21-21 Nov 2014 VACO ECA E24.pdf

PDF 4 MB Posted

Attached to
Correct Electrical Deficiencies
Solicitation number
36C24627B0001
Issued by

About this file

This is a Coordination Study document prepared by Toland Mizell and Clark Nexsen on November 21, 2014, for the VA Fayetteville Medical Center detailing Time-Current-Characteristic (TCC) curves and coordination recommendations for the facility's electrical distribution system. The document provides technical analysis and recommendations for adjusting or replacing circuit breakers, fuses, and relays throughout the medium and low voltage electrical systems to achieve proper protective device coordination. It addresses deficiencies where existing equipment fails to coordinate with upstream and downstream protection devices, ensuring that faults are isolated at the nearest point without exposing feeders or transformers to damage.

The coordination study includes approximately 50 TCC curves organized by system section, each containing descriptions of protective devices, comments on existing coordination, and specific recommendations. Key deficiencies identified include undersized fuses on transformer primaries (MV-TCC-T-1 recommends replacing a 20-amp fuse with a 25-amp fuse), improper overlaps between downstream and relay protection (MV-TCC-T-6 and MV-TCC-T-7 recommend fuse replacements), obsolete circuit breakers requiring replacement with adjustable static trip units (MV-TCC-3-M1DP, MV-TCC-4-MDP, and MV-TCC-8-MDP), ground fault coordination deficiencies requiring delay setting adjustments, and low-voltage panel coordination issues requiring breaker replacements or settings modifications. The document serves as the technical guidance for the contractor to implement electrical corrections under the related federal contract SOW 565-22-500 for correcting electrical deficiencies at Fayetteville VAMC, with all recommendations to be confirmed before adjusting or ordering replacement equipment.

View the file

Other files

File Type Posted
Sign-in sheet_12Nov2026.pdf PDF
19-Outage Plan.pdf PDF
18-Hazmat Survey.pdf PDF
565-22-500 Combined Set 20251118.pdf PDF
ATTACHMENT - BAA TAA COMPLIANCE CERTIFICATION.docx DOCX document
Correct Electrical Deficiencies Specifications.pdf PDF
36C24627B0001.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPENDIX 21

Document ’21 Nov 2014 VACO ECA E24’

The following is a VA Fayetteville supplied document.

This Coordination study, performed by Toland Mizell/Cark Nexsen on 21 Nov 2014, provides circuit breaker adjustment or replacement recommendations for equipment that fails to coordinate with upstream/downstream equipment. These recommendations are the guidance to which the Electrical Contractor shall provide adjustment to existing circuit breakers or replacement new circuit breakers to achieve coordination on the electrical distribution system. This document shall be used in tandem with the Electrical Drawing set, including the Electrical Deficiency Log. Confirm all new circuit breaker adjustment or replacements with Contractor Provided Coordination Study prior to adjusting or ordering new equipment.

4.3-1

4.3 TCC Descriptions, Comments and Recommendations

Below each TCC is a short description of the devices contained in the TCC, comments on the coordination, protection provided, etc. and recommendations where deficiencies are noted.

A Proposed TCC showing the result of device adjustments immediately follows TCCs in which a deficiency is noted.

Cases where circuit breakers cannot be properly coordinated with other system elements, including but not limited to fuses, breakers, and transformers, a proposed circuit breaker that properly coordinates has been selected. While care has been taken to select compatible breakers for the existing panelboards and systems, it is advised that the equipment manufacturer be consulted regarding compatibility and fit prior to any actual system change.

4.3-2

MV-TCC-MV-F3A-52

Description: MV relays for the incoming utility service and the downstream relays.

Comments: The 15 kV feeder relay MV-F3A-51, incoming relay MV-TOKAY-51, and utility protective relay

MV-PWC-TOKAY-51 are all coordinated. The feeder breaker and relay provide long time protection for the system.

MV-TOKAY-51 - Phase

MV-F3A-51

PWC-TOKAY-51

MV-TOKAY-51

WESTINGHOUSE

CO-6

Settings Phase Tap (1-12A) 6.0 (360A) Time Dial (0.5-11) 1.5 CT Ratio 300 / 5 A

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

PWC-TOKAY-51

ABB

CO-9

Settings Phase Tap (1-12A) 7.5 (600A) Time Dial (0.5-11) 8.0 CT Ratio 400 / 5 A

MV-TOKAY-51

WESTINGHOUSE

CO-6

Settings Phase Tap (1-12A) 6.0 (360A) Time Dial (0.5-11) 1.5 CT Ratio 300 / 5 A

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

PWC-TOKAY-51

ABB

CO-9

Settings Phase Tap (1-12A) 7.5 (600A) Time Dial (0.5-11) 8.0 CT Ratio 400 / 5 A

TYPICAL FOR MV-F3A-52

AND MV-F3D-52.

TYPICAL FOR MV-F3A-52

AND MV-F3D-52.

MV-TOKAY-51

MV-F3A-52

MV-F3A-51

MV-E3A-52

MV-37-SWGR

PWC-TOKAY-51

TCC Name: MV-TCC-MV-F3A-52 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 3:04 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-3

MV-TCC-MV-F3A-51-G

Description: MV relays for the incoming utility service and the downstream relays.

Comments: The 15 kV feeder relay MV-F3A-51-G, incoming relay MV-TOKAY-51-G, and utility protective relay MV-PWC-TOKAY-51-G are all coordinated. The incoming relay and feeder relay have an appropriate separation of greater than 6 cycles.

PWC-TOKAY-51-G

MV-TOKAY-51-G

MV-F3A-51-G

PWC-TOKAY-51-G

ABB

CO-9

Settings Phase Tap (1-12A) 3.0 (240A) Time Dial (0.5-11) 8.0 CT Ratio 400 / 5 A

MV-TOKAY-51-G

WESTINGHOUSE

CO-6

Settings GF Tap (0.5-2.5A) 0.6 (3.6A) Time Dial (0.5-11) 1.5 CT Ratio 30 / 5 A

MV-F3A-51-G

WESTINGHOUSE

CO-11

Settings GF Tap (0.5-2.5A) 0.5 (1.5A) Time Dial (0.5-11) 2.0 CT Ratio 15 / 5 A

PWC-TOKAY-51-G

ABB

CO-9

Settings Phase Tap (1-12A) 3.0 (240A) Time Dial (0.5-11) 8.0 CT Ratio 400 / 5 A

MV-TOKAY-51-G

WESTINGHOUSE

CO-6

Settings GF Tap (0.5-2.5A) 0.6 (3.6A) Time Dial (0.5-11) 1.5 CT Ratio 30 / 5 A

MV-F3A-51-G

WESTINGHOUSE

CO-11

Settings GF Tap (0.5-2.5A) 0.5 (1.5A) Time Dial (0.5-11) 2.0 CT Ratio 15 / 5 A

TYPICAL OF MV-F3A-51-G

AND MV-F3D-51-G.

TYPICAL OF MV-F3A-51-G

AND MV-F3D-51-G.

PWC-TOKAY

PWC-TOKAY-51-G

MV-TOKAY-51-G

MV-E3A-52

MV-37-SWGR

MV-F3A-51-G

TCC Name: MV-TCC-MV-F3A-51-G Current Scale x 1 Reference Voltage: 12470

November 17, 2014 3:07 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-4

MV-TCC-T-1

Description: Main MV feeder relay, sectionalizing switch fuse, and transformer.

Comments: 15 kV relay and breaker MV-F3A-51 and 15 kV fuse MV-SS-1-FUSE-1 are properly coordinated.

The MV fuse MV-SS-1-FUSE-1 falls below the transformer FLA. Feeders are not exposed to damage.

Recommendation: It is recommended that the fuse be replaced with the next size higher similar style fuse (SMU-

20 25E) to properly conduct the FLA of the transformer.

MV-F3A-51

MV-CBL-SS-1-A

TX Inrush

T-1

MV-CBL-T-1

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-1-FUSE-1

S&C

SMU-20, 20E

Trip 20.0 A Settings Phase 20 Amps

MV-CBL-SS-1-A

2 AWG/kcmil

T-1

1000.0 kVA

MV-CBL-T-1

2 AWG/kcmil

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-1-FUSE-1

S&C

SMU-20, 20E

Trip 20.0 A Settings Phase 20 Amps

MV-CBL-SS-1-A

2 AWG/kcmil

T-1

1000.0 kVA

MV-CBL-T-1

2 AWG/kcmil

MV-F3A-52

MV-F3A-51

MV-SS-1-SW-1

MV-CBL-SS-1-A

MV-SWGR-SS-1

MV-SS-1-FUSE-1

S

P

T-1

MV-CBL-T-1

TCC Name: MV-TCC-T-1 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 3:09 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-5

MV-TCC-T-1 – PROPOSED

Comments: The sectionalizing switch fuse has been replaced with the next size up and now properly conducts the

FLA of the transformer.

MV-F3A-51

MV-CBL-SS-1-A

TX Inrush

T-1

MV-CBL-T-1

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-1-FUSE-1

S&C

SMU-20, 25E

Trip 25.0 A Settings Phase 25 Amps

MV-CBL-SS-1-A

2 AWG/kcmil

T-1

1000.0 kVA

MV-CBL-T-1

2 AWG/kcmil

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-1-FUSE-1

S&C

SMU-20, 25E

Trip 25.0 A Settings Phase 25 Amps

MV-CBL-SS-1-A

2 AWG/kcmil

T-1

1000.0 kVA

MV-CBL-T-1

2 AWG/kcmil

MV-F3A-52

MV-F3A-51

MV-SS-1-SW-1

MV-CBL-SS-1-A

MV-SWGR-SS-1

MV-SS-1-FUSE-1

S

P

T-1

MV-CBL-T-1

TCC Name: MV-TCC-T-1 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 3:12 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-6

MV-TCC-T-3

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. The overlap between fuses MV-SS-3-FUSE-1 and MV-FUSE-T-3 is acceptable as they are in series with no other loads between them. While the assumed inrush point of the transformer is above the fuse curve, no tripping problems have been reported upon energization of the transformer. Feeders are not exposed to damage. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

MV-F3D-51

MV-CBL-SS-3-B

TX Inrush

T-3

MV-CBL-T-3

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-3-FUSE-1

S&C

SMU-20, 15E

Trip 15.0 A Settings Phase 15 Amps

MV-FUSE-T-3

GE

EJO-1, 15E

Trip 15.0 A Settings Phase 15 Amps

MV-CBL-SS-3-B

2/0 AWG/kcmil

T-3

225.0 kVA

MV-CBL-T-3

2 AWG/kcmil

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-3-FUSE-1

S&C

SMU-20, 15E

Trip 15.0 A Settings Phase 15 Amps

MV-FUSE-T-3

GE

EJO-1, 15E

Trip 15.0 A Settings Phase 15 Amps

MV-CBL-SS-3-B

2/0 AWG/kcmil

T-3

225.0 kVA

MV-CBL-T-3

2 AWG/kcmil

MV-CBL-SS-3-B

MV-F3D-52

MV-F3D-51

MV-SS-3-FUSE-1

S

P

T-3

MV-CBL-T-3

MV-FUSE-T-3

MV-SW-T-3

MV-SWGR-SS-3

MV-SS-3-SW-2

TCC Name: MV-TCC-T-3 Current Scale x 1 Reference Voltage: 12470

November 17, 2014 3:16 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-7

MV-TCC-T-4

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. The overlap between fuses MV-SS-5-FUSE-1 and MV-FUSE-T-4 is acceptable as they are in series with no other loads between them. While the assumed inrush point of the transformer is above the fuse curve, no tripping problems have been reported upon energization of the transformer. Feeders are not exposed to damage. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

MV-F3D-51

TX Inrush

T-4

MV-CBL-T-4

MV-CBL-SS-3-B

MV-CBL-SS-5-B

MV-SS-5-FUSE-1

S&C

SMU-20, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-FUSE-T-4

GE

EJO-1, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-4

150.0 kVA

MV-CBL-T-4

2 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-CBL-SS-5-B

2/0 AWG/kcmil

MV-SS-5-FUSE-1

S&C

SMU-20, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-FUSE-T-4

GE

EJO-1, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-4

150.0 kVA

MV-CBL-T-4

2 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-CBL-SS-5-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

MV-F3D-52

MV-F3D-51

MV-SS-5-FUSE-1

S

P

T-4

MV-CBL-T-4

MV-FUSE-T-4

MV-SW-T-4

MV-SWGR-SS-5

MV-SS-5-SW-2

MV-CBL-SS-5-B

TCC Name: MV-TCC-T-4 Current Scale x 1 Reference Voltage: 12470

November 17, 2014 3:18 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-8

MV-TCC-T-5A

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. While the assumed inrush point of the transformer is above the fuse curve, no tripping problems have been reported upon energization of the transformer. Feeders are not exposed to damage. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

MV-F3D-51

MV-CBL-T-5

TX Inrush

T-5A

MV-CBL-T-5A

MV-CBL-SS-4-B

MV-CBL-SS-3-B

MV-SS-4-FUSE-1

S&C

SMU-20, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-FUSE-T-5A

GE

EJO-1, 7E

Trip 7.0 A Settings Phase 7 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-CBL-T-5

2/0 AWG/kcmil

T-5A

150.0 kVA

MV-CBL-T-5A

2 AWG/kcmil

MV-CBL-SS-4-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-4-FUSE-1

S&C

SMU-20, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-FUSE-T-5A

GE

EJO-1, 7E

Trip 7.0 A Settings Phase 7 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-CBL-T-5

2/0 AWG/kcmil

T-5A

150.0 kVA

MV-CBL-T-5A

2 AWG/kcmil

MV-CBL-SS-4-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-4-FUSE-1

MV-CBL-T-5

MV-SWGR-SS-4

MV-SS-4-SW-2

MV-CBL-SS-4-B

MV-CBL-SS-3-B

MV-F3D-52

MV-F3D-51

S

P

T-5A

MV-CBL-T-5A

MV-FUSE-T-5A

TCC Name: MV-TCC-T-5A Current Scale x 1 Reference Voltage: 12470

November 17, 2014 3:19 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-9

MV-TCC-T-5B

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. While the assumed inrush point of the transformer is above the fuse curve, no tripping problems have been reported upon energization of the transformer. Feeders are not exposed to damage. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

MV-F3D-51

MV-CBL-T-5

TX Inrush

T-5B

MV-CBL-SS-4-B

MV-CBL-SS-3-B

MV-SS-4-FUSE-1

S&C

SMU-20, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-FUSE-T-5B

GE

EJO-1, 7E

Trip 7.0 A Settings Phase 7 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-CBL-T-5

2/0 AWG/kcmil

T-5B

112.5 kVA

MV-CBL-SS-4-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-4-FUSE-1

S&C

SMU-20, 10E

Trip 10.0 A Settings Phase 10 Amps

MV-FUSE-T-5B

GE

EJO-1, 7E

Trip 7.0 A Settings Phase 7 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-CBL-T-5

2/0 AWG/kcmil

T-5B

112.5 kVA

MV-CBL-SS-4-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-4-FUSE-1

MV-CBL-T-5

MV-SWGR-SS-4

S

P

T-5B

MV-FUSE-T-5B

MV-SW-T-5B

MV-SS-4-SW-2

MV-CBL-SS-4-B

MV-CBL-SS-3-B

MV-F3D-52

MV-F3D-51

TCC Name: MV-TCC-T-5B Current Scale x 1 Reference Voltage: 12470

November 17, 2014 3:20 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-10

MV-TCC-T-6

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. The overlap of fuses MV-SS-2-FUSE-1 and MV-FUSE-T6 is acceptable as they are in series with no other loads between them. The overlap between the downstream fuse and the relay is not acceptable. Feeders are not exposed to damage. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

Recommendation: Replace MV-FUSE-T-6 to improve coordination.

MV-F3A-51

TX Inrush

T-6

MV-CBL-T-6

MV-CBL-SS-1-A

MV-SS-2-FUSE-1

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-6

GE

EJO-1, 100E

Trip 100.0 A Settings Phase 100 Amps

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-6

1000.0 kVA

MV-CBL-T-6

2 AWG/kcmil

MV-CBL-SS-1-A

2 AWG/kcmil

MV-SS-2-FUSE-1

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-6

GE

EJO-1, 100E

Trip 100.0 A Settings Phase 100 Amps

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-6

1000.0 kVA

MV-CBL-T-6

2 AWG/kcmil

MV-CBL-SS-1-A

2 AWG/kcmil

MV-SS-2-FUSE-1

MV-SS-2-SW-1

S

P

T-6

MV-CBL-T-6

MV-FUSE-T-6

MV-SW-T-6

MV-CBL-SS-1-A

MV-F3A-51

MV-F3A-52

TCC Name: MV-TCC-T-6 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 3:23 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-11

MV-TCC-T-6 - PROPOSED

Comments: Fuse MV-FUSE-T-6 has been replaced and coordination has improved.

MV-F3A-51

TX Inrush

T-6

MV-CBL-T-6

MV-CBL-SS-1-A

MV-SS-2-FUSE-1

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-6

GE

EJO-1, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-6

1000.0 kVA

MV-CBL-T-6

2 AWG/kcmil

MV-CBL-SS-1-A

2 AWG/kcmil

MV-SS-2-FUSE-1

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-6

GE

EJO-1, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-F3A-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-6

1000.0 kVA

MV-CBL-T-6

2 AWG/kcmil

MV-CBL-SS-1-A

2 AWG/kcmil

MV-SS-2-FUSE-1

MV-SS-2-SW-1

S

P

T-6

MV-CBL-T-6

MV-FUSE-T-6

MV-SW-T-6

MV-CBL-SS-1-A

MV-F3A-51

MV-F3A-52

TCC Name: MV-TCC-T-6 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 3:53 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-12

MV-TCC-T-7

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. The overlap of fuses MV-SS-3-FUSE-2 and MV-FUSE-BLDG 35 XFMR is acceptable as they are in series with no other loads between them. Fuse MV-SS-3-FUSE-2 provides thermal and mechanical protection of the transformer.

Feeders are not exposed to damage. Overlap between downstream fuse and relay is unacceptable. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

Recommendation: Replace MC-FUSE-BLDG 35 XFMR with a smaller fuse to improve coordination.

MV-F3D-51

TX Inrush

T-7

MV-CBL-T-7

MV-CBL-SS-3-B

MV-SS-3-FUSE-2

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-BLDG 35 XFMR

CUTLER-HAMMER

CLE, 100E

Trip 100.0 A Settings Phase

100.0 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-7

1500.0 kVA

MV-CBL-T-7

2 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-3-FUSE-2

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-BLDG 35 XFMR

CUTLER-HAMMER

CLE, 100E

Trip 100.0 A Settings Phase

100.0 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-7

1500.0 kVA

MV-CBL-T-7

2 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-3-FUSE-2

MV-SS-3-SW-2

S

P

T-7

MV-SW-BLDG35 XFMR

MV-FUSE-BLDG 35 XFMR

MV-BLDG 35 XFMR

MV-CBL-T-7

MV-CBL-SS-3-B

MV-SWGR-SS-3

MV-F3D-52

MV-F3D-51

TCC Name: MV-TCC-T-7 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 3:24 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-13

MV-TCC-T-7 - PROPOSED

Comments: Fuse MV-FUSE-BLDG 35 XFMR has been replaced and coordination has improved.

MV-F3D-51

T-7

MV-CBL-T-7

MV-CBL-SS-3-B

MV-SS-3-FUSE-2

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-BLDG 35 XFMR

CUTLER-HAMMER

CLE, 50E

Trip 50.0 A Settings Phase

50.0 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 7 (210A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-7

1500.0 kVA

MV-CBL-T-7

2 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-3-FUSE-2

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-BLDG 35 XFMR

CUTLER-HAMMER

CLE, 50E

Trip 50.0 A Settings Phase

50.0 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 7 (210A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-7

1500.0 kVA

MV-CBL-T-7

2 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-3-FUSE-2

MV-SS-3-SW-2

S

P

T-7

MV-SW-BLDG35 XFMR

MV-FUSE-BLDG 35 XFMR

MV-BLDG 35 XFMR

MV-CBL-T-7

MV-CBL-SS-3-B

MV-SWGR-SS-3

MV-F3D-52

MV-F3D-51

TCC Name: MV-TCC-T-7 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 4:10 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-14

MV-TCC-T-8

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. The overlap between fuses MV-SS-3-FUSE-1 and MV-FUSE-T-3 is acceptable as they are in series with no other loads between them. While the assumed inrush point of the transformer is above the fuse curve, no tripping problems have been reported upon energization of the transformer. Feeders are not exposed to damage. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

MV-F3D-51

TX Inrush

T-8

MV-CBL-T-8

MV-CBL-SS-6-B

MV-CBL-SS-3-B

MV-SS-6-FUSE-1

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-8

GE

EJO-1, 25E

Trip 25.0 A Settings Phase 25 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-8

750.0 kVA

MV-CBL-T-8

2/0 AWG/kcmil

MV-CBL-SS-6-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-6-FUSE-1

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-8

GE

EJO-1, 25E

Trip 25.0 A Settings Phase 25 Amps

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

T-8

750.0 kVA

MV-CBL-T-8

2/0 AWG/kcmil

MV-CBL-SS-6-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

2/0 AWG/kcmil

MV-SS-6-FUSE-1

S

P

T-8

MV-CBL-T-8

MV-FUSE-T-8

MV-SWGR-SS-6

MV-SS-6-SW-2

MV-CBL-SS-6-B

MV-CBL-SS-3-B

MV-F3D-52

MV-F3D-51

TCC Name: MV-TCC-T-8 Current Scale x 1 Reference Voltage: 12470

November 17, 2014 3:25 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-15

MV-TCC-T-9

Description: Main MV feeder relay, MV sectionalizing switch fuse, transformer MV fuse, and transformer.

Comments: The 15 kV relay and breaker MV-F3D-51 are coordinated with the downstream fuses. The overlap of fuses MV-SS-4-FUSE-2 and MV-FUSE-T9 is acceptable as they are in series with no other loads between them. Feeders are not exposed to damage. Overlap with the MV relay has been corrected with settings adjustments in a previous curve. The protective devices on the secondary side of the transformer provide adequate protection from fault currents and some protection of the internal windings from overloads. Long term overload conditions are not expected based on the actual transformer loading.

MV-F3D-51

MV-CBL-SS-3-B

TX Inrush

T-9

MV-CBL-T-9

MV-CBL-SS-4-B

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-4-FUSE-2

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-9

GE

EJO-1, 100E

Trip 100.0 A Settings Phase 100 Amps

MV-CBL-SS-3-B

2/0 AWG/kcmil

T-9

1000.0 kVA

MV-CBL-T-9

2/0 AWG/kcmil

MV-CBL-SS-4-B

2/0 AWG/kcmil

MV-F3D-51

WESTINGHOUSE

CO-11

Settings Phase Tap (4-12A) 5 (150A) Time Dial (0.5-11) 2.0 CT Ratio 150 / 5 A

MV-SS-4-FUSE-2

S&C

SMU-20, 65E

Trip 65.0 A Settings Phase 65 Amps

MV-FUSE-T-9

GE

EJO-1, 100E

Trip 100.0 A Settings Phase 100 Amps

MV-CBL-SS-3-B

2/0 AWG/kcmil

T-9

1000.0 kVA

MV-CBL-T-9

2/0 AWG/kcmil

MV-CBL-SS-4-B

2/0 AWG/kcmil

MV-CBL-SS-3-B

MV-F3D-52

MV-F3D-51

MV-SS-4-FUSE-2

MV-SS-4-SW-2

S

P

T-9

MV-CBL-T-9

MV-CBL-SS-4-B

MV-FUSE-T-9

TCC Name: MV-TCC-T-9 Current Scale x 10 Reference Voltage: 12470

November 17, 2014 3:27 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-16

MV-TCC-1-MS

Description: Transformer damage curve down to service entrance equipment.

Comments: Long time thermal damage protection is not adequately provided by 1-MS-MB. Feeders are not exposed to damage.

Recommendation: It is recommended that the LTD setting of the circuit breaker be adjusted from 20.0 to 12.0 to provide better protection of the transformer.

TX Inrush

T-9

1-CBL-MS

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Settings Phase

LTPU 1.0 (2000A)

LTD 20.0

INST 4.0 (8000A)

T-9

1000.0 kVA

1-CBL-MS

500 AWG/kcmil

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Settings Phase

LTPU 1.0 (2000A)

LTD 20.0

INST 4.0 (8000A)

T-9

1000.0 kVA

1-CBL-MS

500 AWG/kcmil

S

P

T-9

1-CBL-MS

1-MS-MB-GF

1-MS

TCC Name: MV-TCC-1-MS Current Scale x 10 Reference Voltage: 12470 Oneline: MV-TCC-1-MS August 7, 2014 11:56 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-17

MV-TCC-1-MS – PROPOSED

Comments: The LTD setting of the circuit breaker be adjusted from 20.0 to 12.0 to provide better protection of the transformer.

TX Inrush

T-9

1-CBL-MS

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Settings Phase

LTPU 1.0 (2000A)

LTD 12.0

INST 8.0 (16000A)

T-9

1000.0 kVA

1-CBL-MS

500 AWG/kcmil

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Settings Phase

LTPU 1.0 (2000A)

LTD 12.0

INST 8.0 (16000A)

T-9

1000.0 kVA

1-CBL-MS

500 AWG/kcmil

S

P

T-9

1-CBL-MS

1-MS-MB-GF

1-MS

TCC Name: MV-TCC-1-MS Current Scale x 1 Reference Voltage: 12470

September 18, 2014 12:54 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-18

MV-TCC-3-M1DP

Comments: Adequate long time thermal damage protection is not provided by T-6-CB-MB. Feeders are not exposed to damage

Recommendation: As this is an obsolete FPE thermal magnetic circuit breaker, it is recommend that this breaker be replaced with a fully adjustable static trip circuit breaker.

TX Inrush

T-6

3-CBL-M1DP

T-6-CB-MB

FPE

NP

Trip 2000.0 A Settings Phase Thermal Curve Inst 4 (8000A)

T-6

1000.0 kVA

3-CBL-M1DP

350 AWG/kcmil

T-6-CB-MB

FPE

NP

Trip 2000.0 A Settings Phase Thermal Curve Inst 4 (8000A)

T-6

1000.0 kVA

3-CBL-M1DP

350 AWG/kcmil

S

P

T-6

T-6-CB-MB

3-CBL-M1DP

3-M1DP

T-6-CB

TCC Name: MV-TCC-3-M1DP Current Scale x 10 Reference Voltage: 12470 Oneline: MV-TCC-3-M1DP August 7, 2014 11:58 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-19

MV-TCC-3-M1DP – PROPOSED

Comments: The circuit breaker has been replaced with a fully adjustable static trip type breaker and now provides long time thermal damage protection for the transformer.

TX Inrush

T-6

3-CBL-M1DP

T-6-CB-MB

SQUARE D

NT16N

Trip 1200.0 A Settings Phase

LTPU (A);LTD 1 (1200A); 12

STPU 2 (2400A)

STD 0.4 (I^2t Off) INST (NTxxN, NTxxH) 15 (18000A)

T-6

1000.0 kVA

3-CBL-M1DP

350 AWG/kcmil

T-6-CB-MB

SQUARE D

NT16N

Trip 1200.0 A Settings Phase

LTPU (A);LTD 1 (1200A); 12

STPU 2 (2400A)

STD 0.4 (I^2t Off) INST (NTxxN, NTxxH) 15 (18000A)

T-6

1000.0 kVA

3-CBL-M1DP

350 AWG/kcmil

S

P

T-6

T-6-CB-MB

3-CBL-M1DP

3-M1DP

T-6-CB

TCC Name: MV-TCC-3-M1DP Current Scale x 10 Reference Voltage: 480

September 18, 2014 1:01 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-20

MV-TCC-4-MDP

Comments: Long time thermal damage protection is not adequately provided by T-4-CB-MB. The overlap between T-4-CB-MB and 4-MDP-MB is acceptable, as they are in series with no other loads between them.

Feeders are not exposed to damage.

Recommendation: As this is an obsolete FPE thermal magnetic circuit breaker, it is recommend that this breaker be replaced with a fully adjustable static trip circuit breaker.

TX Inrush

T-4

4-CBL-MDP

T-4-BUSWAY

T-4-CB-MB

FPE

NJL

Trip 400.0 A Settings Phase Thermal Curve Instantaneous 2.9 (1160A)

4-MDP-MB

SQUARE D

LA

Trip 400.0 A Settings Phase Thermal Curve

INST LO (2000A)

T-4

150.0 kVA

4-CBL-MDP

500 AWG/kcmil

T-4-BUSWAY

600 AWG/kcmil

T-4-CB-MB

FPE

NJL

Trip 400.0 A Settings Phase Thermal Curve Instantaneous 2.9 (1160A)

4-MDP-MB

SQUARE D

LA

Trip 400.0 A Settings Phase Thermal Curve

INST LO (2000A)

T-4

150.0 kVA

4-CBL-MDP

500 AWG/kcmil

T-4-BUSWAY

600 AWG/kcmil

S

P

T-4

T-4-CB-MB

4-CBL-MDP

4-MDP-MB

4-MDP

T-4-CB

T-4-BUSWAY

TCC Name: MV-TCC-4-MDP Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-4-MDP August 7, 2014 12:00 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-21

MV-TCC-4-MDP – PROPOSED

Comments: The circuit breaker has been replaced with a fully adjustable static trip type breaker and now provides long time thermal damage protection for the transformer.

T-4

4-CBL-MDP

T-4-BUSWAY

T-4-CB-MB

SQUARE D

LE

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (0.5-1.0 x P) 1.0 (400A) LTD (2-14 Sec.) 10 STPU (2-8 x P) 8 (3200A) STD (0.1-0.5 Sec.) 0.5 (I^2t Off) INST (2.5-8 x P) 8.0 (3200A)

4-MDP-MB

SQUARE D

LA

Trip 400.0 A Settings Phase Thermal Curve

INST LO (2000A)

T-4

150.0 kVA

4-CBL-MDP

500 AWG/kcmil

T-4-BUSWAY

600 AWG/kcmil

T-4-CB-MB

SQUARE D

LE

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (0.5-1.0 x P) 1.0 (400A) LTD (2-14 Sec.) 10 STPU (2-8 x P) 8 (3200A) STD (0.1-0.5 Sec.) 0.5 (I^2t Off) INST (2.5-8 x P) 8.0 (3200A)

4-MDP-MB

SQUARE D

LA

Trip 400.0 A Settings Phase Thermal Curve

INST LO (2000A)

T-4

150.0 kVA

4-CBL-MDP

500 AWG/kcmil

T-4-BUSWAY

600 AWG/kcmil

S

P

T-4

T-4-CB-MB

4-CBL-MDP

4-MDP-MB

4-MDP

T-4-CB

T-4-BUSWAY

TCC Name: MV-TCC-4-MDP Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-4-MDP August 7, 2014 3:25 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-22

MV-TCC-6-SUBPANEL A-CB

Comments: The circuit breaker 6-SUBPANEL A-CB fully protects the transformer and cables. It is noted that the service entrance conductors are not adequately protected per the requirements of the NEC and the building also has eight service entrance disconnecting means. Remediation of this deficiency is included in section 7.6

Summary of Costs.

6-CBL-DIST A&B

6-CBL-SPLICE BOX 1

TX Inrush

T-4

6-SUBPANEL A-CB

SIEMENS

QSH

Trip 200.0 A Settings Phase Thermal Curves Fixed INST Fixed (2000A)

6-CBL-DIST A&B

3/0 AWG/kcmil

6-CBL-SPLICE BOX 1

400 AWG/kcmil

T-4

150.0 kVA

6-SUBPANEL A-CB

SIEMENS

QSH

Trip 200.0 A Settings Phase Thermal Curves Fixed INST Fixed (2000A)

6-CBL-DIST A&B

3/0 AWG/kcmil

6-CBL-SPLICE BOX 1

400 AWG/kcmil

T-4

150.0 kVA

TYPICAL FOR 6-SUBPANEL A-CB

AND 6-SUBPANEL C-CB

TYPICAL FOR 6-SUBPANEL A-CB

AND 6-SUBPANEL C-CB

6-SUBPANEL A-CB

6-DIST A&B

6-CBL-DIST A&B

6-SPLICE BOX 1

6-CBL-SPLICE BOX 1

S

P

T-4

TCC Name: MV-TCC-6-SUBPANEL A-CB Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-6-SUBPANEL A-CB August 7, 2014 12:01 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-23

MV-TCC-6-SUBPANEL D-CB

Comments: The circuit breaker 6-SUBPANEL D-CB fully protects the transformer and cables. It is noted that the service entrance conductors are not adequately protected per the requirements of the NEC and the building also has eight service entrance disconnecting means. Remediation of this deficiency is encapsulated in section 7.6

Summary of Costs.

TX Inrush

T-4

6-CBL-SPLICE BOX 2

6-CBL-DIST D&E

6-SUBPANEL D-CB

SIEMENS

QSH

Trip 200.0 A Settings Phase Thermal Curves Fixed INST Fixed (2000A)

T-4

150.0 kVA

6-CBL-SPLICE BOX 2

400 AWG/kcmil

6-CBL-DIST D&E

3/0 AWG/kcmil

6-SUBPANEL D-CB

SIEMENS

QSH

Trip 200.0 A Settings Phase Thermal Curves Fixed INST Fixed (2000A)

T-4

150.0 kVA

6-CBL-SPLICE BOX 2

400 AWG/kcmil

6-CBL-DIST D&E

3/0 AWG/kcmil

TYPICAL FOR 6-SUBPANEL-D-CB,

6-SUBPANEL H-CB, AND

6-SUBPANEL F-CB

TYPICAL FOR 6-SUBPANEL-D-CB,

6-SUBPANEL H-CB, AND

6-SUBPANEL F-CB

S

P

T-4

6-CBL-SPLICE BOX 2

6-SPLICE BOX 2

6-SUBPANEL D-CB

6-CBL-DIST D&E

6-DIST D&E

TCC Name: MV-TCC-6-SUBPANEL D-CB Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-6-SUBPANEL D-CB

4.3-24

MV-TCC-8-MDP

Comments: Long time thermal damage protection is not adequately provided by 8-MDP-MB. It is recommended that the thermal magnetic main circuit breaker 8-MDP-MB be replaced with an adjustable static trip type. Due to the dimensional differences between the existing breaker and the static trip type, it will be necessary to replace the panelboard to accommodate the new breaker. Feeder is not exposed to damage. Remediation of this deficiency is encapsulated in section 7.6 Summary of Costs.

TX Inrush

T-5B

8-CBL-MDP

8-MDP-MB

SQUARE D

LA

Trip 400.0 A Settings Phase Thermal Curve

INST HI (4000A)

T-5B

112.5 kVA

8-CBL-MDP

500 AWG/kcmil

8-MDP-MB

SQUARE D

LA

Trip 400.0 A Settings Phase Thermal Curve

INST HI (4000A)

T-5B

112.5 kVA

8-CBL-MDP

500 AWG/kcmil

S

P

T-5B

8-MDP-MB

8-CBL-MDP

8-MDP

TCC Name: MV-TCC-8-MDP Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-8-MDP

4.3-25

MV-TCC-9-MAIN

Comments: The transformer is fully protected by 9-FUSE-MAIN. The overlap between 9-FUSE-MAIN and T-

3-CB-1 is acceptable as they are in series with no other loads between them. Feeders are not exposed to damage.

TX Inrush

T-3

CBL-T-3-CB-1

9-CBL-MAIN

T-3-CB-1-MB

FPE

NM

Trip 500.0 A Settings Phase Thermal Curve (Fixed)

INST(FIXED) 2000 (2000A)

9-FUSE-MAIN

BUSSMANN

DLS-R

Trip 400.0 A

T-3

225.0 kVA

CBL-T-3-CB-1

250 AWG/kcmil

9-CBL-MAIN

250 AWG/kcmil

T-3-CB-1-MB

FPE

NM

Trip 500.0 A Settings Phase Thermal Curve (Fixed)

INST(FIXED) 2000 (2000A)

9-FUSE-MAIN

BUSSMANN

DLS-R

Trip 400.0 A

T-3

225.0 kVA

CBL-T-3-CB-1

250 AWG/kcmil

9-CBL-MAIN

250 AWG/kcmil

S

P

T-3

T-3-CB-1-MB

CBL-T-3-CB-1

9-CBL-MAIN

T-3-CB-1

9-FUSE-MAIN

9-MAIN

TCC Name: MV-TCC-9-MAIN Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-9-MAIN August 8, 2014 6:57 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-26

MV-TCC-10-LE1-CB

Comments: The transformer and feeder cable 10-CBL-MDP are fully protected by the circuit breaker 10-LE1-

CB. Note that 10-LE1-CB is the largest of five service entrance breakers in panelboard 10-MDP.

TX Inrush

T-8

10-CBL-MDP

10-LE1-CB

WESTINGHOUSE

KDB

Trip 400.0 A Settings Phase

LTD

INST 10.0 (4000A)

T-8

750.0 kVA

10-CBL-MDP

500 AWG/kcmil

10-LE1-CB

WESTINGHOUSE

KDB

Trip 400.0 A Settings Phase

LTD

INST 10.0 (4000A)

T-8

750.0 kVA

10-CBL-MDP

500 AWG/kcmil

S

P

T-8

10-CBL-MDP

10-MDP

10-LE1-CB

TCC Name: MV-TCC-10-LE1-CB Current Scale x 10 Reference Voltage: 12470 Oneline: MV-TCC-10-LE1-CB August 7, 2014 11:56 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-27

MV-TCC-35-MCC

Comments: The transformer and feeder cable 35-CBL-MCC are fully protected by the circuit breaker 35-MCC-

CB.

TX Inrush

T-7

35-CBL-MCC

35-MCC-CB

CUTLER-HAMMER

HLD

Trip 600.0 A Plug 600.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (600A) LTD I2t (2-24 Sec.) 24 STPU (1.5-8 x LTPU) 1.5 (900A) STD (0.1-0.5 Sec.) 0.1 (I^2t Off) INST (1.0 x ST Rating) Fixed (5500A)

T-7

1500.0 kVA

35-CBL-MCC

350 AWG/kcmil

35-MCC-CB

CUTLER-HAMMER

HLD

Trip 600.0 A Plug 600.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (600A) LTD I2t (2-24 Sec.) 24 STPU (1.5-8 x LTPU) 1.5 (900A) STD (0.1-0.5 Sec.) 0.1 (I^2t Off) INST (1.0 x ST Rating) Fixed (5500A)

T-7

1500.0 kVA

35-CBL-MCC

350 AWG/kcmil

TYPICAL FOR 35-CHILLER-1-CB,

35-CHILLER-2-CB, AND 35-CHILLER-3-CB

TYPICAL FOR 35-CHILLER-1-CB,

35-CHILLER-2-CB, AND 35-CHILLER-3-CB

35-MCC

35-MCC-CB

35-CBL-MCC

35-SWBD

S

P

T-7

TCC Name: MV-TCC-35-MCC Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-35-MCC-CB August 8, 2014 7:04 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-28

MV-TCC-40T-1

Comments: The transformer and feeder cable 40T-CBL-1 are fully protected by the circuit breakers. The overlap of circuit breakers T-3-CB-3-MB and 40T-1-MB is acceptable as they are in series with no other loads between them.

TX Inrush

T-3

CBL-T-3-CB-3

40T-CBL-1

40T-1-MB

CUTLER-HAMMER

CSR

Trip 200.0 A Settings Phase Thermal Curve INST Fixed (2480A)

T-3-CB-3-MB

SQUARE D

Q2 Trip 200.0 A Settings Phase Fixed

T-3

225.0 kVA

CBL-T-3-CB-3

4/0 AWG/kcmil

40T-CBL-1

4/0 AWG/kcmil

40T-1-MB

CUTLER-HAMMER

CSR

Trip 200.0 A Settings Phase Thermal Curve INST Fixed (2480A)

T-3-CB-3-MB

SQUARE D

Q2 Trip 200.0 A Settings Phase Fixed

T-3

225.0 kVA

CBL-T-3-CB-3

4/0 AWG/kcmil

40T-CBL-1

4/0 AWG/kcmil TYPICAL OF 40T-1

AND 40T-2.

TYPICAL OF 40T-1

AND 40T-2.

S

P

T-3

CBL-T-3-CB-3

40T-CBL-1

T-3-CB-3

40T-1-MB

40T-1

T-3-CB-3-MB

TCC Name: MV-TCC-40T-1 Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-40T-1 August 8, 2014 7:09 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-29

MV-TCC-44-CDP

Comments: The transformer is protected by the downstream circuit breaker 44-CDP-MB.

TX Inrush

T-1

44-BUSWAY-CDP

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

T-1

1000.0 kVA

44-BUSWAY-CDP

4000 AWG/kcmil

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

T-1

1000.0 kVA

44-BUSWAY-CDP

4000 AWG/kcmil

S

P

T-1

44-BUSWAY-CDP

44-CDP-MB

44-CDP

TCC Name: MV-TCC-44-CDP Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-44-CDP August 7, 2014 11:59 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-30

MV-TCC-49T-MAIN

Comments: The transformer and feeder cable 49T-CBL-MAIN are fully protected by the fuse 49T-FUSE-MAIN.

T-5A

49T-CBL-MAIN

49T-FUSE-MAIN

EDISON

ECSR

Trip 100.0 A

T-5A

150.0 kVA

49T-CBL-MAIN

4/0 AWG/kcmil

49T-FUSE-MAIN

EDISON

ECSR

Trip 100.0 A

T-5A

150.0 kVA

49T-CBL-MAIN

4/0 AWG/kcmil

S

P

T-5A

49T-CBL-MAIN

49T-FUSE-MAIN

49T-SW-MAIN

49T-MAIN

TCC Name: MV-TCC-49T-MAIN Current Scale x 1 Reference Voltage: 12470 Oneline: MV-TCC-49T-MAIN August 7, 2014 12:00 PM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-31

TCC-1-2L

Description: Phase overcurrent trip curves for LV breaker 1-MS-MB-GF through breaker 1-2L-MB and cable damage curve.

Comments: The overlap between breakers 1-2L-MB and 1-2L-CB-GF is acceptable as they are in series with no other loads between them. Cable is protected.

1-CBL-2L

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Settings Phase

LTPU 1.0 (2000A)

LTD 20.0

INST 4.0 (8000A)

1-2L-CB-GF

SQUARE D

MEC

Trip 225.0 A Plug 100.0 A Settings Phase LTPU (0.50-1.0 x P) 1.0 (100A)

LTD (1-8) 3

STPU (2-9 x P) 4.0 (400A) STD (1-4) 3 (I^2t Off)

1-2L-MB

SQUARE D

KA

Trip 225.0 A Settings Phase Thermal Curve

INST LO (1125A)

1-CBL-2L

4/0 AWG/kcmil

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Settings Phase

LTPU 1.0 (2000A)

LTD 20.0

INST 4.0 (8000A)

1-2L-CB-GF

SQUARE D

MEC

Trip 225.0 A Plug 100.0 A Settings Phase LTPU (0.50-1.0 x P) 1.0 (100A)

LTD (1-8) 3

STPU (2-9 x P) 4.0 (400A) STD (1-4) 3 (I^2t Off)

1-2L-MB

SQUARE D

KA

Trip 225.0 A Settings Phase Thermal Curve

INST LO (1125A)

1-CBL-2L

4/0 AWG/kcmil

1-MS-MB-GF

1-MS

1-2L-CB-GF

1-CBL-2L

1-2L-MB

1-2L

TCC Name: TCC-1-2L Current Scale x 10 Reference Voltage: 480

September 10, 2014 8:36 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-32

TCC-1-C2L

Description: Phase overcurrent trip curves for LV breakers 1-CD-MB through breaker 1-C2L-MB and cable damage curve.

Comments: The three breakers are not properly coordinated. Breaker 1-C2L-MB is oversized. The cable is protected.

Recommendation: Replace breakers 1-CD-MB and 1-C2L-MB to improve coordination.

1-CBL-C2L

1-C2L-CB

SQUARE D

KA

Trip 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

1-C2L-MB

SQUARE D

KA

Trip 200.0 A Settings Phase Thermal Curve

INST 2 (1202A)

1-CD-MB

SQUARE D

MA

Trip 600.0 A Settings Phase Thermal Curve

INST LO (3000A)

1-CBL-C2L

2/0 AWG/kcmil

1-C2L-CB

SQUARE D

KA

Trip 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

1-C2L-MB

SQUARE D

KA

Trip 200.0 A Settings Phase Thermal Curve

INST 2 (1202A)

1-CD-MB

SQUARE D

MA

Trip 600.0 A Settings Phase Thermal Curve

INST LO (3000A)

1-CBL-C2L

2/0 AWG/kcmil

1-C2L-CB

1-CBL-C2L

1-C2L-MB

1-CD

1-CD-MB

1-C2L

TCC Name: TCC-1-C2L Current Scale x 10 Reference Voltage: 480

September 10, 2014 8:42 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-33

TCC-1-C2L – PROPOSED

Comments: The breakers have been replaced and coordination has improved. The overlap of the two downstream breakers is acceptable as they are in series with no other loads between them.

1-CBL-C2L

1-C2L-CB

SQUARE D

KA

Trip 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

1-C2L-MB

SQUARE D

KI

Trip 175.0 A Settings Phase Thermal Curve

INST 6 (1645A)

1-CD-MB

SQUARE D

MG

Trip 600.0 A Settings Phase Thermal Curve

INST 8 (4800A)

INST OR (Fixed, No User-Adjustable Setting) Fixed (6000A)

1-CBL-C2L

2/0 AWG/kcmil

1-C2L-CB

SQUARE D

KA

Trip 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

1-C2L-MB

SQUARE D

KI

Trip 175.0 A Settings Phase Thermal Curve

INST 6 (1645A)

1-CD-MB

SQUARE D

MG

Trip 600.0 A Settings Phase Thermal Curve

INST 8 (4800A)

INST OR (Fixed, No User-Adjustable Setting) Fixed (6000A)

1-CBL-C2L

2/0 AWG/kcmil

1-C2L-CB

1-CBL-C2L

1-C2L-MB

1-CD

1-CD-MB

1-C2L

TCC Name: TCC-1-C2L Current Scale x 10 Reference Voltage: 480

September 18, 2014 12:35 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-34

TCC-1-2IA

Description: Phase overcurrent trip curves for LV breaker 1-C2L-MB through breaker 1-2IA-MB and cable damage curve.

Comments: There is slight overlap between 1-2A-MB and 1-C2L-MB in the short time region. The overlap between the two downstream breakers is acceptable as they are in series with no other loads between them. Cable

1-CBL-ISO PANEL A is undersized (refer to Summary of Costs for adjustment).

Recommendation: Circuit breaker 1-C2L-MB was changed in the previous curve, so breakers are coordinated.

1-CBL-ISO PANEL A

1-C2L-MB

SQUARE D

KA

Trip 200.0 A Settings Phase Thermal Curve

INST 2 (1202A)

1-ISO PANEL A-CB

SQUARE D

FY

Trip 30.0 A Settings Phase Fixed

1-2IA-MB

SQUARE D

FD

Trip 35.0 A Settings Phase Fixed

1-CBL-ISO PANEL A

10 AWG/kcmil

1-C2L-MB

SQUARE D

KA

Trip 200.0 A Settings Phase Thermal Curve

INST 2 (1202A)

1-ISO PANEL A-CB

SQUARE D

FY

Trip 30.0 A Settings Phase Fixed

1-2IA-MB

SQUARE D

FD

Trip 35.0 A Settings Phase Fixed

1-CBL-ISO PANEL A

10 AWG/kcmil

TYPICAL OF 1-2IA, 1-2IB, 1-2IC,

1-2ID, 1-2IE, 1-2IF, AND 1-2IG.

TYPICAL OF 1-2IA, 1-2IB, 1-2IC,

1-2ID, 1-2IE, 1-2IF, AND 1-2IG.

1-C2L-MB

1-C2L

1-ISO PANEL A-CB

1-CBL-ISO PANEL A

1-2IA

1-2IA-MB

TCC Name: TCC-1-2IA Current Scale x 10 Reference Voltage: 480

September 10, 2014 8:20 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-35

TCC-1-2IA – PROPOSED

Comments: The change of breaker 1-C2L-MB and cable 1-CBL-ISO PANEL A have improved coordination.

1-CBL-ISO PANEL A

1-C2L-MB

SQUARE D

KI

Trip 175.0 A Settings Phase Thermal Curve

INST 6 (1645A)

1-ISO PANEL A-CB

SQUARE D

FY

Trip 30.0 A Settings Phase Fixed

1-2IA-MB

SQUARE D

FD

Trip 35.0 A Settings Phase Fixed

1-CBL-ISO PANEL A

8 AWG/kcmil

1-C2L-MB

SQUARE D

KI

Trip 175.0 A Settings Phase Thermal Curve

INST 6 (1645A)

1-ISO PANEL A-CB

SQUARE D

FY

Trip 30.0 A Settings Phase Fixed

1-2IA-MB

SQUARE D

FD

Trip 35.0 A Settings Phase Fixed

1-CBL-ISO PANEL A

8 AWG/kcmil

TYPICAL OF 1-2IA, 1-2IB, 1-2IC,

1-2ID, 1-2IE, 1-2IF, AND 1-2IG.

TYPICAL OF 1-2IA, 1-2IB, 1-2IC,

1-2ID, 1-2IE, 1-2IF, AND 1-2IG.

1-C2L-MB

1-C2L

1-ISO PANEL A-CB

1-CBL-ISO PANEL A

1-2IA

1-2IA-MB

TCC Name: TCC-1-2IA Current Scale x 10 Reference Voltage: 480

September 18, 2014 12:38 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-36

TCC-1-2IX

Description: Phase overcurrent trip curves for LV breaker 1-C2L-MB through breaker 1-ISO PANEL 2IX-CB and cable damage curve.

Comments: The two breakers are coordinated in the short time but not in the long time. The cable is protected.

Recommendation: Both breakers will need to be replaced for proper coordination.

1-CBL-ISO PANEL 2IX

1-C2L-MB

SQUARE D

KA

Trip 200.0 A Settings Phase Thermal Curve

INST 2 (1202A)

1-ISO PANEL 2IX-CB

SQUARE D

KA

Trip 125.0 A Settings Phase Thermal Curve

INST LO (625A)

1-CBL-ISO PANEL 2IX

1 AWG/kcmil

1-C2L-MB

SQUARE D

KA

Trip 200.0 A Settings Phase Thermal Curve

INST 2 (1202A)

1-ISO PANEL 2IX-CB

SQUARE D

KA

Trip 125.0 A Settings Phase Thermal Curve

INST LO (625A)

1-CBL-ISO PANEL 2IX

1 AWG/kcmil

1-C2L-MB

1-C2L

1-ISO PANEL 2IX-CB

1-CBL-ISO PANEL 2IX

1-2IX

TCC Name: TCC-1-2IX Current Scale x 10 Reference Voltage: 480

September 10, 2014 9:55 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-37

TCC-1-2IX – PROPOSED

Comments: The two circuit breakers have been replaced and now are fully coordinated.

1-CBL-ISO PANEL 2IX

1-C2L-MB

SQUARE D

LA/MC

Trip 200.0 A Settings Phase Fixed

1-ISO PANEL 2IX-CB

SQUARE D

KC

Trip 125.0 A Settings Phase Thermal Curve

INST 3 (845A)

1-CBL-ISO PANEL 2IX

1 AWG/kcmil

1-C2L-MB

SQUARE D

LA/MC

Trip 200.0 A Settings Phase Fixed

1-ISO PANEL 2IX-CB

SQUARE D

KC

Trip 125.0 A Settings Phase Thermal Curve

INST 3 (845A)

1-CBL-ISO PANEL 2IX

1 AWG/kcmil

1-C2L-MB

1-C2L

1-ISO PANEL 2IX-CB

1-CBL-ISO PANEL 2IX

1-2IX

TCC Name: TCC-1-2IX Current Scale x 10 Reference Voltage: 480

September 18, 2014 9:51 AM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-38

TCC-1-2L-CB-GF

Description: Ground fault curves for 1-MS-MB-GF and 1-2L-CB-GF.

Comments: Ground fault pickups of both breakers are well coordinated. Ground fault delays are not coordinated.

Recommendation: Adjust ground fault delay settings on breakers to achieve coordination.

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Plug 1000.0 A Settings GF GFPU (In=100-1200A) A (250A) GFD-I2T 0.3 (I^2t Off)

1-2L-CB-GF

SQUARE D

MEC

Trip 225.0 A Plug 100.0 A Settings GF GFPU (0.2-0.75 x S) 0.3 (67.5A) GFD (1-4) 3 (I^2t Off)

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Plug 1000.0 A Settings GF GFPU (In=100-1200A) A (250A) GFD-I2T 0.3 (I^2t Off)

1-2L-CB-GF

SQUARE D

MEC

Trip 225.0 A Plug 100.0 A Settings GF GFPU (0.2-0.75 x S) 0.3 (67.5A) GFD (1-4) 3 (I^2t Off)

1-MS-MB-GF

1-MS

1-2L-CB-GF

TCC Name: TCC-1-2L-CB-GF Current Scale x 10 Reference Voltage: 480

September 10, 2014 8:22 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-39

TCC-1-2L-CB-GF - PROPOSED

Comments: The ground fault delays have been adjusted on the breakers and they now have 6 cycles of separation.

DS-420

Trip 2000.0 A Plug 1000.0 A Settings GF GFPU (In=100-1200A) A (250A) GFD-I2T 0.5 (I^2t Off)

1-2L-CB-GF

SQUARE D

MEC

Trip 225.0 A Plug 100.0 A Settings GF GFPU (0.2-0.75 x S) 0.3 (67.5A) GFD (1-4) 2 (I^2t Off)

1-MS-MB-GF

SQUARE D

DS-420

Trip 2000.0 A Plug 1000.0 A Settings GF GFPU (In=100-1200A) A (250A) GFD-I2T 0.5 (I^2t Off)

1-2L-CB-GF

SQUARE D

MEC

Trip 225.0 A Plug 100.0 A Settings GF GFPU (0.2-0.75 x S) 0.3 (67.5A) GFD (1-4) 2 (I^2t Off)

1-MS-MB-GF

1-MS

1-2L-CB-GF

TCC Name: TCC-1-2L-CB-GF Current Scale x 10 Reference Voltage: 480

September 11, 2014 1:06 PM VAMC Fayetteville (Proposed) SKM Systems Analysis, Inc.

4.3-40

TCC-1-21R

Description: Phase overcurrent trip curves for LV breaker 1-2R-R-MB through breaker 1-21R-MB, transformer damage curve, and cable damage curve.

Comments: The three breakers are not coordinated. The transformer is not fully protected as circuit breaker 1-

2R-R-MB is oversized. The cables are protected.

Recommendation: All three circuit breakers need to be replaced. Due to the similar amperages of all three circuit breakers it is recommended that a new distribution scheme be implemented in order to provide proper coordination.

TX Inrush

1-XFMR 2R-R

1-CBL-2R-R

1-CBL-2R-L

1-CBL-21R

1-2R-R-MB

SQUARE D

KA

Trip 150.0 A Settings Phase Thermal Curve

INST 3 (1050A)

1-21R-CB

SQUARE D

QO

Trip 100.0 A Settings Phase Fixed (730-7, 100A)

1-21R-MB

GE

TFJ

Trip 125.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) HI (1250A)

1-XFMR 2R-R

45.0 kVA

1-CBL-2R-R

1/0 AWG/kcmil

1-CBL-2R-L

1/0 AWG/kcmil

1-CBL-21R

1 AWG/kcmil

1-2R-R-MB

SQUARE D

KA

Trip 150.0 A Settings Phase Thermal Curve

INST 3 (1050A)

1-21R-CB

SQUARE D

QO

Trip 100.0 A Settings Phase Fixed (730-7, 100A)

1-21R-MB

GE

TFJ

Trip 125.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) HI (1250A)

1-XFMR 2R-R

45.0 kVA

1-CBL-2R-R

1/0 AWG/kcmil

1-CBL-2R-L

1/0 AWG/kcmil

1-CBL-21R

1 AWG/kcmil

S

P

1-XFMR 2R-R

1-CBL-2R-R

1-2R-R-MB

1-CBL-2R-L

1-2R-L

1-21R-CB

1-CBL-21R

1-21R-MB

1-21R

1-2R-R

TCC Name: TCC-1-21R Current Scale x 10 Reference Voltage: 208

September 18, 2014 11:42 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-41

TCC-1-A

Description: Phase overcurrent trip curves for LV breaker 44-CDP-MB through breaker 44-PNL-A-CB, transformer damage curve, and cable damage curve.

Comments: Breakers are coordinated, transformer is protected, and cable is protected.

44-CBL-PNL-A

44-BUSWAY-CDP

TX Inrush

T-1

44-PNL-A-CB

CUTLER-HAMMER

EDH

Trip 200.0 A Settings Phase Fixed

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

44-CBL-PNL-A

3/0 AWG/kcmil

44-BUSWAY-CDP

4000 AWG/kcmil

T-1

1000.0 kVA

44-PNL-A-CB

CUTLER-HAMMER

EDH

Trip 200.0 A Settings Phase Fixed

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

44-CBL-PNL-A

3/0 AWG/kcmil

44-BUSWAY-CDP

4000 AWG/kcmil

T-1

1000.0 kVA

TYPICAL OF 1-A, 1-A1,

1-B1, 1-C1, AND 1-A2.

TYPICAL OF 1-A, 1-A1,

1-B1, 1-C1, AND 1-A2.

44-PNL-A-CB

44-CBL-PNL-A

1-A

44-CDP

44-BUSWAY-CDP

44-CDP-MB

S

P

T-1

TCC Name: TCC-1-A Current Scale x 10 Reference Voltage: 208

September 10, 2014 8:36 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-42

TCC-1-A3

Description: Phase overcurrent trip curves for LV breaker 44-CDP-MB through breaker 44-PNL-A2-CB, transformer damage curve, and cable damage curve.

Comments: Breakers are coordinated, transformer is protected, and cable is protected.

44-CBL-PNL-A2

1-CBL-A3

44-BUSWAY-CDP

TX Inrush

T-1

44-PNL-A2-CB

CUTLER-HAMMER

EDH

Trip 200.0 A Settings Phase Fixed

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

44-CBL-PNL-A2

3/0 AWG/kcmil

1-CBL-A3

3/0 AWG/kcmil

44-BUSWAY-CDP

4000 AWG/kcmil

T-1

1000.0 kVA

44-PNL-A2-CB

CUTLER-HAMMER

EDH

Trip 200.0 A Settings Phase Fixed

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

44-CBL-PNL-A2

3/0 AWG/kcmil

1-CBL-A3

3/0 AWG/kcmil

44-BUSWAY-CDP

4000 AWG/kcmil

T-1

1000.0 kVA

44-PNL-A2-CB

44-CBL-PNL-A2

1-CBL-A3

1-A3

1-A2

44-CDP

44-BUSWAY-CDP

44-CDP-MB

S

P

T-1

TCC Name: TCC-1-A3 Current Scale x 10 Reference Voltage: 208

September 10, 2014 8:38 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-43

TCC-1-AC

Description: Phase overcurrent trip curves for LV breaker 44-CDP-MB through breaker 44-PNL-AC-CB, transformer damage curve, and cable damage curve.

Comments: Breakers are coordinated, transformer is protected, and cable is protected.

44-BUSWAY-CDP

TX Inrush

T-1

44-CBL-PNL-AC

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

44-PNL-AC-CB

CUTLER-HAMMER

HLD

Trip 600.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (3000A)

44-BUSWAY-CDP

4000 AWG/kcmil

T-1

1000.0 kVA

44-CBL-PNL-AC

350 AWG/kcmil

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t On) INST (2-12 x P) 2 (8000A)

44-PNL-AC-CB

CUTLER-HAMMER

HLD

Trip 600.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (3000A)

44-BUSWAY-CDP

4000 AWG/kcmil

T-1

1000.0 kVA

44-CBL-PNL-AC

350 AWG/kcmil

44-BUSWAY-CDP

44-CDP-MB

S

P

T-1

44-CDP

44-PNL-AC-CB

44-CBL-PNL-AC

1-AC

TCC Name: TCC-1-AC Current Scale x 10 Reference Voltage: 208

September 10, 2014 8:38 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-44

TCC-1-AC1

Description: Phase overcurrent trip curves for LV breaker 44-MDA-CB through breaker 1-AC-1-MB and cable damage curves.

Comments: The overlap of the two downstream breakers is acceptable as they are in series with no other loads between them. Cables are protected.

44-CBL-PNL-MDA

1-CBL-AC1

44-PNL-MDA-CB

CUTLER-HAMMER

HND

Trip 1200.0 A Plug 1200.0 A Settings Phase LTPU (1.0 x P) Fixed (1200A) LTD (Fixed) Fixed STPU (2-8 x P) 6 (7200A) STD (Fixed) Fixed (I^2t On) INST (14000A) Fixed (14000A)

1-AC1-CB

CUTLER-HAMMER

ED

Trip 200.0 A Settings Phase Fixed

1-AC-1-MB

CUTLER-HAMMER

JD

Trip 250.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)

44-CBL-PNL-MDA

350 AWG/kcmil

1-CBL-AC1

3/0 AWG/kcmil

44-PNL-MDA-CB

CUTLER-HAMMER

HND

Trip 1200.0 A Plug 1200.0 A Settings Phase LTPU (1.0 x P) Fixed (1200A) LTD (Fixed) Fixed STPU (2-8 x P) 6 (7200A) STD (Fixed) Fixed (I^2t On) INST (14000A) Fixed (14000A)

1-AC1-CB

CUTLER-HAMMER

ED

Trip 200.0 A Settings Phase Fixed

1-AC-1-MB

CUTLER-HAMMER

JD

Trip 250.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)

44-CBL-PNL-MDA

350 AWG/kcmil

1-CBL-AC1

3/0 AWG/kcmil

44-PNL-MDA-CB

44-CBL-PNL-MDA

1-MDA

1-AC1-CB

1-CBL-AC1

1-AC-1-MB

1-AC1

TCC Name: TCC-1-AC1 Current Scale x 10 Reference Voltage: 208

September 10, 2014 8:40 AM VAMC Fayetteville (Existing) SKM Systems Analysis, Inc.

4.3-45

TCC-1-AC-2

Description: Phase overcurrent trip curves for LV breaker 44-CDP-MB through breaker 44-PNL-AC2-CB, transformer damage curve, and cable damage curve.

Comments: Breakers are coordinated, transformer is protected, and cable is protected.

44-CBL-PNL-AC2

44-BUSWAY-CDP

TX Inrush

T-1

44-PNL-AC2-CB

CUTLER-HAMMER

EDH

Trip 150.0 A Settings Phase Fixed

44-CDP-MB

CUTLER-HAMMER

MDS-840

Trip 4000.0 A Plug 4000.0 A Settings Phase LTPU (0.4-1.0 x P) 1 (4000A) LTD (2-24 Sec.) 2 STPU (2-10 x LTPU) 2 (8000A) STD (0.1-0.5…