This document consists of mechanical schedules and specifications for a Cath Lab replacement project at a Department of Veterans Affairs medical center. Key details include replacement of existing Cath Lab equipment with a new GE system and Stryker boom, installation of a CleanSuite ceiling system, and demolition and new work ductwork and piping. Additional specifications cover terminal unit schedules by size and manufacturer, air handling unit schedules with notes on accessories, and requirements for a hospital laminar flow diffuser system with integrated LED lighting. The project is located at the Ralph H. Johnson VA Medical Center in Charleston, South Carolina and involves the Veterans Health Administration and Veterans Integrated Service Network 7.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TERMINAL
NO.
CFM E.A.T.
(°F)
HEATING
L.A.T.
(°F)
MINIMUM
OPERATING
PD (in.wg)
GPM MBH E.W.T.
(°F) L.W.T.
(°F)
WATER
PRESSURE
DROP(FT)MAX. MIN.
ROOM NUMBER AND NAME
AIR
RUNOUT
SIZE
UNIT SIZE
WATER
RUNOUT
SIZE
55 160 140CAV BOX 1 435 435 8 8 100 .20 2.2 21.7 .76 AA221 - SCRUB AREA
ROWS
REHEAT
GENERAL NOTES
1. BOXES SHALL HAVE PIPE CONNECTIONS ON SAME SIDE AND BE STRAIGHT COPPER FITTINGS.
2. COIL AND BOX SIZE MAY BE INCREASED TO MEET REQUIRED CONDITIONS; BUT SHALL NOT BE DECREASED FROM SIZE SHOWN.
3. BOXES SHALL BE SET FOR MAXIMUM CFM SHOWN ON PLANS.
4. DUCT CONNECTIONS TO BOXES SHALL BE SAME SIZE AS BOX INLET UNLESS SHOWN OTHERWISE.
5. MAXIMUM WATER PRESSURE DROP SHALL BE 4 FEET.
6. VARIABLE VOLUME BOXES SHALL OPERATE DOWN TO 50% OF MAXIMUM FLOW.
7. CONSTANT VOLUME BOXES SHALL BE THE SAME BOX USED FOR VARIABLE VOLUME BOX EXCEPT CFM SHALL BE LOCKED AT CAPACITY SHOWN. BOX SHALL NOT OPERATE AS
VARIABLE VOLUME.
8. CONTROLS SHALL BE SIEMENS PROVIDED BY CONTROLS CONTRACTOR AND INSTALLED BY CMI. CONTACT ED REAMER AT (803) 765-9070..
9. BASIS OF DESIGN SHALL BE PRICE SINGLE DUCT VARIABLE OR CONSTANT VOLUME SDV SERIES. APPROVED EQUALS: KREUGER, ENVIRO-TEC, & NAILOR.
10. MAXIMUM NC LEVEL OF 30 ON ALL BOXES. PROVIDE SOUND ATTENUATOR AS REQUIRED.
11. PROVIDE DIFFERENTIAL AIRFLOW SWITCH.
3/4"
TERMINAL UNIT SCHEDULE
SYMBOL SIZE TYPE
111-250 CFM 10"x8"
0-110 CFM 8"x4"
251-480 CFM 14"x10"
481-650 CFM 18"x12"
651-835 CFM 20"x14"
836-1400 CFM 24"x18"
PRICE 530/630
PRICE 530/630
PRICE 530/630
PRICE 530/630
PRICE 530/630
PRICE 530/630
ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 5145/6145, TITUS 350FL/350RL.
SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
SYMBOL REGISTER SIZE 24"x24" TYPE
136-210 CFM 8" ROUND NECK
0-135 CFM 6" ROUND NECK PRICE PDDR
211-325 CFM 10" ROUND NECK
326-475 CFM 12" ROUND NECK
651-840 CFM 16" ROUND NECK
841-2000 CFM 22"x22" NECK
476-650 CFM 14" ROUND NECK
CFM
A
CFM
B
CFM
C
CFM
D
CFM
E
CFM
F
CFM
G
PRICE PDDR
PRICE PDDR
PRICE PDDR
PRICE PDDR
PRICE PDDR
PRICE PDDR
NOTES:
1. ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 4360, TITUS PAR. SEE
ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. REGISTERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE
MOUNTED FRAMES.
SYMBOL REGISTER SIZE 24"x24" TYPE
136-210 CFM 8" ROUND NECK
0-135 CFM 6" ROUND NECK PRICE PDDR
211-325 CFM 10" ROUND NECK
326-475 CFM 12" ROUND NECK
651-840 CFM 16" ROUND NECK
841-2000 CFM 22"x22" NECK
476-650 CFM 14" ROUND NECK
CFM
CFM
CFM
CFM
CFM
CFM
CFM
PRICE PDDR
PRICE PDDR
PRICE PDDR
PRICE PDDR
PRICE PDDR
PRICE PDDR
NOTES:
1. ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 4360, TITUS PAR. SEE
ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. GRILLES LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE
MOUNTED FRAMES.
12"x12" REGISTER
CFM
H PRICE PDDR0-135 CFM 6" ROUND NECK
SYMBOL TYPICAL MODULE SIZE - 24"x24" TYPE
136-210 CFM 9"x9" FACE 8" ROUND NECK
0-135 CFM 6"x6" FACE 6" ROUND NECK PRICE SMD
211-325 CFM 12"x12" FACE 10" ROUND NECK
326-475 CFM 12"x12" FACE 12" ROUND NECK
476-650 CFM 15"x15" FACE 14" ROUND NECK
CFM
CFM
CFM
CFM
CFM
CFM
CFM
650-840 CFM 18"x18" FACE 16" ROUND NECK
841-1125 CFM 18"X18" FACE & NECK
PRICE SMD
PRICE SMD
PRICE SMD
PRICE SMD
PRICE SMD
PRICE SMD
NOTES:
1. ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 6500, TITUS TDC. SEE
ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. DIFFUSERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE
MOUNTED FRAMES.
3. PROVIDE SR MODEL ROUND NECK ADAPTER.
CFM RANGE, FACE SIZE, & NECK SIZE
CFM
0-120 CFM 6"X6" FACE 6" ROUND NECK PRICE SMD
CFM
121-240 CFM 9"X9" FACE 8" ROUND NECK PRICE SMD
12"x12" REGISTER
12"x12" REGISTER
CFM
8 PRICE PDDR
CFM
9 PRICE PDDR
CFM
10 PRICE PDDR
0-120 CFM 6" ROUND NECK
12"x12" REGISTER
0-135 CFM 6" ROUND NECK
24"x12" REGISTER
0-130 CFM 6" ROUNDNECK
16"x16" REGISTER
SIDEWALL RETURN REGISTER
PERFORATED EXHAUST REGISTERS
PERFORATED RETURN REGISTERS
LOUVERED SUPPLY DIFFUSER
CFM
CFM
CFM
CFM
CFM
CFM
CFM
0-130 CFM 6"X6" FACE 6" ROUND NECK PRICE SMD24"x12" REGISTER
LOCATION TONS CFM HUMIDIFIER
TYPE
FAN
H.P.
FLA/
MOCP
NOTES
VOLTS/
PHASE
TAG WATER
SUPPLY
1. PROVIDE WITH DISCONNECT SWITCH
2. PROVIDE WITH CONDENSATE PUMP
3. PROVIDE WITH 2" MERV 8 FILTER
4. PROVIDE WITH HOT WATER RE-HEAT COIL
5. PROVIDE WITH INTEGRAL THERMOSTAT.
6. PROVIDE WITH MODULATING 3-WAY CONTROL VALVES. SET VALVE TO ALLOW CONTINUOUS FLOW OF CHILLED AND/OR HOT WATER (MIN 2GPM) AT ALL TIMES.
EQUIPMENT 8 4400 ELECTRIC 4.1 11.0/20 460/3ØAHU-15 1 1/8"
REHEAT
TYPE
HOT WATER
E.W.T L.W.T P.D. (FT)
42° 52° MAX 19
ROWS
CAPACITY
TOTAL
(MBH)
CAPACITY
SENSIBLE
(MBH)
94.17 87.35
FAN SP
(IN)
0.5
MANUFACTURER
STULZ COS-096-C-U-EC
COOLING COIL
E.W.T L.W.T P.D. (FT)
180° 160° 5.3
ROWS
CAPACITY
TOTAL
(MBH)
94.2
HEATING COILEQUIPMENT ROOM A/C UNIT SCHEDULE
TAG SERVICE TYPE
NOMINAL
CAPACITY
(LB./HR.)
POWER
RATING
(OUTPUT)
MANUFACTURER & MODEL NO.
NOTES
1. PROVIDE UNITS WITH SHORT ABSORPTION MANIFOLD (SAM-E), CONDENSATE COOLER OPTION.
2.
3. ALL VENTING SHALL BE PROVIDED BY HUMIDIFIER MANUFACTURER AND INSTALLED BY MECHANICAL CONTRACTOR.
4. PROVIDE BACNET CARD FOR CONTROLS MONITORING. ONBOARD CONTROLS SHALL CONTROL OPERATION OF THE UNIT.
5. PROVIDE REMOTE TEMPERATURE/HUMIDITY SENSOR AND INTERFACE TO BE INSTALLED IN BUILDING. UNIT SHALL BE
PROVIDED WITH INTEGRAL DRAIN COOLER. REFER TO STRUCTURAL PLANS FOR EQUIPMENT SUPPORT ON ROOF.
6. H-1 MANIFOLD SHALL BE INSTALLED IN DUCTWORK, SEE PLANS.
DESIGN
CAPACITY
(LB./HR.)
STEAM ELECTRODE HUMIDIFIER SCHEDULE
OA
DESIGN
TEMP/RH
7.
PROVIDE DISCONNECT SWITCH.
VOLT/
PHASE
H-1 55°F/60%AHU-16 ELECTRODE 30 24.5 11.2 KW 460/3ø NORTEC EL 030
FIELD MEASURE DUCT FOR MANIFOLD SIZES. ALL DISPERSION TUBES SHALL BE SIZED FOR NO LONGER THAN 18" DISPERSION DISTANCE (WHERE
POSSIBLE).
A. BASIS OF DESIGN: PRICE INDUSTRIES, INC.
1. HOSPITAL OR LAMINAR FLOW DIFFUSER SYSTEM WITH INTEGRATED LED LIGHTING
B. GENERAL:
1. THE INTEGRATED PLENUM CEILING SYSTEM SHALL INCORPORATE LAMINAR FLOW DIFFUSERS, INTEGRATED HIGH PERFORMANCE LED LIGHTING AND A COMMON PLENUM ALL INTO A SINGLE
MODULAR ASSEMBLY DESIGN, TO ACT AS A SINGLE LARGE DIFFUSER ARRAY. THE COMMON
PRESSURIZED PLENUM DESIGN RESULTS IN FEWER INLET CONNECTIONS, AND REDUCED PLENUM
HEIGHT.
2. ALL COMPONENTS OF THE INTEGRATED CEILING SYSTEM SHALL BE FROM A SINGLE MANUFACTURER
AND SHALL BE IN ACCORDANCE WITH ASHRAE STANDARD 170 AND FGI 2018.
C. HOSPITAL OR LAMINAR FLOW DIFFUSER SYSTEM WITH INTEGRATED LED LIGHTING: [PRICE MODEL USA]:
1. SYSTEM CONSTRUCTION:
a. THE INTEGRATED PLENUM SHALL INCORPORATE LAMINAR FLOW DIFFUSERS, PROVIDING NON- ASPIRATING, UNIDIRECTIONAL AIRFLOW ABOVE THE STERILE ZONE, COMPLETE WITH ROOM SIDE
ADJUSTABLE APERTURE PLATE DAMPERS WITH LOCKING MECHANISM.
b. SYSTEM SHALL INCLUDE INTEGRATED LED LIGHTING AND CERTIFIED TO MEET UL1598/CSA 22.2 NO.
250.0 STANDARD FOR AIR-HANDLING LUMINAIRE.
c. LAMINAR DIFFUSER FACE FRAME SHALL BE 1/8” THICK ALUMINUM EXTRUSION WITH WELDED MITER CORNERS AND SECURED WITH FOUR (4) STAINLESS STEEL COUNTER-SUNK BOLTS AND STAINLESS
STEEL RETAINING CABLES.
d. LAMINAR DIFFUSER FACE SHALL BE COMPOSED OF 1/8” THICK FIRE-RESISTANT ENGINEERED POLYMER WITH 13% FREE AREA. PERFORATED FACE AREA SHALL BE AT LEAST 82% OF NOMINAL
SQUARE FOOTAGE FOR EACH DIFFUSER.
e. THE INTEGRATED PLENUM SHALL BE PROVIDED WITH 14 GAUGE ALUMINUM CONSTRUCTION AND
FULLY WELDED VERTICAL SEAMS
f. LAMINAR MODULES WILL COME WITHOUT HEPA FILTERS WITH GEL SEAL, PROVIDING NON-
ASPIRATING, UNIDIRECTIONAL AIRFLOW ABOVE THE STERILE ZONE.
g. EACH INTEGRATED PLENUM DIFFUSER MODULE SHALL INCLUDE FOUR (4) EYE BOLTS FOR HANGER
WIRE SUPPORT.
h. THE INTEGRATED PLENUM INLET COLLARS SHALL BE SIZED BASED ON AIRFLOW REQUIREMENTS
FOR THE INTENDED SPACE.
i. MODULES SHALL BE FACTORY ASSEMBLED UP TO 48 INCHES X 120 INCHES FOR ATTACHMENT TO
ADDITIONAL MODULES IN THE FIELD BY OTHERS.
2. INTEGRATED LIGHTING:
a. EACH LAMINAR DIFFUSER MODULE SHALL INCLUDE INTEGRATED LED LIGHTING, MOUNTED SO AS
TO NOT INTERFERE WITH THE AIRFLOW OF THE SYSTEM. LED STRIP LIGHTS AND FLUORESCENT
TUBES DIRECTLY IN THE AIRFLOW PATH ARE NOT ACCEPTABLE.
b. THE ENTIRE PERFORATED FACE OF THE LAMINAR DIFFUSER SHALL BE FULLY EQUALIZED WITH
LIGHT. SEPARATE LED CHANNELS SEPARATING LAMINAR DIFFUSERS OR EMBEDDED INTO THE
DIFFUSER FRAMES ARE NOT ACCEPTABLE.
c. LED LIGHTING SHALL HAVE AN EFFICIENCY GREATER THAN 100 LUMENS PER WATT, AND LIGHTING POWER SHALL BE EQUIVALENT TO 25 WATTS PER METER FOR INDIVIDUAL LED STRIP LIGHTING.
d. LED LIGHTING SHALL BE IP67 RATED AND NOT SUSCEPTIBLE TO DUST AND LIQUID CLEANING
AGENTS.
e. LED LIGHTING SHALL ACHIEVE COLOR RENDERING INDEX (CRI) OF 85 OR HIGHER.
f. LED LIGHTING SHALL BE RATED FOR L80 > 60,000 HOURS BASED ON LM-80 TESTING.
g. LED LIGHTING SHALL BE CERTIFIED TO MEET UL2108 AND MEET FIRE/SMOKE RATINGS OF UL2043.
h. PHOTOMETRIC IES FILES, ACHIEVED WITH A TYPE-C GONIOMETER, SHALL BE AVAILABLE TO
VALIDATE LIGHTING PERFORMANCE.
i. LED LIGHTING SHALL BE PAIRED WITH DRIVERS SUPPLIED FROM THE INTEGRATED LAMINAR FLOW
DIFFUSER ASSEMBLY MANUFACTURER. DRIVER SHALL BE CAPABLE OF 10% DIMMING, AND PWM
DIMMING SHALL MEET IEEE1789.
j. LED DRIVER SHALL COMPLY WITH UL8750/CSA 22.2 NO. 223-M91.
k. LED DRIVER SHALL ACHIEVE TOTAL HARMONIC DISTORTION (THD) < 20% AT MAXIMUM POWER
3. PAINT FINISH:
a. THE CEILING SYSTEM FINISH SHALL HAVE A B12 WHITE BAKED-ON POWDER COAT FINISH MATCHING
THE LAMINAR FLOW DIFFUSERS AND FILL-IN PANELS.
1. THE PAINT FINISH MUST DEMONSTRATE NO DEGRADATION WHEN TESTED IN ACCORDANCE
WITH ASTM D1308 (COVERED AND SPOT IMMERSION) AND ASTM D4752 (MEK DOUBLE RUB) PAINT
DURABILITY TESTS.
2. THE PAINT FILM THICKNESS SHALL BE A MINIMUM OF 2.0 MILS.
3. THE FINISH SHALL HAVE A HARDNESS OF 2H.
4. THE FINISH SHALL WITHSTAND A MINIMUM SALT SPRAY EXPOSURE OF 1000 HOURS.
5. THE FINISH SHALL HAVE AN IMPACT RESISTANCE OF 80 IN-LB.
HOSPITAL OR LAMINAR FLOW DIFFUSER SYSTEM WITH
INTEGRATED LED LIGHTING
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Firm License Number: F-0674
Project No. 4415
Charlotte Engineers, LLP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% - CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Megan C. Day, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves
E:
\L oc al
R ev it\
\4
- C E
C en tra l M od el
.rv t
8/
/2
:5 4:
P
M
M-004
MECHANICAL - SCHEDULES CATH LAB SITE PREP at
RALPH JOHNSON VAMC
109 BEE STREET CHARLESTON, SC
534-CSI-555
MAY 08, 2020 GAT ESM
Revisions: Date:
ADDENDUM 2 08/12/2020
| Sheets |
| M-004 - MECHANICAL - SCHEDULES |
| M-005 - MECHANICAL - SCHEDULES |
| MD-100 - MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK |
| MD-101 - MECHANICAL - SECOND FLOOR - DEMOLITION - PIPING |
| MH-200 - SECOND FLOOR - NEW WORK - DUCTWORK |
| MP-201 - SECOND FLOOR - NEW WORK - PIPING |
File details come from the government source that posted it. Updated .