AllPanelSch_Electrical.pdf

PDF 12 MB Posted

Attached to
6515--OR LIGHT-EQUIPMENT AND ANESTHESIA BOOM Federal contract opportunity
Solicitation number
36C24626Q0418
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document is an electrical schedules drawing package for the VA Charlotte Health Care Center project, containing detailed specifications for transformers, feeders, circuit breakers, lighting fixtures, and related electrical equipment.

The transformer schedule specifies primary feeders at 480V delta with secondary distribution at 208Y/120V, with kVA ratings ranging from 9 to 500, circuit breaker sizes from 20 to 800 amperes, and grounding electrodes sized from #8 copper to 3/0. The feeder schedule details conductor sizes, equipment ground sizes, and conduit specifications for 80 different feeder designations, accommodating loads from 20 to 4000 amperes across multiple sets of conductors. The lighting fixture schedule identifies 46 fixture types (F1-F46) including 2x4 and 2x2 fluorescent recessed troffers with various ballast configurations, LED downlights, surgical asymmetric luminaires, and specialty fixtures such as MRI downlights and cove lights, with manufacturers including Cooper Metalux, Kirlin, and Gotham. Site lighting fixtures (EF1-EF12) include LED luminaires on 30-foot and 12-foot poles, wall packs, canopy lights, bollards, and step lights from Lithonia and Cooper. The automatic transfer switch (ATS) schedule specifies nine switches rated from 100 to 600 amperes at 480V with bypass isolation options and withstand ratings between 14,000 and 35,000 amperes. Exit sign fixtures (X1-X4) are die-cast aluminum dual-voltage units from Cooper Lighting Sure-Lites in various mounting configurations. The mechanical equipment circuit schedule provides comprehensive details for approximately 200 loads including air handling units, chillers, boilers, elevators, water pumps, compressors, and specialized medical equipment, specifying source panels, circuit numbers, voltages (208V, 277V, and 480V), load ratings in VA, feeder specifications, circuit breaker sizes (ranging from 15 to 600 amperes), and detailed comments regarding disconnects, VFDs, and equipment-specific requirements.

View the file

Other files for this federal contract opportunity

Other files attached to 6515--OR LIGHT-EQUIPMENT AND ANESTHESIA BOOM, newest first.
File Type Posted
5-6thFlr_Structural.pdf PDF
5thFlrArch Vol2 Binder1.pdf PDF
36C24626Q0418 0002.pdf PDF
5thFlrMG_Mechanical_Plumbing_FireProtection.pdf PDF
5thFlr_Electrical.pdf PDF
FP_KHCC_3rd_Floor_11-01-2024.pdf PDF
FP_CHCC_5th_Floor_01-15-2025.pdf PDF
36C24626Q0418 0001.pdf PDF
36C24626Q0418_1 - OR Lights and Booms.pdf PDF
Attachment A - Line-Item Spreadsheet.xlsx XLSX spreadsheet
36C24626Q0418_2.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

kVA

RATING

TRANSFORMER SCHEDULE

PRIMARY

[1] FEEDER

DESIGNATION

[2] CIRCUIT

BREAKER

GROUNDING

ELECTRODE

SIZE (CU)

9 20 20 #8

480V DELTA

SECONDARY

[3] FEEDER

DESIGNATION

[2] CIRCUIT

BREAKER

40 40

208Y/120V

15 35 35 #850 50 30 50 50 #6100 100 45 70 70 #8150 150 75 125 125 #2250 250

112.5 175 175 1/0400 400 150 225 225 2/0500 500 225 350 350 3/0800 800 300 500 500 3/01000 1000 500 800 800 3/01600 1600

KEYNOTES:

[1] PRIMARY FEEDER IS (3) PHASE CONDUCTORS, NO NEUTRAL.

[2] CIRCUIT BREAKERS ARE 3-POLE AND RATED FOR SCHEDULED VOLTAGE.

[3] SECONDARY FEEDER IS (3) PHASE, (1) NEUTRAL, AND (1) EQUIP. GROUND

CONDUCTOR.

GENERAL NOTES:

1. REFER TO FEEDER SCHEDULE FOR CONDUCTOR AND CONDUIT SIZES.

2. VOLTAGE DROP SHALL BE CONSIDERED IN FEEDER SIZING. REFER TO ONE LINE

DIAGRAM FOR INCREASED SIZES.

GROUNDING

ELECTRODE

DESIGNATION

A B C D E F G H I J

FEEDER

DESIGNATION

FEEDER SCHEDULE

NUMBER

OF SETS

SIZES (CU)

PHASE +

NEUTRAL

EQUIP.

GROUND

CONDUIT

SIZE

20 1 #12 #12 3/4" 30 1 #10 #10 3/4"

40 1 #8 #10 1" 50 1 #6 #10 1-1/4" 60 1 #4 #10 1-1/4" 70 1 #4 #8 1-1/4" 80 1 #3 #8 1-1/2" 90 1 #2 #8 1-1/2"

100 1 #1 #6 2" 125 1 1/0 #6 2" 150 1 1/0 #6 2" 175 1 2/0 #6 2-1/2" 200 1 3/0 #4 2-1/2" 225 1 4/0 #4 3" 250 1 250 #4 3" 300 1 350 #3 3-1/2" 350 1 500 #3 4" 400 2 3/0 #3 2-1/2" 500 2 250 #2 3" 600 2 350 #1 3-1/2" 700 2 400 1/0 3-1/2" 800 2 500 1/0 4" 1000 3 400 2/0 3-1/2" 1200 4 350 3/0 3-1/2" 1600 5 500 4/0 4" 2000 5 600 250 4" 2500 7 500 350 4" 3000 8 500 400 4" 4000 10 600 500 4"

SME SEE MECHANICAL EQUIP. SCHEDULE

EACH FEEDER DESIGNATION REPRESENTS (3)

PHASE, (1) NEUTRAL, AND (1) EQUIP. GROUND

CONDUCTORS UNLESS OTHERWISE NOTED.

35 1 #8 #10 1"

Revisions:

2 3 4 5 6 7 8 9

Date

Drawing Title:

Approved: Project Director

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Dwg. of

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

VA FORM 08-6231

on e eig hth in ch o ne f oo t on e qu art er inc h on e foo t thr ee e igh ths in ch o ne fo ot on e ha lf inc h on e foo t thr ee q ua rte rs inc h on e foo t

6" on e inc h on e foo t

6" on e an d on e ha lf inc he s on e foo t

6" thr ee in ch es o ne fo ot

6"

5960 Fairview Road Suite 500 Charlotte, NC 28210 704.887.3500

704.887.3507 fax

1201 Peachtree St., NE 400 Colony Square Suite 1600 Atlanta, GA 30361 Voice: 404.898.9620 Fax: 404.898.9659

1821 Cumberland Ave Suite #100 Charlotte, North Carolina 28203

(704) 348-3097

500-K Clanton Road Charlotte, NC 28217

(704) 525-2003

VA Charlotte Health Care Center

SFO# VA-101-10-RP-0081

Charlotte, NC

This document is the property of RPA Design (including consultants) and RPA Design retains all rights therein, including copyrights.

It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.

It may not be used for any other purpose ecept with the express written agreement of, and compensation to, RPA Design.

8/3 /20

3:

:22

PM

BCERJA

E601

ELECTRICAL SCHEDULES

07/21/2014

ISSUED FOR CONSTRUCTION

LIGHTING FIXTURE SCHEDULE

Type Description Manufacturer Model Ballast Mounting Voltage Lamp Qty. Lamp Cat. No.

Total Load

F1 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START BALLAST.

PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-232-A125-UNV-ER81; DRYWALL FRAME KIT:

FCTKA-24W-U

1 RECESSED GRID OR

GYP

UNV 2 F32T8/835 62 VA

F2 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START BALLAST.

PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-332-A125-UNV-ER81; DRYWALL FRAME KIT:

FCTKA-24W-U

1 RECESSED GRID OR

GYP

UNV 3 F32T8/835 86 VA

F4 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START STEP DIMMING BALLAST WITH 0.88 BALLAST FACTOR. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-232-A125-UNV-HR8-DIM; DRYWALL FRAME KIT:

FCTKA-24W-U

1SD RECESSED GRID OR

GYP

UNV 2 F32T8/835 62 VA

F5 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START STEP DIMMING BALLAST WITH 0.88 BALLAST FACTOR. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-332-A125-UNV-HR8-DIM; DRYWALL FRAME KIT:

FCTKA-24W-U

1SD RECESSED GRID OR

GYP

UNV 3 F32T8/835 86 VA

F6 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START STEP DIMMING BALLAST WITH 0.88 BALLAST FACTOR. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-432-A125-UNV-HR8-DIM; DRYWALL FRAME KIT:

FCTKA-24W-U

1SD RECESSED GRID OR

GYP

UNV 4 F32T8/835 107 VA

F7 2X2 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START BALLAST.

PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-217-A125-UNV-ER81; DRYWALL FRAME KIT:

FCTKA-22W-U

1 RECESSED GRID OR

GYP

UNV 2 F17T8/835 33 VA

F8 2X2 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START BALLAST.

PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-317-A125-UNV-ER81; DRYWALL FRAME KIT:

FCTKA-22W-U

1 RECESSED GRID OR

GYP

UNV 3 F17T8/835 48 VA

F9 2X2 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START BALLAST.

PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-417-A125-UNV-ER81; DRYWALL FRAME KIT:

FCTKA-22W-U

1 RECESSED GRID OR

GYP

UNV 4 F17T8/835 60 VA

F10 2X2 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START STEP DIMMING BALLAST WITH 0.88 BALLAST FACTOR. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-217-A125-UNV-HR8-DIM; DRYWALL FRAME KIT:

FCTKA-22W-U

1SD RECESSED GRID OR

GYP

UNV 2 F17T8/835 33 VA

F11 2X2 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START STEP DIMMING BALLAST WITH 0.88 BALLAST FACTOR. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-317-A125-UNV-HR8-DIM; DRYWALL FRAME KIT:

FCTKA-22W-U

1SD RECESSED GRID OR

GYP

UNV 3 F17T8/835 48 VA

F12 2X2 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START STEP DIMMING BALLAST WITH 0.88 BALLAST FACTOR. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-417-A125-UNV-HR8-DIM; DRYWALL FRAME KIT:

FCTKA-22W-U

1SD RECESSED GRID OR

GYP

UNV 4 F17T8/835 60 VA

F13 4' SURFACE MOUNTED LUMINAIRE STAIRWELL WITH OCCUPANCY SENSOR AND ELECTRONIC BALLAST LUTRON FXSWXX14SLLC4LL51SMXXWH WITH RADIO POWR SAVR

WIRELESS OCCUPANCY SENSOR LRF2-OWLB-P

- WALL, PER

ARCHITECT

UNV - PROVIDED WITH

FIXTURE

44 VA

F14 2X4 RECESSED GENERAL SURGICAL ASYMMETRIC LUMINAIRE WITH COLD ROLLED STEEL CONSTRUCTION, STAINLESS STEEL DOOR AND HARDWARE, ACYLIC LENS GASKETED IN CHANNEL DOOR FRAME, (2) ELECTRONIC PROGRAM START

BALLASTS WITH 0.77 BALLAST

KURTZON ML-F-2-2X4-6/T8-UNV-(2)EBPRS-2/EM 2 + 1 EM RECESSED FLANGE UNV 6 FO32/850/XPS/ ECO3 204 VA

F15 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START BALLAST.

PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CEILING

COOPER FAIL-SAFE: CFF-24-332-UNV-IK12-ER82-AM 2 RECESSED GRID OR

GYP

UNV 3 FO32/835/XPS/ ECO3 73 VA

F16 ADJUSTABLE LED MRI DOWNLIGHT KIRLIN MRR-04220 - RECESS 120 - LED PROVIDED WITH

FIXTURE

20 VA

F17 RECESSED LED MULTI-LAMP ADJUSTABLE FIXTURE KIRLIN MRR-06426 - RECESS 120 - LED PROVIDED WITH

FIXTURE

38 VA

F18 6" RECESSED, LENSED 1500 LUMEN LED DOWNLIGHT SELF-FLANGED, LOW IRIDESCENT FINISH WITH ELECTRONIC

DIMMING DRIVER

COOPER PORTFOLIO: LD6A-15-DL3-ERM6A15-935-6LM1-LI - RECESSED UNV - LED PROVIDED WITH

FIXTURE

22 VA

F19 6" RECESSED, LENSED 2000 LUMEN LED DOWNLIGHT SELF-FLANGED, LOW IRIDESCENT FINISH WITH ELECTRONIC

DIMMING DRIVER

COOPER PORTFOLIO: LD6A-20-DL3-ERM6A20-935-6LM1-LI - RECESSED UNV - LED PROVIDED WITH

FIXTURE

32 VA

F21 4' SURFACE MOUNTED LUMINAIRE WITH SMOOTH OPAL VIRGIN ACRYLIC DIFFUSER, WHITE POWDER COATED FINISH AND

ELECTRONIC PROGRAM START BALLAST

NULITE 16-232T8-UNV-ISN 1 SUSPENDED AT 8'-0" UNV 2 F32T8/835 64 VA

F22 4'-0" LED COVE LIGHT WITH ADJUSTABLE MOUNTING CLIP. PROVIDE ALL ACCESSORIES NECESSARY FOR A COMPLETE

AND OPERATIONAL SYSTEM AND INSTALLATION

ECOSENSE 04LC-48-35-277-120-04-A-MNT-ADJ - SURFACE COVE 277 - LED PROVIDED WITH

FIXTURE

21 VA

F23 1'-0" LED COVE LIGHT WITH ADJUSTABLE MOUNTING CLIP. PROVIDE ALL ACCESSORIES NECESSARY FOR A COMPLETE

AND OPERATIONAL SYSTEM AND INSTALLATION

ECOSENSE 04LC-12-35-277-120-04-A-MNT-ADJ - SURFACE COVE 277 - LED PROVIDED WITH

FIXTURE

5 VA

F24 4'-0" LINEAR DIRECT/INDIRECT FLUORESCENT PENDANT WITH ELECTRONIC BALLAST COOPER CORELITE: AP-SP-2T8-1C-277-AC48"-4FT-EF 1 PENDANT, 18" BFC 277 2 F32T8/835 62 VA F25 6" DIAMETER 5500 LUMEN LED DOWNLIGHT WITH ELECTRONIC DRIVER, CLEAR REFLECTOR AND MATTE DIFFUSE FINISH GOTHAM ICO-35/55-6AR-LD-45-277 - RECESS 277 - LED PROVIDED WITH

FIXTURE

83 VA

F26 2X4 FLUORESCENT LOW PROFILE FIXTURE WITH NANO PRISM LENS AND ELECTRONIC STEP DIMMING BALLAST FOR DUAL

LEVEL SWITCHING

COOPER CORELITE: Z3WN-2T8-1D-277-24-T1-SD 1SD RECESSED GRID 277 2 F32T8/835 67 VA

F27 RETAIL AREA PENDANT: DIRECT/INDIRECT FLUORESCENT PENDANT WITH EXTRUDED ALUMINUM FRAME AND FROSTED

GLASS LENS

FORUM LIGHTING RGP-4-40-120-EL-WHITE 2 PENDANT 120 4 PL-L-40W/385 170 VA

F28 TRACK LIGHTING: PROVIDE ALL CONNECTORS, CANOPIES, END CAPS, ETC. AS NECESSARY FOR A COMPLETE AND

OPERATIONAL SYSTEM

TECH LIGHTING T-TRAK WITH LOW VOLTAGE AERO HEAD. PROVIDE (5) HEADS

PER 4 FEET OF TRACK. ALL FINISHES TO BE SELECTED BY

ARCHITECT.

- TRACK 120 1 PER HEAD 50W MR16 300 VA

F29 LOBBY FIXTURE: 6'-0" DIAMETER SKY OCULUS CUSTOM FIXTURE WITH RGB LEDS (SKY BLUE COLOR) AND ELECTRONIC

DMX DRIVER

PRUDENTIAL P8960-(CUSTOM RGB LED)-VWA-TMW-SC-277 - RECESS 277 - LED PROVIDED WITH

FIXTURE

400 VA

F30 4" DIAMETER LED WALL WASH DOWNLIGHT WITH SPECULAR CLEAR REFLECTOR AND ELECTRONIC DRIVER COOPER PORTFOLIO: LD4A-09-D010TE-ERM4A09-835-4LM111-L1 - RECESS 277 - LED PROVIDED WITH

FIXTURE

14 VA

F31 4'-0" LINEAR RECESSED FLUORESCENT FIXTURE WITH SATIN WHITE REGRESS LENS AND ELECTRONIC BALLAST COOPER NEO-RAY: 23DR-2T8-4-2-EB-SI-S93 1 RECESS 277 2 F32T8/835 67 VA F33 ELEVATOR PIT LIGHT: VAPOR-TIGHT FLUORESCENT LIGHT FIXTURE WITH CAST GUARD GLASS GLOBE PHOENIX LIGHTING VP-32CFL-120-GCL-G-BLK 1 SURFACE WALL 120 1 PL-T-32W/835 37 VA F34 4'-0" LINEAR DIRECT/INDIRECT FLUORESCENT PENDANT WITH ELECTRONIC BALLAST COOPER CORELITE: AP-SP-2T8-1C-277-AC48"-4FT-EF 1 PENDANT, 12" BFC 277 2 F32T8/835 62 VA F35 WAITING ROOMS: 2X2 FLUORESCENT LOW PROFILE FIXTURE WITH NANO PRISM LENS AND ELECTRONIC BALLAST COOPER CORELITE: Z3WN-2T8-1C-277-22-T1 1 RECESSED GRID 277 2 F17T8/835 33 VA F36 2X2 FLUORESCENT RECESSED TROFFER CLASS I, DIV. 2 RATED KENALL HSEGO22-2-17-RS-1-277-2F-2H-U 1 RECESSED GRID 277 2 F17T8/835 33 VA F37 DECORATIVE VANITY FIXTURE FOR PUBLIC TOILETS COOPER SHAPER: 604-36"-W-T5/2/21-277V-SN 1 SURFACE WALL 277 2 F21T5/835 44 VA F38 (SAME AS F4) 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START

STEP DIMMING BALLAST WITH 0.88 BALLAST FACTOR. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM

CELING.

COOPER METALUX: 2GC8-232-A125-UNV-HR8-DIM; DRYWALL FRAME KIT:

FCTKA-24W-U

1SD RECESSED GRID OR

GYP

120 2 F32T8/835 62 VA

F39 (SAME AS F15) 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START

BALLAST. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CEILING

COOPER FAIL-SAFE: CFF-24-332-UNV-IK12-ER82-AM 2 RECESSED GRID OR

GYP

120 3 FO32/835/XPS/ ECO3 73 VA

F40 (SAME AS F2) 2X4 FLUORESCENT RECESSED TROFFER WITH 0.125" ACRYLIC LENS AND ELECTRONIC PROGRAM START

BALLAST. PROVIDE DRYWALL FRAME KIT WHERE MOUNTED IN GYPSUM CELING.

COOPER METALUX: 2GC8-332-A125-UNV-ER81; DRYWALL FRAME KIT:

FCTKA-24W-U

1 RECESSED GRID OR

GYP

120 3 F32T8/835 86 VA

F41 6" RECESSED, LENSED 2000 LUMEN LED DOWNLIGHT SELF-FLANGED, LOW IRIDESCENT FINISH WITH ELECTRONIC

DIMMING DRIVER

COOPER PORTFOLIO: LD6A-20-DL3-ERM6A20-935-6LM1-LI - RECESS 120 - LED PROVIDED WITH

FIXTURE

32 VA

F42 4' SURFACE MOUNTED LUMINAIRE WITH SMOOTH OPAL VIRGIN ACRYLIC DIFFUSER, WHITE POWDER COATED FINISH AND

ELECTRONIC PROGRAM START BALLAST

NULITE 16-232T8-UNV-ISN 1 SUSPENDED AT 8'-0" 120 2 F32T8/835 64 VA

F43 DECORATIVE LED PENDANT LIGHT WITH LAMP ENCLOSURE FOR FOOD HANDLING AREA OR AS REQUIRED BY STATE

HEALTH DEPARTMENT

TECH LIGHTING 700FJ-FIRFAS-LED WITH LAMP ENCLOSURE FOR FOOD AREA - PENDANT 120 - LED PROVIDED WITH

FIXTURE

6 VA

F44 DECORATIVE PENDANT LIGHT TECH LIGHTING 700FJ-FIRAS-12V - PENTANT 120 1 50W HALOGEN 50 VA F45 1X4 RECESSED GENERAL SURGICAL ASYMMETRIC LUMINAIRE WITH COLD ROLLED STEEL CONSTRUCTION, STAINLESS

STEEL DOOR AND HARDWARE, ACYLIC LENS GASKETED IN CHANNEL DOOR FRAME, (2) ELECTRONIC PROGRAM START

BALLASTS WITH 0.77 BALLAST

KURTZON ML-F-2-1X4-3/T8-UNV-(2)EBPRS-2/EM 2 + 1 EM RECESSED FLANGE UNV 3 FO32/850/XPS/ ECO3 101 VA

F46 2X2 RECESSED GENERAL SURGICAL ASYMMETRIC LUMINAIRE WITH COLD ROLLED STEEL CONSTRUCTION, STAINLESS STEEL DOOR AND HARDWARE, ACYLIC LENS GASKETED IN CHANNEL DOOR FRAME, (2) ELECTRONIC PROGRAM START

BALLASTS WITH 0.77 BALLAST

KURTZON ML-F-2-2X2-6/T8-UNV-(2)EBPRS-2/EM 2 + 1 EM RECESSED FLANGE UNV 6 FO17/850/XPS/ ECO3 110 VA

SITE LIGHTING FIXTURE SCHEDULE

Type Description Manufacturer Model Ballast Mounting Voltage Lamp Qty. Lamp Cat. No.

Total Load

EF1 SITE LED LUMINAIRE WITH TYPE III OPTICS WITH SPILL CONTROL, 30'-0'' POLE, DUAL HEAD LITHONIA DSX2 LED 80C 1000 40K T5W MVOLT - POLE MOUNT, +28'-0" MVOLT 2 LED PROVIDED WITH FIXTURE 550 VA EF2 SITE LED LUMINAIRE WITH TYPE III OPTICS WITH SPILL CONTROL, 30'-0'' POLE, SINGLE HEAD LITHONIA DSX2 LED 80C 1000 40K T3M MVOLT-HS - POLE MOUNT, +28'-0" MVOLT 1 LED PROVIDED WITH FIXTURE 275 VA EF3 SITE LED LUMINAIRE WITH TYPE III OPTICS WITH SPILL CONTROL, 12'-0'' POLE, DUAL HEAD LITHONIA DSX1 LED 60C 700 40K T3M MVOLT - POLE MOUNT, +12'-0" MVOLT 2 LED PROVIDED WITH FIXTURE 262 VA EF4 SITE LED LUMINAIRE WITH TYPE III OPTICS WITH SPILL CONTROL, 12'-0'' POLE, SINGLE HEAD LITHONIA DSX1 LED 60C 1000 40K T3M MVOLT - POLE MOUNT, +12'-0" MVOLT 1 LED PROVIDED WITH FIXTURE 209 VA EF5 HYDREL LED LIGHTED BOLLARD HYDREL 3110-36-LED-WHT30K-277-SYM-ELN-BZ/PL BOLLARD, 3'-0" 277 16 LED PROVIDED WITH FIXTURE 60 VA EF6 QUADRA INGRADE LED STEP LIGHT INSIGHT QD/12/40K/CW/15/2/TLB/VS - CONCRETE WALL 277 - LED PROVIDED WITH FIXTURE 15 VA EF7 ROOF: LED WALL PACK WITH BRONZE FINISH COOPER MCGRAW-EDISON: IST-B02-LED-E1-BL2-BZ - SURFACE WALL 120/277 - LED PROVIDED WITH FIXTURE 51 VA EF8 FLAG POLE: IN-GRADE NARROW SPOT ADJUSTABLE LED FIXTURE COOPER LUMIERE: 3002A-RD-18LED4000-SP-NSL-UNV-BZ IN-GRADE 120/277 1 LED PROVIDED WITH FIXTURE 18 VA EF9 WALL WASH: IN-GRADE MEDIUM FLOOD ADJUSTABLE LED FIXTURE COOPER LUMIERE: 3002A-RD-18LED4000-MFL-NSL-UNV-BZ IN-GRADE 120/277 1 LED PROVIDED WITH FIXTURE 18 VA EF10 LED CANOPY LUMINAIRE COOPER MCGRAW-EDISON: TTA1-LED-E1-MQ-(FINISH) - SURFACE 120/277 - LED PROVIDED WITH FIXTURE 34 VA EF11 LED CANOPY LUMINAIRE COOPER MCGRAW-EDISON: CNC-C04-LED-E1-SQ-(FINISH)-SM - SURFACE 120/277 - LED PROVIDED WITH FIXTURE 101 VA EF12 SITE LED LUMINAIRE WITH TYPE III OPTICS WITH SPILL CONTROL, 30'-0'' POLE, SINGLE HEAD LITHONIA DSX2 LED 80C 1000 40K T3M MVOLT - POLE MOUNT, +28'-0" MVOLT - LED PROVIDED WITH FIXTURE 275 VA

ATS SCHEDULES

DESIGNATION PRIORITY OPTIONS AMPS VOLTAGE

WITHSTAND

RATING

ATS-LS1 1 4P BYPASS ISOLATION 100 A 480V 30,000

ATS-LS2 1 4P BYPASS ISOLATION 260 A 480V 25,000

FP ATS & CONTROLLER 1 SERVICE ENTRANCE RATED 150 A 480V 14,000

ATS-CR1 2 4P BYPASS ISOLATION 600 A 480V 35,000

ATS-CR2 2 4P BYPASS ISOLATION 400 A 480V 35,000

ATS-EQ1 3 4P BYPASS ISOLATION 400 A 480V 35,000

ATS-EQ2 3 4P BYPASS ISOLATION 600 A 480V 35,000

ATS-EQ3 3 4P BYPASS ISOLATION 400 A 480V 35,000

EXIT SIGN FIXTURE SCHEDULE

Type Description Manufacturer Model Ballast Mounting Voltage Lamp Qty. Lamp Cat. No.

Total Load

X1 DIE-CAST ALUMINUM EMERGENCY EXIT SIGN WITH BLACK HOUSING, RED LETTERS, DUAL VOLTAGE, SINGLE FACE, CEILING MOUNTED, CHEVRONS PER DRAWINGS

COOPER LIGHTING SURE-LITES: CX6 (FACES PER DRAWINGS) BK-RED LETTERS - SURFACE CEILING UNV - LED 3 VA

X2 DIE-CAST ALUMINUM EMERGENCY EXIT SIGN WITH BLACK HOUSING, RED LETTERS, DUAL VOLTAGE, DOUBLE FACE, CEILING MOUNTED, CHEVRONS PER DRAWINGS

COOPER LIGHTING SURE-LITES: CX6 (FACES PER DRAWINGS) BK-RED LETTERS - SURFACE CEILING UNV - LED 3 VA

X3 DIE-CAST ALUMINUM EMERGENCY EXIT SIGN WITH BLACK HOUSING, RED LETTERS, DUAL VOLTAGE, FLUSH MOUNTED ON

WALL, FACES/CHEVRONS PER DRAWINGS

COOPER LIGHTING SURE-LITES: CX6 (FACES PER DRAWINGS) BK-RED LETTERS - END MOUNTED ON

WALL

UNV - LED 3 VA

X4 DIE-CAST ALUMINUM EMERGENCY EXIT SIGN WITH BLACK HOUSING, RED LETTERS, DUAL VOLTAGE, END-MOUNTED ON

WALL, FACES/CHEVRONS PER DRAWINGS

COOPER LIGHTING SURE-LITES: CX6 (FACES PER DRAWINGS) BK-RED LETTERS - FLUSH MOUNTED ON

WALL

UNV - LED 3 VA

1 ASI #008 - CD2 Submission 08/08/14

Revisions:

2 3 4 5 6 7 8 9

Date

Drawing Title:

Approved: Project Director

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Dwg. of

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

VA FORM 08-6231

on e eig hth in ch o ne f oo t on e qu art er inc h on e foo t thr ee e igh ths in ch o ne fo ot on e ha lf inc h on e foo t thr ee q ua rte rs inc h on e foo t

6" on e inc h on e foo t

6" on e an d on e ha lf inc he s on e foo t

6" thr ee in ch es o ne fo ot

6"

5960 Fairview Road Suite 500 Charlotte, NC 28210 704.887.3500

704.887.3507 fax

1201 Peachtree St., NE 400 Colony Square Suite 1600 Atlanta, GA 30361 Voice: 404.898.9620 Fax: 404.898.9659

1821 Cumberland Ave Suite #100 Charlotte, North Carolina 28203

(704) 348-3097

500-K Clanton Road Charlotte, NC 28217

(704) 525-2003

VA Charlotte Health Care Center

SFO# VA-101-10-RP-0081

Charlotte, NC

This document is the property of RPA Design (including consultants) and RPA Design retains all rights therein, including copyrights.

It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.

It may not be used for any other purpose ecept with the express written agreement of, and compensation to, RPA Design.

8/3 /20

3:

:26

PM

BCERJA

E602

ELECTRICAL SCHEDULES

07/21/2014

ISSUED FOR CONSTRUCTION

MECHANICAL EQUIPMENT CIRCUIT SCHEDULE

Load Name Source Panel

Circuit # Volts Load Feeders

Circuit Breaker Poles Comments

EF-6A05 AHQP 37,39,41 480 V 2390 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6A06 AHP 2,4,6 480 V 2390 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6A07 ALP 1 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6A08A AHQP 2,4,6 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6A08B AHQP 7,9,11 480 V 0 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6A09 AHP 8,10,12 480 V 3810 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B01 BLP 6 120 V 1587 VA (#12+#12N+#12G) 3/4"C 30 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6B02 BHP 14,16,18 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B03 BHP 2,4,6 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B04 BLP 11 120 V 667 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6B05 BLP 3 120 V 696 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6B06 BHP 17,19,21 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B07 BLP 8 120 V 1127 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6B08 BLP 9 120 V 1587 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6B09 BHQP 8,10,12 480 V 6055 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B10 BHQP 20,22,24 480 V 2390 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B11 BHP 8,10,12 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B12 BHP 11,13,15 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-6B13A BHQP 26,28,30 480 V 8764 VA (3#12+#12G) 3/4"C 25 A 3 PROVIDE CONNECTION TO VFD.

EF-6B13B BHQP 29,31,33 480 V 0 VA (3#12+#12G) 3/4"C 25 A 3 PROVIDE CONNECTION TO VFD.

EF-6C01 CLP 5,7 208 V 1580 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT.

EF-6C02 CLP 4 120 V 1127 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6C03 CLP 9,11 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT SWITCH.

EF-6C04 CLP 6,8 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT SWITCH.

EF-6C05 CHP 2,4,6 480 V 2390 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

ELEV-1 ELEVATOR MACH 0D01 BHQG 1,3,5 480 V 37150 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 50 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ELEV-2 ELEVATOR MACH 0D01 CHGA 7,9,11 480 V 37150 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 50 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ELEV-3 ELEVATOR MACH 0D01 BHQG 2,4,6 480 V 37150 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 50 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ELEV-4 ELEVATOR MACH 0D01 CHGA 20,22,24 480 V 37150 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 50 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ELEV-5 AHQP 32,34,36 480 V 45358 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 60 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ELEV-6 AHP 17,19,21 480 V 45358 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 60 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ELEV-7 BHQP 47,49,51 480 V 45438 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 60 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ELEV-8 BHP 53,55,57 480 V 45438 VA (3#6+#6G) 1"C 60 A 3 PROVIDE 60A FUSIBLE DISCONNECT WITH 60 A CURRENT LIMITING

FUSES PER SHOP DRAWINGS.

ESP-1 ELEV SUMP PUMP-1 BLQG 9,11 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-2 ELEV SUMP PUMP-2 BLQG 10,12 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-3 ELEV SUMP PUMP-3 BLQG 13,15 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-4 ELEV SUMP PUMP-4 BLQG 14,16 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-5 ELEV SUMP PUMP-5 BLQG 1,3 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-6 ELEV SUMP PUMP-6 BLQG 2,4 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-7 ELEV SUMP PUMP-7 BLQG 22,24 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-8 ELEV SUMP PUMP-8 BLQG 21,23 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-DW-1 ELEV SUMP PUMP-1 BLQG 5,7 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-DW-2 ELEV SUMP PUMP-2 BLQG 6,8 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-DW-3 ELEV SUMP PUMP-DW-3 BLQG 18,20 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

ESP-DW-4 ELEV SUMP PUMP-4 BLQG 17,19 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

EWH-1 ELECTRIC WATER HEATER-1 5B104 CPLB 12 120 V 1440 VA (#12+#12N+#12G) 3/4"C 20 A 1 F-1 COPPER-SILVER FILTER SYSTEM CP CLP 15 120 V 250 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

FCU-0A01,0A02,0A03, 1A02,1A03,2A02 ALCG 22,24 208 V 600 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-0B01,0B02,0C01, 1C02,1C03,2C02 CLC1 48,50 208 V 300 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-0B03 ALCG 14,16 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-0B04 MCLCG 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-0B05 ALCG 21,23 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-1 FAN COIL UNIT-1 CPHQ 10 277 V 1644 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

FCU-1A01 ALC1T 8,10 208 V 84 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-1B01 BLC1T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-1B02,1B03,1B04 PLC1 24,26 208 V 300 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-1C01 CLC1T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-2A01 ALC2T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-2B01 BLC2T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-2B02,3B02,4B02,5B02,5B03 BLC5 25,27 208 V 500 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-2C01 CLC2T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-3A01 ALC3T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-3A02,3A03,4A02 ALC4 54,56 208 V 300 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-3B01 BLC3T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-3C01 CLC3T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-3C02 CLC1 52,54 208 V 400 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-4A01 ALC4T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-4B01 BLC4T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-4C01 CLC4T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-4C02,4C03,5C02,6C01 CLQP 8,10 208 V 400 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-5A01 ALC5T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-5A02,5A03 ALC5 26,28 208 V 400 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-5B01 BLC5T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-5C01 CLC5T 8,10 208 V 100 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECT.

FCU-6A01,6A02 ALQP 17,19 208 V 200 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FCU-6B01,6B02 BLQP 9,11 208 V 200 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P DISCONNECTS FOR EACH FCU.

FOP-1 CPLS 1,3 208 V 832 VA (2#12+#12G) 3/4"C 15 A 2 PROVIDE NEMA 3R EXPLOSION-PROOF 30A 2P DISCONNECT.

FOP-2 CPLS 14,16 208 V 832 VA (2#12+#12G) 3/4"C 15 A 2 PROVIDE NEMA 3R EXPLOSION-PROOF 30A 2P DISCONNECT.

FPCP CPLS 10 120 V 500 VA (2#12+#12G) 3/4"C 20 A 1

FPFU FUEL POLISHER FILTRATION UNIT

0CEP05

CPLS 4 120 V 1127 VA (#12+#12N+#12G) 3/4"C 20 A 1

GAP-1 GENERATOR ANNUNCIATOR PANEL-1 CLS1 2 120 V 120 VA (#12+#12N+#12G) 1/2"C 20 A 1 GEF-1B01 BHQG 25,27,29 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO INTERIOR VFD. PROVIDE 30A 3P NEMA 3R

DISCONNECT AT MOTOR. PROVIDE CONNECTION FROM VFD TO

DISCONNECT.

H-1 HUMIDIFIER FOR AHU-1 ALGB 39 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

H-2 HUMIDIFIER FOR AHU-2 ALGB 37 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

H-3 HUMIDIFIER FOR AHU-3 ALGB 41 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

H-4 HUMIDIFIER FOR AHU-4 ALP 9 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

H-5 HUMIDIFIER FOR AHU-5 CLP 13 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

H-6 HUMIDIFIER FOR AHU-6 BLP 17 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

H-7 HUMIDIFIER FOR AHU-7 ALQP 21 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

H-8 HUMIDIFIER FOR AHU-8 BLP 15 120 V 600 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

HT HEAT TAPE CPLQ 24,26 208 V 4500 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE GROUND FAULT CIRCUIT INTERRUPTING MEANS ON CIRCUIT.

HWP-1 HEATING WATER PUMP-1 5B103 CPHQ 22,24,26 480 V 21480 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

HWP-2 HEATING WATER PUMP-2 5B103 CPHQ 23,25,27 480 V 21480 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

HWP-3 HEATING WATER PUMP-3 5B103 CPHQ 28,30,32 480 V 21480 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

IAC-1 INSTR. AIR COMPRESSOR-1 0B46-1 BHGC 1,3,5 480 V 6055 VA (3#12+#12N+#12G) 3/4"C 25 A 3 PROVIDE CONNECTION TO INTERNAL VFD.

JP-1 JOCKEY PUMP-1 FIRE PUMP 0D29 CHSG 2,4,6 480 V 6055 VA (3#12+#12G) 3/4"C 15 A 3 COORDINATE ELECTRICAL REQUIREMENTS AND SIZE PRIOR TO

INSTALLATION. PROVIDE 60A FUSIBLE DISCONNECT WITH 12 A FRS-R

FUSES.

MAC -1 MEDICAL AIR COMPRESSOR BHCG 36,38,40 480 V 17528 VA (3#10+#10N+#10G) 3/4"C 35 A 3 MUA-1 FAN-MAKE-UP AIR UNIT-1 BHP 56,58,60 480 V 5418 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

MUA-1-C1 CONDENSOR-1 BHP 20,22,24 480 V 6773 VA (3#12+#12G) 3/4"C 15 A 3 COORDINATE DISCONNECT REQUIREMENTS WITH MANUFACTURER

PRIOR TO INSTALLATION.

MUA-1-C2 CONDENSOR-2 BHP 23,25,27 480 V 6773 VA (3#12+#12G) 3/4"C 15 A 3 COORDINATE DISCONNECT REQUIREMENTS WITH MANUFACTURER

PRIOR TO INSTALLATION.

MUA-1-C3 CONDENSOR-3 BHP 26,28,30 480 V 6773 VA (3#12+#12G) 3/4"C 15 A 3 COORDINATE DISCONNECT REQUIREMENTS WITH MANUFACTURER

PRIOR TO INSTALLATION.

RM REFRIGERANT MONITOR 5B104 CPLQ 8 120 V 250 VA (#12+#12N+#12G) 3/4"C 20 A 1

SSP-1 STORM SUMP PUMP-1 BLQG 25,27 208 V 1127 VA (2#12+#12G) 3/4"C 15 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT.

SSP-2 STORM SUMP PUMP-2 BLQG 26,28 208 V 1127 VA (2#12+#12G) 3/4"C 15 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT.

TLCP TANK LEAK CONTROL PNL 5B104 CPLS 5 120 V 250 VA (#12+#12N+#12G) 3/4"C 20 A 1 UH-1 UNIT HEATER-1 5B104 CPLQ 13 120 V 828 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

UH-2 UNIT HEATER-2 5B104 CPLQ 15 120 V 828 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

UH-3 UNIT HEATER-3 5B104 CPLQ 25 120 V 828 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

UH-4 UNIT HEATER-4 5B102 CPLQ 33 120 V 828 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

UH-5 UNIT HEATER-5 5B103 CPLQ 30 120 V 828 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

VAC-1 MEDICAL VACUUM PUMP BHCG 30,32,34 480 V 17847 VA (3#10+#10N+#10G) 3/4"C 35 A 3 WH-1 DOMESTIC WATER HEATER CLQP 9 120 V 1080 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

WH-1 WATER HEATER-1 MECHANICAL 0B44 ALGB 11 120 V 1080 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

WH-2 DOMESTIC WATER HEATER CLQP 13 120 V 1080 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

WH-3 DOMESTIC WATER HEATER CLQP 11 120 V 1080 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

MECHANICAL EQUIPMENT CIRCUIT SCHEDULE

Load Name Source Panel

Circuit # Volts Load Feeders

Circuit Breaker Poles Comments

AC-1 LOADING DOCK AIR CURTAIN-1 BLGB 44,46 208 V 3680 VA (2#10+#10G) 3/4"C 30 A 2 VERIFY ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION.

PROVIDE 30A 2P DISCONNECT.

AHU-1-R1 RETURN FAN 0B46-1 BHGC 7,9,11 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-1-R2 RETURN FAN 0B44 BHGC 2,4,6 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-1-S1 SUPPLY FAN 0B46-1 BHGC 13,15,17 480 V 47008 VA (3#2+#8G) 1-1/4"C 90 A 3 PROVIDE CONNECTION TO VFD.

AHU-1-S2 SUPPLY FAN 0B44 BHGC 8,10,12 480 V 47008 VA (3#2+#8G) 1-1/4"C 90 A 3 PROVIDE CONNECTION TO VFD.

AHU-2-R1 RETURN FAN 0B46-1 BHGC 20,22,24 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-2-R2 RETURN FAN 0B44 BHGC 14,16,18 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-2-S1 SUPPLY FAN 0B46-1 BHGC 25,27,29 480 V 57366 VA (3#2+#8G) 1-1/4"C 110 A 3 PROVIDE CONNECTION TO VFD.

AHU-2-S2 SUPPLY FAN 0B44 BHGC 26,28,30 480 V 57366 VA (3#2+#8G) 1-1/4"C 110 A 3 PROVIDE CONNECTION TO VFD.

AHU-3-R1 RETURN FAN 0B46-1 BHGC 31,33,35 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-3-R2 RETURN FAN 0B44 BHGC 19,21,23 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-3-S1 SUPPLY FAN 0B46-1 BHGC 37,39,41 480 V 57366 VA (3#2+#8G) 1-1/4"C 110 A 3 PROVIDE CONNECTION TO VFD.

AHU-3-S2 SUPPLY FAN 0B44 BHGC 38,40,42 480 V 57366 VA (3#2+#8G) 1-1/4"C 110 A 3 PROVIDE CONNECTION TO VFD.

AHU-4-R1 RETURN FAN 6B03 AHP 11,13,15 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-4-R2 RETURN FAN 6B04 AHP 14,16,18 480 V 24699 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-4-S1 SUPPLY FAN 6B03 AHP 20,22,24 480 V 47008 VA (3#2+#8G) 1-1/4"C 110 A 3 PROVIDE CONNECTION TO VFD.

AHU-4-S2 SUPPLY FAN 6B04 AHP 23,25,27 480 V 47008 VA (3#2+#8G) 1-1/4"C 110 A 3 PROVIDE CONNECTION TO VFD.

AHU-5-R1 RETURN FAN 6E01 CHP 8,10,12 480 V 18325 VA (3#10+#10G) 3/4"C 50 A 3 PROVIDE CONNECTION TO VFD.

AHU-5-R2 RETURN FAN 6E01 CHP 11,13,15 480 V 18325 VA (3#10+#10G) 3/4"C 50 A 3 PROVIDE CONNECTION TO VFD.

AHU-5-S1 SUPPLY FAN 6E01 CHP 14,16,18 480 V 35057 VA (3#4+#8G) 1-1/4"C 70 A 3 PROVIDE CONNECTION TO VFD.

AHU-5-S2 SUPPLY FAN 6E01 CHP 17,19,21 480 V 35057 VA (3#4+#8G) 1-1/4"C 70 A 3 PROVIDE CONNECTION TO VFD.

AHU-6-R1 RETURN FAN 6D01 BHP 29,31,33 480 V 18325 VA (3#10+#10G) 3/4"C 50 A 3 PROVIDE CONNECTION TO VFD.

AHU-6-R2 RETURN FAN 6D01 BHP 32,34,36 480 V 18325 VA (3#10+#10G) 3/4"C 50 A 3 PROVIDE CONNECTION TO VFD.

AHU-6-S1 SUPPLY FAN-1 6D01 BHP 41,43,45 480 V 30277 VA (3#6+#8G) 1"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-6-S2 SUPPLY FAN-2 BHP 44,46,48 480 V 30277 VA (3#6+#8G) 1"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-7-R1 RETURN FAN AHQP 20,22,24 480 V 18325 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-7-R2 RETURN FAN 6B04 AHQP 25,27,29 480 V 18325 VA (3#8+#10G) 3/4"C 60 A 3 PROVIDE CONNECTION TO VFD.

AHU-7-S1 SUPPLY FAN AHQP 26,28,30 480 V 35057 VA (3#4+#8G) 1-1/4"C 70 A 3 PROVIDE CONNECTION TO VFD.

AHU-7-S2 SUPPLY FAN-2 AHQP 38,40,42 480 V 35057 VA (3#4+#8G) 1-1/4"C 70 A 3 PROVIDE CONNECTION TO VFD.

AHU-8-R1 RETURN FAN 6D01 BHP 38,40,42 480 V 18325 VA (3#10+#10G) 3/4"C 50 A 3 PROVIDE CONNECTION TO VFD.

AHU-8-R2 RETURN FAN 6D01 BHP 35,37,39 480 V 18325 VA (3#10+#10G) 3/4"C 50 A 3 PROVIDE CONNECTION TO VFD.

AHU-8-S1 SUPPLY FAN MECHANICAL 6D01 BHP 47,49,51 480 V 35057 VA (3#4+#8G) 1-1/4"C 70 A 3 PROVIDE CONNECTION TO VFD.

AHU-8-S2 6D01 BHP 50,52,54 480 V 35057 VA (3#4+#8G) 1-1/4"C 70 A 3 PROVIDE CONNECTION TO VFD.

B-1 BOILER-1 5B103 CPHQ 11,13,15 480 V 13200 VA (3#10+#10N+#10G) 3/4"C 25 A 3 PROVIDE 30A 3P FUSIBLE DISCONNECT.

B-2 BOILER-2 5B103 CPHQ 16,18,20 480 V 13200 VA (3#10+#10N+#10G) 3/4"C 25 A 3 PROVIDE 30A 3P FUSIBLE DISCONNECT.

B-3 BOILER-3 5B103 CPHQ 17,19,21 480 V 13200 VA (3#10+#10N+#10G) 3/4"C 25 A 3 PROVIDE 30A 3P FUSIBLE DISCONNECT.

CAD-1 COMPRESSED AIR DRYER-1 AL4A 23 120 V 1560 VA (#12+#12N+#12G) 3/4"C 20 A 1

CF-1 CONDENSER FILTER-1 CPHB 1,3,5 480 V 11154 VA (3#12+#12N+#12G) 3/4"C 35 A 3

CF-2 CONDENSER FILTER-2 CPHB 2,4,6 480 V 11154 VA (3#12+#12N+#12G) 3/4"C 35 A 3

CH-1 CHILLER-1 5B104 CP-SWGR 4 480 V 369689 VA 2-(3-350KCMIL+#1G) 3-1/2"C 600 A 3 PROVIDE CONNECTION TO INTERNAL VFD.

CH-2 CHILLER-2 5B104 CP-SWGR 5 480 V 369689 VA 2-(3-350KCMIL+#1G) 3-1/2"C 600 A 3 PROVIDE CONNECTION TO INTERNAL VFD.

CH-MRI-1A65 AH2 1,3,5 480 V 38244 VA (3#4+#10G) 1"C 60 A 3 PROVIDE 60A 3P NEMA 3R FUSIBLE DISCONNECT. CONFIRM

ELECTRICAL REQUIREMENTS WITH SITE SPECIFIC DRAWINGS.

CH-MRI-1A67 AH2 2,4,6 480 V 38244 VA (3#4+#10G) 1"C 60 A 3 PROVIDE 60A 3P NEMA 3R FUSIBLE DISCONNECT. CONFIRM

ELECTRICAL REQUIREMENTS WITH SITE SPECIFIC DRAWINGS.

CONDENSOR FOR CANTEEN WALK-IN

REFRIGERATED SPACE.

<unnamed> 480 V 0 VA TBD 0 A 3 CONFIRM ALL ELECTRICAL REQUIREMENTS WITH VENDOR SHOP

DRAWINGS WHEN AVAILABLE.

CP-1 CONDENSER PUMP-1 5B104 CPHA 20,22,24 480 V 51720 VA (3#2+#6G) 1-1/4"C 100 A 3 PROVIDE CONNECTION TO VFD.

CP-2 CONDENSER PUMP-2 5B104 CPHA 25,27,29 480 V 51720 VA (3#2+#6G) 1-1/4"C 100 A 3 PROVIDE CONNECTION TO VFD.

CP-3 CONDENSER PUMP-3 5B104 CPHA 26,28,30 480 V 51720 VA (3#2+#6G) 1-1/4"C 100 A 3 PROVIDE CONNECTION TO VFD.

CRAC-0A01 MCR 0B39 BHQG 19,21,23 480 V 31232 VA (3#6+#6N+#10G) 1"C 50 A 3 PROVIDE CONNECTION TO VFD.

CRAC-0A02 MCR 0B39 BHQG 14,16,18 480 V 31232 VA (3#6+#6N+#10G) 1"C 50 A 3 PROVIDE CONNECTION TO VFD.

CT-1 FAN-1 COOLING TOWER CPHA 14,16,18 480 V 41431 VA (3#4+#8G) 1-1/4"C 125 A 3 PROVIDE CONNECTION TO VFD IN CEP. PROVIDE 100A 3P NEMA 3R

DISCONNECT OUTSIDE AT THE COOLING TOWER. PROVIDE

CONNECTION FROM VFD TO DISCONNECT.

CT-1 FAN-2 COOLING TOWER CPHA 19,21,23 480 V 41431 VA (3#4+#8G) 1-1/4"C 125 A 3 PROVIDE CONNECTION TO VFD IN CEP. PROVIDE 100A 3P NEMA 3R

DISCONNECT OUTSIDE AT THE COOLING TOWER. PROVIDE

CONNECTION FROM VFD TO DISCONNECT.

CT-1H1 COOLING TOWER HEATER-1 CPHA 31,33,35 480 V 24000 VA (3#8+#10G) 3/4"C 40 A 3 PROVIDE 60A 3P NEMA 3R FUSIBLE DISCONNECT. PROVIDE GROUND

FAULT OVERCURRENT RELAY. PROVIDE CONNECTION TO BASIN

HEATER CONTROL PANEL.

CT-1H2 COOLING TOWER HEATER-2 CPHA 32,34,36 480 V 24000 VA (3#8+#10G) 3/4"C 20 A 3 PROVIDE 60A 3P NEMA 3R FUSIBLE DISCONNECT. PROVIDE GROUND

FAULT OVERCURRENT RELAY. PROVIDE CONNECTION TO BASIN

HEATER CONTROL PANEL.

CU-6A01 AHQP 13,15,17 480 V 5657 VA (3#12+#12G) 3/4"C 20 A 3 PROVIDE 30A 3P NEMA 3R DISCONNECT.

CU-6A02 AHQP 14,16,18 480 V 9321 VA (3#10+#10G) 3/4"C 25 A 3 PROVIDE 30A 3P NEMA 3R DISCONNECT.

CU-6A03 AHQP 8,10,12 480 V 9321 VA (3#10+#10G) 3/4" 25 A 3 PROVIDE 30A 3P NEMA 3R DISCONNECT.

CU-6B01 BHQP 32,34,36 480 V 5657 VA (3#12+#12G) 3/4"C 20 A 3 PROVIDE 30A 3P NEMA 3R FUSIBLE DISCONNECT.

CU-6B02 BHQP 44,46,48 480 V 9321 VA (3#10+#10G) 3/4"C 25 A 3 PROVIDE 30A 3P NEMA 3R FUSIBLE DISCONNECT.

CU-6B03 BHQP 38,40,42 480 V 12110 VA (3#8+#10G) 3/4"C 35 A 3 PROVIDE 30A 3P NEMA 3R FUSIBLE DISCONNECT.

CU-6B04 PRE-OP 5C54 BHQP 14,16,18 480 V 2789 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

CU-6B05 PRE-OP 5C54 BHQP 17,19,21 480 V 2789 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

CU-6C01 CONDENSING UNIT-6C01 CHQP 13,15,17 480 V 5657 VA (3#12+#12G) 3/4"C 20 A 3 PROVIDE 30A 3P NEMA 3R DISCONNECT.

CU-6C02 CHQP 7,9,11 480 V 5657 VA (3#12+#12G) 3/4"C 20 A 3 PROVIDE 30A 3P NEMA 3R DISCONNECT.

CU-6C03 CHQP 2,4,6 480 V 9321 VA (3#10+#10G) 3/4"C 25 A 3 PROVIDE 30A 3P NEMA 3R DISCONNECT.

CU-LAB CONDENSER FOR GROUND LEVEL

LAB WALK-IN REFRIGERATED SPACE

BLQP 20,22,24 208 V 4107 VA (3#12+#12N+#12G) 3/4"C 20 A 3 VERIFY ALL ELECTRICAL REQUIREMENTS WITH VENDOR SHOP

DRAWINGS WHEN RECEIVED.

CUH CABINET UNIT HEATER STAIR 1 BL1B 49 120 V 64 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

CUH-1 CABINET UNIT HEATER 0S03 ALGB 3 120 V 64 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

CUH-1 CABINET UNIT HEATER 2 1S02 AL1B 3 120 V 64 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

CUH-1 CABINET UNIT HEATER 4 1S04 BL1A 5 120 V 64 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

CUH-1 CABINET UNIT HEATERS 1S07, 1S06 CL1B 5 120 V 128 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

CUH-1,CUH-2 CABINET UNIT HEATER 0S01-1

0S05

BLGA 5 120 V 128 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

CWP-1 CHILLED WATER PUMP-1 5B104 CPHQ 29,31,33 480 V 41380 VA (3#4+#8G) 1-1/4"C 80 A 3 PROVIDE CONNECTION TO VFD.

CWP-2 CHILLED WATER PUMP-2 5B104 CPHA 8,10,12 480 V 41380 VA (3#4+#8G) 1-1/4"C 80 A 3 PROVIDE CONNECTION TO VFD.

CWP-3 CHILLED WATER PUMP-3 5B104 CPHA 13,15,17 480 V 41380 VA (3#4+#8G) 1-1/4"C 80 A 3 PROVIDE CONNECTION TO VFD.

DAC-1 DENTAL AIR COMPRESSOR AH4 10,12,14 480 V 11154 VA (3#12+#12N+#12G) 3/4"C 30 A 3 PROVIDE 30A 3P FUSIBLE DISCONNECT.

DAC-1 DENTAL AIR COMPRESSOR AH4 13,15,17 480 V 11154 VA (3#12+#12N+#12G) 3/4"C 30 A 3 PROVIDE 30A 3P FUSIBLE DISCONNECT.

DHWP-1 DOMESTIC HOT WATER PUMP-1 ALGB 43 120 V 506 VA (3#12+#12G) 3/4"C 20 A 1 CONFIRM ALL ELECTRICAL REQUIREMENTS WITH SHOP DRAWINGS

PRIOR TO INSTALLATION. PROVIDE THERMAL DISCONNECT SWITCH.

DHWP-2 DOMESTIC HOT WATER PUMP-2 CHP 20,22,24 480 V 1673 VA (3#12+#12G) 3/4"C 15 A 3 CONFIRM ALL ELECTRICAL REQUIREMENTS WITH SHOP DRAWINGS

PRIOR TO INSTALLATION. PROVIDE 30A 3P FUSIBLE DISCONNECT.

DHWP-3 DOMESTIC HOT WATER PUMP-3 CHP 23,25,27 480 V 1673 VA (3#12+#12G) 3/4"C 15 A 3 CONFIRM ALL ELECTRICAL REQUIREMENTS WITH SHOP DRAWINGS

PRIOR TO INSTALLATION. PROVIDE 30A 3P FUSIBLE DISCONNECT.

DVC-1 DENTAL VACUUM PUMP AH4 4,6,8 480 V 8764 VA (3#12+#12N+#12G) 3/4"C 25 A 3 CONNECTION TO INTERNAL VFD.

DVC-1 DENTAL VACUUM PUMP AH4 7,9,11 480 V 8764 VA (3#12+#12N+#12G) 3/4"C 25 A 3 CONNECTION TO INTERNAL VFD.

DW-1 DUMBWAITER-1 ELEVATOR MACH 0D01 BHQG 7,9,11 480 V 25495 VA (3#8+#8G) 1"C 40 A 3 PROVIDE A 60A FUSIBLE DISCONNECT WITH CURRENT LIMITING FUSES

PER SHOP DRAWINGS.

DW-2 DUMBWAITER-2 ELEVATOR MACH 0D01 BHQG 8,10,12 480 V 25495 VA (3#8+#8G) 1"C 40 A 3 PROVIDE A 60A FUSIBLE DISCONNECT WITH CURRENT LIMITING FUSES

PER SHOP DRAWINGS.

DW-3 DUMBWAITER-3 ELEVATOR MACH 0D01 BHQG 31,33,35 480 V 25495 VA (3#8+#8G) 1"C 40 A 3 PROVIDE A 60A FUSIBLE DISCONNECT WITH CURRENT LIMITING FUSES

PER SHOP DRAWINGS.

DW-4 DUMBWAITER-4 ELEVATOR MACH 0D01 BHQG 32,34,36 480 V 25495 VA (3#8+#8G) 1"C 40 A 3 PROVIDE A 60A FUSIBLE DISCONNECT WITH CURRENT LIMITING FUSES

PER SHOP DRAWINGS.

DWBP-1 DOMESTIC WATER BOOSTER

PUMP-1

BHQG 13,15,17 480 V 8764 VA (3#12+#12G) 3/4"C 25 A 3 PROVIDE CONNECTION TO VFD.

DWBP-2 DOMESTIC WATER BOOSTER

PUMP-2

BHQG 38,40,42 480 V 8764 VA (3#12+#12G) 3/4"C 25 A 3 PROVIDE CONNECTION TO VFD.

DWBP-3 DOMESTIC WATER BOOSTER

PUMP-3

BHQG 37,39,41 480 V 8764 VA (3#12+#12G) 3/4"C 25 A 3 PROVIDE CONNECTION TO VFD.

EF-0B01 BLGB 13 120 V 1127 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE THERMAL OVERLOAD SWITCH.

EF-1B01 BH1 9,11,13 480 V 2709 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-1B02 PLC1 7 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-1B03 PLC1 9 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-1B04 BL1A 32 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-1B05 BL1A 33 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-1B06 BL1A 35 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-1B07 ALGA 5 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-1B08 ALGA 14,16 208 V 1580 VA (2#12+#12G) 3/4"C 15 A 2 PROVIDE 30A NEMA 3R DISCONNECT.

EF-1P01 CPLQ 20,22 208 V 1840 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT.

EF-1P02 CPLQ 21,23 208 V 1587 VA (2#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT.

EF-1P03 CPLQ 16 120 V 1127 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-2A01 ALQP 8,10 208 V 1840 VA (3#12+#12G) 3/4"C 20 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT.

EF-2A02 AH2 19,21,23 480 V 1673 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

EF-2A03 AL2A 11 120 V 667 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-2A04 AL2A 20 120 V 1127 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-2C01 CL2B 4 120 V 667 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-3A01 AL3B 8 120 V 667 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-3A02 AL3A 7 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-5A01 AL5A 6 120 V 1127 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-5A02 AL5B 9 120 V 667 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-5A03 AH5 19,21,23 480 V 2709 VA (3#12+#12G) 3/4"C 20 A 3 PROVIDE CONNECTION TO VFD.

EF-5A04 AH5 18,20,22 480 V 1673 VA (3#12+#12G) 3/4"C 20 A 3 PROVIDE CONNECTION TO VFD.

EF-6A01 ALQP 7 120 V 506 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6A02 ALP 4 120 V 1587 VA (#12+#12N+#12G) 3/4"C 20 A 1 PROVIDE WEATHERPROOF THERMAL OVERLOAD SWITCH.

EF-6A03 ALP 6,8 208 V 1840 VA (2#12+#12G) 3/4"C 15 A 2 PROVIDE 30A 2P NEMA 3R DISCONNECT.

EF-6A04 AHQP 31,33,35 480 V 2390 VA (3#12+#12G) 3/4"C 15 A 3 PROVIDE CONNECTION TO VFD.

USER EQUIPMENT CIRCUIT SCHEDULE

Load Name Source Panel Circuit # Volts Amps Feeders

Circuit Breaker Poles Comments

ACW AUTO-CART WASHER 0B09 A-SWGR 6 480 V 77 A (3-1/0+6G) 2"C 125 A 3 PROVIDE 200A 3P FUSIBLE DISCONNECT WITH 125A FUSES.

CT SCAN DISC. 1A23 RH1 20,22,24 480 V 24 A (3#2+#2N+#8G) 1-1/2"C 90 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

CT SCAN DISC. 1A25 RH1 26,28,30 480 V 24 A (3#2+#2N+#8G) 1-1/2"C 90 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

ELECTRIC DRYER 2A56 AL2B 66,68,70 208 V 12 A (3#10+#10N+#10G) 3/4"C 30 A 3 PROVIDE A NEMA14-30R RECEPTACLE TO MATCH MANUFACTURER'S

DRAWINGS.

LARGE STERILIZER CLEAN PREP. 0B23 ALGA 23,25,27 208 V 24 A (3#10+#10N+#10G) 3/4"C 30 A 3 PROVIDE NEMA L21-30 TWIST LOCK RECEPTACLE PER VENDOR SHOP

DRAWINGS.

LD-1 LOADING DOCK-1 5B106 BHGA 26,28,30 480 V 2 A (3#12+#12G) 3/4"C 20 A 3 PROVIDE 30A 3P NEMA 3R FUSIBLE DISCONNECT.

LD-2 LOADING DOCK-2 5B106 BHGA 33,35,37 480 V 2 A (3#12+#12G) 3/4"C 20 A 3 PROVIDE 30A 3P NEMA 3R FUSIBLE DISCONNECT.

MRI SCAN DISC. 1A65 RH1 31,33,35 480 V 61 A (3#3+#3N+#8G) 1-1/2"C 80 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

MRI SCAN DISC. 1A67 RH1 32,34,36 480 V 61 A (3#3+#3N+#8G) 1-1/2"C 80 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

MULTICHANNEL ANALYSER CLINICAL LAB-1 0D11-1 BLGA 80,82 208 V 38 A (2#6+#6G) 1"C 50 A 2 PROVIDE RECEPTACLE PER VENDOR SHOP DRAWINGS, LIKELY HUBBELL

CS8269 OR EQUIVALENT.

MULTICHANNEL ANALYSER CLINICAL LAB-1 0D11-1 BLGA 84,86 208 V 14 A (2#12+#12G) 3/4"C 20 A 2 PROVIDE RECEPTACLE PER VENDOR SHOP DRAWINGS, LIKELY NEMA

6-20R.

MULTICHANNEL ANALYSER CLINICAL LAB-1 0D11-1 BLGA 81,83 208 V 38 A (2#6+#6G) 1"C 50 A 2 PROVIDE RECEPTACLE PER VENDOR SHOP DRAWINGS, LIKELY HUBBELL

CS8269 OR EQUIVALENT.

NM SCAN DISC. 1B17 RH1 19,21,23 480 V 14 A (3#8+#8N+#10G) 1"C 40 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

PET SCAN DISC. 1B19 RH1 25,27,29 480 V 36 A (3#2+#2N+#8G) 1-1/2"C 90 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

R/F X-RAY DISC. 1A41 RH1 14,16,18 480 V 78 A (3#1+#1N+#6G) 2"C 100 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

R/F X-RAY DISC. 1A42 RH1 2,4,6 480 V 78 A (3#1+#1N+#6G) 2"C 100 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

R/O SYSTEM WATER 0B14 ALGA 20,22,24 208 V 6 A (3#12+#12N+#12G) 3/4"C 20 A 3 CONFIRM EQUIPMENT ELECTRICAL REQUIREMENTS. PROVIDE SPECIAL

RECEPTACLE OR DIRECT CONNECTION WITH A DISCONNECT AS

REQUIRED BY THE MANUFACTURER.

RADIOGRAPHIC UNIT PANO X-RAY 4A30 AL4B 21,23 208 V 12 A (2#10+#10G) 3/4"C 25 A 2 CONFIRM ELECTRICAL REQUIREMENTS WITH EQUIPMENT PRIOR TO

INSTALLATION. PROVIDE SPECIAL RECEPTACLE OR DISCONNECT WITH

DIRECT CONNECTION.

RO IMAGER-WATER TREATMENT 1E17 CLC1 53,55,57 208 V 6 A (3#12+#12N+#12G) 3/4"C 20 A 3 CONFIRM EQUIPMENT ELECTRICAL REQUIREMENTS. PROVIDE SPECIAL

RECEPTACLE OR DIRECT CONNECTION WITH A DISCONNECT AS

REQUIRED BY THE MANUFACTURER.

SL-1 SCISSORS LIFT-1 5B106 BHGA 32,34,36 480 V 2 A (3#12+#12G) 3/4"C 20 A 3 CONFIRM EQUIPMENT ELECTRICAL REQUIREMENTS. PROVIDE 30A NEMA

3R FUSIBLE DISCONNECT.

STAINER SLIDE PROCESSOR HISTOL. 5B36 AL5A 65,67 208 V 13 A (2#12+#12G) 3/4"C 20 A 2 PROVIDE SPECIAL RECEPTACLE PER MANUFACTURER'S CUTSHEET.

STEAM GUN MAN. WASH 0B12 ALGA 32,34,36 208 V 25 A (3#8+#10G) 3/4"C 35 A 3 CONFIRM CIRCUIT BREAKER SIZE, DISCONNECT OR SPECIAL OUTLET, AND OTHER ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION.

STEAM GUN MAN. WASH 0C12 BLGB 80,82,84 208 V 25 A (3#8+#10G) 3/4"C 35 A 3 CONFIRM CIRCUIT BREAKER SIZE, DISCONNECT OR SPECIAL OUTLET, AND OTHER ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION.

STEAM STERILIZER AREA 5B13 AHC5 31,33,35 480 V 34 A (3#6+#10G) 1-1/4"C 50 A 3 PROVIDE 60A 3P NEMA 3R FUSIBLE DISCONNECT.

STEAM STERILIZER-1 0B22 BHCG 33,35,37 480 V 46 A (3#4+#4N+#10G) 1-1/4"C 60 A 3 PROVIDE 60A 3P FUSIBLE DISCONNECT AND CONFIRM ELECTRICAL

REQUIREMENTS WITH MANUFACTURER PRIOR TO INSTALLATION.

STEAM STERILIZER-2 0B22 AHGB 17,19,21 480 V 46 A (3#4+#4N+#10G) 1-1/4"C 60 A 3 PROVIDE 60A 3P FUSIBLE DISCONNECT AND CONFIRM ELECTRICAL

REQUIREMENTS WITH MANUFACTURER PRIOR TO INSTALLATION.

TREADMILL 2A26 AL2B 65,67 208 V 9 A (2#12+#12N+#12G) 3/4"C 15 A 2 CONFIRM ELECTRICAL REQUIREMENTS. PROVIDE A NEMA 6-20R

RECEPTACLE TO MATCH MANUFACTURER'S REQUIREMENTS.

TREADMILL 2A26 AL2B 69,71 208 V 9 A (2#12+#12N+#12G) 3/4"C 15 A 2 CONFIRM ELECTRICAL REQUIREMENTS. PROVIDE A NEMA 6-20R

RECEPTACLE TO MATCH MANUFACTURER'S REQUIREMENTS

TREADMILL 2A26 AL2B 62,64 208 V 9 A (2#12+#12N+#12G) 3/4"C 15 A 2 CONFIRM ELECTRICAL REQUIREMENTS. PROVIDE A NEMA 6-20R

RECEPTACLE TO MATCH MANUFACTURER'S REQUIREMENTS

TREADMILL STRESS ECHO/ TEE 1B37 AL1A 32,34 208 V 9 A (2#12+#12N+#12G) 3/4"C 15 A 2 CONFIRM ELECTRICAL REQUIREMENTS. PROVIDE A NEMA 6-20R

RECEPTACLE TO MATCH MANUFACTURER'S REQUIREMENTS

TREADMILL STRESS TEST 1B38 AL1A 36,38 208 V 9 A (2#12+#12N+#12G) 3/4"C 15 A 2 CONFIRM ELECTRICAL REQUIREMENTS. PROVIDE A NEMA 6-20R

RECEPTACLE TO MATCH MANUFACTURER'S REQUIREMENTS

UC-1 ULTRASONIC CLEANER-1 0B08 ALCG 17,19 208 V 6 A (3#12+#12N+#12G) 3/4"C 15 A 2 PROVIDE 30A 2P FUSIBLE DISCONNECT PER MANUFACTURER'S SHOP

DRAWINGS.

UC-2 ULTRASONIC CLEANER-2 0B08 ALGA 15,17 208 V 6 A (3#12+#12N+#12G) 3/4"C 15 A 2 PROVIDE 30A 2P FUSIBLE DISCONNECT PER MANUFACTURER'S SHOP

DRAWINGS.

WD-1 WASHER/DISINFECTOR-1 0B08 ALCG 79,81,83 208 V 48 A (3#6+#8G) 1"C 60 A 3 PROVIDE 60A 3P NEMA 3R DISCONNECT.

WD-2 WASHER/DISINFECTOR-2 0B08 ALGA 38,40,42 208 V 48 A (3#6+#8G) 1"C 60 A 3 PROVIDE 60A 3P NEMA 3R DISCONNECT.

X-RAY DISC. 1A32 RH1 7,9,11 480 V 30 A (3#3+#3N+#8G) 1-1/2"C 80 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

X-RAY DISC. 1A33 RH1 8,10,12 480 V 30 A (3#3+#3N+#8G) 1-1/2"C 80 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

X-RAY DISC. 1A36 RH1 13,15,17 480 V 30 A (3#3+#3N+#8G) 1-1/2"C 80 A 3 PROVIDE SHUNT TRIP CIRCUIT BREAKER AND CONNECTION TO EPO

BUTTON.

SITE EQUIPMENT CIRCUIT SCHEDULE

Load Name Source Panel Circuit # Volts Amps Feeders

Circuit Breaker Poles Comments

BACK CANOPY AIR COMPRESSOR ALS1 5 120 V 9 A (#12+#12N+#12G) 3/4"CF 20 A 1 VERIFY LOCATION AND ELECTRICAL REQUIREMENTS. PROVIDE THERMAL

DISCONNECT SWITCH WHERE APPLICABLE.

ELECTRIC VEHICLE CHARGING-1 CLGA 4,6,8 208 V 19 A (2#8+#10G) 1-1/4"C 40 A 3 VERIFY ELECTRICAL REQUIREMENTS WITH SHOP DRAWINGS.

ELECTRIC VEHICLE CHARGING-2 CLGA 7,9,11 208 V 19 A (2#8+#10G) 1-1/4"C 40 A 3 VERIFY ELECTRICAL REQUIREMENTS WITH SHOP DRAWINGS.

ELECTRIC VEHICLE CHARGING-3 CLGA 10,12,14 208 V 19 A (2#8+#10G) 1-1/4"C 40 A 3 VERIFY ELECTRICAL REQUIREMENTS WITH SHOP DRAWINGS.

ELECTRIC VEHICLE CHARGING-4 CLGA 13,15,17 208 V 19 A (2#8+#10G) 1-1/4"C 40 A 3 VERIFY ELECTRICAL REQUIREMENTS WITH SHOP DRAWINGS.

FRONT CANOPY AIR COMPRESSOR CLS1 5 120 V 9 A (#12+#12N+#12G) 3/4"C 20 A 1 VERIFY LOCATION AND ELECTRICAL…

This is the start of the file's text. The full file is on GovTribe.