M-004 - MECHANICAL - SCHEDULES.pdf

PDF 222 KB Posted

Attached to
CATH LAB Federal contract opportunity
Solicitation number
36C24720B0024
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7

About this file

This document consists of mechanical schedules and specifications for a Cath Lab replacement project at a Department of Veterans Affairs medical center. Key details include replacement of existing Cath Lab equipment with a new GE system and Stryker boom, installation of a CleanSuite ceiling system, and demolition and new work ductwork and piping. Additional specifications cover terminal unit schedules by size and manufacturer, air handling unit schedules with notes on accessories, and requirements for a hospital laminar flow diffuser system with integrated LED lighting. The project is located at the Ralph H. Johnson VA Medical Center in Charleston, South Carolina and involves the Veterans Health Administration and Veterans Integrated Service Network 7.

View the file

Other files for this federal contract opportunity

Other files attached to CATH LAB, newest first.
File Type Posted
Project 534-CSI-555 Cardiac Lab Prep Pre-Bid Sign-In.pdf PDF
PreBid Site Visit Sign In sheet.doc DOC document
Project No. 534-CSI-555 Card Cath Lab Questions from 8-26-2020.docx DOCX document
36C24720B0024 A00003.pdf PDF
28 13 00 Physical Access Control System.pdf PDF
Project 534-CSI-555 Answers to Questions.pdf PDF
26 08 00 Commissioning of Electrical Systems.pdf PDF
EP-201 - ELECTRICAL - SECOND FLOOR - POWER SYSTEMS.pdf PDF
280800 Commissioning of Electronic Safety and Security Systems.pdf PDF
Addendum 2 - Project No. 534-CSI-555.pdf PDF
ED-100 - ELECTRICAL - SECOND FLOOR - DEMOLITION.pdf PDF
270800 Commissioning of Communications Systems.pdf PDF
01 91 00 Commissioning.pdf PDF
226300 - GAS SYSTEMS FOR LABORATORY AND HEALTHCARE FACILITIES.pdf PDF
S02 36C24720B0024 A00002.pdf PDF
MD-101 - MECHANICAL - SECOND FLOOR - DEMOLITION - PIPING.pdf PDF
230711 HVAC INSULATION.pdf PDF
000110 Specifications.pdf PDF
MP-201 - SECOND FLOOR - NEW WORK - PIPING.pdf PDF
M-005 - MECHANICAL - SCHEDULES.pdf PDF
MD-100 - MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK.pdf PDF
MH-200 - SECOND FLOOR - NEW WORK - DUCTWORK.pdf PDF
Card Cath Lab Prep Dwgs ED100 ED10 EL200 EP-201.pdf PDF
36C24720B0024 Drawing Bid Documents.pdf PDF
20200511 - VAMC CHSSC - CLSP - Project Manual SPECS - BID DOCUMENTS - Combined - REV 3.zip ZIP file
Addendum 1.pdf PDF
20200508-VAMCCHSSC-CLSP-DRAWINGS-BIDDOCUMENTS-COMPLETE.pdf PDF
36C24720B0024 A00001.pdf PDF
20200511 - VAMC CHSSC - CLSP - Project Manual SPECS - BID DOCUMENTS - Combined - REV 3.pdf PDF
S02 36C24720B0024 Solicitation.pdf PDF
S02 36C24720B0024 CATH Lab Solicitation.pdf PDF
Bid Drawings Document.pdf PDF
SC Wage Determination SC20190023.pdf PDF
Specs Bid Documents.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TERMINAL

NO.

CFM E.A.T.

(°F)

HEATING

L.A.T.

(°F)

MINIMUM

OPERATING

PD (in.wg)

GPM MBH E.W.T.

(°F) L.W.T.

(°F)

WATER

PRESSURE

DROP(FT)MAX. MIN.

ROOM NUMBER AND NAME

AIR

RUNOUT

SIZE

UNIT SIZE

WATER

RUNOUT

SIZE

55 160 140CAV BOX 1 435 435 8 8 100 .20 2.2 21.7 .76 AA221 - SCRUB AREA

ROWS

REHEAT

GENERAL NOTES

1. BOXES SHALL HAVE PIPE CONNECTIONS ON SAME SIDE AND BE STRAIGHT COPPER FITTINGS.

2. COIL AND BOX SIZE MAY BE INCREASED TO MEET REQUIRED CONDITIONS; BUT SHALL NOT BE DECREASED FROM SIZE SHOWN.

3. BOXES SHALL BE SET FOR MAXIMUM CFM SHOWN ON PLANS.

4. DUCT CONNECTIONS TO BOXES SHALL BE SAME SIZE AS BOX INLET UNLESS SHOWN OTHERWISE.

5. MAXIMUM WATER PRESSURE DROP SHALL BE 4 FEET.

6. VARIABLE VOLUME BOXES SHALL OPERATE DOWN TO 50% OF MAXIMUM FLOW.

7. CONSTANT VOLUME BOXES SHALL BE THE SAME BOX USED FOR VARIABLE VOLUME BOX EXCEPT CFM SHALL BE LOCKED AT CAPACITY SHOWN. BOX SHALL NOT OPERATE AS

VARIABLE VOLUME.

8. CONTROLS SHALL BE SIEMENS PROVIDED BY CONTROLS CONTRACTOR AND INSTALLED BY CMI. CONTACT ED REAMER AT (803) 765-9070..

9. BASIS OF DESIGN SHALL BE PRICE SINGLE DUCT VARIABLE OR CONSTANT VOLUME SDV SERIES. APPROVED EQUALS: KREUGER, ENVIRO-TEC, & NAILOR.

10. MAXIMUM NC LEVEL OF 30 ON ALL BOXES. PROVIDE SOUND ATTENUATOR AS REQUIRED.

11. PROVIDE DIFFERENTIAL AIRFLOW SWITCH.

3/4"

TERMINAL UNIT SCHEDULE

SYMBOL SIZE TYPE

111-250 CFM 10"x8"

0-110 CFM 8"x4"

251-480 CFM 14"x10"

481-650 CFM 18"x12"

651-835 CFM 20"x14"

836-1400 CFM 24"x18"

PRICE 530/630

PRICE 530/630

PRICE 530/630

PRICE 530/630

PRICE 530/630

PRICE 530/630

ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 5145/6145, TITUS 350FL/350RL.

SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

SYMBOL REGISTER SIZE 24"x24" TYPE

136-210 CFM 8" ROUND NECK

0-135 CFM 6" ROUND NECK PRICE PDDR

211-325 CFM 10" ROUND NECK

326-475 CFM 12" ROUND NECK

651-840 CFM 16" ROUND NECK

841-2000 CFM 22"x22" NECK

476-650 CFM 14" ROUND NECK

CFM

A

CFM

B

CFM

C

CFM

D

CFM

E

CFM

F

CFM

G

PRICE PDDR

PRICE PDDR

PRICE PDDR

PRICE PDDR

PRICE PDDR

PRICE PDDR

NOTES:

1. ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 4360, TITUS PAR. SEE

ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. REGISTERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE

MOUNTED FRAMES.

SYMBOL REGISTER SIZE 24"x24" TYPE

136-210 CFM 8" ROUND NECK

0-135 CFM 6" ROUND NECK PRICE PDDR

211-325 CFM 10" ROUND NECK

326-475 CFM 12" ROUND NECK

651-840 CFM 16" ROUND NECK

841-2000 CFM 22"x22" NECK

476-650 CFM 14" ROUND NECK

CFM

CFM

CFM

CFM

CFM

CFM

CFM

PRICE PDDR

PRICE PDDR

PRICE PDDR

PRICE PDDR

PRICE PDDR

PRICE PDDR

NOTES:

1. ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 4360, TITUS PAR. SEE

ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. GRILLES LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE

MOUNTED FRAMES.

12"x12" REGISTER

CFM

H PRICE PDDR0-135 CFM 6" ROUND NECK

SYMBOL TYPICAL MODULE SIZE - 24"x24" TYPE

136-210 CFM 9"x9" FACE 8" ROUND NECK

0-135 CFM 6"x6" FACE 6" ROUND NECK PRICE SMD

211-325 CFM 12"x12" FACE 10" ROUND NECK

326-475 CFM 12"x12" FACE 12" ROUND NECK

476-650 CFM 15"x15" FACE 14" ROUND NECK

CFM

CFM

CFM

CFM

CFM

CFM

CFM

650-840 CFM 18"x18" FACE 16" ROUND NECK

841-1125 CFM 18"X18" FACE & NECK

PRICE SMD

PRICE SMD

PRICE SMD

PRICE SMD

PRICE SMD

PRICE SMD

NOTES:

1. ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 6500, TITUS TDC. SEE

ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. DIFFUSERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE

MOUNTED FRAMES.

3. PROVIDE SR MODEL ROUND NECK ADAPTER.

CFM RANGE, FACE SIZE, & NECK SIZE

CFM

0-120 CFM 6"X6" FACE 6" ROUND NECK PRICE SMD

CFM

121-240 CFM 9"X9" FACE 8" ROUND NECK PRICE SMD

12"x12" REGISTER

12"x12" REGISTER

CFM

8 PRICE PDDR

CFM

9 PRICE PDDR

CFM

10 PRICE PDDR

0-120 CFM 6" ROUND NECK

12"x12" REGISTER

0-135 CFM 6" ROUND NECK

24"x12" REGISTER

0-130 CFM 6" ROUNDNECK

16"x16" REGISTER

SIDEWALL RETURN REGISTER

PERFORATED EXHAUST REGISTERS

PERFORATED RETURN REGISTERS

LOUVERED SUPPLY DIFFUSER

CFM

CFM

CFM

CFM

CFM

CFM

CFM

0-130 CFM 6"X6" FACE 6" ROUND NECK PRICE SMD24"x12" REGISTER

LOCATION TONS CFM HUMIDIFIER

TYPE

FAN

H.P.

FLA/

MOCP

NOTES

VOLTS/

PHASE

TAG WATER

SUPPLY

1. PROVIDE WITH DISCONNECT SWITCH

2. PROVIDE WITH CONDENSATE PUMP

3. PROVIDE WITH 2" MERV 8 FILTER

4. PROVIDE WITH HOT WATER RE-HEAT COIL

5. PROVIDE WITH INTEGRAL THERMOSTAT.

6. PROVIDE WITH MODULATING 3-WAY CONTROL VALVES. SET VALVE TO ALLOW CONTINUOUS FLOW OF CHILLED AND/OR HOT WATER (MIN 2GPM) AT ALL TIMES.

EQUIPMENT 8 4400 ELECTRIC 4.1 11.0/20 460/3ØAHU-15 1 1/8"

REHEAT

TYPE

HOT WATER

E.W.T L.W.T P.D. (FT)

42° 52° MAX 19

ROWS

CAPACITY

TOTAL

(MBH)

CAPACITY

SENSIBLE

(MBH)

94.17 87.35

FAN SP

(IN)

0.5

MANUFACTURER

STULZ COS-096-C-U-EC

COOLING COIL

E.W.T L.W.T P.D. (FT)

180° 160° 5.3

ROWS

CAPACITY

TOTAL

(MBH)

94.2

HEATING COILEQUIPMENT ROOM A/C UNIT SCHEDULE

TAG SERVICE TYPE

NOMINAL

CAPACITY

(LB./HR.)

POWER

RATING

(OUTPUT)

MANUFACTURER & MODEL NO.

NOTES

1. PROVIDE UNITS WITH SHORT ABSORPTION MANIFOLD (SAM-E), CONDENSATE COOLER OPTION.

2.

3. ALL VENTING SHALL BE PROVIDED BY HUMIDIFIER MANUFACTURER AND INSTALLED BY MECHANICAL CONTRACTOR.

4. PROVIDE BACNET CARD FOR CONTROLS MONITORING. ONBOARD CONTROLS SHALL CONTROL OPERATION OF THE UNIT.

5. PROVIDE REMOTE TEMPERATURE/HUMIDITY SENSOR AND INTERFACE TO BE INSTALLED IN BUILDING. UNIT SHALL BE

PROVIDED WITH INTEGRAL DRAIN COOLER. REFER TO STRUCTURAL PLANS FOR EQUIPMENT SUPPORT ON ROOF.

6. H-1 MANIFOLD SHALL BE INSTALLED IN DUCTWORK, SEE PLANS.

DESIGN

CAPACITY

(LB./HR.)

STEAM ELECTRODE HUMIDIFIER SCHEDULE

OA

DESIGN

TEMP/RH

7.

PROVIDE DISCONNECT SWITCH.

VOLT/

PHASE

H-1 55°F/60%AHU-16 ELECTRODE 30 24.5 11.2 KW 460/3ø NORTEC EL 030

FIELD MEASURE DUCT FOR MANIFOLD SIZES. ALL DISPERSION TUBES SHALL BE SIZED FOR NO LONGER THAN 18" DISPERSION DISTANCE (WHERE

POSSIBLE).

A. BASIS OF DESIGN: PRICE INDUSTRIES, INC.

1. HOSPITAL OR LAMINAR FLOW DIFFUSER SYSTEM WITH INTEGRATED LED LIGHTING

B. GENERAL:

1. THE INTEGRATED PLENUM CEILING SYSTEM SHALL INCORPORATE LAMINAR FLOW DIFFUSERS, INTEGRATED HIGH PERFORMANCE LED LIGHTING AND A COMMON PLENUM ALL INTO A SINGLE

MODULAR ASSEMBLY DESIGN, TO ACT AS A SINGLE LARGE DIFFUSER ARRAY. THE COMMON

PRESSURIZED PLENUM DESIGN RESULTS IN FEWER INLET CONNECTIONS, AND REDUCED PLENUM

HEIGHT.

2. ALL COMPONENTS OF THE INTEGRATED CEILING SYSTEM SHALL BE FROM A SINGLE MANUFACTURER

AND SHALL BE IN ACCORDANCE WITH ASHRAE STANDARD 170 AND FGI 2018.

C. HOSPITAL OR LAMINAR FLOW DIFFUSER SYSTEM WITH INTEGRATED LED LIGHTING: [PRICE MODEL USA]:

1. SYSTEM CONSTRUCTION:

a. THE INTEGRATED PLENUM SHALL INCORPORATE LAMINAR FLOW DIFFUSERS, PROVIDING NON- ASPIRATING, UNIDIRECTIONAL AIRFLOW ABOVE THE STERILE ZONE, COMPLETE WITH ROOM SIDE

ADJUSTABLE APERTURE PLATE DAMPERS WITH LOCKING MECHANISM.

b. SYSTEM SHALL INCLUDE INTEGRATED LED LIGHTING AND CERTIFIED TO MEET UL1598/CSA 22.2 NO.

250.0 STANDARD FOR AIR-HANDLING LUMINAIRE.

c. LAMINAR DIFFUSER FACE FRAME SHALL BE 1/8” THICK ALUMINUM EXTRUSION WITH WELDED MITER CORNERS AND SECURED WITH FOUR (4) STAINLESS STEEL COUNTER-SUNK BOLTS AND STAINLESS

STEEL RETAINING CABLES.

d. LAMINAR DIFFUSER FACE SHALL BE COMPOSED OF 1/8” THICK FIRE-RESISTANT ENGINEERED POLYMER WITH 13% FREE AREA. PERFORATED FACE AREA SHALL BE AT LEAST 82% OF NOMINAL

SQUARE FOOTAGE FOR EACH DIFFUSER.

e. THE INTEGRATED PLENUM SHALL BE PROVIDED WITH 14 GAUGE ALUMINUM CONSTRUCTION AND

FULLY WELDED VERTICAL SEAMS

f. LAMINAR MODULES WILL COME WITHOUT HEPA FILTERS WITH GEL SEAL, PROVIDING NON-

ASPIRATING, UNIDIRECTIONAL AIRFLOW ABOVE THE STERILE ZONE.

g. EACH INTEGRATED PLENUM DIFFUSER MODULE SHALL INCLUDE FOUR (4) EYE BOLTS FOR HANGER

WIRE SUPPORT.

h. THE INTEGRATED PLENUM INLET COLLARS SHALL BE SIZED BASED ON AIRFLOW REQUIREMENTS

FOR THE INTENDED SPACE.

i. MODULES SHALL BE FACTORY ASSEMBLED UP TO 48 INCHES X 120 INCHES FOR ATTACHMENT TO

ADDITIONAL MODULES IN THE FIELD BY OTHERS.

2. INTEGRATED LIGHTING:

a. EACH LAMINAR DIFFUSER MODULE SHALL INCLUDE INTEGRATED LED LIGHTING, MOUNTED SO AS

TO NOT INTERFERE WITH THE AIRFLOW OF THE SYSTEM. LED STRIP LIGHTS AND FLUORESCENT

TUBES DIRECTLY IN THE AIRFLOW PATH ARE NOT ACCEPTABLE.

b. THE ENTIRE PERFORATED FACE OF THE LAMINAR DIFFUSER SHALL BE FULLY EQUALIZED WITH

LIGHT. SEPARATE LED CHANNELS SEPARATING LAMINAR DIFFUSERS OR EMBEDDED INTO THE

DIFFUSER FRAMES ARE NOT ACCEPTABLE.

c. LED LIGHTING SHALL HAVE AN EFFICIENCY GREATER THAN 100 LUMENS PER WATT, AND LIGHTING POWER SHALL BE EQUIVALENT TO 25 WATTS PER METER FOR INDIVIDUAL LED STRIP LIGHTING.

d. LED LIGHTING SHALL BE IP67 RATED AND NOT SUSCEPTIBLE TO DUST AND LIQUID CLEANING

AGENTS.

e. LED LIGHTING SHALL ACHIEVE COLOR RENDERING INDEX (CRI) OF 85 OR HIGHER.

f. LED LIGHTING SHALL BE RATED FOR L80 > 60,000 HOURS BASED ON LM-80 TESTING.

g. LED LIGHTING SHALL BE CERTIFIED TO MEET UL2108 AND MEET FIRE/SMOKE RATINGS OF UL2043.

h. PHOTOMETRIC IES FILES, ACHIEVED WITH A TYPE-C GONIOMETER, SHALL BE AVAILABLE TO

VALIDATE LIGHTING PERFORMANCE.

i. LED LIGHTING SHALL BE PAIRED WITH DRIVERS SUPPLIED FROM THE INTEGRATED LAMINAR FLOW

DIFFUSER ASSEMBLY MANUFACTURER. DRIVER SHALL BE CAPABLE OF 10% DIMMING, AND PWM

DIMMING SHALL MEET IEEE1789.

j. LED DRIVER SHALL COMPLY WITH UL8750/CSA 22.2 NO. 223-M91.

k. LED DRIVER SHALL ACHIEVE TOTAL HARMONIC DISTORTION (THD) < 20% AT MAXIMUM POWER

3. PAINT FINISH:

a. THE CEILING SYSTEM FINISH SHALL HAVE A B12 WHITE BAKED-ON POWDER COAT FINISH MATCHING

THE LAMINAR FLOW DIFFUSERS AND FILL-IN PANELS.

1. THE PAINT FINISH MUST DEMONSTRATE NO DEGRADATION WHEN TESTED IN ACCORDANCE

WITH ASTM D1308 (COVERED AND SPOT IMMERSION) AND ASTM D4752 (MEK DOUBLE RUB) PAINT

DURABILITY TESTS.

2. THE PAINT FILM THICKNESS SHALL BE A MINIMUM OF 2.0 MILS.

3. THE FINISH SHALL HAVE A HARDNESS OF 2H.

4. THE FINISH SHALL WITHSTAND A MINIMUM SALT SPRAY EXPOSURE OF 1000 HOURS.

5. THE FINISH SHALL HAVE AN IMPACT RESISTANCE OF 80 IN-LB.

HOSPITAL OR LAMINAR FLOW DIFFUSER SYSTEM WITH

INTEGRATED LED LIGHTING

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Firm License Number: F-0674

Project No. 4415

Charlotte Engineers, LLP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% - CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Megan C. Day, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves

E:

\L oc al

R ev it\

\4

- C E

C en tra l M od el

.rv t

8/

/2

:5 4:

P

M

M-004

MECHANICAL - SCHEDULES CATH LAB SITE PREP at

RALPH JOHNSON VAMC

109 BEE STREET CHARLESTON, SC

534-CSI-555

MAY 08, 2020 GAT ESM

Revisions: Date:

ADDENDUM 2 08/12/2020

Sheets
M-004 - MECHANICAL - SCHEDULES
M-005 - MECHANICAL - SCHEDULES
MD-100 - MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK
MD-101 - MECHANICAL - SECOND FLOOR - DEMOLITION - PIPING
MH-200 - SECOND FLOOR - NEW WORK - DUCTWORK
MP-201 - SECOND FLOOR - NEW WORK - PIPING