565-22-500 Combined Set 20251118.pdf
PDF 42 MB Posted
- Attached to
- Correct Electrical Deficiencies
- Solicitation number
- 36C24627B0001
About this file
This is a Statement of Work (SOW) for electrical deficiencies correction at the Fayetteville VA Medical Center (VAMC) under VA solicitation number 36C24627B0001. The project encompasses a comprehensive overhaul of the facility's electrical infrastructure over a period of 1,174 calendar days, including replacement of the medium voltage entrance building, medium voltage loop replacement, electrical distribution equipment upgrades, ground conductor corrections, and incidental electrical equipment cleanup throughout the campus. Additionally, minor HVAC and plumbing improvements are included as part of the scope.
The medium voltage work scope involves replacing the existing medium voltage entrance equipment at the campus entrance with new infrastructure, including a new slab-on-grade building with brick-on-CMU walls and slate roof tile (matching existing facility architecture), new VA-owned medium voltage cables in a concrete-encased duct bank spanning approximately 300 feet, and demolition of the existing medium voltage entrance metal structure. The project also requires installation of new metal-clad switchgear with draw-out vacuum circuit breakers and replacement of one medium voltage oil-filled transformer. Panel replacement and branch circuit improvements address identified deficiencies in electrical panels and branch circuit wiring that are incorrectly sized, improperly protected, or at end of useful life. The work requires phasing plans for VA approval, with approximately 2 normal service entrance switchboards, 2 generator switchboards, 7 automatic transfer switches, and 5 distribution panels requiring replacement or modification. All replacements must include temporary power solutions to minimize electrical outages to existing operational areas, and the contractor must implement a comprehensive phasing approach throughout project execution.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sign-in sheet_12Nov2026.pdf | ||
| 19-Outage Plan.pdf | ||
| 18-Hazmat Survey.pdf | ||
| 21-21 Nov 2014 VACO ECA E24.pdf | ||
| ATTACHMENT - BAA TAA COMPLIANCE CERTIFICATION.docx | DOCX document | |
| Correct Electrical Deficiencies Specifications.pdf | ||
| 36C24627B0001.docx | DOCX document |