CATH LAB 2
AHU-16
400/NA
ECM MOTOR
2,600 2.0
5.5
80/67 54.4/53.7
CHILLED WATER
72.6
HOT WATER
92.8
MERV 8
6.3 FT2
0.18 "
2,600
PLEATED
2,600
CAC006GBAM
460V/3PH
C O
O
LI
N G
C O
IL
SU
PP
LY
F
AN
H
EA
TI
N
G C
O
IL
PR
EF
IL
TE
R
MODULAR AIR HANDLING UNIT SCHEDULE GENERAL NOTES:
1.
2.
FILTERS SHALL BE PROVIDED BY THE UNIT
MANUFACTURER. ONE SET OF NEW FILTERS
SHALL BE INSTALLED IN EACH FILTER BANK
WHEN BUILDING IS TURNED OVER TO OWNER
AND ONE COMPLETE SET SHALL BE PROVIDED
FOR OWNER'S STOCK.
3.
REFER TO UNIT PLANS FOR ARRANGEMENT OF
UNITS, ACCESS DOORS, ETC.
REFER TO SPECIFICATIONS FOR SPECIFIC
REQUIREMENTS FOR ACCESSORIES AND DETAILS
OF CONSTRUCTION FOR THE AIR HANDLING
UNIT.
4.
5.
6.
UNIT WILL BE PROVIDED WITH DOUBLE WALL
CONSTRUCTION.
UNIT WILL BE PROVIDED WITH STAINLESS STEEL
DRAIN PANS.
REMARKS:
VIBRATION ISOLATORS (FANS)
DISCHARGE AIR PLENUM W/AD
MIXING SECTION W/AD
YES
YES
YES
AC
C
ES
S.
REMARKS:
PREFILTER MIN. EFF.
FINAL FILTER MIN. EFF.
FINAL FILTER TYPE
FINAL FILTER (SF)
MERV 17 (99.97%)
HEPA
6.0 FT2
MERV 8
-FI
N
AL
F
IL
TE
R
FLUID FLOW RATE (GPM) 14.2
1.0MAX WATER P.D. (FT.)
FILTERS SHALL BE SEALED INTO A METAL
HEADER WITH A GASKET INSTALLED ON THE
METAL HEADER. FILTERS SHALL BE TESTED
IN ACCORDANCE WITH ANSI/ASHRAE
STANDARD 52.2.
AA237A
4.04
TOTAL STATIC
6.27".
HEATING
COIL
ECM
CONTROLS NOTES:
1. ALL CONTROLS SHALL BE AN EXTENSION OF THE EXISTING SIEMENS CONTROLS SYSTEM.
UPDATE GRAPHICS FOR ALL ADDED EQUIPMENT, DEVICES, TERMINAL UNITS, SENSORS,
ETC.
2. CONTACT SIEMENS REPRESENTATIVE ED REAMER (803)765-9070 FOR INFORMATION AND
DETAILS TO CONNECT INTO VAMC CHARLESTON BAS.
3. CMI TO UPDATE CHARLESTON BAS SYTEM TO REMOVE ANY OLD DEVICES, INSTALL NEW
DEVICES AND UPDATE GRAPHICS.
TS HS
V-2B
HEATING
WATER
CONTROL
VALVE
NC
TO FIRE
ALARM
SYSTEM, SHUT
DOWN
CONTACT
SD
SD-1
1NTS
AIRFLOW SHALL BE BALANCED TO 1900 CFM
FOR AIRFLOW DISTRIBUTION
7.
M
OUTSIDE AIR
DAMPER
M
RETURN AIR
DAMPER
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Firm License Number: F-0674
Project No. 4415
Charlotte Engineers, LLP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% - CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Megan C. Day, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves
E:
\L oc al
R ev it\
\4
- C E
C en tra l M od el
.rv t
8/
/2
:5 4:
P
M
M-005
MECHANICAL - SCHEDULES CATH LAB SITE PREP at
RALPH JOHNSON VAMC
109 BEE STREET CHARLESTON, SC
534-CSI-555
MAY 08, 2020 GAT ESM
1/4" = 1'-0"2 DETAILS-AHU-16
Revisions: Date:
ADDENDUM 2 08/12/2020
| Sheets |
| M-004 - MECHANICAL - SCHEDULES |
| M-005 - MECHANICAL - SCHEDULES |
| MD-100 - MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK |
| MD-101 - MECHANICAL - SECOND FLOOR - DEMOLITION - PIPING |
| MH-200 - SECOND FLOOR - NEW WORK - DUCTWORK |
| MP-201 - SECOND FLOOR - NEW WORK - PIPING |
File details come from the government source that posted it. Updated .