ED-100 - ELECTRICAL - SECOND FLOOR - DEMOLITION.pdf

PDF 299 KB Posted

Attached to
CATH LAB Federal contract opportunity
Solicitation number
36C24720B0024
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7

About this file

This document package includes an electrical demolition drawing and details for a Cath Lab renovation project at a Veterans Affairs medical center, along with information on the related federal contract opportunity. The demolition drawing outlines the scope of work to remove existing electrical equipment, lighting, devices, and conduit in preparation for the Cath Lab upgrade. Key areas of demolition include removal of the isolated power panel, VAV unit, Liebert unit, and equipment in and serving the Cath Lab space. The federal contract opportunity is for replacement of the Cath Lab equipment with a new GE system, Stryker boom, and Cleansuite ceiling system. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration for work at the Ralph H. Johnson VA Medical Center.

View the file

Other files for this federal contract opportunity

Other files attached to CATH LAB, newest first.
File Type Posted
Project 534-CSI-555 Cardiac Lab Prep Pre-Bid Sign-In.pdf PDF
PreBid Site Visit Sign In sheet.doc DOC document
Project No. 534-CSI-555 Card Cath Lab Questions from 8-26-2020.docx DOCX document
36C24720B0024 A00003.pdf PDF
28 13 00 Physical Access Control System.pdf PDF
Project 534-CSI-555 Answers to Questions.pdf PDF
26 08 00 Commissioning of Electrical Systems.pdf PDF
EP-201 - ELECTRICAL - SECOND FLOOR - POWER SYSTEMS.pdf PDF
280800 Commissioning of Electronic Safety and Security Systems.pdf PDF
M-004 - MECHANICAL - SCHEDULES.pdf PDF
Addendum 2 - Project No. 534-CSI-555.pdf PDF
270800 Commissioning of Communications Systems.pdf PDF
01 91 00 Commissioning.pdf PDF
226300 - GAS SYSTEMS FOR LABORATORY AND HEALTHCARE FACILITIES.pdf PDF
S02 36C24720B0024 A00002.pdf PDF
MD-101 - MECHANICAL - SECOND FLOOR - DEMOLITION - PIPING.pdf PDF
230711 HVAC INSULATION.pdf PDF
000110 Specifications.pdf PDF
MP-201 - SECOND FLOOR - NEW WORK - PIPING.pdf PDF
M-005 - MECHANICAL - SCHEDULES.pdf PDF
MD-100 - MECHANICAL - SECOND FLOOR - DEMOLITION - DUCTWORK.pdf PDF
MH-200 - SECOND FLOOR - NEW WORK - DUCTWORK.pdf PDF
Card Cath Lab Prep Dwgs ED100 ED10 EL200 EP-201.pdf PDF
36C24720B0024 Drawing Bid Documents.pdf PDF
20200511 - VAMC CHSSC - CLSP - Project Manual SPECS - BID DOCUMENTS - Combined - REV 3.zip ZIP file
Addendum 1.pdf PDF
20200508-VAMCCHSSC-CLSP-DRAWINGS-BIDDOCUMENTS-COMPLETE.pdf PDF
36C24720B0024 A00001.pdf PDF
20200511 - VAMC CHSSC - CLSP - Project Manual SPECS - BID DOCUMENTS - Combined - REV 3.pdf PDF
S02 36C24720B0024 Solicitation.pdf PDF
S02 36C24720B0024 CATH Lab Solicitation.pdf PDF
Bid Drawings Document.pdf PDF
SC Wage Determination SC20190023.pdf PDF
Specs Bid Documents.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S S

S S

EP

O S

N B

WAP

EP

O

NS

NCL

PS

PS

PS

A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION

PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR

GENERAL REFERENCE ONLY.

B. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.

C. OPERATION OF CATH LAB 1 NOT TO BE INTERRUPTED BY

DEMOLITION. ANY ELECTRICAL CONDUIT OR WIRE SERVING

CATH LAB 2 EXISTING ABOVE CATH LAB 1 SHALL BE EXISTING

TO REMAIN.

D. ALL DEMOLITION WORK ASSOCIATED WITH EQUIPMENT

OUTSIDE OF CATH LAB 2 TO BE A PART OF PHASES 1-3.

DEMO WORK INSITE CATH LAB 2 AND DEMO OF EXISTING

ISOLATED POWER PANEL TO BE A PART OF PHASE 4

GENERAL NOTES

EXISTING FLOOR PEDESTAL TO REMAIN.

ALL LIGHTING AND CEILING DEVICES TO BE REMOVED UNLESS OTHERWISE

NOTED AS BEING RELOCATED. DEMO WIRING AS REQUIRED BACK TO

SOURCE. EXISTING WALL DEVICES TO REMAIN.

ALL EXISTING ELECTRICAL AND MECHANICAL EQUIPMENT TO BE REMOVED.

ALL ASSOCIATED WIRE AND CONDUIT IS TO BE REMOVED TO THE EXTENT

POSSIBLE. EXISTING CEILING DEVICES TO REMAIN. RELOCATED INTO NEW

CEILING AS REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS.

EXISTING ISO PANEL TO BE REMOVED. PULL ALL WIRES AND CONDUIT

BACK TO SOURCE AND LABEL SOURCE BREAKER AS SPARE. ALL

ASSOCIATE WIRING AND CONDUIT TO LOADS AND RECEPTACLES IN CATH

LAB TO BE DEMOLISHED. EXISTING RECEPTACLE BOXES AND JUNCTION

BOXES TO REMAIN FOR RE-USE.

EXISTING EQUIPMENT IN CONTROL ROOM TO REMAIN UNLESS OTHERWISE

NOTED.

EXISTING RECEPTACLE COVERS TO BE REPLACED WITH GFI TYPE.

NO WORK IN THIS AREA UNLESS OTHERWISE NOTED. SEE PANEL

SCHEDULES AND RISER DIAGRAM FOR ADDITIONAL INFORMATION.

ALL CONDUIT IN CATH LAB WALL TO REMAIN. REUSE AS NEEDED TO

SERVE NEW LOADS. REPLACE RECEPTACLE COVERS WITH NEW.

CONDUIT THAT EXTENDS OVER EXISTING CATH LAB 1 THAT WOULD

INTERFERE WITH FUNCTION OF THIS AREA IS TO BE ABANDONED RATHER

THAN DEMOLISHED.

EXISTING LEIBERT UNIT TO BE REMOVED, INCLUDING ALL WIRE AND

CONDUIT TO CONDENSOR UNIT ON ROOF ABOVE. COORDINATE WITH

MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.

EXISTING VAV ABOVE CEILING TO BE REMOVED. WIRE AND CONDUIT BACK

TO SOURCE AND LABEL CIRCUIT AS SPARE. CONSTRUCTION CONTRACTOR

SHALL COORDINATE WITH COR FOR TRACING CIRCUITS. CONTRACTOR

SHALL TRACE CIRCUITS WHILE VA IS PRESENT.

EXISTING CONDUITS IN WALLS AND ABOVE CEILINGS IN THESE AREAS ARE

TO BE RELOCATED AS REQUIRED TO ACCOMODATE NEW WORK.

DEMOLITION KEYED NOTES

DRAWINGS. SEE SCHEDULE FOR TYPE (*).

CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON

LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,

LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.

CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT*

LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

SEE SCHEDULE FOR TYPE (*).*

HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.* * *

LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).

SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).

SINGLE POLE SWITCH, MOUNTED 42" AFF TO CENTER OF DEVICE.S

EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED

OTHERWISE. CONNECT UNSWITCHED.

DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 42" AFF TO CENTER OF OUTLET

OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES

OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY

DUPLEX RECEPTACLE, MOUNTED 42" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH

INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

POWER SYSTEM.

CONNECTED TO THE EMERGENCY POWER SYSTEM.

JUNCTION OR PULL BOX. W = WEATHERPROOF.J

FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.15

PANELBOARD SURFACE MOUNTED.

PANELBOARD FLUSH MOUNTED.

PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.PP

CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.CR

EMERGENCY SYSTEM OFF PUSH BUTTONEPO

DD FIRE ALARM DUCT MOUNTED SMOKE DETECTOR.

SYMBOLS LEGEND

RL = EXISTING DEVICE TO BE RELOCATED.

DASHED SYMBOLS INDICATE EXISTING DEVICES.

RLD = RELOCATED DEVICE SHOWN IN FINAL LOCATION.

RM = EXISTING DEVICE TO REMAIN.

RM

RM

RV = EXISTING DEVICE TO BE REMOVED.

RP = EXISTING DEVICE TO BE REPLACED WITH NEW DEVICE.

EX = EXISTING DEVICE

PROJECT LOCATION:

CARDIAC CATH LAB (2ND FLOOR)

BEE STREET

MAIN HOSPITAL ENTRANCE

BEE STREET/BRAVO STREET

MENTAL HEALTH CLINIC ENTRANCE

N

KEY PLAN

14.513.512.511.510.59.57.46.1

AA

BB

CC

A

A.8

B.8

C

B

ATS LS

ATS LL

SWBD HDCC

SWBD HDLS

MDP

CRIT ISO PANEL #1

POWER LINE FILTER

SWBD 2HEDP1

ATS EE

RM

RM

RM RM

RMRM RM

RM

RM

RV

RM

RM

RM

RM

RM

RP RP RM

RMRP

RL

RL

RL

RL

RL

RL

RV RV

RV RV

RV RV

RV

RV RV

RV

RV

RV

RV

RV

RV RV

RV RV

RV

RV

RM

RM

PANEL A PANEL CCB

PANEL HA

PANEL LSA

PANEL HCCC

PANEL 2LE-AA231PANEL 2HE-AA231

CRIT ISO PANEL #2

RM

7 7

RM

SMOKE TIGHT WALL (EXISTING)

1-HR FIRE RATED WALL (EXISTING)

2-HR FIRE RATED WALL (EXISTING)

WALL RATING LEGEND

LEAD-LINED WALL (EXISTING - MAINTAIN & PATCH AS NEEDED IN RENOVATION)

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Firm License Number: F-0674

Project No. 4415

Charlotte Engineers, LLP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% - CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Megan C. Day, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves

D :\l oc al re vi t m od el s\

\4

- C

E C en tra l M od el .rv t 8/

/2

:4

5:

P M

ED-100

ELECTRICAL - SECOND FLOOR - DEMOLITION CATH LAB SITE PREP at

RALPH JOHNSON VAMC

109 BEE STREET CHARLESTON, SC

534-CSI-555

MAY 08, 2020 CLH JCE

1/8" = 1'-0"1 ELECTRICAL - FIRST FLOOR - DEMOLITION

Revisions: Date:

ADDENDUM 2 08/12/2020

Sheets
ED-100 - ELECTRICAL - SECOND FLOOR - DEMOLITION
EP-201 - ELECTRICAL - SECOND FLOOR - POWER & SYSTEMS

File details come from the government source that posted it. Updated .