36C24718R0653-004.pdf

PDF 11 MB Posted

Attached to
534-15-105 Renovation of Common and Supporting Areas in Building 1
Solicitation number
36C24718R0653
Issued by

About this file

36C24718R0653 FINAL SEALED DRAWINGS 1 of 4.pdf

View the file

Other files

File Type Posted
36C24718R0653-0002001.pdf PDF
36C24718R0653-0002002.pdf PDF
36C24718R0653-0002000.docx DOCX document
36C24718R0653-0001000.docx DOCX document
36C24718R0653-007.pdf PDF
36C24718R0653-009.pdf PDF
36C24718R0653-002.pdf PDF
36C24718R0653-008.pdf PDF
36C24718R0653-006.pdf PDF
36C24718R0653-010.pdf PDF
36C24718R0653-001.docx DOCX document
36C24718R0653-003.pdf PDF
36C24718R0653-005.pdf PDF
36C24718R0653-011.pdf PDF
36C24718R0653-000.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/16/2016

REVISED 10.04.2017 FA

A205 FAMILY LOUNGE CONSULTATION ROOM 72 SF

34,550 SF

PROJECT TEAM

V et er an s A ff ai rs D ep ar tm en t of

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

Date CONSULTANTS

DESIGN/BUILD

1 3/64" = 1'-0"

LEGEND

EX

UP

UP

UP

UP

A

B

C

D

E

F

G

H

J

K

L

2 5 6 7 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 304.3.1

LIQUID

NITROGEN

STORAGE

WC-01

WC-02

NIC

WC-03

WC-04

NIC

WC-08

NIC

WC-09

NIC

WC-07

NIC

WC-06

NIC

WC-05

LC LC

EX

EX

EX EX EX EX

EX

EX

EX

EX

EP

EX

EP

et er an s A ff ai rs D ep ar tm en t of

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

Date CONSULTANTS

DESIGN/BUILD

1 3/64" = 1'-0"

LEGEND

EX

UP

DN

DN

DN

4 4 4

4 4

WC-23

WC-22

WC-21

WC-20

WC-19

WC-17

WC-15

WC-16

WC-18

WC-14WC-13

WC-12

WC-11

WC-10

WC-11 NEW

LOCATION

et er an s A ff ai rs D ep ar tm en t of

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

Date CONSULTANTS

DESIGN/BUILD

1 3/64" = 1'-0"

LEGEND

EX

2 5 6 7 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 304.3.1

WC-24

WC-25

WC-26

et er an s A ff ai rs D ep ar tm en t of

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

Date CONSULTANTS

DESIGN/BUILD

1 3/64" = 1'-0"

LEGEND

EX

2 5 6 7 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 304.3.1

WC-31

NIC

WC-27

NIC

WC-28

NIC

WC-29

NIC

WC-30

NIC

et er an s A ff ai rs D ep ar tm en t of

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

Date CONSULTANTS

DESIGN/BUILD

1 3/64" = 1'-0"

LEGEND

EX

2 5 6 7 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 304.3.1

WC-32

NIC

WC-33

NIC

MIV AEJ

MIV AEJ

ACM MASTIC (REDDISH-BROWN)

PLIABLE APPLIED TO SEAM OF METAL

DUCT.

PIPE INSULATION (FIBERGLASS) WITH

BLACK ACM MASTIC AT ELBOWS,

FITTINGS AND HANGERS.

LEGEND

HA101.0JF DjH

22615

3/32"=1'-0"1 PARTIAL FIRST FLOOR PLAN

N

KEY PLAN

SCALE: 3/32" = 1'-0"

0 5'-4" 10'-8" 21'-4"

ACM BLACK MASITC,

TO BE ABATED AS

SHOWN SHADED,

ON PIPE INSULATION

ELBOW FITTINGS (2 EA)

3/32"=1'-0"2 PARTIAL FIRST FLOOR PLAN

VA-36-03 (+)

VA-36-02 (+)

VA-36-01 (+)

SURFACING MATERIAL

(WHITE) SKIMCOAT

ON CEILING PLASTER,

TO BE ABATED AS

SHOWN SHADED

VA-179-03 (+)

VA-179-02 (+)

VA-179-01 (+)

VA-154-03 (+)

VA-96-06 (+)

ACM PIPE ELBOW

INSULATION (FRIABLE),

TO BE ABATED AS

SHOWN SHADED

PIPE INSULATION (FIBERGLASS)

WITH BLACK ACM MASTIC AT

ELBOWS, FITTINGS AND HANGERS,

TO BE ABATED AS SHOWN SHADED

3/32"=1'-0"3 PARTIAL FIRST FLOOR PLAN

LARGE HVAC DUCT WITH

ACM INSULATION (FRIABLE),

TO BE ABATED AS SHOWN

SHADED

CONSTRUCTION DOCUMENTS SUBMISSION

RENOVATION OF COMMON

AND SUPPORT AREAS IN

BUILDING 1

534-15-105

06-30-2016

PROJECT TEAM

V et er an s A ff ai rs D ep ar tm en t of

CHARLESTON, S.C.

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

Date CONSULTANTS

FULLY SPRINKLERED

DESIGN/BUILD

GENERAL NOTES:

1. REFER TO THE SPECIFICATION SECTION 02.82.11 FOR TRADITIONAL

ASBESTOS ABATEMENT INFORMATION.

2. THIS DRAWING INDICATES AREAS OF ASBESTOS ABATEMENT.

OTHER ABATEMENT REQUIRED INCLUDING MODIFICATIONS THAT

MAY EXTEND BEYOND THE AREAS SHOWN SHALL INCLUDE ANY

NECESSARY DEMOLITION OF SPACES ADJACENT TO, ABOVE AND/

OR BELOW REQUIRED FOR THE INSTALLATION OF WORK IN THIS

PROJECT.

3. DRAWINGS ARE DIAGRAMMATIC AND SINCE EXISTING CONDITIONS,

INCLUDING AREA ABOVE ACCESSIBLE CEILING MAY AFFECT

ABATEMENT WORK, THE CONTRACTOR SHALL COORDINATE ALL

ABATEMENT WORK WITH DEMOLITION CONTRACTOR.

4. CONTRACTOR SHALL DELIVER TO CONSTRUCTION MANAGER

COPIES OF ALL ENVIRONMENTAL PERMITS AND ALL WASTE

MANIFESTS. WASTE MAY NOT BE STORED AND MUST BE DISPOSED

OF IMMEDIATELY FOLLOWING ABATEMENT.

5. THE ASBESTOS ABATEMENT CONTRACTOR SHALL

DECONTAMINATE ALL BUILDING MATERIALS, WHICH BECOME

CONTAMINATED OR ARE DISTURBED FROM ASBESTOS REMOVAL.

6. ASBESTOS ABATEMENT CONTRACTOR IS TO ADHERE TO THE OSHA

STANDARD 29CFR 1926.62 LEAD EXPOSURE IN CONSTRUCTION

WHEN PERFORMING SELECTIVE DEMOLITION WORK PRACTICE,

IMPACTING, OR DISTURBING ANY BUILDING MATERIALS. THE

HAZARDOUS MATERIAL ABATEMENT CONTRACTOR MUST CONDUCT

DAILY EXPOSURE MONITORING FOR LEAD-IN-THE-AIR AND COMPLY

WITH ALL APPLICABLE REGULATIONS.

7. ASBESTOS ABATEMENT CONTRACTOR SHALL COORDINATE ON

SITE WORK WITH THE VAMC,AE,ENVIRONMENTAL ENGINEER,

CONSTRUCTION MANAGER, AND GENERAL AND

SUB-CONTRACTORS TO FACILITATE THE PROMPT COMPLETION OF

ALL ASPECTS OF THE DEMOLITION RENOVATION PROJECTS.

8. SPECIAL CARE SHOULD BE TAKEN WHEN WORKING NEAR

ELECTRIC, WATER, STEAM AND GAS SUPPLY LINES.

9. ASBESTOS ABATEMENT CONTRACTOR MAY BE RESPONSIBLE FOR

REMOVING NON-ASBESTOS MATERIALS TO ACCESS ASBESTOS

CONTAINING AND OTHER HAZARDOUS MATERIALS INCLUDING BUT

NOT LIMITED TO, DROP CEILINGS, DRYWALL ENCLOSURES, ECT.

COORDINATE SELECTIVE DEMOLITION WITH THE DEMOLITION

CONTRACTOR.

10. ASBESTOS ABATEMENT CONTRACTOR SHALL COMPLY WITH THE

REQUIREMENTS OF OSHA REGARDING CONFINED SPACE

INCLUDING ASSOCIATED PROGRAMS, PERMITS, TRAINING AND

TESTING.

11. DEPICTION OF EXISTING CONDITIONS BASED ON

OWNER-FURNISHED DOCUMENTS AND LIMITED FIELD

OBSERVATIONS. EXISTING ELEMENTS AND CONDITIONS

CONCEALED BY IN-PLACE EQUIPMENT AND FINISHES WERE NOT

OBSERVED OR INVESTIGATED. ONCE CUTTING AND SELECTIVE

DEMOLITION WORK IS COMPLETE, REPORT ANY CONFLICTS TO

DESIGNER. THE CONTRACTOR SHALL MAKE ADJUSTMENTS

AND/OR ALTERATIONS AS NECESSARY TO INSTALL COMPLETE AND

OPERABLE SYSTEMS IN ACCORDANCE WITH THE CODES HAVING

JURISDICTION AT NO ADDITIONAL COST TO THE GOVERNMENT.

12. ABATEMENT CONTRACTOR TO COORDINATE, WITH GENERAL

CONTRACTOR, DEVELOPMENT OF INFECTION CONTROL PLAN AND

SAFETY PLAN FOR APPROVAL BY COR PRIOR TO BEGINNING THEIR

WORK. PLAN TO INCLUDE MEANS AND METHODS OF DEBRIS

STAGING AND REMOVAL, BOTH INTERNALLY AND EXTERNALLY.

SEE GI002.

13. PROTECT AND MAINTAIN EXISTING FIRE PARTITIONS AND

BARRIERS; PENETRATION AND JOINT FIRE STOPPING AND APPLIED

FIREPROOFING. RESTORE TO EXISTING RATING WHERE DAMAGED

OR REMOVED AS PART OF WORK.

14. COORDINATE ALL WORK AS SPECIFIED IN SECTION 02 82 11 & 02 82

13.19.

RAMP UP

TO RAISED

FLOOR

D276

D276

AA215

C O

R 2A

A

ACM MASTIC (REDDISH-BROWN)

PLIABLE APPLIED TO SEAM OF METAL

DUCT.

PIPE INSULATION (FIBERGLASS) WITH

BLACK ACM MASTIC AT ELBOWS,

FITTINGS AND HANGERS.

LEGEND

3/32"=1'-0"1 PARTIAL SECOND FLOOR PLAN

N

KEY PLAN

SCALE: 3/32" = 1'-0"

0 5'-4" 10'-8" 21'-4"

PIPE INSULATION (FIBERGLASS) WITH

BLACK ACM MASTIC AT ELBOWS,

FITTINGS AND HANGERS,

TO BE ABATED AS SHOWN SHADED

ACM MASTIC

(REDDISH-BROWN) PLIABLE

APPLIED TO SEAM OF METAL

DUCT, TO BE ABATED AS

SHOWN SHADED

PIPE INSULATION (FIBERGLASS)

WITH BLACK ACM MASTIC AT ELBOWS,

FITTINGS AND HANGERS, TO BE

ABATED AS SHOWN SHADED

ACM PIPE

INSULATION

(2 ELBOWS)

(FRIABLE),

TO BE ABATED AS

SHOWN SHADED

PIPE INSULATION (FIBERGLASS) WITH

BLACK ACM MASTIC AT ELBOWS,

FITTINGS AND HANGERS

TO BE ABATED AS SHOWN SHADED

HA102.0JF DjH

22616

RENOVATION OF COMMON

AND SUPPORT AREAS IN

BUILDING 1

534-15-105

06-30-2016

PROJECT TEAM

V et er an s A ff ai rs D ep ar tm en t of

CHARLESTON, S.C.

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

Date CONSULTANTS

CONSTRUCTION DOCUMENTS SUBMISSION

FULLY SPRINKLERED

DESIGN/BUILD

ACM BLACK MASITC

BELOW NON-ACM RUBBER

TILES AT STAIR LANDING,

TO BE ABATED AS SHOWN SHADED

GENERAL NOTES:

1. REFER TO THE SPECIFICATION SECTION 02.82.11 FOR TRADITIONAL

ASBESTOS ABATEMENT INFORMATION.

2. THIS DRAWING INDICATES AREAS OF ASBESTOS ABATEMENT.

OTHER ABATEMENT REQUIRED INCLUDING MODIFICATIONS THAT

MAY EXTEND BEYOND THE AREAS SHOWN SHALL INCLUDE ANY

NECESSARY DEMOLITION OF SPACES ADJACENT TO, ABOVE AND/

OR BELOW REQUIRED FOR THE INSTALLATION OF WORK IN THIS

PROJECT.

3. DRAWINGS ARE DIAGRAMMATIC AND SINCE EXISTING CONDITIONS,

INCLUDING AREA ABOVE ACCESSIBLE CEILING MAY AFFECT

ABATEMENT WORK, THE CONTRACTOR SHALL COORDINATE ALL

ABATEMENT WORK WITH DEMOLITION CONTRACTOR.

4. CONTRACTOR SHALL DELIVER TO CONSTRUCTION MANAGER

COPIES OF ALL ENVIRONMENTAL PERMITS AND ALL WASTE

MANIFESTS. WASTE MAY NOT BE STORED AND MUST BE DISPOSED

OF IMMEDIATELY FOLLOWING ABATEMENT.

5. THE ASBESTOS ABATEMENT CONTRACTOR SHALL

DECONTAMINATE ALL BUILDING MATERIALS, WHICH BECOME

CONTAMINATED OR ARE DISTURBED FROM ASBESTOS REMOVAL.

6. ASBESTOS ABATEMENT CONTRACTOR IS TO ADHERE TO THE OSHA

STANDARD 29CFR 1926.62 LEAD EXPOSURE IN CONSTRUCTION

WHEN PERFORMING SELECTIVE DEMOLITION WORK PRACTICE,

IMPACTING, OR DISTURBING ANY BUILDING MATERIALS. THE

HAZARDOUS MATERIAL ABATEMENT CONTRACTOR MUST CONDUCT

DAILY EXPOSURE MONITORING FOR LEAD-IN-THE-AIR AND COMPLY

WITH ALL APPLICABLE REGULATIONS.

7. ASBESTOS ABATEMENT CONTRACTOR SHALL COORDINATE ON

SITE WORK WITH THE VAMC,AE,ENVIRONMENTAL ENGINEER,

CONSTRUCTION MANAGER, AND GENERAL AND

SUB-CONTRACTORS TO FACILITATE THE PROMPT COMPLETION OF

ALL ASPECTS OF THE DEMOLITION RENOVATION PROJECTS.

8. SPECIAL CARE SHOULD BE TAKEN WHEN WORKING NEAR

ELECTRIC, WATER, STEAM AND GAS SUPPLY LINES.

9. ASBESTOS ABATEMENT CONTRACTOR MAY BE RESPONSIBLE FOR

REMOVING NON-ASBESTOS MATERIALS TO ACCESS ASBESTOS

CONTAINING AND OTHER HAZARDOUS MATERIALS INCLUDING BUT

NOT LIMITED TO, DROP CEILINGS, DRYWALL ENCLOSURES, ECT.

COORDINATE SELECTIVE DEMOLITION WITH THE DEMOLITION

CONTRACTOR.

10. ASBESTOS ABATEMENT CONTRACTOR SHALL COMPLY WITH THE

REQUIREMENTS OF OSHA REGARDING CONFINED SPACE

INCLUDING ASSOCIATED PROGRAMS, PERMITS, TRAINING AND

TESTING.

11. DEPICTION OF EXISTING CONDITIONS BASED ON

OWNER-FURNISHED DOCUMENTS AND LIMITED FIELD

OBSERVATIONS. EXISTING ELEMENTS AND CONDITIONS

CONCEALED BY IN-PLACE EQUIPMENT AND FINISHES WERE NOT

OBSERVED OR INVESTIGATED. ONCE CUTTING AND SELECTIVE

DEMOLITION WORK IS COMPLETE, REPORT ANY CONFLICTS TO

DESIGNER. THE CONTRACTOR SHALL MAKE ADJUSTMENTS

AND/OR ALTERATIONS AS NECESSARY TO INSTALL COMPLETE AND

OPERABLE SYSTEMS IN ACCORDANCE WITH THE CODES HAVING

JURISDICTION AT NO ADDITIONAL COST TO THE GOVERNMENT.

12. ABATEMENT CONTRACTOR TO COORDINATE, WITH GENERAL

CONTRACTOR, DEVELOPMENT OF INFECTION CONTROL PLAN AND

SAFETY PLAN FOR APPROVAL BY COR PRIOR TO BEGINNING THEIR

WORK. PLAN TO INCLUDE MEANS AND METHODS OF DEBRIS

STAGING AND REMOVAL, BOTH INTERNALLY AND EXTERNALLY.

SEE GI002.

13. PROTECT AND MAINTAIN EXISTING FIRE PARTITIONS AND

BARRIERS; PENETRATION AND JOINT FIRE STOPPING AND APPLIED

FIREPROOFING. RESTORE TO EXISTING RATING WHERE DAMAGED

OR REMOVED AS PART OF WORK.

14. COORDINATE ALL WORK AS SPECIFIED IN SECTION 02 82 11 & 02 82

13.19.

SEE STATEMENT OF WORK THIS DWG 20 OF 223

A205 FAMILY LOUNGE

PF

PF

P F

A

B

C

D

E

F

G

H

J

K

L

6 7 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 304.3.1

AD105.0

3 WC-24

WC-25

WC-26

PROJECT TEAM

V et er an s A ff ai rs D ep ar tm en t of

CHARLESTON, S.C.

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

THESE DRAWINGS ARE

NOT TO BE USED FOR

CONSTRUCTION,

BIDDING, RECORDATION,

CONVEYANCE, SALES,

OR AS THE BASIS FOR

THE ISSUANCE OF A

PERMIT

Date CONSULTANTS

FULLY SPRINKLERED

DESIGN/BUILD

6/

/2

6:

:3

P

M

CONSTRUCTION DOCUMENTS SUBMISSION

RENOVATION OF COMMON

AND SUPPORT AREAS IN

BUILDING 1

534-15-105

AD103.0

06-30-2016

AEJMIV

22324

LEVEL 3 - OVERALL DEMOLITION

PLAN

1" = 20'-0"1 DEMOLITION FLOOR PLAN - 3RD FLOOR

SCALE: 1" = 20'-0"

0 10'-0" 20'-0" 40'-0"

1 ALL ITEMS SHOWN DASHED INDICATE ITEMS TO BE DEMOLISHED OR SALVAGED.

SEE SPECIFIC NOTES BELOW FOR ADDITIONAL INFORMATION. REFER TO

MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL DRAWINGS FOR

ADDITIONAL DEMOLITION NOTES.

2 ALL OPENINGS AND SURFACES MADE BARE BY DEMOLITION AND/OR REMOVAL OF

MATERIALS SHALL BE REPAIRED AND/OR PATCHED TO MATCH ADJACENT FINISH.

PREPARE SURFACES TO RECEIVE NEW FINISH(ES).

3 CONTRACTOR TO DEVELOP AND PUBLISH INFECTION CONTROL PLAN AND SAFETY

PLAN FOR APPROVAL BY COR PRIOR TO BEGINNING THEIR WORK. PLAN TO

INCLUDE MEANS AND METHODS OF DEBRIS STAGING AND REMOVAL, BOTH

INTERNALLY AND EXTERNALLY.

4 INSTALL TEMPORARY DUST AND DEBRIS BARRIERS AND VESTIBULES AROUND

PROJECT LIMITS IN ACCORDANCE WITH THE VA'S INFECTON CONTROL PLAN.

TEMPORARY BARRIERS ARE NOT TO RESTRICT REQUIRED MEANS OF EGRESS

PATHS AND WIDTHS.

5 HAZARDOUS MATERIAL ABATEMENT IS REQUIRED IN PROJECT SCOPE. REF.

HA-SERIES DRAWINGS FOR ADDITIONAL INFORMATION.

6 REMOVE ALL INDICATED ACOUSTICAL CEILING TILE, OVERHEAD MECHANICAL

EQUIPMENT, A/C DUCTS AND RETURNS, LIGHT FIXTURES.

7 EXISTING TO REMAIN: ANY FIRE SPRINKLER HEADS, RISERS, VALVES, OF ANY

OTHER RELATED FIRE PROTECTION EQUIPMENT, UNLESS OTHERWISE NOTED.

8 FIELD VERIFY ALL EXISTING DIMENSIONS PRIOR TO ANY CONSTRUCTION OR

EQUIPMENT INSTALLATION. IMMEDIATELY NOTIFY COR OF ANY DISCREPANCY.

9 ALL EQUIPMENT IN HISTOLOGY LAB TO BE RELOCATED DURING DEMOLITION

10 ALL EXISTING DOORS, UNLESS OTHERWISE NOTED, ARE TO REMAIN. PROTECT

DURING DEMOLITION AND NEW CONSTRUCTION, AND ARE TO RECEIVE PAINT

WHERE NECESSARY.

11 CONTRACTOR TO SALVAGE AND PROPERLY STORE ALL TOILET ACCESSORIES,

FEMININE PRODUCT DISPENSERS AND BABY CHANGING STATIONS FOR RE-USE BY

VA. IF NOT REUSED IN THIS PROJECT TURN OVER ITEM TO VA.

12 THE EXTENT OF DEMOLITION WORK IS SHOWN ON DRAWINGS AND

SPECIFICATIONS.

13 THE USE OF EXPLOSIVES WILL NOT BE PERMITTED.

14 BURNING OF REMOVED MATERIALS FROM DEMOLISHED STRUCTURES WILL NOT BE

PERMITTED IN THE SITE.

15 CONDUCT DEMOLITION OPERATIONS AND THE REMOVAL OF DEBRIS TO ENSURE

MINIMUM INTERFERENCE WITH ANOTHER ADJACENT OCCUPIED OR USED SPACE.

16 PROVIDE COVERED PASSAGEWAY TO ENSURE THE SAVE PASSAGE OF PEOPLE

AROUND THE AREA OF DEMOLITION. CONDUCT OPERATIONS TO PREVENT DAMAGE

TO FALLING DEBRIS OR OTHER CAUSE TO ADJACENT SPACES. PROVIDE PHASING

PLAN FOR MATERIAL, WORK PERFORMED FOR APPROVAL.

17 DO NOT CLOSE OR OBSTRUCT CORRIDOR OR OCCUPIED SPACES WITHOUT

PERMISSION FROM THE COR. PROVIDE ALTERNATE ROUTES AROUND CLOSED OR

OBSTRUCTED TRAFFIC.

18 PROVIDE INTERIOR BRACING OR SUPPORTS AS REQUIRED TO PREVENT MOVEMENT

OR COLLAPSE OF ITEMS TO BE REMOVED OR DEMOLISHED DURING DEMOLITION

PHASE.

19 PROMPTLY REPAIR DAMAGE CAUSED TO ADJACENT SPACES BY DEMOLITION

OPERATIONS, AT NO COST TO THE VA.

20 MAINTAIN EXISTING UTILITIES, KEEP IN SERVICE AND PROTECT AGAINST DAMAGE

DURING DEMOLITION AND OPERATIONS.

21 DO NOT INTERRUPT EXISTING UTILITIES SERVING OCCUPIED SPACES, EXCEPT

WHEN AUTHORIZED BY COR.

22 PROVIDE TEMPORARY ENCLOSURES, AND OTHER SUITABLE METHODS AS

NECESSARY TO LIMIT THE AMOUNT OF DUST AND DIRT RISING AND SCATTERING IN

THE AIR TO THE LOWEST LEVELS OF AIR POLLUTION PRACTICAL FOR THE

CONDITION OF WORK. WRAP EITHER DUCT OPENING OR THE OUTLET WITH BLUE

CELLOPHANE TO PREVENT DUST FROM ENTERING OR REMOVE OUTLET OR GRILLE

AND INSTALL A CARD CAP TO PREVENT DUST FROM ENTERING. REMOVE AFTER

DEMO AND REPLACE WITH OUTLET. COMPLY WITH GOVERNMENT REGULATIONS.

23 CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS FROM DUST, DIRT AND

DEBRIS CAUSED BY THE DEMOLITION WORK.

24 REMOVE FROM THE SITE ALL DEBRIS, RUBBLE AND OTHER MATERIALS RESULTING

FROM DEMOLITION WORK.

25 ALL DEBRIS PRODUCED BY THE DEMOLITION DUE TO REMOVAL OF CONSTRUCTION

MATERIAL OR EQUIPMENT, SHALL BE DISPOSED OFF SITE LEGALLY AND IN A TIMELY

MANNER.

26 ALL EXISTING EQUIPMENT NOT SHOWN ON THE DEMOLITION PLANS BUT FOUND ON

THE HOSPITAL, SHALL BE NOTIFIED TO THE COR PRIOR TO ANY ACTION TAKEN BY

THE CONTRACTOR.

27 ALL DEMOLITION WORK WILL BE COORDINATED WITH THE COR PRIOR TO

COMMENCING OF WORK.

28 REMOVE ALL EXISTING TACKBOARDS, BULLETIN BOARDS, PEGBOARDS, AND WALL

MOUNTED EQUIPMENT AND STORE FOR LATER RE-INSTALLATION

GENERAL DEMOLITION NOTES

PLAN

NORTH

? DEMOLITION KEY NOTES

1 EXISTING FLOORING AND BASE TO BE REMOVED. SEE SPECIFICATIONS FOR

FLOOR PREPARATION.

2 EXISTING STAIR RAILING TO BE REMOVED/ REPLACED. SEE STAIR DETAILS SHEET

AE504.

3 EXISTING WALL PROTECTION TO BE REMOVED.

4 EXISTING APPLIED WALL FINISH TO BE REMOVED.

5 EXISTING FLOOR TILE TO BE REMOVED.

6 EXISTING DOOR AND FRAME TO BE REMOVED.

7 EXISTING PLUMBING FIXTURE TO BE REMOVED. REFER TO PLUMBING DEMO

SHEETS.

8 EXISTING INTERIOR WALL TO REMAIN, PROTECT DURING DEMOLITION AND NEW

CONSTRUCTION.

9 EXISTING WATER FOUNTAIN TO BE REMOVED, LINES CAPPED, WALLS REPAIRED.

REFER TO PLUMBING DEMOLITION DRAWING FOR EXTENT OF WORK.

10 EXISTING FLOOR EXPANSION JOINT COVER. REFER TO DWG AE505 FOR

LOCATION AND DETAILS.

11 FIRE DOOR/ FRAME TO BE REMOVED/ REPLACED. TO BE DETERMINED BY FPC

12 EXISTING WALL MOUNTED RETURN AIR GRILL TO BE REMOVED.

13 EXISTING CIPHER LOCK AND HARDWARE TO BE REMOVED.

14 REMOVE AND STORE EXISTING WALL MOUNTED FIXTURES, EQUIPMENT,

ACCESSORIES, AND SIGNAGE FOR REUSE.

15 INTERIOR WALL TO BE REMOVED.

16 EXISTING STRUCTURE TO REMAIN. PROTECT DURING CONSTRUCTION.

17 EXISTING TOILET PARTITIONS TO BE REMOVED.

18 EXISTING FIRE RISER PIPES TO REMAIN. PROTECT DURING CONSTRUCTION.

19 EXISTING MARBLE SLAB DIRECTORY SIGN TO BE REMOVED, STORED FOR REUSE

E.J. NIC

A304

E.J. NIC

A303

E.J. NIC

B303

E.J. NIC

B304

E.J. NIC

A301

E.J. NIC

A302

E.J. NIC

B302

E.J. NIC

B301

P F

P F

P F

PF

P

F

A

B

C

D

E

F

G

H

J

K

L

6 7 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 304.3.1

AD105.0

AE705

WC-27

NIC

WC-28

NIC

WC-29

NIC

WC-30

NIC

WC-31

NIC

P F

P F

A

B

C

D

E

F

G

H

J

K

L

6 7 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 304.3.1

AD105.0

WC-32

NIC

WC-33

NIC

PROJECT TEAM

V et er an s A ff ai rs D ep ar tm en t of

CHARLESTON, S.C.

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

THESE DRAWINGS ARE

NOT TO BE USED FOR

CONSTRUCTION,

BIDDING, RECORDATION,

CONVEYANCE, SALES,

OR AS THE BASIS FOR

THE ISSUANCE OF A

PERMIT

Date CONSULTANTS

FULLY SPRINKLERED

DESIGN/BUILD

6/

/2

6:

:1

P

M

CONSTRUCTION DOCUMENTS SUBMISSION

RENOVATION OF COMMON

AND SUPPORT AREAS IN

BUILDING 1

534-15-105

AD104.0

06-30-2016

AEJMIV

22325

LEVEL 4/5 - OVERALL DEMOLITION

PLAN

1" = 20'-0"1 DEMOLITION FLOOR PLAN - 4TH FLOOR

SCALE: 1" = 20'-0"

0 10'-0" 20'-0" 40'-0"

1 ALL ITEMS SHOWN DASHED INDICATE ITEMS TO BE DEMOLISHED OR SALVAGED.

SEE SPECIFIC NOTES BELOW FOR ADDITIONAL INFORMATION. REFER TO

MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL DRAWINGS FOR

ADDITIONAL DEMOLITION NOTES.

2 ALL OPENINGS AND SURFACES MADE BARE BY DEMOLITION AND/OR REMOVAL OF

MATERIALS SHALL BE REPAIRED AND/OR PATCHED TO MATCH ADJACENT FINISH.

PREPARE SURFACES TO RECEIVE NEW FINISH(ES).

3 CONTRACTOR TO DEVELOP AND PUBLISH INFECTION CONTROL PLAN AND SAFETY

PLAN FOR APPROVAL BY COR PRIOR TO BEGINNING THEIR WORK. PLAN TO

INCLUDE MEANS AND METHODS OF DEBRIS STAGING AND REMOVAL, BOTH

INTERNALLY AND EXTERNALLY.

4 INSTALL TEMPORARY DUST AND DEBRIS BARRIERS AND VESTIBULES AROUND

PROJECT LIMITS IN ACCORDANCE WITH THE VA'S INFECTON CONTROL PLAN.

TEMPORARY BARRIERS ARE NOT TO RESTRICT REQUIRED MEANS OF EGRESS

PATHS AND WIDTHS.

5 HAZARDOUS MATERIAL ABATEMENT IS REQUIRED IN PROJECT SCOPE. REF.

HA-SERIES DRAWINGS FOR ADDITIONAL INFORMATION.

6 REMOVE ALL INDICATED ACOUSTICAL CEILING TILE, OVERHEAD MECHANICAL

EQUIPMENT, A/C DUCTS AND RETURNS, LIGHT FIXTURES.

7 EXISTING TO REMAIN: ANY FIRE SPRINKLER HEADS, RISERS, VALVES, OF ANY

OTHER RELATED FIRE PROTECTION EQUIPMENT, UNLESS OTHERWISE NOTED.

8 FIELD VERIFY ALL EXISTING DIMENSIONS PRIOR TO ANY CONSTRUCTION OR

EQUIPMENT INSTALLATION. IMMEDIATELY NOTIFY COR OF ANY DISCREPANCY.

9 ALL EQUIPMENT IN HISTOLOGY LAB TO BE RELOCATED DURING DEMOLITION

10 ALL EXISTING DOORS, UNLESS OTHERWISE NOTED, ARE TO REMAIN. PROTECT

DURING DEMOLITION AND NEW CONSTRUCTION, AND ARE TO RECEIVE PAINT

WHERE NECESSARY.

11 CONTRACTOR TO SALVAGE AND PROPERLY STORE ALL TOILET ACCESSORIES,

FEMININE PRODUCT DISPENSERS AND BABY CHANGING STATIONS FOR RE-USE BY

VA. IF NOT REUSED IN THIS PROJECT TURN OVER ITEM TO VA.

12 THE EXTENT OF DEMOLITION WORK IS SHOWN ON DRAWINGS AND

SPECIFICATIONS.

13 THE USE OF EXPLOSIVES WILL NOT BE PERMITTED.

14 BURNING OF REMOVED MATERIALS FROM DEMOLISHED STRUCTURES WILL NOT BE

PERMITTED IN THE SITE.

15 CONDUCT DEMOLITION OPERATIONS AND THE REMOVAL OF DEBRIS TO ENSURE

MINIMUM INTERFERENCE WITH ANOTHER ADJACENT OCCUPIED OR USED SPACE.

16 PROVIDE COVERED PASSAGEWAY TO ENSURE THE SAVE PASSAGE OF PEOPLE

AROUND THE AREA OF DEMOLITION. CONDUCT OPERATIONS TO PREVENT DAMAGE

TO FALLING DEBRIS OR OTHER CAUSE TO ADJACENT SPACES. PROVIDE PHASING

PLAN FOR MATERIAL, WORK PERFORMED FOR APPROVAL.

17 DO NOT CLOSE OR OBSTRUCT CORRIDOR OR OCCUPIED SPACES WITHOUT

PERMISSION FROM THE COR. PROVIDE ALTERNATE ROUTES AROUND CLOSED OR

OBSTRUCTED TRAFFIC.

18 PROVIDE INTERIOR BRACING OR SUPPORTS AS REQUIRED TO PREVENT MOVEMENT

OR COLLAPSE OF ITEMS TO BE REMOVED OR DEMOLISHED DURING DEMOLITION

PHASE.

19 PROMPTLY REPAIR DAMAGE CAUSED TO ADJACENT SPACES BY DEMOLITION

OPERATIONS, AT NO COST TO THE VA.

20 MAINTAIN EXISTING UTILITIES, KEEP IN SERVICE AND PROTECT AGAINST DAMAGE

DURING DEMOLITION AND OPERATIONS.

21 DO NOT INTERRUPT EXISTING UTILITIES SERVING OCCUPIED SPACES, EXCEPT

WHEN AUTHORIZED BY COR.

22 PROVIDE TEMPORARY ENCLOSURES, AND OTHER SUITABLE METHODS AS

NECESSARY TO LIMIT THE AMOUNT OF DUST AND DIRT RISING AND SCATTERING IN

THE AIR TO THE LOWEST LEVELS OF AIR POLLUTION PRACTICAL FOR THE

CONDITION OF WORK. WRAP EITHER DUCT OPENING OR THE OUTLET WITH BLUE

CELLOPHANE TO PREVENT DUST FROM ENTERING OR REMOVE OUTLET OR GRILLE

AND INSTALL A CARD CAP TO PREVENT DUST FROM ENTERING. REMOVE AFTER

DEMO AND REPLACE WITH OUTLET. COMPLY WITH GOVERNMENT REGULATIONS.

23 CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS FROM DUST, DIRT AND

DEBRIS CAUSED BY THE DEMOLITION WORK.

24 REMOVE FROM THE SITE ALL DEBRIS, RUBBLE AND OTHER MATERIALS RESULTING

FROM DEMOLITION WORK.

25 ALL DEBRIS PRODUCED BY THE DEMOLITION DUE TO REMOVAL OF CONSTRUCTION

MATERIAL OR EQUIPMENT, SHALL BE DISPOSED OFF SITE LEGALLY AND IN A TIMELY

MANNER.

26 ALL EXISTING EQUIPMENT NOT SHOWN ON THE DEMOLITION PLANS BUT FOUND ON

THE HOSPITAL, SHALL BE NOTIFIED TO THE COR PRIOR TO ANY ACTION TAKEN BY

THE CONTRACTOR.

27 ALL DEMOLITION WORK WILL BE COORDINATED WITH THE COR PRIOR TO

COMMENCING OF WORK.

28 REMOVE ALL EXISTING TACKBOARDS, BULLETIN BOARDS, PEGBOARDS, AND WALL

MOUNTED EQUIPMENT AND STORE FOR LATER RE-INSTALLATION

PLAN

NORTH

1" = 20'-0"2 DEMOLITION FLOOR PLAN - 5TH FLOOR

GENERAL DEMOLITION NOTES

? DEMOLITION KEY NOTES

1 EXISTING FLOORING AND BASE TO BE REMOVED. SEE SPECIFICATIONS FOR

FLOOR PREPARATION.

2 EXISTING STAIR RAILING TO BE REMOVED/ REPLACED. SEE STAIR DETAILS SHEET

AE504.

3 EXISTING WALL PROTECTION TO BE REMOVED.

4 EXISTING APPLIED WALL FINISH TO BE REMOVED.

5 EXISTING FLOOR TILE TO BE REMOVED.

6 EXISTING DOOR AND FRAME TO BE REMOVED.

7 EXISTING PLUMBING FIXTURE TO BE REMOVED. REFER TO PLUMBING DEMO

SHEETS.

8 EXISTING INTERIOR WALL TO REMAIN, PROTECT DURING DEMOLITION AND NEW

CONSTRUCTION.

9 EXISTING WATER FOUNTAIN TO BE REMOVED, LINES CAPPED, WALLS REPAIRED.

REFER TO PLUMBING DEMOLITION DRAWING FOR EXTENT OF WORK.

10 EXISTING FLOOR EXPANSION JOINT COVER. REFER TO DWG AE505 FOR

LOCATION AND DETAILS.

11 FIRE DOOR/ FRAME TO BE REMOVED/ REPLACED. TO BE DETERMINED BY FPC

12 EXISTING WALL MOUNTED RETURN AIR GRILL TO BE REMOVED.

13 EXISTING CIPHER LOCK AND HARDWARE TO BE REMOVED.

14 REMOVE AND STORE EXISTING WALL MOUNTED FIXTURES, EQUIPMENT,

ACCESSORIES, AND SIGNAGE FOR REUSE.

15 INTERIOR WALL TO BE REMOVED.

16 EXISTING STRUCTURE TO REMAIN. PROTECT DURING CONSTRUCTION.

17 EXISTING TOILET PARTITIONS TO BE REMOVED.

18 EXISTING FIRE RISER PIPES TO REMAIN. PROTECT DURING CONSTRUCTION.

19 EXISTING MARBLE SLAB DIRECTORY SIGN TO BE REMOVED, STORED FOR REUSE

E.J. NIC

A401

E.J. NIC

A402

E.J. NIC

B401

E.J. NIC

B402

E.J. NIC

A501

E.J. NIC

A502

E.J. NIC

B501

E.J. NIC

B502

P

FF

G

H

14 15 16

ELEVATOR

LOBBY

ELEVLOB3

STAIR #3

3-3

ELEV.

P-2

ELEV.

P-3

ELEV.

P-1

ELEV.

S-1

ELEV.

S-2

AE504.0

P F

F

G

H

14 15 16

ELEVATOR

LOBBY

ELEVLOB4

STAIR #3

3-4

ELEV.

P-2

ELEV.

P-3

ELEV.

P-1

ELEV.

S-1

ELEV.

S-2

AE504.0

P F

F

G

H

14 15 16

ELEVATOR

LOBBY

ELEVLOB5

STAIR #3

3-5

CORRIDOR

COR5C1

ELEV.

P-2

ELEV.

P-3

ELEV.

P-1

ELEV.

S-1

ELEV.

S-2

AE504.0

PF

UP

F

G

H

14 15 16

1ST FLOOR

ELEVATOR

LOBBY

ELEVLOB1

3-1

AE504.0

ELEV.

P-2

ELEV.

P-3

ELEV.

P-1

ELEV.

S-1

ELEV.

S-2

ATM

DN

P F

F

G

H

J

K

14 15 16

ELEVATOR

LOBBY

ELEVLOB2

COR2AB1

STAIR #3

3-2

1 3

AE504.0

ELEV.

P-2

ELEV.

P-3

ELEV.

P-1

ELEV.

S-1

ELEV.

S-2

PROJECT TEAM

V et er an s A ff ai rs D ep ar tm en t of

CHARLESTON, S.C.

Architect/Engineer

Seal Architect/Engineer AddressRevisions Date

Project No.

DRAWING NO.

Project Title

Building Number Checked Drawn

Location Dwg. Of

Drawing Title

Approved: Chief Engineering Service

JEFFERY A. SAGE

Approved: Project Manager

AVIS R. THOMAS

THESE DRAWINGS ARE

NOT TO BE USED FOR

CONSTRUCTION,

BIDDING, RECORDATION,

CONVEYANCE, SALES,

OR AS THE BASIS FOR

THE ISSUANCE OF A

PERMIT

Date CONSULTANTS

FULLY SPRINKLERED

DESIGN/BUILD

6/

/2

6:

:5

P

M

CONSTRUCTION DOCUMENTS SUBMISSION

RENOVATION OF COMMON

AND SUPPORT AREAS IN

BUILDING 1

534-15-105

AD105.0

06-30-2016

AEJMIV

22326

ENLARGED - ELEVATOR LOBBIES -

DEMOLITION PLANS

? DEMOLITION KEY NOTES

1 EXISTING FLOORING AND BASE TO BE REMOVED. SEE SPECIFICATIONS FOR

FLOOR PREPARATION.

2 EXISTING STAIR RAILING TO BE REMOVED/ REPLACED. SEE STAIR DETAILS SHEET

AE504.

3 EXISTING WALL PROTECTION TO BE REMOVED.

4 EXISTING APPLIED WALL FINISH TO BE REMOVED.

5 EXISTING FLOOR TILE TO BE REMOVED.

6 EXISTING DOOR AND FRAME TO BE REMOVED.

7 EXISTING PLUMBING FIXTURE TO BE REMOVED. REFER TO PLUMBING DEMO

SHEETS.

8 EXISTING INTERIOR WALL TO REMAIN, PROTECT DURING DEMOLITION AND NEW

CONSTRUCTION.

9 EXISTING WATER FOUNTAIN TO BE REMOVED, LINES CAPPED, WALLS REPAIRED.

REFER TO PLUMBING DEMOLITION DRAWING FOR EXTENT OF WORK.

10 EXISTING FLOOR EXPANSION JOINT COVER. REFER TO DWG AE505 FOR

LOCATION AND DETAILS.

11 FIRE DOOR/ FRAME TO BE REMOVED/ REPLACED. TO BE DETERMINED BY FPC

12 EXISTING WALL MOUNTED RETURN AIR GRILL TO BE REMOVED.

13 EXISTING CIPHER LOCK AND HARDWARE TO BE REMOVED.

14 REMOVE AND STORE EXISTING WALL MOUNTED FIXTURES, EQUIPMENT,

ACCESSORIES, AND SIGNAGE FOR REUSE.

15 INTERIOR WALL TO BE REMOVED.

16 EXISTING STRUCTURE TO REMAIN. PROTECT DURING CONSTRUCTION.

17 EXISTING TOILET PARTITIONS TO BE REMOVED.

18 EXISTING FIRE RISER PIPES TO REMAIN. PROTECT DURING CONSTRUCTION.

19 EXISTING MARBLE SLAB DIRECTORY SIGN TO BE REMOVED, STORED FOR REUSE

1/8" = 1'-0"3 DEMOLITION PLAN - 3RD FLOOR LOBBY

1/8" = 1'-0"4 DEMOLITION PLAN - 4TH FLOOR LOBBY

1/8" = 1'-0"5 DEMOLITION PLAN - 5TH FLOOR LOBBY

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

1/8" = 1'-0"1 DEMOLITION PLAN - 1ST FLOOR LOBBY

1/8" = 1'-0"2 DEMOLITION PLAN - 2ND FLOOR LOBBY

KEY PLAN

LEVEL 3 FFE: 025.56'

PLAN

NORTH KEY PLAN

LEVEL 4 FFE: 037.34'

PLAN

NORTH

KEY PLAN

PLAN

NORTH

LEVEL 5 FFE: 049.13'KEY PLAN

LEVEL 2 FFE: 013.78'

PLAN

NORTH

KEY PLAN

LEVEL 1 FFE: 000.00'

PLAN

NORTH

21 Should the Contractor encounter any existing equipment, piping, ductwork, electrical, data, supports that interfere with new work installation, they should remove/relocate same at no cost to the Government. REVISED FA 06.09.2017

File details come from the government source that posted it.