18-Hazmat Survey.pdf
PDF 5 MB Posted
- Attached to
- Correct Electrical Deficiencies
- Solicitation number
- 36C24627B0001
About this file
This is Appendix 18, a Hazmat Survey Report documenting an asbestos and lead paint sampling inspection conducted at Fayetteville VA Medical Center in Fayetteville, North Carolina on April 24, 2025, in preparation for electrical room renovations in Buildings 1, 3, and 35 (Project 565-22-500).
The survey identified asbestos-containing materials (ACM) in two locations: passage door frame caulking (17 linear feet) and interior window frame caulking (12 linear feet), both in Building 1's electrical room, with 2% chrysotile asbestos content detected in bulk samples. Lead-based paint above the EPA action level (greater than 1.0 mg/cm²) was found on four metal traffic bollards outside Building 1 (4 bollards), the passage door frame in Building 1 (1 door frame), the interior window frame and sash in Building 1 (1 window), and metal columns in Building 35's chiller room (12 columns). The inspection included 33 bulk asbestos samples analyzed by Eurofins Built Environment Testing Central, LLC using polarized light microscopy (PLM) per EPA methods, with laboratory accreditation by NIST/NVLAP and AIHA. Lead testing was conducted using a Viken Detection Pb200i XRF analyzer. The report recommends that all identified asbestos-containing materials must be removed by a North Carolina licensed asbestos contractor if they will be disturbed during renovation activities, and that lead-based paint components must be properly handled if disturbed. The inspection was conducted and report prepared by Brett L. Brumbaugh, a State of North Carolina licensed asbestos inspector (License #12411) and EPA licensed lead risk assessor (License #LBP-R-I216003-2) with environmental certifications including REPA and CESCO credentials.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sign-in sheet_12Nov2026.pdf | ||
| 19-Outage Plan.pdf | ||
| 21-21 Nov 2014 VACO ECA E24.pdf | ||
| 565-22-500 Combined Set 20251118.pdf | ||
| ATTACHMENT - BAA TAA COMPLIANCE CERTIFICATION.docx | DOCX document | |
| Correct Electrical Deficiencies Specifications.pdf | ||
| 36C24627B0001.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX 18
Hazmat Survey
ASBESTOS & LEAD PAINT SAMPLING REPORT
for
FAYETTEVILLE VA MEDICAL CENTER
FAYETTEVILLE, NC
PROJECT:
CORRECT ELECTRICAL DEFICIENCIES
BUILDINGS 1, 3, & 35
PROJECT 565-22-500
INSPECTION DATE:
APRIL 24, 2025
CONSULTANT:
CASTLE HILL ASSOCIATES, LLC
1197 FARNSWORTH RD., UNIT E
WATERVILLE, OH 43566
567-952-0212 www.CASTLEHILLASSOCIATES.com
ASBESTOS & HAZMAT MATERIALS SURVEY REPORT
FAYETTEVILLE VA MEDICAL CENTER – FAYETTEVILLE, NC
CORRECT ELECTRICAL DEFICIENCIES PROJECT 550-22-500
ASBESTOS INSPECTION SUMMARY
On April 24, 2025, Brett Brumbaugh of Castle Hill Associates performed an asbestos survey and lead XRF testing prior to the planned electrical room renovations in Buildings 1, 3, and 35 of the Fayetteville VAMC in Fayetteville, NC. Bulk samples were collected of suspect asbestos containing materials that had not been previously sampled during previous asbestos surveys in the building. There were 33 bulk samples taken as part of this survey with the materials identified in the report included in this submission.
The asbestos bulk sampling conducted as part of this project was based upon the appearance, texture, and location of the suspect materials. All bulk samples were analyzed utilizing current EPA methods for PLM (Polarized Light Microscopy) by Eurofins in Naperville, IL. Eurofins is accredited by the NIST, NVLAP program (National Institute of Standards and Technology, National Voluntary Laboratory Accreditation Program) and also an American Industrial Hygiene Association (AIHA) accredited laboratory.
Prior to this sampling, Castle Hill was provided with previous sampling results conducted by the VA including the last 3-year reinspection conducted by Castle Hill Associates in 2019.
Lead paint testing was conducted on all painted surfaces in the renovation areas using a Viken Detection Pb200i direct read XRF analyzer. Painted components that were tested in the areas are considered to be “lead-based” paint as defined by the US EPA (greater than 1.0 mg/cm2).
The inspection was conducted and the report was prepared by Brett Brumbaugh who is licensed by the State of North Carolina as an Asbestos Inspector and is also an EPA Licensed Lead Risk Assessor. Mr. Brumbaugh has been conducting asbestos surveys and lead sampling since 1987, and is a registered environmental property assessor (REPA) and certified environmental and safety officer (CESCO) through the NREP (National Registry of Environmental Professionals)
ASBESTOS INSPECTION FINDINGS
As a result of this inspection, current sampling, and previous surveys/sampling, it has been determined that the following asbestos containing materials are present in the renovation areas:
Asbestos Materials Summary
Asbestos Containing Material Locations Quantity
Passage door frame caulking B1 Electrical room int. passage door 17 lf (1 door)
Int. window frame caulking B1 Electrical room interior metal window 12 lf (1 window)
LEAD-BASED PAINT FINDINGS
As a result of the XRF testing of the building components in the work areas, the following components were determined to contain quantities of lead above the EPA & HUD “Lead Based Paint Federal Action Level” for a painted surface containing less than 1.0 mg/cm² or greater using the XRF technology:
Lead Painted Component Locations Quantity
Metal traffic bollards Outside B1 Electrical Room 4 bollards
Passage door frame B1 Electrical room int. passage door 1 door frame
Int. window frame & sash B1 Electrical room interior metal window 1 window
Metal column B35 Chiller Room columns 12 columns
CONCLUSIONS/RECOMMENDATIONS
ASBESTOS: The asbestos containing materials identified in the renovation area must be removed if they will be disturbed as part of the renovation activities. If no disturbance is planned, they can be left in-place indefinitely until removal is required prior to demolition. All removal must be conducted by a North Carolina licensed Asbestos Contractor.
LEAD-BASED PAINT: The building components coated with lead-based paint in the renovation area must be properly handled if they will be disturbed as part of the renovation activities. If no disturbance is planned, they can be left in-place indefinitely.
Respectfully Submitted, Brett L. Brumbaugh, REPA, CESCO State of North Carolina Asbestos Inspector, License # 12411 Lead Risk Assessor – EPA License # LBP-R-I216003-2
ASBESTOS SAMPLING PROTOCOL
The bulk samples were collected from locations that were selected to be representative of the building materials. Sampling was accomplished using the simplified sampling scheme referenced in the AHERA regulations and found in the “Pink Book”. Locations of individual samples are referenced on this report.
The samples were either collected with a coring tool designed for asbestos sampling or placed into a plastic bag for laboratory analysis. The samples were analyzed via polarized light microscopy with dispersion staining, using the “Interim method for the Determination of Asbestos in Bulk Insulation Samples” found in Appendix A to Subpart F in 40 CFR Part 763.
The regulations require specific numbers of samples be obtained per homogeneous area. For example, when sampling for joint compound or asbestos in hard plaster (sprayed-on or troweled-on surfacing materials) samples are to be taken based on the following increments: 0 to 1000 square feet of material, 3 samples are necessary. From 1001 to 5000 square feet, 5 samples are necessary, over 5000 square feet 7 samples are required. If during analysis any samples are found to contain asbestos, the entire homogeneous area is delineated as asbestos containing material. In the case of pipe insulation or other types of manufactured materials, the regulations require only enough samples to ascertain whether asbestos is present. In this case, the minimum number of samples to collect and analyze is usually three.
The sampling performed in this inspection followed these sampling guidelines.
ASBESTOS GLOSSARY OF TERMS
Friable asbestos material: means any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 section 1, Polarized Light Microscopy, that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
Category I Non-friable Asbestos Containing Material (ACM) means asbestos containing packings, gaskets, resilient floor coverings, and asphalt roofing products containing more that 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, Section 1, Polarized Light Microscopy.
Category II Non-friable ACM means any material, excluding Category I non-friable ACM, containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy that when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
Regulated Asbestos Containing Material (RACM): means (a) Friable asbestos material, (b) Category I non-friable ACM that has become friable, (c) category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or (d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material expected in the course of demolition or renovation operations regulated by this subpart.
ASBESTOS BULK SAMPLE DESCRIPTIONS & RESULTS
PLM Asbestos Bulk Sampling Data
Site: Fayetteville VA Medical Center - Faytteville, NC
Building: Correct Electrical Deficiencies
Project: 565-22-500
Sampling Date: April 26, 2025
Inspector: Brett L. Brumbaugh
Certification: N. Carolina Licensed Asbestos Inspector
Analysis Date: April 30-May 1, 2025
Laboratory: Eurofins Built Environment Testing Central, LLC - Naperville, IL
1 1 B1 Elect. Room Ext. door frame caulking No Asbestos Detected
2 1 B1 Elect. Room Ext. door frame caulking No Asbestos Detected
3 1 B1 Elect. Room Ext. door frame caulking No Asbestos Detected
4 1 B1 Elect. Room Ext. wall panel caulking No Asbestos Detected
5 1 B1 Elect. Room Ext. wall panel caulking No Asbestos Detected
6 1 B1 Elect. Room Ext. wall panel caulking No Asbestos Detected
7 1 B1 Elect. Room Fire stop caulking (red) No Asbestos Detected
8 1 B1 Elect. Room Fire stop caulking (red) No Asbestos Detected
9 1 B1 Elect. Room Fire stop caulking (red) No Asbestos Detected
10 1 B1 Elect. Room Int. passage door caulking 2% Chrysotile Asbestos
11 1 B1 Elect. Room Int. passage door caulking 2% Chrysotile Asbestos
12 1 B1 Elect. Room Int. passage door caulking 2% Chrysotile Asbestos
13 1 B1 Elect. Room Int. window frame caulking 2% Chrysotile Asbestos
14 1 B1 Elect. Room Int. window frame caulking 2% Chrysotile Asbestos
15 1 B1 Elect. Room Int. window frame caulking No Asbestos Detected
16 1 B1 Elect. Room Glazing on interior window No Asbestos Detected
17 1 B1 Elect. Room Glazing on interior window No Asbestos Detected
18 1 B1 Elect. Room Glazing on interior window No Asbestos Detected
19 1 EB-1 Elect. Room Int. door frame caulking No Asbestos Detected
20 1 EB-1 Elect. Room Int. door frame caulking No Asbestos Detected
21 1 EB-1 Elect. Room Int. door frame caulking No Asbestos Detected
22 1 EB-1 Elect. Room Ext. door frame caulking No Asbestos Detected
23 1 EB-1 Elect. Room Ext. door frame caulking No Asbestos Detected
24 1 EB-1 Elect. Room Ext. door frame caulking No Asbestos Detected
25 1 EB-1 Elect. Room Fire stop caulking (red) No Asbestos Detected
26 1 EB-1 Elect. Room Fire stop caulking (red) No Asbestos Detected
27 1 EB-1 Elect. Room Fire stop caulking (red) No Asbestos Detected
28 35 100 Chiller Room Drywall mud/joint compound No Asbestos Detected
29 35 100 Chiller Room Drywall mud/joint compound No Asbestos Detected
30 35 100 Chiller Room Drywall mud/joint compound No Asbestos Detected
31 35 100 Chiller Room Drywall Board No Asbestos Detected
32 35 100 Chiller Room Drywall Board No Asbestos Detected
33 35 100 Chiller Room Drywall Board No Asbestos Detected
ASBESTOS CONTENT
SAMPLE
ROOMBUILDING MATERIAL
ASBESTOS SAMPLE LOCATIONS
*NOT TO SCALE
ABESTOS MATERIALS & LEAD COMPONENTS PHOTOS
CORRECT ELECTRICAL DEFICIENCIES PROJECT 550-22-500
PHOTOGRAPHS OF ASBESTOS MATERIALS
Photo A-1 Caulk on the interior passage door frame in B1 Electrical Room
Photo A-2 Caulk on the interior window frame in B1
Electrical Room
CORRECT ELECTRICAL DEFICIENCIES PROJECT 550-22-500
PHOTOGRAPHS OF LEAD COMPONENTS
Photo L-1 Metal traffic bollards outside B1
Electrical room
Photo L-2 Passage door frame in B1 Electrical room
Photo L-3 Int. window frame & sash in B1
Electrical room
Photo L-4 Metal column in B35 Chiller Room
ASBESTOS LABORATORY REPORT
Approved by:
Laboratory Manager Itzel Cuellar
Report for:
Mr. Brett Brumbaugh, REPA Castle Hill Associates PO Box 283 Waterville, OH 43566
Regarding:
Eurofins Built Environment Testing Central, LLC Project: Fayetteville VAMC; Correct Elect. Defic.
EML ID: 4050941
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Built Environment Testing Central, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 04-30-2025 and 05-01-2025
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EB-AS-S-1267) NVLAP Lab Code 600194-0
EMLab ID: 4050941, Page 1 of 11Eurofins Built Environment Testing Central, LLC
Eurofins Built Environment Testing Central, LLC 1815 West Diehl Road, Suite 800, Naperville, IL 60563
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Total Samples Submitted: 33 Total Samples Analyzed: 33
Total Samples with Layer Asbestos Content > 1%: 5
Location: 1, Ext. DF caulk Lab ID-Version‡: 20184772-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 2, Ext. DF caulk Lab ID-Version‡: 20184773-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 3, Ext. DF caulk Lab ID-Version‡: 20184774-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 4, Wall panel caulk Lab ID-Version‡: 20184775-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 2 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 5, Wall panel caulk Lab ID-Version‡: 20184776-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 3 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 6, Wall panel caulk Lab ID-Version‡: 20184777-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 7, Fire stop caulk Lab ID-Version‡: 20184778-1
Sample Layers Asbestos Content Red Fire Stop ND
Sample Composite Homogeneity: Good
Location: 8, Fire stop caulk Lab ID-Version‡: 20184779-1
Sample Layers Asbestos Content Red Fire Stop ND
Sample Composite Homogeneity: Good
Location: 9, Fire stop caulk Lab ID-Version‡: 20184780-1
Sample Layers Asbestos Content Red Fire Stop ND
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 4 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 10, Int. Passage door caulk Lab ID-Version‡: 20184781-1
Sample Layers Asbestos Content Gray Caulk 2% Chrysotile
Sample Composite Homogeneity: Good
Location: 11, Int. Passage door caulk Lab ID-Version‡: 20184782-1
Sample Layers Asbestos Content Gray Caulk 2% Chrysotile
Sample Composite Homogeneity: Good
Location: 12, Int. Passage door caulk Lab ID-Version‡: 20184783-1
Sample Layers Asbestos Content Gray Caulk 2% Chrysotile
Sample Composite Homogeneity: Good
Location: 13, Int. window caulk Lab ID-Version‡: 20184784-1
Sample Layers Asbestos Content Gray Caulk 2% Chrysotile
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 5 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 14, Int. window caulk Lab ID-Version‡: 20184785-1
Sample Layers Asbestos Content Gray Caulk 2% Chrysotile
Sample Composite Homogeneity: Good
Location: 15, Int. window caulk Lab ID-Version‡: 20184786-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 16, Int. Window Glazing Lab ID-Version‡: 20184787-1
Sample Layers Asbestos Content White Window Glazing ND
Sample Composite Homogeneity: Good
Location: 17, Int. Window Glazing Lab ID-Version‡: 20184788-1
Sample Layers Asbestos Content White Window Glazing ND
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 6 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 18, Int. Window Glazing Lab ID-Version‡: 20184789-1
Sample Layers Asbestos Content White Window Glazing ND
Sample Composite Homogeneity: Good
Location: 19, Int. DF caulk Lab ID-Version‡: 20184790-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 20, Int. DF caulk Lab ID-Version‡: 20184791-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 21, Int. DF caulk Lab ID-Version‡: 20184792-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 7 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 22, Ext. DF caulk Lab ID-Version‡: 20184793-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 23, Ext. DF caulk Lab ID-Version‡: 20184794-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 24, Ext. DF caulk Lab ID-Version‡: 20184795-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 25, Red fire stop caulk Lab ID-Version‡: 20184796-1
Sample Layers Asbestos Content Red Fire Stop ND
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 8 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 26, Red fire stop caulk Lab ID-Version‡: 20184797-1
Sample Layers Asbestos Content Red Fire Stop ND
Sample Composite Homogeneity: Good
Location: 27, Red fire stop caulk Lab ID-Version‡: 20184798-1
Sample Layers Asbestos Content Red Fire Stop ND
Sample Composite Homogeneity: Good
Location: 28, Drywall Mud Lab ID-Version‡: 20184799-1
Sample Layers Asbestos Content White Mud with Paint ND
Sample Composite Homogeneity: Good
Location: 29, Drywall Mud Lab ID-Version‡: 20184800-1
Sample Layers Asbestos Content White Mud with Paint ND
Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 9 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
Location: 30, Drywall Mud Lab ID-Version‡: 20184801-1
Sample Layers Asbestos Content White Mud with Paint ND
Sample Composite Homogeneity: Good
Location: 31, Drywall Board Lab ID-Version‡: 20184802-1
Sample Layers Asbestos Content White Drywall with Brown Paper ND
Composite Non-Asbestos Content: 10% Cellulose Sample Composite Homogeneity: Good
Location: 32, Drywall Board Lab ID-Version‡: 20184803-1
Sample Layers Asbestos Content White Drywall with Brown Paper ND
Composite Non-Asbestos Content: 10% Cellulose Sample Composite Homogeneity: Good
Location: 33, Drywall Board Lab ID-Version‡: 20184804-1
Sample Layers Asbestos Content White Drywall with Brown Paper ND
Composite Non-Asbestos Content: 10% Cellulose Sample Composite Homogeneity: Good
EMLab ID: 4050941, Page 10 of 11Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Fayetteville VAMC; Correct Elect. Defic.
Date of Sampling: 04-24-2025 Date of Receipt: 04-29-2025 Date of Report: 05-02-2025
ASBESTOS PLM REPORT
PROJECT ANALYST AND SIGNATORY REPORT
Project Analyst
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Analyst: Kimberly Bugarin
EMLab ID: 4050941, Page 11 of 11Eurofins Built Environment Testing Central, LLC
LEAD XRF TESTING DATA
Project: Fayetteville VA Medical Center - Faytteville, NC
Project: Correct Electrical Deficiencies Project 565-22-500
Inspector: Brett Brumbaugh
Date: 4/24/2025
XRF Mfg.: Viken Detection
Model: Pb200i
Type: XRF Lead Paint Analyzer
Serial # 2757
Reading # Building Area Component Paint Color Pb Conc.
mg/cm2 Result
1 B1 Electrical Room Ext. metal door frame White 0.5 Negative
2 B1 Electrical Room Ext. metal door White 0.0 Negative
3 B1 Electrical Room Ext. metal wall panel White 0.1 Negative
4 B1 Electrical Room Ext. wall panel frame White 0.0 Negative
5 B1 Electrical Room Traffic Bollard - Metal Yellow 4.3 POSITIVE
6 B1 Electrical Room Int. metal passage door frame Tan 15.4 POSITIVE
7 B1 Electrical Room Int. metal window frame Brown 17.5 POSITIVE
8 B1 Electrical Room Int. metal window sash Brown 22.1 POSITIVE
9 B1 Electrical Room Ceramic wall tiile White 0.0 Negative
10 B1 Electrical Room Wood window sill White -0.2 Negative
11 B1 Electrical Room Wood window sill White -0.1 Negative
12 B1 Electrical Room Passage door frame White -0.2 Negative
13 B1 Electrical Room Drywall wall White 0.4 Negative
14 EB-1 Elect. Room Ext. metal door frame Gray 0.0 Negative
15 EB-1 Elect. Room Ext. entry door Gray 0.2 Negative
16 EB-1 Elect. Room Int. metal door frame White 0.0 Negative
17 EB-1 Elect. Room Int. metal door White 0.1 Negative
18 EB-1 Elect. Room Int. block wall White 0.0 Negative
19 EB-1 Elect. Room Int. concrete column White 0.1 Negative
20 EB-1 Elect. Room Int. concrete floor Gray 0.0 Negative
21 EB-1 Elect. Room Int. door lentil White 0.0 Negative
22 EB-1 Elect. Room Int. passage door frame White 0.0 Negative
23 EB-1 Elect. Room Int. metal passage door White 0.0 Negative
24 B-3 Elec. Room 10-3 Concrete floor Red 0.4 Negative
25 B-3 Elec. Room 10-3 Brick wall White 0.2 Negative
26 B-3 Elec. Room 10-3 Block wall White 0.1 Negative
27 B-3 Elec. Room 10-3 Concrete column White 0.2 Negative
28 B-3 Elec. Room 10-3 Door frame White 0.1 Negative
29 B-3 Elec. Room 10-3 Metal entry dloor White 0.2 Negative
30 B-35 Chiller Room 100 Block wall Blue 0.0 Negative
31 B-35 Chiller Room 100 Entry metal entry door Gray 0.0 Negative
32 B-35 Chiller Room 100 Entry door frame Gray 0.3 Negative
33 B-35 Chiller Room 100 Drywall wall (W. wall) Tan 0.0 Negative
34 B-35 Chiller Room 100 Int. window frame Red 0.1 Negative
35 B-35 Chiller Room 100 Int. concrete window sill White 0.0 Negative
36 B-35 Chiller Room 100 Concrete floor Gray 0.1 Negative
37 B-35 Chiller Room 100 Metal column Gray 11.4 POSITIVE
LABORATORY CERTIFICATIONS
United States Department of Commerce National Institute of Standards and Technology
Certificate of Accreditation to ISO/IEC 17025:2017
NVLAP LAB CODE: 600194-0
Eurofins EMLab P&K Naperville, IL is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Asbestos Fiber Analysis
2024-07-01 through 2025-06-30
Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique on ISO/IEC 17025).
INSPECTOR CERTIFICATIONS
National Registry of Environmental Professionals
For Environmental Certifications
This is to Certify that
Brett Brumbaugh having sucessfully demonstrated to the Academic Board of this organization the required level of knowledge and ability, is here by awarded the distinction of
Registered Environmental Property Assessor together with all rights, benefits and privileges attached thereto and that the name and title of the aforementioned registrant is today placed upon the register of the organization.
Given under our hands on this 31st day of October, 1996.
Registrant Number
This Certificate is the property of the National Registry of Environmental Professionals and must, upon demand, be returned.
Powered by TCPDF (www.tcpdf.org)
National Registry of Environmental Professionals
For Environmental Certifications
This is to Certify that
Brett L. Brumbaugh having sucessfully demonstrated to the Academic Board of this organization the required level of knowledge and ability, is here by awarded the distinction of
Certified Environmental and Safety Compliance Officer together with all rights, benefits and privileges attached thereto and that the name and title of the aforementioned registrant is today placed upon the register of the organization.
Given under our hands on this 15th day of September, 2016.
123337
Registrant Number
This Certificate is the property of the National Registry of Environmental Professionals and must, upon demand, be returned.
Powered by TCPDF (www.tcpdf.org)
| Cover |
| Summary |
| Findings |
| Conclusion |
| Bulk Results |
| Sample Locations |
| Photos |
| Asbestos Laboratory Report |
| LEAD XRF Testing Data |
| Laboratory Certifications |
| Inspector Certifications |
File details come from the government source that posted it. Updated .