ATTACH 3 0003 - 100 Percent EL Study Report 2023-09-01.pdf
PDF 13 MB Posted
- Attached to
- Z2DA--565-26-110 REPLACE AHU 34
- Solicitation number
- 36C24626Q0827
About this file
This is an electrical distribution system condition assessment report for the Fayetteville Veterans Affairs Medical Center (VAMC) in Fayetteville, North Carolina, prepared by AES Group, Inc. under Contract # VA101F-17-D-3087.
The report documents comprehensive electrical system analysis conducted across three site surveys from February through October 2022, covering 40+ buildings on the VAMC campus. The facility receives dual 12.47 kV utility feeds from Fayetteville Public Works Commission (Tokay and Hoffner substations), with distribution through a looped medium voltage system serving eleven transformers and powering 1,000+ connected loads. The electrical infrastructure includes seven emergency generators (ranging from 150-450 kW), one 850 kW Combined Heat and Power generator for parallel utility operation, and extensive low-voltage distribution networks. The assessment identified 93 pieces of equipment with failed interrupting ratings (77 overcurrent protective devices and 16 panels) that require replacement or adjustment, and 44 overcurrent protective devices requiring replacement or setting modifications to achieve proper selective coordination. Short circuit analysis across four scenarios (normal utility power with/without motors running, emergency generator power with/without motors) determined available fault currents throughout the system. The report includes fault current calculations, protective device coordination studies with time-current characteristic graphs, voltage drop and load flow analysis, arc flash hazard assessments, equipment condition evaluations, grounding system analysis, and cost estimates for remediation. The overall assessment concluded the electrical system is in good condition and well-maintained, though some distribution panelboards and components are beyond their half-life and warrant consideration for replacement. The report comprises over 200 pages including detailed appendices with one-line diagrams, input data reports, equipment specifications, cost estimates, photographs, and compliance documentation.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs
Fayetteville Veterans Affairs Medical Center
Fayetteville, NC
VISN 6
ELECTRICAL DISTRIBUTION SYSTEM
CONDITION ASSESSMENT
Contract # VA101F-17-D-3087
Project Number E54
100% Submission
16 August 2023
Fayetteville VAMC – Fayetteville, NC Electrical Condition Assessment
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Page 1 Prepared by: AES Group, Inc.
11031 S. Pikes Peak Dr., Suite #202
Parker, CO 80138
TABLE OF CONTENTS
1. EXECUTIVE SUMMARY
2. INTRODUCTION
2.1. Facility Support
2.2. Site Information
2.3. Site Plan
2.4. Medium Voltage Distribution System Overview
2.5. Emergency Power System Overview
2.6. Calculation Methods
2.7. Ground Resistance Test Reports
2.8. Study Assumptions
3. FAULT CURRENT ANALYSIS
3.1. Introduction
3.2. Sources of Fault Current
3.3. Calculation Scenarios
3.4. SKM Power*Tools Input Data Reports
3.5. Short Circuit Calculation Results
3.6. Equipment Evaluation Results
4. PROTECTIVE DEVICE COORDINATION STUDY
4.1. Introduction
4.2. Existing and Proposed Protective Device Settings
4.3. Underrated Feeders
4.4. Replacement of System Components
4.5. Analysis and Recommendations
4.6. Time-Current Characteristic Graphs Descriptions and Analysis
4.7. Time-Current Characteristic Graphs
5. VOLTAGE DROP ANALYSIS
5.1. Introduction
5.2. Basis of Evaluation
5.3. Results
5.4. Load Flow Calculations
6. ARC FLASH HAZARD ANALYSIS
6.1. Introduction
6.2. Basis of Study
6.3. Disclaimer
6.4. Results
7. CONDITION ASSESSMENT
7.1. General Information
7.2. Medium Voltage Distribution System
7.3. Low Voltage Distribution System
7.4. Equipment Condition Assessment
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Page 2 Prepared by: AES Group, Inc.
7.5. Grounding System
7.6. Emergency Electrical System
7.7. Summary of Costs
7.8. Existing Condition Assessment Photographs.
APPENDICES
A. Site Data and Site Plan B. Available Utility Fault Current Information C. Utility Demand Data D. Minutes of Entrance Briefing, Presentation E. Photographs F. Comments and Responses G. VHA Electrical Directive Compliance Survey H. One-Line Diagrams I. Ground Test Reports J. Cost Estimate Detail K. AES Group, Inc. - Statement of Work L. Equipment Condition Assessment Sheets M. Generator Datasheets N. Floorplans
Fayetteville, NC
ELECTRICAL DISTRIBUTION
SYSTEM CONDITION ASSESSMENT
Section 1
Executive Summary
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Section 1 Page 1 Prepared by: AES Group, Inc.
1. EXECUTIVE SUMMARY
The Department of Veterans Affairs – Office of Construction and Facilities Management (CFM), commissioned AES Group, Inc. to perform the electrical system condition assessment of the Fayetteville Veterans Affairs Medical Center (VAMC). The Veterans Health Administration (VHA) directive 1028 provides policy regarding the installation, operation, testing, and maintenance of Facility Electrical Power Systems at Department of Veterans Affairs (VA) medical facilities. The scope of this assessment is to provide short circuit analysis, protective device coordination study, voltage drop (load flow) analysis, arc flash hazard analysis, and equipment condition assessment with the purpose of improving the safety and reliability of the electrical distribution system.
AES Group performed the first on-site survey February 7th to February 18th, 2022. A second site visit on August 14th to August 27th, 2022 and a third site survey on October 2nd to October 8th, 2022.
Only minor issues have been found.
The electrical system is in good condition and has been well maintained. Some distribution panelboards, lighting and appliance panelboards are beyond their half-life and should be considered for replacement. A complete listing of deficiencies along with the associated cost for remediation can be found in Section 7 of this report.
The essential electrical system is also in good condition. Some of the components need adjusting in order to achieve a proper selective coordination, but no major replacements were needed.
AES Group performed calculations and analyses for the electrical power system for the Fayetteville VAMC campus, which has a dual utility feed, and various backup generators for emergency power.
The site also includes a Combined Heat and Power (CHP) generator. This generator provides boiler heat & electrical power for improved fuel efficiency.
The short circuit analysis, which aims to verify that circuit breakers and/or equipment are properly rated for the available fault current, has identified ninety three (93) devices that are not properly rated for the calculated available short circuit currents. The model includes multiple scenarios to determine worst-case short circuit current and arc flash energy. The operating scenarios include Normal Utility Power and Emergency Generator Power, as well as additional scenarios with motors off and on.
The protective device coordination study uses both the fixed ratings and adjustable settings of the existing Overcurrent Protective Devices (OCPDs) to graphically display how those devices respond to a short or overload event. The settings were then adjusted to allow the protective device closest to the fault to interrupt the circuit first, thereby minimizing electrical service disruption. Forty four (44) OCPD’s requiring replacement or adjustment have been identified. This report includes a summary of the specific OCPD’s and the recommended changes in Section 4: Protective Device Coordination Study.
This study includes time/current characteristic (TCC) graphs, which show OCPD’s with existing and recommended settings applied.
Section 2
Introduction
Prepared for:
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 1 Prepared by: AES Group, Inc.
2 INTRODUCTION
2.1 Key personnel
Key personnel for the VA have been involved with supporting survey efforts and providing review of these submissions. They are:
Jason Hardy, PE Contracting officer Jason.Hardy@va.gov (240-431-3644)
Victoria Wayne, Contracting Officer
Victoria.Wayne@va.gov
Dat Tran, P.E. Contract Officer Representative Dat.Tran2@va.gov (202-632-5263)
Joseph Ragland, P.E. Fayetteville VAMC Assistant Chief, Engineering Service
Joseph.Ragland@va.gov (910-488-2120 x5234)
Hy Dang, P.E - Task Order Technical Lead hy.dang@va.gov
AES-Group
Key personnel from AES-Group involved in the field surveys and in the production of this report are:
Jeremy Landrith, PE, Project Lead Jeremy.landrith@aes-grp.com (303-841-3922 x133)
Dan Brown, Senior Engineering Designer, Site Technical Lead Dan.Brown@aes-grp.com (303-841-3922 x126)
Ben Miller, Senior Engineering Designer, Site Technical Lead Ben.Miller@aes-grp.com (303-841-3922 x117)
Nate Quesada, Engineering Analyst, Technical Support Nate.Quesada@aes-grp.com (303-841-3922 x119)
A local electrical contractor, Allegiance Industries, whose electricians were instrumental in providing safe access to the interior components of the energized electrical equipment was also involved.
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 2 Prepared by: AES Group, Inc.
2.2 Site Information
The Fayetteville VAMC is located at 2300 Ramsey St, Fayetteville, NC 28301. The following buildings comprise the Fayetteville VAMC campus and the scope of this study:
Table 1.
Building List
Building # Description
1 Main Hospital
3 Medical Center Ancillary Services
4 Admin/Education/Library/Telehealth 8 Admin/HAS/EEO
9 Engineering Shops/Garages
10 Laundry Plant
11 Boiler Plant
14 Flagpole
15 Garage (Quarters)
16 Garage
18 Garage/Storage
20 Engineering Storage 21 Computer Building
22 Incinerator Building
24 Hazardous Waste Storage
30 Quonset Hut Storage Building
34 Generator Building
35 Chiller Plant 37 Electrical Distribution
40T Laundry Storage
44 Electrical Distribution 45 Mental Health Modular
46 PRRC
47 Mental Health Modular Building 48 Mental Health Primary Care
49T Emergency Management Trailer
50 Pact/Mental Health Clinic 51T Mental Health -Modular Building
52T Mental Health Outpatient Clinic
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 3 Prepared by: AES Group, Inc.
Building # Description
52 Main Building Pump House
56 Vacuum Pump building 57 Behavior Health Outpatient
62 Smoking Shelter
63 Solar Tank Collection (near B-3) 64 Solar Tank Collection (near B-11)
70 Community Center for CLC
71 Community Living Center Small House 1 72 Community Living Center Small House 2
73 Community Living Center Small House 3
2.3 Site Plan
The Site plan and data for the Fayetteville VAMC is included in Appendix A.
2.4 Electrical Distribution System Overview
The local electrical utility, Fayetteville Public Works Commission (PWC) provides two primary
12.47 kV electrical feeds to the Fayetteville VAMC campus: One from their Tokay substation (feeder E3A), and one from their Hoffner substation (feeder E3B). The feeders are routed to the 15kV switchgear housed in Building 37.
A request was made for utility bills in order to determine consumption and demand information for each point of service. Appendix C has a summary of the main utility power usage for 2013-2014 from utility bills and shows the usage information for several other months.
From the main switch gear, the medium voltage supply is routed in a loop to the campus, through six (6) sectionalizers, allowing for isolation of specific sections of the loop. This loop supplies eleven (11) medium to low voltage transformers, which power the campus. Normal operation has the medium voltage loop open between sectionalizers 2 & 5.
Buildings 41T, 42T, 45, 46, 47, 48, 49, and 50 are separately fed from utility owned transformers.
The site contains one Combined Heat and Power generator (CHP) located in building 35. The generator installation is designed for parallel operation with the main utility feed. It does not have the capability, and is not designed to independently supply power for the site.
It is a 480V, 850 kW generator, with a dedicated step-up transformer, and is connected to the main 12.47 kV distribution system through sectionalizer #6.
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 4 Prepared by: AES Group, Inc.
Building 1 normal power is supplied from 3 sources: sectionalizer 1 by transformer T1, rated at 1,000 kVA, 12.47kV/208V, protected by a 20 amp S&C SMU-20 fuse, sectionalizer 4 by transformer T9, rated at 1,000 kVA, 12.47kV/480V, protected by a 65 amp S&C SMU-20 fuse, and sectionalizer 5 by transformer T6 (CLC), rated at 500kVA, 12.47kV/208V, and protected by a 10 amp S&C SMU-20 fuse.
Building 4 normal power is supplied from sectionalizer 5 by transformer T4, rated at 150 kVA, 12.47kV/208V, and protected by a 20 amp S&C SMU-20 fuse.
Building 8 normal power is supplied from sectionalizer 4 by transformer T5B, rated at 112.5kVA, 12.47kV/208V, and protected by a 7 amp S&C SMU-20 fuse.
Buildings 9 & 30 normal power is supplied from sectionalizer 1 by transformer T3, rated at 225 kVA, 12.47kV/208V, and protected by a 25 amp S&C SMU-20 fuse.
Building 10 normal power is supplied from sectionalizer 6 by transformer T8, rated at 750 kVA, 12.47kV/480V, and protected by an S&C SMU-20 fuse.
Buildings 11, 22, 24, & 35 normal power is supplied from sectionalizer 1 by transformer T7, rated at 1500 kVA, 12.47kV/480V, and protected by an S&C SMU-20 fuse.
Building 37 normal power is supplied from sectionalizer 1 by an unlabeled transformer, rated at 30 kVA, 12.47kV/240V, and protected by an S&C SMU-20 fuse.
Buildings 45, 46, 47, & 48 are supplied by a 300kVA, 12.47kV/208V utility transformer that is separate from the main medium voltage loop.
Building 49 normal power is supplied from sectionalizer 4 by transformer T5A, rated at 150 kVA, 12.47kV/480V, and protected by a 7 amp S&C SMU-20 fuse.
Building 50 is supplied by a 100 kVA, 12.47kV/240V utility transformer that is separate from the main medium voltage loop.
Buildings 71 & 72 normal power is supplied from sectionalizer 5 by transformer T5, rated at 150 kVA, 12.47kV/208V, and protected by a 10 amp S&C SMU-20 fuse.
Buildings 70 & 73 normal power is supplied from sectionalizer 2 is supplied from sectionalizer 5 by transformer T6 (CLC), rated at 500 kVA, 12.47kV/208V, and protected by a 10 amp S&C SMU-20 fuse.
There is an additional 1,000 kVA, 480V/12.47kV transformer connecting the CHP generator to the medium voltage electrical system at sectionalizer 3.
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 5 Prepared by: AES Group, Inc.
Table 2.
Medium Voltage Transformers
Name Voltage kVA Location Loads
T1 12.47k/208 1000 Outside building 44 Building 1
T3 12.47k/208 225 Outside building 3 Building 9
T4 12.47k/208 150 Outside building 4 Building 4
T5 12.47k/208 150 Outside building 71 Building 71,72
T5A 12.47k/480 150 Outside building 8 Building 49
T5B 12.47k/208 112.5 Outside building 8 Building 8
T6 12.47k/480 1000 Outside building 3 Building 73
T6 (CLC) 12.47k/208 500 Outside building 1 Building 1
T7 12.47k/480 1500 Outside building 35 Buildings 11,22,24,35
T8 12.47k/480 750 Outside building 10 Building 10
T9 12.47k/480 1000 Outside building 1 Building 1
PWC-1 12.47k/208 300 Outside building 50 Building 50
PWC-2 12.47k/240 100 Outside building 45 Buildings 45,46,47,48
No label 12.47k/240 30 Outside building 37 Building 37
CHP 480/12.47k 1000 Outside building 35 CHP Generator
2.5 Generators
2.5.1 Emergency Power System
The emergency power system consists of seven (7) generators, the specifics of which are shown in Table 3.
Two generators, located in building 34, supply building 21 and portions of the main hospital.
Two generators, located in the main hospital, supply emergency power to the remainder of the hospital.
One generator supply emergency power to Building 11 and 22. Two generators outside building 50 supply emergency power to buildings 71,72, & 73.
Alternator specifications are obtained from generator manuals or manufacturer’s data to provide accurate short-circuit behavior for modeling. Specific generator time constants and resistances are relevant as to how the current from the generators decay with time during a fault. This data is included in Appendix M when available. When not available, the PTW software provides estimated values.
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 6 Prepared by: AES Group, Inc.
Table 3.
Emergency Power System Generators
2.5.2 Non-Emergency Generators
There is a single Combined Heat & Power generator (CHP) feeding into a pad-mounted 15kv switchgear through a 1000kva step-up transformer. This supplies co-generation power to the chiller plant B-35 and operates in parallel with the utility supply. This generator is not capable of emergency operation.
Table 4
Non-Emergency Generators
Name Make Voltage Rating (kW)
Location Loads
11-GEN CATERPILLAR 480 175 B11 B11
B22
GENERATOR #6 KOHLER 208 180 Outside
B50
B71
B72
GENERATOR #7 KOLHER 208 150 Outside
B50
B73
B34 GEN 1 CATERPILLAR 480 365 B34 B1, B34, B3
B34 GEN 2 CATERPILLAR 480 365 B34 B1, B34, B3
B1 GEN 1 CATERPILLAR 480 450 B1 –
RM EB2
B1
B1 GEN 2 CATERPILLAR 480 450 B1 –
RM EB2
B1
Name Make Voltage Rating (kW)
Location Loads
CHP GEN STAMFORD 480 850 Level 2 outdoor enclosure
B35
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 7 Prepared by: AES Group, Inc.
2.6 Calculation Methods
This study includes the following elements: short circuit calculations, overcurrent protective device coordination, and a condition assessment of electrical equipment.
As required by the project’s Statement of Work, all calculations have been performed using Power*Tools software, developed by SKM Systems Analysis, Inc, Version 9.0.0.5.
The following modules were utilized for this study:
System Model Development: DAPPER & Unbalanced/Single Phase
Short Circuit Calculations: A_Fault
Protective Device Coordination: CAPTOR
Voltage Drop Analysis: DAPPER
Arc Flash Hazard Analysis: Arc Flash Evaluation
Condition Assessment: Equipment Evaluation
2.7 Ground Resistance Test Reports
The VAMC Grounding System Test report was not available at the time of this submission.
2.8 Data Estimation
While AES has examined all of the electrical equipment at the Fayetteville VAMC, there were instances where data could not be obtained. This can occur due to inaccessible equipment caused by age or location, data missing from the equipment, or the inability to take the equipment out of service for thorough inspection.
To fill in the holes created by this lack of data, the following estimation methods were used:
2.8.1. Transformers
X/R ratios based on typical values for transformers of like type and size.
2.8.2. Loads
Loads on the system were estimated by taking the highest utility power draw from historic utility data, adding 20% and applying the loads to the lowest tier electrical panels. The load values are apportioned in accordance with the cable ampacities at each branch in the system.
Loads that are known to be motors are modeled with a 0.80 power factor. All other loads use a power factor of 0.95.
425 I Street, NW, (CFM3A) Washington, DC 20001
Section 2 Page 8 Prepared by: AES Group, Inc.
2.8.1. Conductor Lengths
Cable length is approximated using floor plans, Google maps or field observations.
2.8.2. Equipment Labels
Equipment is labeled based on the load it supplies.
Section 3
Fault Current Analysis
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Section 3 Page 1 Prepared by: AES Group, Inc.
3. FAULT CURRENT ANALYSIS
3.1. Introduction
Electrical fault current analysis was based on data collected during field surveys of the Fayetteville VAMC electrical distribution system. The analysis examined the available fault current at buses throughout the electrical system and was used to determine the capability of the electrical equipment to withstand an electrical fault at that location.
Both three-phase and single-phase-to-ground calculations were performed.
One-line diagrams are included in Appendix H. Reports showing the complete input data used to construct each model are included in Section 3.4.
3.2. Sources of Fault Current
The fault current calculations performed on the Fayetteville VAMC electrical system were based on available fault current values provided by Fayetteville Public Works Commission, the electrical utility supplying the Fayetteville VAMC campus. This data is shown below and attached in Appendix B.
Table 4
Primary Utility Service Feeds
Source Primary Voltage 3 Phase Fault Singe Phase Fault
Tokay 12.47 / 7.2 kV 3,705 amps 2,655 amps
Hoffer 12.47 / 7.2 kV 3,965 amps 2,729 amps
In addition to the primary utility service feeds, the site includes a Combined Heat & Power (CHP) generator, providing up to 850 kW of power at 480 volts. This generator is connected into the medium voltage distribution system through a dedicated transformer, connected to sectionalizer 6.
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Section 3 Page 2 Prepared by: AES Group, Inc.
Emergency Generators:
Generators supplying emergency power are listed in Table 5.
Table 5
Generators
Generator Label Voltage Rating
(kW)
B1 GEN 1 480 450
B1 GEN 2 480 450
B34 GEN 1 480 365
B34 GEN 2 480 365
11-GEN 480 175
GENERATOR #6 208 162
GENERATOR #7 208 150
3.3. Calculation Scenarios
Induction motors provide additional sources of fault current and were included in different study calculation scenarios.
Multiple calculation scenarios were used to calculate available fault current values based on Utility power, Generator power and whether motor contribution is considered. These scenarios are listed in Table 6 Calculation Scenarios.
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Section 3 Page 3 Prepared by: AES Group, Inc.
Table 6
Calculation Scenarios
Scenario Power Source Motors Protection Settings
0 Normal On Existing
1 Normal Off Existing
2 Emergency On Existing
3 Emergency Off Existing
In the Base scenario; Scenario 0, the generators are off, power comes from the utility, and all motors are running. The power system setting reflects the current settings found during the investigation.
Scenario 0 power sources consist of the CHP generator and the utility feed from the “Hoffer” substation. Normal operation of the distribution system uses only one of the utility feeds, of which the “Hoffer” connection has the greatest potential short circuit current. The CHP generator is included as it is designed for parallel operation with the utility connection, and can therefore be expected to be in operation during a fault.
All of the motors connected were in operation as motors contribute fault current during a fault; they become electrical generators.
This is the worst case for short circuit current.
In scenario 1, the power comes from the utility and all motors are off. The power system settings were the ones found during the site investigation as during scenario 0.
In scenario 2, the utility power is off and the main power source are the emergency generators.
All motors were running and the settings matched the existing settings.
Scenario 3 was similar to Scenario 2 with the exception that the motors were turned off.
3.4. SKM Power*Tools Input Data Report
The system components used to calculate fault currents for the scenarios listed in table 6 are included in the DAPPER Fault Analysis Input Report.
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Section 3.5 Page 1 Prepared by: AES Group, Inc.
3.5. Short Circuit Calculation Results
The DAPPER Fault Contribution Complete Report show the available fault current values at various buses for the scenarios described in Table 6, section 3.3. This information is used to verify that the equipment is properly rated to withstand the available fault current to which it may be subjected.
Prepared for: Dept. of Veterans Affairs 425 I Street, NW, (CFM3A) Washington, DC 20001
Section 3.6 Page 1 Prepared by: AES Group, Inc.
11031 S. Pikes Peak Dr., Suite #202
Parker, CO 80138
3.6. Equipment Evaluation Results
The Equipment Evaluation compares equipment ratings against calculated available fault currents values. The buses listed in the Bus evaluation table as “Estimated” refers to the buses which information was taken from previous Condition assessment reports and were not confirmed by the field team due to limited access or locked equipment.
Ninety three (93) pieces – 77 OCDP’s and 16 Panels – of equipment have failed the equipment evaluation for interrupting rating.
Table Header Definitions:
Calc Int kA: Calculated Interrupting Current.
Dev Int kA: Device Interrupting Current Rating.
Int Rating %: Calculated Interrupting Current divided by Device Interrupting Current Rating.
Series Rating: The combination of two or more OCPD’s connected in series where the interrupting current data of the downstream device(s) is less than the interrupting rating of the system.
Calc Mom kA: Calculated Momentary Current.
Dev Mom kA: Device Momentary Current Rating.
Color Code Legend for Device Evaluation Comprehensive Bus Report
Fail:
maximum calculated fault current higher than device interrupt rating
Marginal:
Maximum calculated fault current greater than 90% of device interrupt rating.
Normal Site Gen Emergency Normal Site Gen Emergency Device Power Generation Power Device Power Generation Power
Connected Device Device Bus Interrupt Calculated Calculated Calculated Momentary Calculated Calculated Calculated Bus Name Voltage Voltage Rating (kA) Fault (kA) Fault (kA) Fault (kA) Rating (kA) Fault (kA) Fault (kA) Fault (kA)
B1 ATS 2 MAIN DISC B1 ATS 2 MAIN DISC CB 600 208 25 9.33 ‐ ‐ ‐ ‐ ‐ ‐
B1 ATS EDP‐E DISC B1 ATS EDP E CB 600 208 25 4.02 ‐ ‐ ‐ ‐ ‐ ‐
B1 DISC AHU‐A1 B1 DISC AHU‐A1 FUSE 250 208 200 8.10 ‐ ‐ ‐ ‐ ‐ ‐
B1 DISC EF#1 B1 DISC EF#1 FUSE 250 208 200 1.33 ‐ ‐ ‐ ‐ ‐ ‐
B1 DISC EF#4 B1 DISC EF#4 FUSE 250 208 200 1.33 ‐ ‐ ‐ ‐ ‐ ‐
B1 DISC EMRG PWR BLDG 21 B1 EMRG PWR DISC B21 CB 600 208 25 10.04 ‐ ‐ ‐ ‐ ‐ ‐
B1 DISC XFMR T‐11 B1 DISC XFMR T‐11 FUSE 600 480 200 3.35 ‐ ‐ ‐ ‐ ‐ ‐
B1 DISC XFMR T‐12 EMERG B1 DISC XFMR T‐12 EMERG ECB 600 480 25 4.16 ‐ ‐ ‐ ‐ ‐ ‐
B1 DISC XFMR T‐13 EMERG B1 DISC XFMR T‐13 EMERG ECB 600 480 22 4.36 ‐ ‐ ‐ ‐ ‐ ‐
B1 DUMBWAITER DISC B1 DUMBWAITER DISC FUSE 600 480 200 5.62 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 21A 120V BUS B1 ISO PNL 21A 120V BUS MCB 240 120 10 2.42 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 21B 120V BUS B1 ISO PNL 21B 120V BUS MCB 240 120 10 2.60 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 22A 120V BUS B1 ISO PNL 22A 120V BUS MCB 240 120 10 2.71 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 22B 120V BUS B1 ISO PNL 22B 120V BUS MCB 240 120 10 2.71 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 23A 120V BUS B1 ISO PNL 23A 120V BUS MCB 240 120 10 2.71 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 23B 120V BUS B1 ISO PNL 23B 120V BUS MCB 240 120 10 2.78 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 24A 120V BUS B1 ISO PNL 24A 120V BUS MCB 240 120 10 2.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 24B 120V BUS B1 ISO PNL 24B 120V BUS MCB 240 120 10 2.89 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 25A 120V BUS B1 ISO PNL 25A 120V BUS MCB 240 120 10 2.92 ‐ ‐ ‐ ‐ ‐ ‐
B1 ISO PNL 25B 120V BUS B1 ISO PNL 25B 120V BUS MCB 240 120 10 0.13 ‐ ‐ ‐ ‐ ‐ ‐
B1 P5 DISC B1 PNL P5 FUSE 600 480 200 13.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 P6 DISC B1 PNL P6 FUSE 600 480 200 13.96 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 1A‐ED B1 ATS 1 CB 240 208 25 10.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 1A‐ED B1 ATS 3 CB 240 208 42 10.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 1A‐ED B1 ATS 6 CB 240 208 22 10.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 1A‐ED B1 PNL 1A‐ED MCB 240 208 42 10.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 2IR B1 PNL 2IR MCB 240 208 25 3.08 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 2L B1 PNL 2L MCB 480 480 25 12.98 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 2L B1 XFMR 2R‐R CB 480 480 18 12.98 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 2RL B1 PNL 2IR CB 480 208 22 3.43 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL 2RR B1 PNL 2RR CB 480 208 25 3.49 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL A1 B1 PNL A1‐1 CB 240 208 22 13.66 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL A2 B1 PNL A3 CB 240 208 10 8.64 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL A2 B1 PNL PB16 CB 240 208 10 8.64 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL AC B1 DISC AHU‐A1 CB 240 208 25 23.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL AC‐1 B1 PNL AC‐1 MCB 240 208 65 18.82 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL AC‐1 B1 PNL FCU CB 240 208 65 18.82 ‐ ‐ ‐ ‐ ‐ ‐
03 ‐ 06.5 ‐ 00 ‐ Device Evaluation Comprehensive Bus Report Fayetteville VAMC
Sustained Fault Momentary Fault
B1 PNL AC‐2 B1 PNL C CB 240 208 22 4.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL B1 B1 PNL B2 CB 240 208 22 13.09 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL BLB B1 XFMR TR1B CB 480 480 14 3.72 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL BRB B1 PNL BRB MCB 240 208 22 1.76 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C1 B1 PNL C2 CB 240 208 22 10.32 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2IR B1 PNL C2IR MCB 240 208 22 6.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 21A 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 21B 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 22A 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 22B 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 23A 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 23B 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 24A 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 24B 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 25A 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 ISO PNL 25B 240 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 PNL C2L MCB 480 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2L B1 XFMR C2R CB 480 480 18 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL C2R B1 PNL C2R MCB 240 208 42 2.29 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CATSCAN MAIN B1 PNL CATSCAN MAIN MCB 480 480 18 9.93 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CBL B1 PNL CBL MCB 480 480 18 8.00 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CBL B1 XFMR CBR CB 480 480 14 8.00 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CBLB B1 XFMR TR2B CB 480 480 35 6.08 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CBR B1 PNL CBR MCB 240 208 42 3.33 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CBR B1 PNL CBRA CB 240 208 5 3.33 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CBRA B1 PNL CBRA MCB 240 208 5 1.94 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CBRB B1 PNL CBRB MCB 240 208 22 2.83 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 PNL C2IR CB 480 480 25 19.88 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 PNL C2L CB 480 480 25 19.88 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 PNL C2L CB REC 480 480 25 19.88 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 PNL CBL CB 480 480 25 19.88 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 PNL CBLB CB 480 480 25 19.88 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 PNL CD MCB 480 480 30 19.88 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 PNL CIL CB 480 480 25 19.88 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CD B1 XFMR EQM DISC CB 480 480 18 22.12 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CIL B1 PNL CIL MCB 480 480 25 12.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CIL B1 PNL X‐RAY 4 CB 480 480 25 12.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CIL B1 XFMR CIR CB 480 480 18 12.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL CIR B1 PNL CIR MCB 240 208 5 6.21 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL D‐A B1 XFMR B CB 480 480 25 10.63 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL DNE B1 ATS 1‐N CB 600 208 25 27.06 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL DNE B1 PNL DNE MCB 600 208 25 27.06 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL E2P B1 PNL E2P MCB 240 208 5 10.02 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EAE B1 PNL CHPIA CB 240 208 200 20.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EAE B1 PNL EPH CB 240 208 65 20.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EAE B1 PNL LOAD CENTER CB 240 208 65 20.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EAE B1 XFMR 0044 CB 240 208 65 20.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D B1 PNL CATSCAN MAIN CB 480 480 18 14.63 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D B1 PNL EC1D MCB 480 480 30 14.63 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D B1 XFMR EC1D‐1 CB 480 480 18 14.63 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D B1 XFMR NEW LAB PANEL CB 480 480 18 14.63 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D‐1 B1 PNL EC1D‐1 MCB 480 208 30 8.73 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D‐1 B1 PNL EC1D‐2 CB 240 208 10 8.73 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D‐1 B1 PNL EC1D‐3L CB 240 208 10 8.73 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D‐2 B1 PNL EC1D‐2 MCB 240 208 42 4.38 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EC1D‐3L B1 PNL EC1D‐3L MCB 240 208 42 5.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD (LD) B1 1EF‐6D EX FAN CB 480 480 25 19.25 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD (LD) B1 PNL BLB CB 480 480 25 19.25 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD (LD) B1 PNL ECBD MCB 480 480 30 19.25 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD (LD) B1 PNL ECBD‐2 CB 480 480 25 19.25 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD (LD) B1 PNL ECBD‐4 CB 480 480 25 19.25 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD (LD) B1 XFMR ECBD‐1 CB 480 480 25 19.25 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐1 B1 PNL ECBD‐1 MCB 240 208 42 6.55 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐1 B1 PNL ECBD‐3L CB 240 208 22 6.55 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐1 B1 PNL ECBD‐5L CB 240 208 22 6.55 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐2 B1 PNL ECBD‐2 MCB 480 480 18 6.43 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐3L B1 PNL ECBD‐3L MCB 240 208 42 1.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐3R B1 PNL BR‐A CB 240 208 10 1.73 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐4 B1 PNL ECBD‐4 MCB 480 480 18 4.27 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECBD‐5L B1 PNL ECBD‐5L MCB 240 208 42 1.32 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDB B1 PNL EC2B CB 240 208 65 8.26 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDB B1 PNL EC3B CB 240 208 65 8.26 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDB B1 PNL EC4B CB 240 208 65 8.26 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDB B1 PNL EC5B CB 240 208 65 8.26 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDB B1 PNL ECBB CB 240 208 65 8.26 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDC B1 PNL EC2C CB 240 208 22 11.65 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDC B1 PNL EC3C CB 240 208 22 11.65 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDC B1 PNL EC4C CB 240 208 22 11.65 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDC B1 PNL EC5C CB 240 208 22 11.65 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDC B1 PNL ECBC CB 240 208 22 11.65 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDP B1 PNL ECDB CB 600 208 25 30.58 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDP B1 PNL ECDC CB 600 208 25 30.58 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDP B3 PNL ECD3 CB 600 208 25 30.58 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ECDP B3 PNL ECD4 CB 600 208 25 30.58 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 DUMBWAITER DISC CB 480 480 25 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 PNL EDA CB 480 480 25 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 PNL EMC3 CB 480 480 65 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 PNL EMCI CB 480 480 25 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 PNL EMP‐1 CB 480 480 65 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 PNL EQLB CB 480 480 25 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 PNL MCC CB 480 480 25 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 PNL P5/P6 CB 480 480 18 24.92 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ED B1 XFMR ER CB 480 480 25 22.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDA B1 PNL PURE AIR COMP CB 480 480 25 17.79 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDP B1 NONE CB 240 208 65 14.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDP B1 PNL EC3A (SECTION 1) CB 240 208 10 15.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDP B1 PNL EC4A (SECTION 1) CB 240 208 10 15.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDP B1 PNL ECBA CB 240 208 25 14.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDP B1 PNL ECC‐1 (CC‐1) CB 240 208 18 14.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDP B1 PNL EEA CB 480 208 14 14.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EDP B1 PNL EMGA CB 240 208 25 14.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EEDP B1 PNL EE3A CB 240 208 22 10.38 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EEDP B1 PNL EE4A CB 240 208 22 10.38 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EEDP B1 PNL MCCA CB 240 208 22 10.38 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ELV B1 PNL ELV MCB 240 208 5 3.02 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 AHU 4 RF CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 AHU 4 SF CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 AHU 5 RF CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 AHU 5 SF CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 AHU 6 RF CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 AHU 6 SF CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 CHILLER UNIT 1 CB 240 480 100 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 CHILLER UNIT 2 CB 240 480 100 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 CHILLER UNIT 3 CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 CWP 3 CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 CWP 4 CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 PNL EMP‐1 MCB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EMP‐1 B1 STEAM STERILIZER CB 480 480 65 17.31 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EQLB B1 XFMR TREQ CB 240 480 22 5.07 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL EQRB B1 PNL EQRB MCB 240 208 22 0.67 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ER B1 PNL ELV CB 240 208 5 6.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ER B1 PNL ER MCB 480 208 25 6.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ER B1 PNL ERA CB 240 208 5 6.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ER B1 PNL IER CB 240 208 5 6.03 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ERA B1 PNL ERA MCB 240 208 42 4.19 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ES B1 ATS 1 E CB 480 480 100 11.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ES B1 ATS 2 E CB 480 480 65 11.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ES B1 ATS 3 E CB 480 480 65 11.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ES B1 ATS 4 E CB 480 480 65 11.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ES B1 ATS 5 E CB 480 480 65 11.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ES B1 PNL ES MCB 480 480 100 11.87 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ES3B B1 PNL ESSP‐3B CB 240 208 22 7.02 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESBA B34 PNL A CB 240 208 10 3.25 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDA B1 PNL ES1A CB 240 208 10 6.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDA B1 PNL ES2A CB 240 208 10 6.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDA B1 PNL ES3A CB 240 208 10 6.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDA B1 PNL ES4A CB 240 208 10 6.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDA B1 PNL ESAC‐1A CB 240 208 10 6.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDA B1 PNL ESBA CB 240 208 10 6.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDA B1 PNL ESDA MCB 240 208 65 6.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDB B1 PNL E2P CB 240 208 22 11.82 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDB B1 PNL ES1B CB 240 208 22 11.82 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDB B1 PNL ES2B CB 240 208 22 11.82 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDB B1 PNL ES3B CB 240 208 22 11.82 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDB B1 PNL ES4B CB 240 208 22 11.82 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDB B1 PNL ESBB CB 240 208 22 11.82 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDC B1 PNL ES1C CB 240 208 22 6.42 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDC B1 PNL ES2C CB 240 208 22 6.42 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDC B1 PNL ES3C CB 240 208 22 6.42 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDC B1 PNL ES4C CB 240 208 22 6.42 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDC B1 PNL ES5C CB 240 208 22 6.42 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B1 PNL EEDP CB 240 208 65 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B1 PNL ESDA CB 240 208 65 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B1 PNL ESDB CB 240 208 65 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B1 PNL ESDC CB 240 208 65 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B1 PNL MECH A CB 240 208 100 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B1 PNL MECH CB 240 208 100 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B3 PNL ES3B CB 480 208 35 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL ESDP B3 PNL ESD3 CB 240 208 65 18.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL F2 DISCONNECT B1 PNL F2 DISCONNECT MCB 240 208 42 14.55 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL GEN CNTRL CABINET B1 GEN CNTRL CAB CB#2 635 480 100 11.36 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL GEN CNTRL CABINET B1 GEN CNTRL CAB CB1 635 480 100 11.36 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL GEN CNTRL CABINET B1 PNL ES CB 635 480 100 11.36 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL I3 B1 PNL I3 MCB 240 208 65 5.13 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL IER B1 PNL IER CB MCB 240 208 5 2.39 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL J3 B1 PNL J3 MCB 240 208 65 5.11 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL J3 B1 PNL P1 CB 240 208 22 5.11 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL LIL B1 PNL LIL MCB 480 480 14 7.36 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL LIL B1 XFMR LIR CB 480 480 14 7.36 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL LIR B1 PNL LIR MCB 240 208 5 1.38 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL LSD B1 PNL L1L CB 240 480 10 7.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL LSD B1 PNL LSD MCB 480 480 14 7.74 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL M2 B1 PNL M2 MCB 240 208 65 14.18 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL M480 B1 PNL M480 MCB 480 480 18 2.22 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MCCA B1 DISC AHU#1 CB 240 208 18 3.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MCCA B1 DISC EF#1 CB 240 208 18 3.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MCCA B1 DISC EF#2 CB 240 208 25 3.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MCCA B1 DISC EF#3 CB 240 208 18 3.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MCCA B1 DISC EF#4 CB 240 208 18 3.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDA B1 PNL AC‐1 CB 240 208 65 21.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDA B1 PNL AC‐2A CB 240 208 65 21.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDA B1 PNL AC3 CB 240 208 65 21.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDA B1 PNL AC4 CB 240 208 65 21.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDA B1 PNL LAB‐1 CB 240 208 65 21.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDA B1 PNL NC (RM 455) CB 240 208 65 21.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL F2 DISCONNECT CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL G2 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL H2 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL H3 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL I2 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL I3 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL J2 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL J3 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MDB B1 PNL K2 CB 240 208 65 20.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH B1 PNL MECH C CB 240 208 65 11.83 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH B1 PNL MECH MCB 240 208 100 11.83 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH B1 XFMR T480 CB 240 208 65 11.83 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐1/RF‐1 CB 240 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐1/SF‐1 CB 480 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐2/RF‐2 CB 240 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐2/SF‐2 CB 240 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐3/RF‐3 CB 240 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐3/SF‐3 CB 240 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐4/RF‐4 CB 240 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 AHU‐4/SF‐4 CB0 240 208 65 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MECH A B1 PNL MECH A MCB 240 208 100 11.51 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MRI DISCONNECT B1 PNL MRI DISCONNECT MCB 480 480 18 13.26 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MRL B1 PNL MRI DISCONNECT CB 240 480 25 14.15 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MRL B1 PNL MRL MCB 480 480 30 14.15 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MRL B1‐XFMR MRI CB 480 480 18 14.63 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MRR B1 PNL MRR CB 240 208 10 1.64 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 ATS 1 N CB 480 480 100 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 ATS 2 N CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 ATS 3 N CB 240 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 ATS 4 N CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 ATS 5 N CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL 2L CB 240 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL D‐A CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL MC1 CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL MC2 CB 240 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL MRI RECEPTACLE CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL MRL CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL MS MCB 600 480 42 22.79 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL MS B1 PNL XD CB 480 480 65 24.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL N2A SECT1 B1 PNL N2C CB 240 208 65 14.20 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL NEW LAB PANEL B1 PNL NEW LAB PANEL MCB 240 208 100 4.13 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PA‐5 B1 MTR ELEVATOR‐1 CB 240 240 65 1.95 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PA‐5 B1 MTR ELEVATOR‐2 CB 240 240 65 1.95 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PA‐5 B1 PNL #1‐A CB 240 240 22 1.95 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PID B1 FCU #1 CB 240 240 25 0.72 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PID B1 MTR ELEV 1 CB 240 240 25 0.72 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PID B1 MTR ELEV 2 CB 240 240 25 0.72 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PID B1 MTR ELEV 3 CB 240 240 25 0.72 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PID B1 PNL L‐A CB 240 240 18 0.72 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PURE AIR COMP B1 PNL PURE AIR COMP FUSE 600 480 200 13.91 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL PURE AIR COMP B1 PNL PURE AIR COMP SW 480 480 10 13.91 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL Q2 B1 PNL Q2A CB 240 208 22 8.76 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL S B1 PNL T CB 240 208 99 3.57 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL XD B1 PNL X‐RAY 1 CB 480 480 25 16.28 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL XD B1 PNL X‐RAY 2 CB 480 480 25 16.28 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL XD B1 PNL X‐RAY 3 CB 480 480 25 16.28 ‐ ‐ ‐ ‐ ‐ ‐
B1 PNL XD B1 PNL XD MCB 480 480 30 16.28 ‐ ‐ ‐ ‐ ‐ ‐
B1 X‐RAY 1 DISC B1 X‐RAY 1 ECB 480 480 25 11.41 ‐ ‐ ‐ ‐ ‐ ‐
B1 X‐RAY 2 DISC B1 X‐RAY 2 ECB 480 480 25 12.69 ‐ ‐ ‐ ‐ ‐ ‐
B1 X‐RAY 3 DISC B1 X‐RAY 3 ECB 480 480 25 10.66 ‐ ‐ ‐ ‐ ‐ ‐
B1 X‐RAY 4 DISC B1 X‐RAY 4 ECB 480 480 25 6.94 ‐ ‐ ‐ ‐ ‐ ‐
B10 DISC LPA B10 DISC LPA ECB 240 208 10 4.18 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL LE4 B10 PNL LE4 MB 240 208 65 3.50 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL LE4 DISC OR PLA AUX B10 PNL LE4 DISC MB OR PLA AUX 600 208 22 4.12 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL MDP B10 CHILLER CB 480 480 25 18.98 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL MDP B10 PNL LE‐1 CB 480 480 35 18.98 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL MDP B10 PNL LE‐2 CB 480 480 25 18.98 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL MDP B10 PNL LE‐3 CB 480 480 35 18.98 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL MDP B10 XFMR CB 600 480 18 21.11 ‐ ‐ ‐ ‐ ‐ ‐
B10 PNL PLA B10 PNL PLA MB 240 208 42 4.16 ‐ ‐ ‐ ‐ ‐ ‐
B11 PNL LP‐R B22 PNL ANN CB 240 208 22 3.98 ‐ 3.01 ‐ ‐ ‐ ‐
B11 PNL MCC B11 BOILDER FEED P1 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 BOILDER FEED P2 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 BOILDER FEED P3 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 CHP COND RETURN P8 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 CHP GLYCOL P7 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 COND TRANS CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 CONDENSATE P1 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 NEW BOILER 1 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 NEW BOILER 2 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MCC B11 NEW BOILER 3 CB 480 480 65 14.64 ‐ 2.70 ‐ ‐ ‐ ‐
B11 PNL MDP B11 AIR COMPRESSOR CB 480 480 25 18.20 ‐ 2.81 ‐ ‐ ‐ ‐
B11 PNL MDP B11 PNL MCC CB 480 480 35 18.20 ‐ 2.81 ‐ ‐ ‐ ‐
B11 PNL MDP B11 PNL MDP CB 480 480 35 18.20 ‐ 2.81 ‐ ‐ ‐ ‐
B11 PNL MDP B11 PNL MDP CB REC 480 480 35 18.20 ‐ 2.81 ‐ ‐ ‐ ‐
B11 PNL MDP B11 PS E85 STATION CB 480 480 35 18.20 ‐ 2.81 ‐ ‐ ‐ ‐
B11 PNL MDP B11 XFMR CB 480 480 65 18.20 ‐ 2.81 ‐ ‐ ‐ ‐
B21 PNL CU B21 PNL CU MCB 240 208 22 17.17 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL LOAD CENTER B21 PNL LOAD CENTER MCB 240 208 10 16.85 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 ACC‐1 CB 480 208 14 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 PNL CRAC CB 240 208 22 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 PNL CRAHU‐1 CB 240 208 22 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 PNL CU CB 240 208 22 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 PNL LOAD CENTER CB 480 208 14 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 PNL MDP MCB 480 208 50 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 PNL P1 CB 220 208 22 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 PNL UPS #1 MCB 240 208 22 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL MDP B21 SPD CB 480 208 14 24.60 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL P1 B21 PNL P1 MCB 240 208 42 21.58 ‐ ‐ ‐ ‐ ‐ ‐
B21 PNL P1 B21 PNL UPS #2 MCB 240 208 22 21.58 ‐ ‐ ‐ ‐ ‐ ‐
B22 PNL ANN B22 PNL ANN MCB 240 208 22 2.36 ‐ 1.83 ‐ ‐ ‐ ‐
B22 PNL ANN B24 PNL MAIN CB 240 208 22 2.36 ‐ 1.83 ‐ ‐ ‐ ‐
B24 PNL MAIN B24 PNL MAIN MCB 240 208 18 1.19 ‐ 1.09 ‐ ‐ ‐ ‐
B3 PNL B B3 PNL NL CB 240 208 22 9.94 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL DP B3 PNL DP MCB 600 208 22 16.07 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL DP B3 PNL LP‐2 CB 240 208 25 16.07 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL DP B3 PNL LP1‐1 CB 240 208 25 16.07 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL DP B3 PNL LP3 CB 240 208 25 16.07 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL DP B3 PNL LP4 CB 240 208 25 16.07 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL DP B3 PNL MCC CB 480 208 35 16.07 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ECD3 B3 DISHWASHER CB 240 208 22 7.56 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ECD3 B3 PNL EC31 CB 240 208 22 7.56 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ECD3 B3 PNL EC32 CB 240 208 22 7.56 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ECD3 B3 PNL EC34 CB 240 208 22 7.56 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ECD3 B3 PNL FREEZER #2 CB 240 208 22 7.56 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ELEV DISC B3 PNL ELEV DISC FUSE 250 208 200 4.36 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ES1A B3 PNL ES1A MCB 240 208 65 2.51 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ES31 B3 PNL ES1A CB 240 208 22 3.20 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ES3B UNK CB 240 208 10 3.69 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ESD3 B3 PNL ES31 CB 240 208 22 5.81 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ESD3 B3 PNL ES32 CB 240 208 22 5.81 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL ESD3 B3 PNL ES33 CB 240 208 22 5.81 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL K3 B3 AHU‐SF CB 240 208 65 6.91 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL K5 B3 PNL K5 MCB 240 208 22 7.72 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL K5 B3 RANGE 14 CB 240 208 10 8.17 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL L2 B1 PNL L1 CB 240 208 22 11.03 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC B3 PNL PUMP PANEL CB 250 208 200 10.49 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC (1‐PHASE) B3 PNL BP1A3 CB 240 208 25 7.83 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC (1‐PHASE) B3 PNL MC‐1 CB 240 208 25 7.83 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC (3‐PHASE) B3 PNL K3 CB 250 208 42 8.70 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC (3‐PHASE) B3 PNL K5 CB 240 208 25 8.70 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC (3‐PHASE) B3 PNL KPPA CB 240 208 25 8.70 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC (3‐PHASE) B3 PNL MC‐3 CB 240 208 25 8.70 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MCC (3‐PHASE) B3 PNL P1 CB 240 208 25 8.70 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MECH‐3 B3 AHU‐1 CB 240 208 22 13.46 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MECH‐3 B3 CHILLER CB 240 208 65 13.46 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MECH‐3 B3 PNL MOBILE MRI CB 240 208 65 13.46 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MIDP B3 XFMR #1 CB 600 480 22 18.83 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MIDP B3 XFMR 2 CB 480 480 30 18.83 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL MIDP ECB BUS B3 PNL MIDP ECB 600 480 65 27.04 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL P3 B1 CB 225A 240 208 10 11.07 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL B CB 240 208 42 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL ELEV DISC CB 480 208 30 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL K1 CB 600 208 22 15.23 ‐ ‐ ‐ ‐ ‐ ‐
VHAFNCFordA Highlight
VHAFNCFordA Highlight
VHAFNCFordA Highlight
VHAFNCFordA Highlight
VHAFNCFordA Highlight
VHAFNCFordA Highlight
B3 PNL SB‐3 SEC 2 B3 PNL K2 CB 600 208 22 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL K3A CB 240 208 42 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL MCC (3‐PHASE) CB 240 208 42 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL OT CB 240 208 200 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL P1D3A CB 240 208 42 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL P3 CB 240 208 42 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 2 B3 PNL SB‐3 FUSE 600 208 200 15.23 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 3 B3 PNL AC‐1 CB 240 208 65 15.14 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 3 B3 PNL AC‐C B CB 240 208 42 15.14 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 3 B3 PNL K4 CB 240 208 42 15.14 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 3 B3 PNL M CB 240 208 65 15.14 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 3 B3 PNL MCC (1‐PHASE) CB 240 208 42 15.14 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 3 B3 PNL MECH‐3 CB 240 208 65 15.14 ‐ ‐ ‐ ‐ ‐ ‐
B3 PNL SB‐3 SEC 3 B3 PNL W CB 240 208 42 15.14 ‐ ‐ ‐ ‐ ‐ ‐
B30 PNL A B30 PNL A MCB 240 240 22 2.63 ‐ ‐ ‐ ‐ ‐ ‐
B34 GEN 1 DISC B34 GEN 1 DISC FUSE 600 480 200 4.28 ‐ ‐ ‐ ‐ ‐ ‐
B34 GEN 2 DISC B34 GEN 2 DISC FUSE 600 480 200 4.28 ‐ ‐ ‐ ‐ ‐ ‐
B34 PNL A B34 PNL A MCB 240 208 10 1.21 ‐ ‐ ‐ ‐ ‐ ‐
B34 PNL GEN DIST B1 XFMR T‐11 DISC CB 480 480 35 5.46 ‐ ‐ ‐ ‐ ‐ ‐
B34 PNL GEN DIST B1 XFMR T‐12 EMERG DISC CB 480 480 65 5.46 ‐ ‐ ‐ ‐ ‐ ‐
B34 PNL GEN DIST B1 XFMR T‐13 EMERG DISC CB 480 480 65 5.46 ‐ ‐ ‐ ‐ ‐ ‐
B34 PNL GEN DIST B34 GEN 1&2 DISCONNECTS CB 480 480 35 5.46 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 CHWP‐3 CB 600 480 18 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 COOLING TOWER 1 CB 600 480 18 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 COOLING TOWER 1 FAN CB 600 480 14 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 COOLING TOWER 2 CB 600 480 18 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 COOLING TOWER 3 CB 600 480 18 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 PNL D CB 600 480 18 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 SUMP HEAT CT #4 CB 600 480 14 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL MCC B35 XFMR PANEL C CB 600 480 14 22.83 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL NHDP B35 CHWP‐1 CB 600 480 25 22.94 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL NHDP B35 CHWP‐2 CB 600 480 25 22.94 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL NHDP B35 CWP‐1 CB 600 480 25 22.94 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL NHDP B35 CWP‐2 CB 600 480 25 22.94 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL NHDP B35 CWP‐3 CB 600 480 25 22.94 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B11 ATS‐N CB 480 480 65 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B11 ATS‐N CB REC 480 480 65 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B35 MTR CHILLER 1 CB 600 480 35 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B35 MTR CHILLER 2 CB 600 480 35 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B35 MTR CHILLER 3 CB 480 480 65 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B35 PNL MCC CB 480 480 65 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B35 PNL MCC CB REC 480 480 65 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B35 PNL NHDP CB 480 480 65 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B35 PNL SWBD B35 PNL NHDP CB REC 480 480 65 28.02 ‐ ‐ ‐ ‐ ‐ ‐
B37 PNL B37 PNL MCB 240 240 10 1.15 ‐ ‐ ‐ ‐ ‐ ‐
B4 PNL MDP B4 PNL 1A CB 240 208 22 8.10 ‐ ‐ ‐ ‐ ‐ ‐
B4 PNL MDP B4 PNL 2A CB 240 208 22 8.10 ‐ ‐ ‐ ‐ ‐ ‐
B4 PNL MDP B4 PNL 2B CB 240 208 18 8.10 ‐ ‐ ‐ ‐ ‐ ‐
B4 PNL MDP B4 PNL BA CB 240 208 22 8.10 ‐ ‐ ‐ ‐ ‐ ‐
B4 PNL MDP B4 PNL MDP MCB 600 208 22 8.10 ‐ ‐ ‐ ‐ ‐ ‐
B4 PNL MDP B4 PNL MDP MCB REC 600 208 22 8.10 ‐ ‐ ‐ ‐ ‐ ‐
B44 PNL BUILDING 44 B44 PNL BUILDING #44 MCB 240 208 10 8.58 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT1 B44 PNL 44 CDP MCB 480 208 100 41.20 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL AC CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL B CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL D CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL DNE CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL EAE CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL ECDP CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL EMG CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL ESDP CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL G CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B1 PNL M CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT2 B21 PNL MDA CB 240 208 100 42.29 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL A CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL A1 CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL A2 CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL AC‐2 CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL B1 CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL C1 CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL E CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL MDB CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL MDC CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B1 PNL S CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B21 PNL MDP CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B44 SWBD 44 CDP SECT3 B44 PNL BUILDING #44 CB 240 208 100 42.28 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL 3 B45 PNL 3 MCB1 240 208 22 2.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL MDP B45 PNL 3 CB 240 208 10 3.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL MDP B45 PNL MDP MCB 240 208 65 3.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL MDP B45 PNL RM 109 CB 240 208 10 3.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL MDP B45 PNL RM 1J8 CB 240 208 10 3.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL MDP B45 PNL SAFETY SHELTER CB 240 208 10 3.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL MDP B45 PNL WAITING RM CB 240 208 10 3.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL RM 109 B45 PNL RM 109 MCB 240 208 22 3.42 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL RM 1J8 B45 PNL RM 1J8 MCB 240 208 22 2.91 ‐ ‐ ‐ ‐ ‐ ‐
B45 PNL WAITING RM B45 PNL WAITING RM MCB 240 208 22 2.62 ‐ ‐ ‐ ‐ ‐ ‐
B46 PNL A B46 PNL A MCB 240 208 22 3.62 ‐ ‐ ‐ ‐ ‐ ‐
B46 PNL B B46 PNL B MCB 240 208 22 3.83 ‐ ‐ ‐ ‐ ‐ ‐
B46 PNL C B46 PNL C MCB 240 208 22 3.95 ‐ ‐ ‐ ‐ ‐ ‐
B46 PNL D B46 PNL D MCB 240 208 22 4.07 ‐ ‐ ‐ ‐ ‐ ‐
B46 PNL E B46 PNL E MCB 240 208 22 4.19 ‐ ‐ ‐ ‐ ‐ ‐
B46…